4
8 Field Selectable Sequences All Common ISA Sequences Including First-Out Switch, Transistor, and Logic Level Inputs 4 or 8-Point Monitoring Free Custom Message Labels Type 4X, NEMA 4X, IP65 Front Universal Power Supply 85-265 VAC 12-36 VDC/12-24 VAC Power Option Built-In 85 dB Horn 2 SPDT Relays for Alarm Activated Devices 24 VDC Isolated Power Supply (AC Models) Multiple-Unit First-Out Indication Silence, Acknowledge, and Reset Functions Sunlight Readable Indication Shallow Depth 1/8 DIN Case VIGILANTE ® II ALARM ANNUNCIATORS PRECISION DIGITAL CORPORATION www.predig.com Model PD154 / 4-Point Model PD158 / 8-Point V igilante II ®

VIgILANTE II ALARM ANNUNCIATORSAck Steady Steady Off Normal Off The Vigilante II Alarm Annunciator can be programmed for all common ISA sequences including A, F1A, F2A, F3A, M, F1M

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • • 8 Field Selectable Sequences• All Common ISA Sequences Including First-Out• Switch, Transistor, and Logic Level Inputs• 4 or 8-Point Monitoring• Free Custom Message Labels• Type 4X, NEMA 4X, IP65 Front• Universal Power Supply 85-265 VAC• 12-36 VDC/12-24 VAC Power Option• Built-In 85 dB Horn• 2 SPDT Relays for Alarm Activated Devices• 24 VDC Isolated Power Supply (AC Models)• Multiple-Unit First-Out Indication• Silence, Acknowledge, and Reset Functions• Sunlight Readable Indication• Shallow Depth 1/8 DIN Case

    VIgILANTE® II ALARM ANNUNCIATORS

    Precision Digital corPoration www.predig.com

    Model PD154 / 4-Point Model PD158 / 8-Point

    Vigilante II®

  • MODEL PD154 & PD158 VIgILANTE® II ANNUNCIATORS

    2

    APPLICATIONS

    Multiple Unit First-Out IndicationIf multiple Vigilante II annunciators are connected for multiple unit first-out indication, only one input from all connected devices will display as a first-out alarm.

    First-Out Alarm Indication

    Temp Monitoring with Trident Meters

    Level Monitoring with Level Switches

    ALARM SEqUENCES

    Multiple Unit First-Out Alarm Indication

    The Vigilante II can be programmed for multiple sequences with first-out alarm indication. This feature indicates the first point of failure of a system when multiple alarms occur.

    The Vigilante® II is ideal for tank level switch monitoring. •Upto8IndividuallyLabeledLevelSwitchInputs •24VDCLevelSwitchPowerSupply •RelaysforExternalHornsandLightAlarms •EasyNEMA4XMountingEnclosures •SunlightReadableIndication

    ConnectPD765TridentalarmrelaystotheVigilanteIIfortemperature alarm monitoring. •First-OutIndicationforHeating/CoolingSystems •MultipleUnitFirst-OutIndication •RemoteSilence,Acknowledge,andReset •Internal85dBHorn •Fail-SafeRelaysforCriticalApplications

    ISA Alarm Sequence AAcknowledgementandAutomaticReset

    Momentary AlarmCondition LED Horn

    Normal Off Off

    Alert Flash On

    Normal Flash On

    User Acknowledged

    Acknowledge Off Off

    Maintained AlarmCondition LED Horn

    Normal Off Off

    Alert Flash On

    User Acknowledged

    Acknowledge Steady Off

    Normal Off Off

    ISA Alarm Sequence F2AFirst-OutAlarmIndicationwithAcknowledgementandAutomaticReset

    Momentary AlarmCondition LED Horn

    1stPt NextPt

    Normal Off Off Off

    Alert Flash Steady On

    Normal Flash Steady On

    User Acknowledged

    Ack Off Off Off

    Maintained AlarmCondition LED Horn

    1stPt NextPt

    Normal Off Off Off

    Alert Flash Steady On

    User Acknowledged

    Ack Steady Steady Off

    Normal Off Off Off

    The VigilanteIIAlarmAnnunciator can be programmed for allcommonISAsequencesincludingA,F1A,F2A,F3A,M,F1M.SelectableISA-1(SilenceButton),-4(NoLock-In),andhorndisableoptions.Twopopularsequencesaredetailed below.

