VM iSystem
C003674-B
Installation andService Manual
300028025-001-01
Contents
1 Introduction ................................................................................................41.1 Symbols used .......................................................4
1.2 Abbreviations ........................................................4
1.3 General ..................................................................41.3.1 Manufacturer's liability .............................................41.3.2 Installer's liability .....................................................5
1.4 Certifications .........................................................5
2 Safety instructions and recommendations ..............................................62.1 Recommendations ................................................6
3 Technical description ................................................................................73.1 Operating modes ..................................................7
3.1.1 Appliance set to VM/MR ..........................................73.1.2 Appliance set to 3WV+ ............................................73.1.3 Appliance set to OTH+3WV ....................................83.1.4 Appliance set to 0/1+V3V ........................................8
3.2 Description of the keys ........................................9
3.3 Description of the display ..................................103.3.1 Key functions .........................................................103.3.2 Flame symbol ........................................................103.3.3 Solar (If connected) ...............................................103.3.4 Operating modes ...................................................113.3.5 Domestic Hot Water override ................................113.3.6 Other information ..................................................12
3.4 Technical specifications ....................................12
4 Installation ................................................................................................134.1 Package list .........................................................13
4.2 Mounting ..............................................................13
4.3 Electrical connections ........................................144.3.1 Recommendations ................................................144.3.2 Access to the connection terminal ........................144.3.3 Description of the connection terminal block .........15
1 19/03/2012 - 300028025-001-01
4.4 Installation and connection examples - Applianceset to VM/MR .......................................................164.4.1 VM iSystem module networked with one or more
generators equipped with a DIEMATIC controlpanel .....................................................................16
4.5 Installation and connection examples - Applianceset to 3WV+ .........................................................184.5.1 Independent control system ..................................184.5.2 VM iSystem module networked with one or more
generators equipped with a DIEMATIC-m3 /DIEMATIC iSystem control panel ..........................25
4.5.3 VM iSystem module controlling a gas absorption heatpump (PGA) ..........................................................26
4.6 Installation and connection examples - Applianceset to OTH+3WV ..................................................274.6.1 Independent control system ..................................274.6.2 Cascade of boilers equipped with OTH bus ..........35
4.7 Installation and connection examples - Applianceset to 0/1+V3V .....................................................394.7.1 Independent control system ..................................394.7.2 Slave control system in cascade ...........................45
5 Operating the appliance ..........................................................................475.1 Powering up for the first time ............................47
5.2 Access to the various browsing levels .............485.2.1 User level ..............................................................485.2.2 Installer level .........................................................485.2.3 After Sales level ....................................................49
5.3 Browsing in the menus ......................................49
5.4 Reading out measured values ...........................50
5.5 Settings after powering up for the firsttime ......................................................................515.5.1 Displaying the parameters in extended
mode .....................................................................515.5.2 Setting the parameters specific to the
installation .............................................................525.5.3 Naming the circuits and generators ......................545.5.4 Setting the heating curve ......................................55
5.6 Changing the settings ........................................575.6.1 Language selection ...............................................575.6.2 Defining the configuration mode ...........................585.6.3 Calibrating the sensors .........................................585.6.4 Professional settings .............................................595.6.5 Configuring the network ........................................665.6.6 Return to the factory settings ................................69
Contents
2 19/03/2012 - 300028025-001-01
6 Switching off the appliance .....................................................................716.1 Installation shutdown .........................................71
6.2 Frost protection ..................................................71
7 Troubleshooting .......................................................................................727.1 Installer's contact details ...................................72
7.2 Messages (type code Mxx) ................................73
7.3 Message history ..................................................73
7.4 Faults ...................................................................747.4.1 Deletion of sensors from the memory in the
PCB .......................................................................76
7.5 Failure history .....................................................77
7.6 Parameter and input/output check (modetests) ....................................................................77
3 19/03/2012 - 300028025-001-01
1 Introduction
1.1 Symbols used
In these instructions, various danger levels are employed to draw theuser's attention to particular information. In so doing, we wish tosafeguard the user's safety, obviate hazards and guarantee correctoperation of the appliance.
DANGER
Risk of a dangerous situation causing serious physicalinjury.
WARNING
Risk of a dangerous situation causing slight physicalinjury.
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in theinstructions.
1.2 Abbreviations
4 DHW: Domestic hot water4 3WV: 3-way valve
1.3 General
1.3.1. Manufacturer's liability
Our products are manufactured in compliance with the requirementsof the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
VM iSystem 1. Introduction
19/03/2012 - 300028025-001-01 4
In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the followingcases:
4 Failure to abide by the instructions on using the appliance.4 Faulty or insufficient maintenance of the appliance.4 Failure to abide by the instructions on installing the appliance.
1.3.2. Installer's liability
The installer is responsible for the installation and inital start up of theappliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals providedwith the appliance.
4 Carry out installation in compliance with the prevailing legislationand standards.
4 Perform the initial start up and carry out any checks necessary.4 Explain the installation to the user.4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.4 Give all the instruction manuals to the user.
1.4 Certifications
This product complies to the requirements to the european directivesand following standards:
4 2006/95/EC Low Voltage Directive. Reference Standard:EN60.335.1.
4 2004/108/EC Electromagnetic Compatibility Directive. Genericstandards: EN1000-6-3 , EN 61000-6-1.
1. Introduction VM iSystem
5 19/03/2012 - 300028025-001-01
2 Safety instructions andrecommendations
2.1 Recommendations
WARNING
Only qualified professionals are authorised to work on theappliance and the installation.
The appliance should be on Summer or Antrifreeze mode rather thanswitched off to guarantee the following functions:
4 Anti blocking of pumps.4 Frost protection.
VM iSystem 2. Safety instructions and recommendations
19/03/2012 - 300028025-001-01 6
3 Technical description
3.1 Operating modes
3.1.1. Appliance set to VM/MR
VM iSystem module networked with one or more generatorsequipped with a DIEMATIC control panel
VM iSense Pro module networked with one or more generatorsequipped with a DIEMATIC / iSense Pro control panel
4 Primary circuit control.4 Circuits B, C, DHW and AUX available.4 Does not require an outside temperature sensor.4 1 to 20VM iSystem modules + 1 to 10 generators equipped with a
DIEMATIC control panel.4 DHW priority is only activated on the secondary circuits connected
to the same VM iSystem module
3.1.2. Appliance set to 3WV+
Independent control system
4 No primary circuit control.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.VM iSystem module networked with one or more generatorsequipped with a DIEMATIC-m3 / DIEMATIC iSystem control panel
4 Primary circuit control.4 Circuits B, C, DHW and AUX available.4 Does not require an outside temperature sensor.4 1 to 10VM iSystem modules configured as 3WV+ or generators
equipped with a DIEMATIC control panel + 20VM iSystemmodules configured as VM/MR.
4 DHW priority is activated on all of the system's secondary circuits.VM iSystem module controlling a gas absorption heat pump(PGA)
4 Control of one gas absorption heat pump.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.
Generator
equipped with
DIEMATIC (Master)
VM iSystemNumber 20
Bus VM iSystem
Number 39
C00
3723
-A-0
4
Generator equipped with DIEMATIC /
iSense Pro (Master)
VM iSense Pro
Number 20
VM iSense Pro
Number 39
Bus
C00
3776
-A-0
4
VM iSystem
C00
3722
-A
Generator equipped with
DIEMATIC-m3 / DIEMATIC iSystem
(Master)
VM iSystemNumber 2
Bus VM iSystemNumber 10
C00
3724
-A-0
4
VM iSystem
Master
PGA mit RS485/RS432
interfaceNumber 2
PGA mit RS485/RS432
interfaceNumber 10
Bus
C00
3725
-A-0
4
3. Technical description VM iSystem
7 19/03/2012 - 300028025-001-01
4 VM iSystem module configured as bus master.4 1 to 10 groups of 3 gas absorption heat pumps.
3.1.3. Appliance set to OTH+3WV
Independent control system
4 ON/OFF and temperature control of the boiler.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.
Cascade of boilers equipped with OTH bus
4 ON/OFF and temperature control of the boiler.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.4 1 to 10VM iSystem modules configured as OTH+3WV or
generators equipped with a DIEMATIC-m3 / DIEMATIC iSystemcontrol panel or an OTH MODBUS interface + 20VM iSystemmodules configured as VM/MR.
