Via Christi Regional Medical Center

Wichita, KS

Lindy PopeSeptember 14, 2007

Electricity Reduction

Page 2: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Presentation OverviewVia Christi OverviewEnergy Consumption AuditLight Audit

Delamping and TimersNew Lamp Purchases

Occupancy SensorsDimming Controls

Air AuditEmployee Awareness

Energy Star ProductsMonitor Power ManagementEnergy Awareness Program

Total SavingsQuestions

Page 3: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Via Christi Overview

Via Christi Regional Medical Center is a non-profit Catholic health organization based in Wichita, Kansas.

I worked at their St. Francis campus. St. Francis is a 1,450,000 square feet Level-1 Trauma Center.

Page 4: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Energy Consumption Audit12 months of energy data was collected for St. Francis, St. Joseph, Our Lady of Lourdes, Good Shepherd, and 30 other locations owned by Via Christi.

The 4 main buildings were placed into Energy Star’s Portfolio Manager to get a benchmark reading.

Page 5: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Energy Consumption Audit

St. Francis’ meters were broken down into: the location they served, what events happen in those locations, and $ per square foot.

All this information was collected to allow the hospital to focus their energy conservation on the locations where they use the most energy.

An example of the final spreadsheet can be seen below.

Page 6: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Light Audit

Overall higher lighting levels than needed.

Recommendations:

¼ Delamping- 25 locations

In locations that are over lit constantly and/or low traffic hallways

Turn off certain lights during the day- 21 locations

Achieve through timers or connecting the lighting to a Building Automation System

21 timers are needed: a purchase price of $630

Benefits

$5,793.27 and 125,068 kWh savings in electricity per year

Removal of 336 lamps

Page 7: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

New Lamp Purchases

A list of the current lamp purchases for St. Francis and St. Joseph was reviewed to determine if there are better options.

11 lamp types were identified that should be changed.

The new lamps reduce electricity, lamp disposal, mercury, and/or maintenance costsT-8: 38,350 to 45,950 T- 8’s in the 4 main buildings

Savings:$81,920 to $97,302 in electricity per year1,638,387 to 1,946,005 kWh per year69,030 to 82,710 mg of mercury

  Bulb Lamp Watts Rated Life Mean Lum CRI Temp Mercury Price

Current: GE F32T8/SP41/ECO T-8 32 30,000 2660 78 4100K N/A $1.37

Replacement: Philips F32T8/ADV841/XEW/ALTO T-8 25 36,000 2400 85 4100K 1.7 mg $3.34

Page 8: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Occupancy Sensors

Location Average Savings Amount Annual Savings (per room)

Private Offices 35% 600 $7.59 - $12.56

Classrooms 40% 35 $18.40 - $49.06

Conference Rooms 47% 62 $10.29 - $20.58

Restrooms 54% 121 $35.50 - $59.13

Storage Areas 60% 264 $7.88 - $15.77

Lounge/Kitchen 35% 90 $13.80 - $27.60

Waiting Room 30% 50 $26.28 - $52.56

Exam Room 50% 121 $6.57 - $13.14

Total Savings:

$15,497 to $28,591 in electricity per year

310,119 to 571,747 kWh per year

Page 9: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Dimming Controls

Dimming controls offer occupants more control over their environment.They can be used in patient rooms, offices, and exam rooms.

Occupancy sensors save more in offices then dimmers do.Dimming controls, in exam rooms, have no research on potential savings.

Patient roomsImplement dimmers during renovations or new construction.There are 730 patient rooms.The chart below shows the estimated savings per year if dimmers were placed in patient rooms.

Lamps Payback (years) Annual Savings per Room in kWh Total per Year in kWh

6 6 $9.20 183.96 $6,716 134,291

10 3.6 $15.33 306.6 $11,191 223,818

Page 10: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Air AuditEquipment used: UE Systems 9000 Ultrasonic Leak Detector

Compressed Air

20 leaks for a total loss of 74.8 CFM

Total loss of $7,862.98 and 157,260 kWh per year

Medical Air

11 leaks for a total loss of 22.9 CFM

Total loss of $3,009.06 60,181 kWh per year

Steam

5 leaks for a total loss of 35.12 lb/hr

Total loss of $3,999 and 331 Mbtu per year

Total: $14,871, 217,441 kWh, and 331 Mbtu per year

Page 11: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Energy Star Products

Product Savings (1 unit per year) Total Savings (per Year)

CRT/LCD Monitor $8 $10,500

TV $3 $2,190

Vending Machine $140 $10,500

Computer $6 $3,600

LED Exit Signs $12 $6,000

Other products:

Copiers, printers, refrigerators, DVD’s, fax, and food service equipment

Total Savings:

$27,090 per year

500,000 kWh per year

Page 12: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Monitor Power ManagementThis free software from Energy Star puts all monitors on the

network into sleep mode after a pre-determined time.

Estimated savings per monitor: $10-$20

Total Savings (based on 1,500 monitors):

$15,000 to $30,000 per year

300,000 to 600,000 kWh per year

Cisco Systems Success Story:

20,000 monitors

Total savings of $528,000 or $26 per monitor per year

Only 16 hours of IT time to implement

Page 13: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Energy Awareness Program

Newsletter Ad

Makes sure employees are an active part of energy savings.

Fact SheetsWill remind people of energy conservation acts and benefits.

Posters

Constant reminder to turn off

the lights and office equipment at night.

Total Estimated Savings (fromEnergy Star):

$30,000-$76,000 per year600,000-1,520,000 kWh per year

Page 14: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Total Savings

Project Annual Cost Savings (in electricity)

Environmental Results per year Status

Delamping $1,895Reduce 37,906 kWh

Reduction of 343 lampsRecommended

Daylight Timers $4,358 Reduce 87,162 kWh Recommended

Air Audit $14,871Reduce 217,441 kWh

Reduce 331 MbtuRecommended

Lamp Changes $81,920 to $97,302

Reduce 1,638,387 to 1,946,004 kWh

RecommendedReduce 69,030 to 82,710 mg

mercury

Occupancy Sensors $15,497 to $28,591 Reduce 310,119 to 571,747 kWh Recommended

Dimming Controls

$2,229.2 to $3,715 (offices)

Reduce 44,584 to 74,307 kWh Not Recommended

$6,716 to $11,191 (patient rooms)

Reduce 134,291 to 223,818 kWh Recommended

Energy Awareness Program

$30,000 to $76,000Reduce 600,000 to 1,520,000

kWhRecommended

Monitor Management $15,000 to $30,000 Reduce 300,000 to 600,000 kWh Recommended

Energy Star Products $27,090 500,000 kWh Recommended

Page 15: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Total Savings

Total Savings in Energy per Year:

$197,347 to $291,298

3,825,306 to 5,704,078 kWh

Page 16: Via Christi Regional Medical Center Wichita, KS Lindy Pope September 14, 2007 Electricity Reduction

Questions?