    PD154 inPDA2801

    Horn

    Light Alarm

    Level Switch

    Level Switch

    High Alarm

    Low Alarm

    High Alarm

    Low Alarm

    PD765

    PD765

    PD154Built-In Horn

    External Buttons

  • MODEL PD154 & PD158 VIgILANTE® II ANNUNCIATORS

    3

    MOUNTINg DIMENSIONS

    CONNECTIONS

    MESSAgE LABELSAlarmmessagelabelsforthealarmannunciatormaybefactory printed at no charge, or field printed using a laser printer with clear self-adhesive labels.Factory printedmessage labelsmay be ordered at anytime by completing the following form. Pleaseincludelabelwithmyorder IhavetheAnnunciator,pleasesendlabelQuantity ____________________________________Name ______________________________________Title ________________________________________Company ___________________________________MailingAddress ______________________________City,St.,Zip _________________________________Phone ______________________________________Fax ________________________________________E-Mail ______________________________________PO# _______________________________________

    Areaavailablepermessage:PD154,1.25"x0.60"(32mmx15mm);PD158,1.25"x0.25"(32mmx6mm);usermayspecifyanysizeandlengththatwillfitinthisarea.Linesof14charactersmaxat9pointtypewillfit.

    PD154 PD158Message1 Message1&2

    Message2 Message3&4

    Message3 Message5&6

    Message4 Message7&8

    Panel

    Gasket

    MountingBracket

    MountingScrew

    RemovableConnectors

    1.772"(45mm)

    Panel Cutoutto DIN 43700

    Square Cornersto 0.060"(1.5mm)

    Max Radius

    B

    Tolerances:A: +0.032 (+0.8mm) -0.000 (-0.0mm)B: +0.024 (+0.6mm) -0.000 (-0.0mm)

    3.622"(92mm)

    A

    Top View

    Front View3.2" (81)

    3.6" (91)

    FRONT PANEL

    LED Test:PressandreleasetheSILENCEandACKpushbuttonstoflashthechannelindicatorLEDsforanLEDfunctiontest.Full Function Test:PressandholdtheSILENCEandACKpushbuttonsfor3secondstoinitiateafullfunctiontest.External Connections:Allthreepushbuttonsmaybeactivated remotely via rear terminal connections.

    Button

    Description SilenceHornAcknowlege

    AlarmResetInputs

    LED DescriptionPointstatusindicatorsIndicates power is on

    PD158connectionsfor85-265VACpoweredmodel.

    DisclaimerTheinformationcontainedinthisdocumentissubjecttochangewithoutnotice.PrecisionDigitalCorporationmakes no representations or warranties with respect to the contents hereof, andspecificallydisclaimsanyimpliedwarrantiesofmerchantabilityorfitnessforaparticularpurpose.

    ©2009-2015PrecisionDigitalCorporation.Allrightsreserved.

  • MODEL PD154 & PD158 VIgILANTE® II ANNUNCIATORS

    4

    LDS158_D 12/15

    SPECIFICATIONSExceptwherenotedallspecificationsapplytooperationat+25°C.

    generalDisplay:PD154;FourredLEDchannelindicators.PD158;EightredLEDchannelindicators.OnegreenLEDpowerindicator.Alarm Messages:Customprintedadhesiveclearlabels.Area:PD154,1.25"x.60"(32mmx15mm),4messagesPD158,1.25"x.25"(32mmx6mm),8messages