4 DHW priority is activated on all of the system's secondary circuits.
3.1.4. Appliance set to 0/1+V3V
Independent control system
4 Control of the boiler with an ON/OFF inlet.4 Circuits B, C and DHW available.4 S.AUX used for the ON/OFF command.4 The LAUX outlet provides 230V.4 Requires an outside temperature sensor.Slave control system in cascade
4 Circuits B, C and DHW available.4 S.AUX used for the ON/OFF command.4 Does not require an outside temperature sensor.4 The VM iSystem module is always a slave in a cascade
installation.4 DHW priority is activated on all of the system's secondary circuits.
VM iSystem
Boiler equipped
with a OTH bus
OTH
C00
3726
-A-0
4
VM iSystem - Number 2
or
Modbus/OTH interface
VM iSystem - Number 10
or
Modbus/OTH interface
OTH
VM iSystemMaster
Boiler equipped
with a OTH bus
Boiler equipped
with a OTH bus
Boiler equipped
with a OTH bus
OTH
Bus
OTH
C00
3727
-A-0
4
VM iSystem
Boiler
0/1
C00
3728
-A-0
4
Generator equipped with
DIEMATIC-m3 / DIEMATIC iSystem
(Master)
VM iSystemNumber 2
Bus VM iSystemNumber 10
Boiler Boiler
0/1 0/1
C00
3729
-A-0
4
VM iSystem 3. Technical description
19/03/2012 - 300028025-001-01 8
3.2 Description of the keys
A Temperature setting key (heating, DHW, swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button:
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the menu selectedor confirm a value modification
G Button AUTO/MANUH FuseJ Button ON/OFF
C003672-B
bar
STD
0 2 4 6 8 10 12 14 16 18 22 2420
AUTO
A
B
C
D E F
J
H
G
3. Technical description VM iSystem
9 19/03/2012 - 300028025-001-01
3.3 Description of the display
3.3.1. Key functions
> Access to the various menus
( Used to scroll through the menus
' Used to scroll through the parameters? The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
3.3.2. Flame symbol
4 The symbol is displayed: The burner is operating.4 The symbol is not displayed: The burner is off.
3.3.3. Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
bar
r
STD( ' t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
VM iSystem 3. Technical description
19/03/2012 - 300028025-001-01 10
3.3.4. Operating modes
p Summer mode: The heating is off. Domestic hot watercontinues to be produced
b WINTER mode: Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode: The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol: Temporary override4 Steady symbol: Permanent override
m Reduced mode: The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol: Temporary override4 Steady symbol: Permanent override
g Holiday mode: The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol: Holiday mode programmed4 Steady symbol: Holiday mode active
m Manual mode
3.3.5. Domestic Hot Water override
A bar is displayed when a DHW override is activated:
4 Flashing bar: Temporary override4 Steady bar: Permanent override
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420C002698-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
3. Technical description VM iSystem
11 19/03/2012 - 300028025-001-01
3.3.6. Other information
r The symbol is displayed when domestic hot waterproduction is running.
w Valve indicator: The symbol is displayed when a 3-wayvalve is connected.
4 x : 3-way valve opens4 c : 3-way valve closes
M The symbol is displayed when the pump is operating.
Name of the circuit for which the parameters aredisplayed.
3.4 Technical specifications
4 Electricity supply: 230 V - 50 Hz4 Output: 10 - 1450 W
Outside sensorTemperature in °C -20 -16 -12 -8 -4 0 4 8 12 16 20 24Resistance in Ω 2392 2088 1811 1562 1342 1149 984 842 720 616 528 454
Outlet sensor circuit B+CDomestic hot water sensorSystem sensorTemperature in °C 0 10 20 25 30 40 50 60 70 80 90Resistance in Ω 32014 19691 12474 10000 8080 5372 3661 2535 1794 1290 941
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002699-B
pb AUTOx c rjMg m
VM iSystem 3. Technical description
19/03/2012 - 300028025-001-01 12
4 Installation
4.1 Package list
The delivery includes:
4 The VM iSystem module4 Quick installation guide4 USB key with the installation and service manual and the user
guide
4.2 Mounting
The VM iSystem module can be affixed to the wall or in an electricalcabinet.
1. Drill 3 holes.(1) Drilling template
2. Affix the module.3. Open the protective hood.4. Secure the unit with the 3 screws.
CAUTION
4 Do not fit a power relay or a power circuit at a distanceof less than 10 cm from the box.
4 Failure to comply with these instructions could leadto interference and control unit malfunctioning oreven damage to the electronic circuitry.
C003570-C
(1)
4. Installation VM iSystem
13 19/03/2012 - 300028025-001-01
4.3 Electrical connections
4.3.1. Recommendations
WARNING
4 Only qualified professionnals may carry out electricalconnections, always with the power off.
4 The appliance is fully pre-wired. Do not modify theconnections inside the control panel.
4 Earth the appliance before making any electricalconnections.
Make the electrical connections of the appliance according to:
4 The instructions of the prevailing standards.4 The instructions on the electrical diagrams provided with the
boiler.4 The recommendations in the instructions.
CAUTION
4 Separate the sensor cables from the 230 V cables.4 Use 2 pipes or cable guides at least 10 cm apart.4 Keep to the polarity shown on the terminals: phase
(L), neutral (N) and earth *.
CAUTION
Failure to comply with these instructions could lead tointerference and control unit malfunctioning or evendamage to the electronic circuitry.
4.3.2. Access to the connection terminal
1. Unscrew the 2 screws.2. Open the protective hood.
C003571-B
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 14
4.3.3. Description of the connection terminalblock
Connecting the BUS cascadeBUS cable - Package AD124 / AD134 / DB119
S.SYST System sensor - Package AD250
CDI C O Remote control (Circuit C) - Package AD254 / AD285 r BF DHW sensor - Package AD212CDI B / CDR Remote control (Circuit B) - Package AD254 / AD285
Radio remote control - Circuit B/C - Package AD253 /AD284
I AF Outside sensor - Package FM46Outside radio-controlled temperaturesensor - Package AD251
kC C Outlet sensor circuit C - Package AD199 0-10 V / E.TEL Inlet 0-10 Voltsvoice remote monitoring module -Package AD152
kC B Outlet sensor circuit B - Package AD199 OT OpenTherm
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
N L
ALIM
230V/50Hz
C003567-C
L C Heating pump circuit C A B 3 way valve circuit BCS Safety contact - Factory fitted bridge(1) Lr D.H.W. load pumpA C 3 way valve circuit C L AUX Auxiliary pumpL B Heating pump circuit B ALIM 230 V/50Hz Electricity supplyCS Safety contact - Factory fitted bridge(1) (1) If using underfloor heating, remove the bridge CS and connect a safety thermostat.
