Upload
logan-batch
View
224
Download
0
Embed Size (px)
Citation preview
Visit us at www.mcscontrols.com
MCS Products
Magnum Hardware & Specification
Presentation Overview
MCS-RO10 Hardware & Specification
MCS-SI16-AO4 Hardware & Specification
MCS Sensors Specification
MCS Design Criteria
MCS Design Criteria
First Priority Quality & Service
Second Priority Cost
Third Priority Ease of Use
Engineering Design Concepts
Standard Algorithm (Flexible)
Control Status (State Machine)
Alarms (Descriptive)
Actual Compressor Amp Draw
Adjustable Setpoints
Serviceability
Suction, Discharge & Oil PSI (Calculated Oil Differential)
Engineering Design Concepts
Suction & Discharge Superheat
Graphing (Static & Dynamic)
Windows® Local & Remote Communications
Network Multiple Units at the Same Location
Expandable
10 Relay Outputs Power Input
Keypad/Display
4 Analog Outputs
4 Digital Inputs
12 Sensor Inputs Extra ½ Amp Fuse
Com
mun
icat
ions
Micro Control Systems, inc. Magnum Board
MCS-MAGNUM-PANL (12.0”w x 8.0”h x 2.0”d)
Panel MountPackage
Micro controller complete and ready to mount in a rain-proof enclosure
Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
MCS-MAGNUM-DOOR (12.0”w x 8.0”h x 2.0”d)
Door MountPackage
Micro controller complete and ready to mount in a door
Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
MCS-MAGNUM-OEM (12.0”w x 8.0”h x 2.0”d)
OEM MountPackage
Micro controller complete and ready to mount
Display / Keypad can be up to 10 feet away using 6-conductor shielded cable
Magnum Specifications 10 Relay Outputs, Fused 6.3 amps, 115/230vac
12 Sensor Inputs, Analog or Digital, 0-5vdc
4 Analog Outputs, 0 to 10vdc
System expandable to 80 RO’s, 80 SI’s, 20 AO’s
Real Time Clock with Battery Backup
Backlit Graphics Display & 9 Button Generic Keypad
4 Digital Inputs (< 0.5 vdc OFF, > 4.5 vdc ON)
Extended Temp. Range -4°F to 158°F (-20°C to 70°C )
Magnum Specifications Common, Normally Open & Normally Closed for each Relay
UL Approved
RS-232 communicates @ 19,200 baud, Modem @ 14,400 baud
MCS-I/O communicates @ 38,400 baud (RS-485)
1 RS-485 communicates @ 19,200 baud
Ethernet port @ 10/100 Mbps
BACnet IP, Modbus Johnson N2 built-in (LonTalk requires adaptor)
Optional Compact Flash Adaptor
Magnum History Specifications
Standard History Samples
With 1 g byte Flash about 1.5 months at 1 sec sample rateWith 1 g byte Flash about 7.5 years at 1 min sample rate
(Air Cooled Chiller w/2 screws, 2 circuits, 5 fans per cir, exv’s)
SAMPLE RATE # MIN DATA # HOURS DATA # DAYS DATA(SEC)
1 16.8 0.28 (1/4 hr +)
60 1008 16.80 (2/3 day +)
90 1512 25.20 (1 day +)
600 10080 168.00 (1 week)
Optional Compact Flash Adaptor
MCS-RO10 (10.87” x 4.00” x 2.50”)
10 Relay Outputs fused at 6.3 amps
1 MCS-I/O Communication (RS-485)
Extended Temperature Range -40º to 158ºF (-40°C to 70°C )
MCS-SI16-AO4 (10.87” x 4.00” x 2.50”)
16 Sensor Inputs 0-5vdc / 4 Analog Outputs 0-10vdc
1 MCS-I/O Communication (RS-485)
Extended Temperature Range -40º to 158ºF (-40°C to 70°C)
MCS-T100 (2.00”L x 0.20”Diameter)
Deep-drawn Stainless Steel Tube
Fast, 32° to 212°F (0° to 100°C) < 30 sec
± 0.36°F from 32° to 212°F (0° to 100°C)
-40.0°F to 230°F (-40° to 110°C)
Bracket available for duct mounting
20’, 40’ or 60’ cable (no breaks)
MCS-200T, MCS-500T, MCS-667T
SS with 1/4 inch female flare
Range 0 to 200 psi (0 to 13.8 bars)
Range 0 to 667 psi (0 to 46.0 bars)
Packard removable connector
20’, 40 or 60’ cable (no breaks)
Accuracy (500) ± 0.5 psi ± 0.03 bars
Accuracy (200) ± 0.2 psi ± 0.01 bars
Range 0 to 500 psi (0 to 34.5 bars)
MCS-CT300, 500 & 1500
Center hole diameter 1.00” (300)
Accuracy ± 2%
PC board on top (Eliminates potential danger)
Removable screw terminal block
Small footprint with integrated PC board
Provides protection for over & under amps
MCS-485-GATEWAY (2.50” x 3.47” x 1.04”
Converts RS-232 to RS-485
Converts RS-485 to RS-232
Nylon collar mount
Removable terminal block
MCS-WELL (TUBE)
2.5” deep drawn nickel plated brass tube
Small, fast acting
1/4”, 1/2” & 3/4” fittings on well
Tube for pipe mounting
Well for conduit installations
MCS-CRADLEPOINT
CTR500 3G/4G Mobile Broadband Router
Mobile Broadband Data Card with Active Subscription
USB or ExpressCard, or Smart Phone
Tethered Data Plan Suggested
Mobile signal at job site.
MCS Magnum Advantages Compressor EEV ( Sporlan / Alco / Siemens)
• Eliminates need for a second EEV controller
• Knows where capacity is moving, adjustment is dynamic
• Provides improved energy efficiency
• Sporlan EXV’s & Interface Boards Stocked in Florida, USA
Support for Scroll, Screws, Recip, & Centrifugal compressors
Last 30 Sensor Sample on Lockout Alarms – Info Button
Built-in BMS support for BACnet-IP, Modbus & Johnson N2
Adapter for BACnet-MSTP & Lontalk
MCS Magnum Advantages
Six Layer Printed Circuit Board
Impervious to Electrical Noise
Generic Keypad / Backlit Display
Control Algorithms Keep System Running
Warning, Safeties and Lockout System
Micro Extended Temperature Range
MCS Magnum Advantages
Windows® Based Support Systems
Control ‘STATE’ Machine
Precise Descriptive Alarms
History Graphing Static & Dynamic
High Speed Local/Remote Communications
HVAC Controls People