    Userspecifiedsizeandlength,upto4lines(PD154)or2lines(PD158)of14charactersofsize9ptfonts.Programming Methods:Rear4-positionswitchforsequenceselection and horn operation. Three front panel pushbuttons for NO/NCinputselection,sequenceoption,andoperation.Audible Alarm:85dBinternalhorn.Noise Filter:40msdebounceoninputs,includingexternalsilence,acknowledge and reset.Shared First-Out Systems:1msunit-to-unitdelay.Maximumof200unitsinthesharedfirst-outsystem.Non-Volatile Memory:Allprogrammedsettingsarestoredinnon-volatile memory for a minimum of ten years if power is lost.Power Options:85-265VAC,50/60Hz;90-265VDC,20Wmax;or12-36VDC,12-24VAC,6Wmax.Fuse:Requiredexternalfuse:ULRecognized,5Amax,slowblow.Upto6annunciatorsmayshareone5AfuseIsolated Power Supply:24VDC±10%@200mAmaxStandardon85-265VACpoweredunitsonly.Isolation:4kVinput/output-to-powerline.Overvoltage Category:InstallationOvervoltageCategoryII:LocallevelwithsmallertransientovervoltagesthanInstallationOvervoltageCategoryIII.Environmental:Operatingtemperaturerange:-40to65°C.Storagetemperaturerange:-40to85°C.Relativehumidity:0to90%non-condensing.Connections:Removablescrewterminalblocksaccept12to22AWGwire.Enclosure:1/8DIN,highimpactplastic,UL94V-0,frontcolor:blackMounting:1/8DINpanelcutoutrequired.Twopanelmountingbrackets included.Tightening Torque:5lb-in(0.5Nm)Overall Dimensions:4.68"x2.45"x4.19"(62mmx119mmx106mm)(HxWxD)Weight:9.6oz(272g)UL File Number:E160849;508IndustrialControlEquipmentWarranty:3yearsparts&labor

    InputsInput Types: NOorNCswitches:Noexternalexcitationrequired.Open collector transistor (NPN):Opencircuitvoltageapprox.3.3VDC.LogicLevels:LOW=0to0.9VDC,HIGH=2.4to28VDCUpdate Rate:41msfollowingalarmstate;1msforalarmstateclear.Sequences:Inputfollower,ISASequencesA,F1A,F2A,F3A,M,F1M,andF3MperISAStandardISA-18.1-1979R2004.Sequence Options:A,F1A,F2A,F3A,M,F1M,F2M,andinputfollowerwithselectableoptions-1(silencepushbutton),-4(nolock-in),and-6(nohorn)perISAStandardISA-18.1-1979R2004.

    RelaysRating: 2SPDT(FormC);rated3A@30VDCor3A@250VACresistiveload;1/14HP@125/250VACforinductiveloads.Electrical Noise Suppression:Asuppressor(snubber)should be connected to each relay contact switching inductive loads to prevent disruption to the microprocessor’s operation. Recommendedsuppressorvalue:0.01µF/470Ω,250VAC(PDX6901).Relay Operation:Relay1:Alarmstateuntilalarmisacknowledged.Relay2:Alarmstateifanychannelindicatingalarm condition.Fail-Safe Operation:Programmableindependentforeachrelay.Note: In fail-safe mode, relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.

    ORDERINg INFORMATIONVigilante II • Alarm Annunciator

    85-265 VAC** Model

    12-36 VDC** Model Description

    PD154-6R2-1* PD154-7R2-0 VigilanteII4-PointAnnunciator

    PD158-6R2-1* PD158-7R2-0 VigilanteII8-PointAnnunciator

    ** AllmodelsmaybepoweredfromACorDC,seeSpecificationsfordetails.* QuickShipmentProgramproduct,typicallyshippedwithin2workingdays

    Enclosures and Accessories

    Model # of Units Description Mounting

    PDA25XX-V 1-10† PlasticNEMA4XEnclosure ThroughDoor

    PDA26XX-V 1-6† StainlessSteelNEMA4X ThroughDoor

    PDA27XX-V 1-6† SteelNEMA4Enclosure ThroughDoor

    PDA2801* 1 Low-CostPlasticNEMA4X ThroughCover

    PDX6901 Snubber0.01μF,470Ω,FlexibleLeads

    Note:XX=thelasttwodigitsofthemodelnumber†Gotowww.predig.comtofindindividualmodelnumbers.* QuickShipmentProgramproduct,typicallyshippedwithin2workingdays

    www.predig.comPrecision Digital corPoration

    1

    Your Local Distributor is:

    46, Jalan SS 22/21, Damansara Jaya, 47400 Petaling Jaya, Selangor Darul Ehsan, Malaysia Email: [email protected] access: http://www.ampmech.com