To connect a wire to the terminal block, proceed as follows:
1. Strip 8 mm of wire.Maximum cross section of the wire: 1.5 mm2
2. Press the spring in the terminal block with a screwdriver.3. Insert the wire into the terminal block.
OT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003730-A
N
M
B
N
L
LAUX
N
LALIM
230V/50H
z
1
2 L000577-A
4. Installation VM iSystem
15 19/03/2012 - 300028025-001-01
4.4 Installation and connection examples - Appliance set to VM/MR
4.4.1. VM iSystem module networked with one ormore generators equipped with aDIEMATIC control panel
n Connecting 2 x 2 valve circuits and a DHW tank
DHW priority is only activated on the secondarycircuits connected to the same VM iSystemmodule.
A Master boiler equipped with a Diematic 3 / Diematic m3 /Diematic iSystem / Diematic m-Delta control panel
Z Secondary boiler
E Low loss header
R BUS cable
T 3 way valve circuit B
Y Heating pump circuit B
U Outlet sensor circuit B
I Heating circuit B
O 3 way valve circuit C
P Heating pump circuit C
a Outlet sensor circuit C
z Heating circuit C
e D.H.W. load pump
r DHW sensor (Package AD212)
t DHW storage tank
4
1
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
17
1 2
3
4
4
5
6
7
9
10
11
128
13
15
14
16
5
6
7
9
10
11
128
13
15
14
16
N°1 N°2
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
17
C003689-D
VM N°20
VM N°21
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 16
y Domestic circulation loop pump (Optional)
u Outside temperature sensor (optional) for control perzone. Otherwise, the outside temperature of the boilertaken into account.
4 It is possible to connect up to 20 appliancesconfigured as VM/MR (address of 20 to 39).
4 Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installation: Appliance set to VM/MRParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode",
page 51VM NUMBER Installer level
Menu #NETWORK20, 21, 22, ... ¼ "Configuring the network", page 66
¼ For setting master and slave boilers, refer to the boiler'sinstallation and service manual.
n Connecting the options
For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank
N L
CSC
N
M C
N L
CSB
N
M B
N NL L
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
V
PRG
TELCOM 2
ALPAL2AL1
321
SET#09
V8765
4321 4
3
5
1
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
2
C003688-B
A Connect the remote control (Package AD254/FM52).
Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).
E Connect the DHW sensor of the second tank.
R Second domestic hot water tank.
T Connect the load pump of the second tank.
4. Installation VM iSystem
17 19/03/2012 - 300028025-001-01
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 51If second tank connected:S.AUX:(1)
Installer levelMenu #SYSTEM
DHW ¼ "Setting the parameters specificto the installation", page 52
If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parameters specificto the installation", page 52
If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
ANTIFR ¼ "Setting the parameters specificto the installation", page 52
I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
CTC.I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
4.5 Installation and connection examples - Appliance set to 3WV+
4.5.1. Independent control system
n 1 mixed heating circuit
2
4
6
3
7
1
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003684-C
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 18
Y Primary
U Connect a safety thermostat if the heating circuit is forunderfloor heating
Earth the various pumps and 3-way valves.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
n 2 mixed heating circuits and 1 DHW circuit
12
14
13
11
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
107
8
9
2
4
6
3
1
C003685-D
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Primary
U DHW storage tank
I DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
O Domestic circulation loop pump (Optional)
P D.H.W. load pump
a 3 way valve circuit C
z Heating pump circuit C
4. Installation VM iSystem
19 19/03/2012 - 300028025-001-01
e Outlet sensor circuit C
r Heating circuit C
If using underfloor heating, remove the bridge CS andconnect a safety thermostat.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
CIRC.CURVE C Installer levelMenu #SECONDARY INSTAL.P
To be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. C Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
S.AUX Installer levelMenu SYSTEM
DHW LOOP ¼ "Setting the parameters specific to theinstallation", page 52
n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit
12
14
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
107
8
9
2
4
6
3
1
C003733-B
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Primary
U DHW storage tank
I DHW sensor
O Domestic circulation loop pump (Optional)
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 20
P D.H.W. load pump
z Heating pump circuit C
r Heating circuit C
If using underfloor heating, remove the bridge CS andconnect a safety thermostat.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters
in extended mode", page 51CIRC.CURVE B Installer level
Menu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings",page 59
If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)
Installer levelMenu #SYSTEM
DIRECT ¼ "Setting the parametersspecific to the installation", page52
CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
n Pool connection
N L
CSC
N
M C
N L
CSB
N
M B
N L L N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
44
1
35
2
C003686-B
A Connect the secondary swimming pool pump.
Z Connect the swimming pool sensor.
E Plate heat exchanger.
R Pool heating cut-off control
When the parameter I.TEL: or S.SYST is set to0/1 B, the swimming pool is no longer heatedwhen the contact is open (factory setting); onlythe antifreeze function continues to run.The contact direction can still be adjusted withparameter CT.TEL or CT.SYST.
T Connect the primary swimming pool pump.
4. Installation VM iSystem
21 19/03/2012 - 300028025-001-01
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the
parameters in extendedmode", page 51
MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS
Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger
¼ "Professional settings",page 59
CIRC. B:(1) Installer levelMenu #SYSTEM
SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
0/1 B ¼ "Setting the parametersspecific to the installation",page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
Controlling the pool circuit
The control system can be used to manage a swimming pool circuitin both cases:
Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.
4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -
39°C.
Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.
The swimming pool can also be connected to circuit C:
4 Make the connection to the terminal blocks markedC.
4 Set the parameters for circuit C.
Hourly programming of the secondary circuit pump
The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 22
To prepare your pool for winter, consult your pool specialist.
n Connecting a mixed tank
A Connect the electric tank
Z Power control relay to the electrical resistor
E DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
R Connect the outside temperature sensor
T D.H.W. load pump
Y Primary
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page
51S.AUX:(1) Installer level
Menu #SYSTEMDHW ELEC ¼ "Setting the parameters specific to the installation",
page 52(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
n Connecting the options
For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank
N L
CSC
N
M C
N L
CSB
N
M B
N NL L
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
3
5
6
41
2
C003687-C
4. Installation VM iSystem
23 19/03/2012 - 300028025-001-01
N L
CSC
N
M C
N L
CSB
N
M B
N NL L
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
V
PRG
TELCOM 2
ALPAL2AL1
321
SET#09
V8765
4321 4
3
5
1
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
2
C003688-B
A Connect the remote control (Package AD254/FM52).
Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).
E Connect the DHW sensor of the second tank.
R Second domestic hot water tank.
T Connect the load pump of the second tank.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 51If second tank connected:S.AUX:(1)
Installer levelMenu #SYSTEM
DHW ¼ "Setting the parameters specificto the installation", page 52
If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parameters specificto the installation", page 52
If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
ANTIFR ¼ "Setting the parameters specificto the installation", page 52
I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
CTC.I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
4.5.2. VM iSystem module networked with one ormore generators equipped with a
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 24
DIEMATIC-m3 / DIEMATIC iSystem controlpanel
n Connecting 2 x 2 valve circuits and a DHW tank
DHW priority is activated on all of the system'ssecondary circuits.
A Master boiler equipped with a Diematic m3 / DiematiciSystem control panel
Z Secondary boiler
E Low loss header
R BUS cable
T 3 way valve circuit B
Y Heating pump circuit B
U Outlet sensor circuit B
I Heating circuit B
O 3 way valve circuit C
P Heating pump circuit C
a Outlet sensor circuit C
z Heating circuit C
e D.H.W. load pump
r DHW sensor (Package AD212)
t DHW storage tank
y Domestic circulation loop pump (Optional)
u Outside temperature sensor (optional) for control perzone. Otherwise, the outside temperature of the boilertaken into account.
4
1
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
17
1 2
3
45
6
7
9
10
11
128
13
15
14
16
5
6
7
9
10
11
128
13
15
14
16
4
N°1 N°2
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
17
C003734-D
VM N°3
VM N°4
4. Installation VM iSystem
25 19/03/2012 - 300028025-001-01
Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
OFF
SLAVE NUMBER(1) Installer levelMenu #SYSTEM
2, 3, ...
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4.5.3. VM iSystem module controlling a gasabsorption heat pump (PGA)
n 1 mixed heating circuit and 1 DHW circuit
7
8
9
2
4
6
232 485
3
1 10
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003749-D
11
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Gas absorption heat pump
U DHW storage tank
I DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
O Domestic circulation loop pump (Optional)
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 26
P D.H.W. load pump
a RS232 / RS485 interface (Package AD277)
Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
ON
SYSTEM NETWORK(1) Installer levelMenu #SYSTEM
ADD SLAVE
PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4.6 Installation and connection examples - Appliance set to OTH+3WV
4.6.1. Independent control system
n 1 mixed heating circuit
2
4
6
3
1
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
OT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003736-C
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor (optional)
Y Boiler with OpenTherm inlet
4. Installation VM iSystem
27 19/03/2012 - 300028025-001-01
4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for
underfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
n 2 mixed heating circuits and 1 DHW circuit
12
14
13
11
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L N N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
107
8
9
2
4
6
15
3
1
C003737-B
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Primary
U DHW storage tank
I DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
O Domestic circulation loop pump (Optional)
P D.H.W. load pump
a 3 way valve circuit C
z Heating pump circuit C
e Outlet sensor circuit C
r Heating circuit C
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 28
t Boiler's OT terminal block
Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit
12
14
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
107
8
9
2
4
6
3
115
C003738-C
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Primary
U DHW storage tank
I DHW sensor
O Domestic circulation loop pump (Optional)
P D.H.W. load pump
z Heating pump circuit C
r Heating circuit C
t Boiler's OT terminal block
4. Installation VM iSystem
29 19/03/2012 - 300028025-001-01
4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for
underfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters
in extended mode", page 51CIRC.CURVE B Installer level
Menu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings",page 59
If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)
Installer levelMenu #SYSTEM
DIRECT ¼ "Setting the parametersspecific to the installation", page52
CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
n Hot water storage tank connection
QUADRO DU storage tankIn this installation example, the storage tank (type QUADRO DU)incorporates a domestic hot water zone. The boiler starts upsystematically to maintain the domestic hot water zone in the storagetank or to maintain the independent tank at temperature.
N L
CSC
N
M C
N L
CSB
N
M B
N L L N N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003739-A
3
4
5
7
6
21
M
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 30
This type of installation only works if the boilerincorporates a boiler pump managed by theboiler regulator.
A Boiler regulator
Z Connect the heating pump (Circuit B).
E DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
R Connect the sensor from the storage tank (PackageAD250).
T Buffer tank.
Y Solar sensor probe.
U Connect the solar station to the solar collectors.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 51I.SYST Installer level
Menu #SYSTEMSTORAGE TANK ¼ "Setting the parameters specific to
the installation", page 52If circuit B is a direct circuit without aflow sensor:CIRC. B:(1)
Installer levelMenu #SYSTEM
DIRECT ¼ "Setting the parameters specific tothe installation", page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensorT falls -6°C below the calculated set temperature.Reheating in the heating zone stops when the heatingbuffer temperature rises above the calculated settemperature.
n Pool connection
N L
CSC
N
M C
N L
CSB
N
M B
N L L N
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
44
1
35
2
C003686-B
4. Installation VM iSystem
31 19/03/2012 - 300028025-001-01
A Connect the secondary swimming pool pump.
Z Connect the swimming pool sensor.
E Plate heat exchanger.
R Pool heating cut-off control
When the parameter I.TEL: or S.SYST is set to0/1 B, the swimming pool is no longer heatedwhen the contact is open (factory setting); onlythe antifreeze function continues to run.The contact direction can still be adjusted withparameter CT.TEL or CT.SYST.
T Connect the primary swimming pool pump.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the
parameters in extendedmode", page 51
MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS
Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger
¼ "Professional settings",page 59
CIRC. B:(1) Installer levelMenu #SYSTEM
SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
0/1 B ¼ "Setting the parametersspecific to the installation",page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
Controlling the pool circuit
The control system can be used to manage a swimming pool circuitin both cases:
Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.
4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -
39°C.
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 32
Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.
The swimming pool can also be connected to circuit C:
4 Make the connection to the terminal blocks markedC.
4 Set the parameters for circuit C.
Hourly programming of the secondary circuit pump
The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping
To prepare your pool for winter, consult your pool specialist.
n Connecting a mixed tank
A Connect the electric tank
Z Power control relay to the electrical resistor
E DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
R Connect the outside temperature sensor
T D.H.W. load pump
Y Primary
U Boiler's OT terminal block
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
3
5
6
7
41
2
C003740-C
4. Installation VM iSystem
33 19/03/2012 - 300028025-001-01
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page
51S.AUX:(1) Installer level
Menu #SYSTEMDHW ELEC ¼ "Setting the parameters specific to the installation",
page 52(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
n Connecting the options
For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank
N L
CSC
N
M C
N L
CSB
N
M B
N NL L
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
V
PRG
TELCOM 2
ALPAL2AL1
321
SET#09
V8765
4321 4
3
5
1
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
MODE
0 2 4 6 8 10 12 14 16 18 22 2420
2
C003688-B
A Connect the remote control (Package AD254/FM52).
Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).
E Connect the DHW sensor of the second tank.
R Second domestic hot water tank.
T Connect the load pump of the second tank.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 51If second tank connected:S.AUX:(1)
Installer levelMenu #SYSTEM
DHW ¼ "Setting the parameters specificto the installation", page 52
If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parameters specificto the installation", page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 34
Settings to be made for this type of installationParameters Access Settings to be made See chapterIf a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
ANTIFR ¼ "Setting the parameters specificto the installation", page 52
I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
CTC.I.SYST Installer levelMenu #SYSTEM
To be customised ¼ "Setting the parameters specificto the installation", page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
4.6.2. Cascade of boilers equipped with OTH bus
n Boiler cascade equipped with VM iSystem
DHW priority is activated on all of the system'ssecondary circuits.
A Master boiler equipped with a OpenTherm control panel
Secondary boiler
Z Low loss header
E BUS cable to make the link between boilers
R 3 way valve circuit B
T Heating pump circuit B
Y Outlet sensor circuit B
U Heating circuit B
I 3 way valve circuit C
O Heating pump circuit C
3
1
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
1617
1 1
2
34
5
6
8
9
10
117
12
14
13
15
4
5
6
8
9
10
117
12
14
13
15
N°1 N°2
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
16
C003741-C
VM N°1
VM N°2
4. Installation VM iSystem
35 19/03/2012 - 300028025-001-01
P Outlet sensor circuit C
a Heating circuit C
z D.H.W. load pump
e DHW sensor (Package AD212)
r DHW storage tank
t Domestic circulation loop pump (Optional)
y Outside sensor (Optional)
u System sensor
Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installation: VM iSystem master moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
ON
SYSTEM NETWORK(1) Installer levelMenu #SYSTEM
ADD GENE MANU
PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
OFF
SLAVE NUMBER(1) Installer levelMenu #SYSTEM
2, 3, ...
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 36
n Cascade of one boiler equipped with VM iSystem andone boiler equipped with an OTH Modbus interfaceboard
DHW priority is activated on all of the system'ssecondary circuits.
A Master boiler equipped with a OpenTherm control panel
Secondary boiler
Z Low loss header
E BUS cable to make the link between boilers
R 3 way valve circuit B
T Heating pump circuit B
Y Outlet sensor circuit B
U Heating circuit B
I 3 way valve circuit C
O Heating pump circuit C
P Outlet sensor circuit C
a Heating circuit C
z D.H.W. load pump
e DHW sensor (Package AD212)
r DHW storage tank
t Domestic circulation loop pump (Optional)
y Outside sensor (Optional)
u OTH Modbus interface board (Package AD286 / AD287)
u System sensor
1
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
OTBUS
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
16
17
17
1 1
2
34
5
6
8
9
10
117
12
14
13
15
N°1 N°2
C003742-E
VM N°1
4. Installation VM iSystem
37 19/03/2012 - 300028025-001-01
Connect a safety thermostat if the heating circuit is forunderfloor heating.
Settings to be made for this type of installation: VM iSystem master moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
ON
SYSTEM NETWORK(1) Installer levelMenu #SYSTEM
ADD SLAVE
PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
OFF
SLAVE NUMBER(1) Installer levelMenu #SYSTEM
2, 3, ...
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 38
4.7 Installation and connection examples - Appliance set to 0/1+V3V
4.7.1. Independent control system
n 1 mixed heating circuit
2
4
6
8
7
3
1
5
N L
CSC
N
M C
N
N
L
L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
C003743-C
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Boiler
U Boiler control at 230 V
I System sensor used as boiler sensor
CAUTION
The VM iSystem module does not fulfil the boiler'soverheating safety functions.
4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for
underfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
4. Installation VM iSystem
39 19/03/2012 - 300028025-001-01
n 2 mixed heating circuits and 1 DHW circuit
13
15
14
12
10
11
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
9
2
4
3
1
6
8
7
N
L
C003744-D
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Boiler
U Boiler control at 230 V
I System sensor used as boiler sensor
O DHW storage tank
P DHW sensor (Package AD212)
Do not use the simulation connector delivered with theDHW sensor.
a D.H.W. load pump
z 3 way valve circuit C
e Heating pump circuit C
r Outlet sensor circuit C
t Heating circuit C
CAUTION
The VM iSystem module does not fulfil the boiler'soverheating safety functions.
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 40
4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for
underfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level
Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
CIRC.CURVE C Installer levelMenu #SECONDARY INSTAL.P
To be customised ¼ "Setting the heating curve", page 55
MAX. CIRC. C Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings", page 59
n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit
12
13
5
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
9
10
11
2
4
3
1
6
7
N
L
8
C003745-C
A 3 way valve circuit B
Z Heating pump circuit B
E Outlet sensor circuit B
R Heating circuit B
T Outside sensor
Y Boiler
U Boiler control at 230 V
I System sensor used as boiler sensor
O DHW storage tank
P DHW sensor
a D.H.W. load pump
z Heating pump circuit C
4. Installation VM iSystem
41 19/03/2012 - 300028025-001-01
e Heating circuit C
CAUTION
The VM iSystem module does not fulfil the boiler'soverheating safety functions.
4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for
underfloor heating.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters
in extended mode", page 51CIRC.CURVE B Installer level
Menu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS
To be customised ¼ "Professional settings",page 59
If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)
Installer levelMenu #SYSTEM
DIRECT ¼ "Setting the parametersspecific to the installation", page52
CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P
To be customised ¼ "Setting the heating curve",page 55
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.
n Pool connection
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
L
N
4
1
35
2
6
7
8
C003746-C
A Connect the secondary swimming pool pump.
Z Connect the swimming pool sensor.
E Plate heat exchanger.
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 42
R Pool heating cut-off control
When the parameter I.TEL: is on 0/1 B, theswimming pool is no longer heated when thecontact is open (factory setting), only theantifreeze continues to be active.The contact direction can still be adjusted by theparameter CT.TEL.
T Connect the primary swimming pool pump.
Y Boiler
U Boiler control at 230 V
I System sensor used as boiler sensor
CAUTION
The VM iSystem module does not fulfil the boiler'soverheating safety functions.
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the
parameters in extendedmode", page 51
MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS
Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger
¼ "Professional settings",page 59
CIRC. B:(1) Installer levelMenu #SYSTEM
SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parametersspecific to the installation",page 52
If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)
Installer levelMenu #SYSTEM
0/1 B ¼ "Setting the parametersspecific to the installation",page 52
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
Controlling the pool circuit
The control system can be used to manage a swimming pool circuitin both cases:
Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.
4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -
39°C.
4. Installation VM iSystem
43 19/03/2012 - 300028025-001-01
Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.
The swimming pool can also be connected to circuit C:
4 Make the connection to the terminal blocks markedC.
4 Set the parameters for circuit C.
Hourly programming of the secondary circuit pump
The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping
To prepare your pool for winter, consult your pool specialist.
n Connecting the options
For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank
N L
CSC
N
M C
N L
CSB
N
M B
N NL L
AUX
N L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
V
PRG
TELCOM 2
ALPAL2AL1
321
SET#09
V8765
4321
1
MODE r
x 0 2 4 6 8 10 12 14 16 18 22 2420
c
MODE r
x 0 2 4 6 8 10 12 14 16 18 22 2420
c
2
C003831-A
A Connect the remote control (Package AD254/FM52).
Z Connect the TELCOM remote vocal monitoring module.
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 44
Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in
extended mode", page 51If a remote monitoring module is connectedto the 0-10V inlet on the terminal block:IN 0-10V
Installer levelMenu #SYSTEM
NO ¼ "Setting the parametersspecific to the installation", page52
If a remote monitoring module is connectedto the 0-10V inlet on the terminal block:I.TEL:(1)
Installer levelMenu #SYSTEM
ANTIFR ¼ "Setting the parametersspecific to the installation", page52
(1) The parameter is only displayed if the parameter IN 0-10V is set to OFF.
4.7.2. Slave control system in cascade
n Connecting 2 x 2 valve circuits and a DHW tank
DHW priority is activated on all of the system'ssecondary circuits.
A Master boiler equipped with a Diematic 3 / Diematic m3 /Diematic iSystem control panelMaster boiler equippedwith a Diematic 3 / Diematic m3 / iSense Pro control panel
Secondary boiler
Z Low loss header
E BUS cable
R 3 way valve circuit B
T Heating pump circuit B
Y Outlet sensor circuit B
U Heating circuit B
I 3 way valve circuit C
1
N L
CSC
N
M C
N L
CSB
N
M B
N L L
AUX
NN L
ALIM
230V/50HzOT
0V +
AFBF0-10V/
E.TELS.SYST
C BCDI C CDI B/
CDR
15
16
17
1 1
16
2
4
5
3
6
8
9
10
117
12
14
13N°1 N°2
C003747-D
VM N°2
4. Installation VM iSystem
45 19/03/2012 - 300028025-001-01
O Heating pump circuit C
P Outlet sensor circuit C
a Heating circuit C
z D.H.W. load pump
e DHW sensor (Package AD212)
r DHW storage tank
t Outside sensor (Optional)
y System sensor used as boiler sensor
u Boiler control at 230 V
Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level
Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended
mode", page 51CASCADE:(1) Installer level
Menu #NETWORKON ¼ "Configuring the network", page 66
MASTER CONTROLLER(1) Installer levelMenu #SYSTEM
OFF
SLAVE NUMBER(1) Installer levelMenu #SYSTEM
2, 3, ...
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
VM iSystem 4. Installation
19/03/2012 - 300028025-001-01 46
5 Operating the appliance
5.1 Powering up for the first time
1. Press the spring-loaded tab to open the protective cover.2. Press button ON.3. Press button AUTO.4. The first time the boiler is powered up, the LANGUAGE menu is
displayed. Select the desired language by turning the rotarybutton.
5. To confirm, press the rotary button.6. Set parameter CONFIGURATION. Select the desired setting:
Setting DescriptionVM/MR Operation with all Diematic control systems - No DHW priority.
If CONFIGURATION parameter is set to VM/MR:
1. Press key - for around 5 seconds.2. Select the menu #SYSTEM.3. Set the parameter INSTALLATION to EXTENDED.4. Select the menu #NETWORK.5. Select the parameter VM NUMBER.6. Assign a code (from 20 to 39) to the appliance. The codes
assigned to the devices must always be done in increasingorder starting with 20 and without omitting any numbers.Never assign the same code to 2 different VM iSystemcontrol systems.
3WV+ Operation with Diematic-m 3 - Diematic iSystem controlsystems - DHW priority available.
0/1+V3V Control for an ON/OFF generatorOTH+3WV Control for a generator by BUS OpenTherm
7. To confirm, press the rotary button.8. Insert the 2 screws (provided in the documentation bag) at the
front of the module to guarantee protection rating IP21.
C003569-A
Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
ÿLANGUE FRANCAIS
C002286-C
C003568-D
5. Operating the appliance VM iSystem
47 19/03/2012 - 300028025-001-01
5.2 Access to the various browsing levels
5.2.1. User level
The information and settings in the User level can be accessed byeveryone.
1. Press the > key.
5.2.2. Installer level
The information and settings in the Installer level can be accessed byexperienced people.
1. Press the > key.
2. Press the - key.
It is also possible to access the installer level by pressingonly the - key for around 5 seconds.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP.: 68°
C002271-F-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 48
5.2.3. After Sales level
The information and settings in the After Sales level can be accessedby initiates.
1. Press the > key.
2. Press key - for around 5 seconds.
It is also possible to access the After Sales level bypressing only the - key for around 10 seconds.
5.3 Browsing in the menus
1. To select the desired menu, turn the rotary button.2. To access the menu, press the rotary button.
To go back to the previous display, press the key j.
3. To select the desired parameter, turn the rotary button.4. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
#MEASURES
#CHOICE TIME PROG.
#TIME PROGRAM
#SETTING
#TIME .DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROG.B
CURRENT PROG.C
P2
P3
a
C002221-C-04
5. Operating the appliance VM iSystem
49 19/03/2012 - 300028025-001-01
5. To modify the parameter, turn the rotary button.6. To confirm, press the rotary button.
To cancel, press key h.
7. To go back to the main display, press key j2 times.
It is possible to use the ( and ' keys instead of the rotarybutton.
5.4 Reading out measured values
The various values measured by the appliance are displayed in the#MEASURES menu.
1. To access user level: Press the > key.2. Select the menu #MEASURES.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.
User level - #MEASURES menu
Parameter Description UnitOUTSIDE TEMP. Outside temperature °CROOMTEMP. B (1) Room temperature of circuit B °C
ROOMTEMP. C (1) Room temperature of circuit C °C
BOILER TEMP.(2) Water temperature in the boiler °C
WATER TEMP. (1) Water temperature in the DHW tank °CSTOR.TANK.TEMP(1)
Water temperature in the storage tank °C
SWIMMING P.T.B(1)
Water temperature of the swimming pool on circuit B °C
SWIMMING P.T.C(1)
Water temperature of the swimming pool on circuit C °C
OUTLET TEMP. B(1)
Temperature of the flow water in circuit B °C
(1) The parameter is only displayed for the options, circuits or sensors actually connected.(2) According to the configuration
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROG.C"Choice of the timeprogram applied C"
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 11:45
C002224-D-04
2x
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 50
User level - #MEASURES menu
Parameter Description UnitOUTLET TEMP. C(1)
Temperature of the flow water in circuit C °C
SYSTEM TEMP. (1) Temperature of the system flow water if multi-generator °CT.DHW BOTTOM(1)
Water temperature in the bottom of the DHW tank °C
TEMP.TANK AUX(1)
Water temperature in the second DHW tank connected to the AUX circuit °C
TEMP.SOL.TANK(1)(2)
Temperature of the hot water produced by solar power (TS) °C
SOLAR.COLL.T. (1)
(2)Solar panel temperature (TC) °C
SOLA.ENERGY (1)
(2)Solar energy accumulated in the tank kWh
IN 0-10V (1)(2) Voltage at input 0-10 V VCTRL Software control number (1) The parameter is only displayed for the options, circuits or sensors actually connected.(2) According to the configuration
5.5 Settings after powering up for the first time
5.5.1. Displaying the parameters in extendedmode
The display mode on the control panel is set as standard in such away as only to show the conventional parameters. It is possible toswitch to extended mode by proceeding as follows:
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. Set parameter INSTALLATION to EXTENDED.
Installer level - Menu #SYSTEMParameter Adjustment range Description Factory setting Customer settingINSTALLATION CLASSIC Displays the parameters of a conventional
installationCLASSIC
EXTENDED Displays all parameters
Regardless of what is done to the keys, the regulatorswitches back to CLASSIC mode after 30 minutes.
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Operating the appliance VM iSystem
51 19/03/2012 - 300028025-001-01
5.5.2. Setting the parameters specific to theinstallation
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. Set the following parameters according to the connections madeto the PCBs:
Installer level - #SYSTEM menu
Parameter Adjustment range Description Factory setting Customersetting
CIRC. B: (1) 3WV Connecting a circuit with 3-way valve ( For example:Underfloor heating)
3WV
SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit
Check and set the heating curve if necessary. Seechapter: ¼ "Setting the heating curve", page55
CIRC. C: (1) 3WV Connecting a circuit with 3-way valve (For example:Underfloor heating)
3WV
SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit
Check and set the heating curve if necessary. Seechapter: ¼ "Setting the heating curve", page55
S.AUX: (1) DHW LOOP Use as a domestic loop pump DHW LOOP PROGRAM. Use as an independent programmable outletPRIMARY PUMP The outlet MAUX is active if a heating demand is
present on the secondary pumpDHW Use of primary circuit of second DHW tankFAILURE The outlet MAUX is active if an fault is detectedDHW ELEC Used to control the electrical resistor according to the
timer programme on circuit AUX in summer mode.CTC.I.SYST(2) CLOSE See table below. CLOSE
OPEN(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if IN 0-10V is set to OFF
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 52
Installer level - #SYSTEM menu
Parameter Adjustment range Description Factory setting Customersetting
I.SYST (1) SYSTEM(2) The inlet sensor is used to connect the common flowsensor of a cascade system
SYSTEM
STORAGETANK(2)
Hot water storage tank affected to heating only
DHW STRAT(2) Using the DHW tank with 2 sensors (top and bottom)
ST.TANK+DHW(2) Hot water storage tank affected to heating anddomestic hot water
ANTIFR Start anti-freeze in boiler command0/1 B ON or OFF contact: I.SYST can be used as an
antifreeze activation inlet on circuit B0/1 C ON or OFF contact: I.SYST can be used as an
antifreeze activation inlet on circuit C0/1 DHW ON or OFF contact: I.SYST can be used as an
antifreeze activation inlet on circuit ECS0/1 AUX(2) ON or OFF contact: I.SYST can be used as an
antifreeze activation inlet on circuit AUXWhenI.SYST is not active, the auxiliary circuit (AUX) followsthe maximum boiler temperature (parameter BOILERMAX).
CT.TEL (1) CLOSE See table below. CLOSE OPEN
I.TEL: (1)(3) ANTIFR Start anti-freeze in boiler command ANTIFR 0/1 B ON or OFF contact: I.TEL: can be used as an
antifreeze activation inlet on circuit B0/1 C ON or OFF contact: I.TEL: can be used as an
antifreeze activation inlet on circuit C0/1 DHW ON or OFF contact: I.TEL: can be used as an
antifreeze activation inlet on circuit ECS0/1 AUX(2) ON or OFF contact: I.TEL: can be used as an
antifreeze activation inlet on circuit AUXWhenI.TEL: is not active, the auxiliary circuit (AUX) followsthe maximum boiler temperature (parameter BOILERMAX).
IN 0-10V(2) OFF The 0-10V inlet on the terminal block can be used asa telephone inlet.
OFF
ON Activating the control at 0-10 V(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if IN 0-10V is set to OFF
Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: I.TEL: contact closed I.TEL: contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.
0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 AUX 4 The MAUX outlet on the connection terminal
block is active.4 The boiler operates at a set point temperature
equal to BOILER MAX.
4 The MAUX outlet on the connection terminalblock is not active.
4 The boiler operates with a set point temperatureas a function of the outside temperature.
5. Operating the appliance VM iSystem
53 19/03/2012 - 300028025-001-01
Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: I.TEL: contact closed I.TEL: contact openOPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.
0/1 B The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 C The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 AUX 4 The MAUX outlet on the connection terminal
block is not active.4 The boiler operates with a set point temperature
as a function of the outside temperature.
4 The MAUX outlet on the connection terminalblock is active.
4 The boiler operates at a set point temperatureequal to BOILER MAX.
Influence of the parameter setting CTC.I.SYST on the I.SYST contactCTC.I.SYST I.SYST I.SYST contact closed I.SYST contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.
0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.
0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 AUX 4 The MAUX outlet on the connection terminal
block is active.4 The boiler operates at a set point temperature
equal to BOILER MAX.
4 The MAUX outlet on the connection terminalblock is not active.
4 The boiler operates with a set pointtemperature as a function of the outsidetemperature.
OPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.0/1 B The antifreeze mode is active on the circuit
concerned.The mode selected on the circuit is active.
0/1 C The antifreeze mode is active on the circuitconcerned.
The mode selected on the circuit is active.
0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 AUX 4 The MAUX outlet on the connection terminal
block is not active.4 The boiler operates with a set point
temperature as a function of the outsidetemperature.
4 The MAUX outlet on the connection terminalblock is active.
4 The boiler operates at a set point temperatureequal to BOILER MAX.
5.5.3. Naming the circuits and generators
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NAMES OF THE CIRCUITS.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 54
3. Select the circuit or generator you wish to rename.
Installer level - #NAMES OF THE CIRCUITS menu
Parameter Description Name given by the customerCIRC. B: Circuit B CIRC. C: Circuit C CIRC.AUX Auxiliary circuit CIRC.DHW Domestic hot water circuit GENE Generator
4. Turn the rotary button to choose the first character from the list.To confirm, press the rotary button.
5. Then press again to enter a second character or turn the rotarybutton to leave an empty space.
6. Choose the other characters in the same way. The input zone maycontain up to 6 characters.
To move from one character to another, turn the rotarybutton. To exit without modifications, press key h.
7. To confirm the name, press the rotary button and then turn thebutton slightly anti-clockwise. When the symbol U appears, pressthe rotary button. The name is confirmed.
If the name reaches 6 characters, it is automaticallyconfirmed when the last character is confirmed.
5.5.4. Setting the heating curve
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SECONDARY INSTAL.P.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CIRC.B I
"Personalize the nameof this circuit B"
a
E
F
G
H
..
.
C002344-E-04
I
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CIRC.B FLOOR1
"Personalize the nameof this circuit B"
a
X
Y
Z
.
.
.
C002345-D-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Operating the appliance VM iSystem
55 19/03/2012 - 300028025-001-01
3. Select the parameter CIRC. CURVE ....
4. To modify the value directly, turn the rotary button.To modify the value by displaying the curve, press key f.
5. To modify the curve, turn the rotary button.6. To confirm, press the rotary button.
To cancel, press key h.
0.7 = Heating curve set.
n Heating curve without BCT
The BCT (Base heat Curve Temperature) parameter allows aminimum operating temperature to be imposed on the heating circuit(this temperature may be constant if the circuit gradient is nil).
A Maximum temperature of the circuit
Z Water temperature in the circuit for an outsidetemperature of 0°C
E DAY set point on the circuit
R Outside temperature for which the maximum watertemperature in the circuit is reached
T Value of the heating curveSelect the parameter CIRC. CURVE ...
When you modify the heating curve, Z and R arerecalculated and repositioned automatically.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
BUILD.INERTIA
CIRC.CURVE B
CIRC.CURVE C
SCREED DRYING
3
2.0
0.7
No a
C002316-E-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
CIRC.CURVE B"Slope of the heatcurve of the circuit B"
2.0
C002317-D-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
7564
50
020 -15
C002318-B-04
0,7
0.7
20 0 -16
50
75
C°
C°
1.5
C002319-B
1
2
3
4
5
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 56
n Heating curve with BCT
The BCT (Base heat Curve Temperature) parameter allows aminimum operating temperature to be imposed on the heating circuit(this temperature may be constant if the circuit gradient is nil).
A Maximum temperature of the circuit
Z Water temperature in the circuit for an outsidetemperature of 0°C
E DAY set point on the circuit
R Outside temperature for which the maximum watertemperature in the circuit is reached
T Value of the heating curveSelect the parameter CIRC. CURVE ...
x Value set to the parameter HCZP D
When you modify the heating curve, Z and R arerecalculated and repositioned automatically.
5.6 Changing the settings
The module is set for the most common heating systems. With thesesettings, practically all heating systems operate correctly. The user orinstaller can optimise the parameters according to own preferences.
¼ For the user settings, refer to the user instructions.
5.6.1. Language selection
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #LANGUAGE.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
Installer level - Menu #LANGUAGEAdjustment range DescriptionFRANCAIS Display in FrenchDEUTSCH Display in GermanENGLISH Display in EnglishITALIANO Display in ItalianESPANOL Display in SpanishNEDERLANDS Display in DutchPOLSKI Display in PolishPУCCKИЙ Display in RussianTÜRK Display in Turkish
20 0 -15
64
50
75
C°
C°
0.7
C002320-B
1
2
X
3
4
5
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Operating the appliance VM iSystem
57 19/03/2012 - 300028025-001-01
5.6.2. Defining the configuration mode
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. Set parameter CONFIGURATION:
Installer level - #SYSTEM menu
Parameter Adjustmentrange
Description Customersetting
CONFIGURATION VM/MR Operation with all Diematic control systems - No DHW priority.If CONFIGURATION parameter is set to VM/MR:
1. Select the menu #NETWORK.2. Select the parameter VM NUMBER.3. Assign a code (from 20 to 39) to the appliance. The codes
assigned to the devices must always be done in increasing orderstarting with 20 and without omitting any numbers. Never assignthe same code to 2 different VM iSystem control systems.
3WV+ Operation with Diematic-m 3 - Diematic iSystem control systems -DHW priority available.
0/1+V3V Control for an ON/OFF generatorOTH+3WV Control for a generator by BUS OpenTherm
5.6.3. Calibrating the sensors
1. To access user level: Press the > key.2. Select the menu #SETTING.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. To set the following parameters:
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
C002219-D-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 58
User level - #SETTING menu
Parameter Adjustment range Description Factory setting Customersetting
SUM/WIN 15 to 30 °C Used to set the outside temperature abovewhich heating will be shut down.
4 The heating pumps are shut down.4 Domestic hot water continues to be
produced.4 The symbol p appears.
22 °C
NO Heating is never shut down automaticallyCALIBR. OUT Outside sensor calibration: Used to
correct the outside temperatureOutside temperature
CALIBR. ROOM B (1)
(2)(3) Calibration of the room sensor on
circuit BMake this setting 2 hours after switchingon, when the room temperature hasstabilised
Room temperatureof circuit B
OFFSET ROOM B (1)
(4)(3)-5.0 to +5.0 °C Room offset on circuit B: Is used to set a
room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised
0.0
ANTIFR. ROOM B (1)
(2)(3)0.5 to 20 °C Room temperature at which the
antifreeze mode is activated on circuit B6 °C
CALIBR. ROOM C (1)
(2)(3) Calibration of the room sensor on
circuit CMake this setting 2 hours after switchingon, when the room temperature hasstabilised
Room temperatureof circuit C
OFFSET ROOM C (1)
(4)(3)-5.0 to +5.0 °C Room offset on circuit C: Is used to set a
room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised
0.0
ANTIFR. ROOM C (1)
(2)(3)0.5 to 20 °C Room temperature antifreeze activation
on circuit C6 °C
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if a room sensor is connected to the circuit concerned(3) The parameter is only displayed if the circuit concerned is actually connected(4) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence
5.6.4. Professional settings
1. Access the installer level: Press key - for around 5 seconds.2. To set the following parameters:
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Operating the appliance VM iSystem
59 19/03/2012 - 300028025-001-01
Installer level - #PRIMARY LIMITS menu(1)
Parameter Adjustment range Description Factory setting Customer settingBOILER MAX(1) 40 to 90 °C Maximum temperature authorised by the boiler 90 °C BOILER MIN(1) 10 to 50 °C Minimum temperature authorised by the boiler 20 °C (1) According to the configuration
Installer level - #SECONDARY LIMITS menu
Parameter Adjustment range Description Factory settingMAX.CIRC.B 20 to 95 °C Maximum temperature (Circuit B)
¼ "MAX.CIRC...", page 6350 °C
MAX.CIRC.C 20 to 95 °C Maximum temperature (Circuit C)¼ "MAX.CIRC...", page 63
50 °C
OUT.ANTIFREEZE OFF, -8 to +10 °C Outside temperature at which the installation's antifreezeprotection is activated.Below this temperature the pumps are permanently on and theminimum temperatures for each circuit are respected.When NIGHT : STOP is set, the reduced temperature ismaintained in each circuit (#SECONDARY INSTAL.P menu).OFF: Antifreeze protection is not activated
+3 °C
HCZP D B (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit B) OFF
HCZP N B (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit B) OFF
HCZP D C (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit C) OFF
HCZP N C (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit C) OFF
PRIM.TEMP.DHW(1) 50 to 90 °C Set point temperature if domestic hot water production 80 °C(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f.
Installer level - #SECONDARY INSTAL.P menu
Parameter Adjustment range Description Factorysetting
Customersetting
BUILD. INERTIA (1) 0 (10 hours) to 10(50 hours)
Characterisation of building's inertia:0 for a building with low thermal inertia.3 for a building with normal thermal inertia.10 for a building with high thermal inertia.Modification of the factory setting isonly useful in exceptional cases.
3 (22 hours)
CIRC.CURVE B(2) 0 to 4 Heating curve of the circuit B¼ "CIRC. CURVE ...", page 63
0.7
ANTICIP.B 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.B, ANTICIP.C ",page 63
NO
ROOM INFL. B (1) 0 to 10 Influence of room sensor B¼ "ROOM S.INFL", page 64
3
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 60
Installer level - #SECONDARY INSTAL.P menu
Parameter Adjustment range Description Factorysetting
Customersetting
CIRC.CURVE C(2) 0 to 4 Heating curve of the circuit C¼ "CIRC. CURVE ...", page 63
0.7
ANTICIP.C 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.B, ANTICIP.C ",page 63
NO
ROOM INFL. C (1) 0 to 10 Influence of room sensor C¼ "ROOM S.INFL", page 64
3
SCREED DRYING NO, B, C, B+C Drying the floor¼ "SCREED DRYING", page64
NO
START DRYINGTEMP(3)
20 to 50 °C Screed drying start temperature 20 °C
STOP DRYINGTEMP(3)
20 to 50 °C Screed drying stop temperature 20 °C
NB DAYS DRYING(3) 0 to 99 0 NIGHT (1) DEC. The lower temperature is maintained (Night
mode)¼ "NIGHT", page 65
DEC.
STOP The boiler is stopped (Night mode)¼ "NIGHT", page 65
IN 0-10V(4) OFF / TEMPERATURE Activating the control at 0-10 V¼ "Function 0-10 V", page 65
OFF
VMIN/OFF 0-10V (1)(5) 0 to 10 V Voltage corresponding to the instructionset minimum
0.5 V
VMAX 0-10V (1)(5) 0 to 10 V Voltage corresponding to the instructionset maximum
9.5 V
CONS.MIN 0-10V (1)
(5)10 to 70 °C Instruction minimum set temperature 20 °C
CONS.MAX 0-10V (1)
(5)10 to 100 °C Maximum set temperature 80 °C
BAND WIDTH (1) 4 to 16 K Control unit bandwidth for the 3-wayvalves.Option of increasing the bandwidth if thevalves are rapid or of reducing it if they areslow.
12 K
BOIL/3WV SHIFT (1) 0 to 16 K Minimum temperature difference betweenthe boiler and the valves
4 K
H. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the heatingpumps.The timing of heating pump shutdownprevents the boiler overheating.
4 minutes
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
5. Operating the appliance VM iSystem
61 19/03/2012 - 300028025-001-01
Installer level - #SECONDARY INSTAL.P menu
Parameter Adjustment range Description Factorysetting
Customersetting
HW. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the domestic hotwater pump.The timing of the domestic hot water loadpump shutdown prevents the boiler and theheating circuits overheating (Only if a loadpump is used).
2 minutes
ADAPT ON Automatic adaptation of the heating curvesfor each circuit with a room sensor with aninfluence of >0.
ON
OFF The heating curves can only be modifiedmanually.
PRIORITY DHW(6) TOTAL Interruption of pool heating and reheatingduring domestic hot water production.
TOTAL
SLIDING Domestic hot water production and heatingon the valve circuits if the available outputis sufficient and the hydraulic connectionallows.
NO Heating and domestic hot water productionin parallel if the hydraulic connectionallows.a Risk of overheating in the direct circuit.
LEG PROTEC The anti legionella function acts to preventthe development of legionella in the dhwtank, these bacteria are responsible forlegionellosis.
OFF
OFF Anti-legionella function not activatedDAILY The tank is overheated every day from
4:00 o'clock to 5:00 o'clockWEEKLY The tank is overheated every Saturday
from 4:00 o'clock to 5:00 o'clock(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
Installer level - Menu #SOLAR(1)
Parameter Adjustment range Description Factorysetting
Customersetting
DEC.SOLAR DHW 0 to 30 °C Maximum drop in the DHW set point whenthe solar pump is running at 100%
5°C
REFERENCE DT 10 to 20 °C Temperature difference that the solarpump tries to maintain between the solarDHW sensor and the panel
10°C
MAX.T.COLLECTOR 100 to 125 °C Temperature of the panel above whichthe solar pump starts up.The pump does not operate if thetemperature of the solar tank is higherthan 80°C
100°C
MAX TPS PUMP 1 to 5 min Minimum operating duration of the solarpump at 100% on start-up
1 minute
(1) The menu is only displayed if the solar control system is connected and the INSTALLATION parameter is set to EXTENDED
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 62
Installer level - Menu #SOLAR(1)
Parameter Adjustment range Description Factorysetting
Customersetting
MIN.PUMP SPEED 50 to 100 % Minimum speed of the solar pump 50% TUBULAR COLLECTOR YES / NO Set to YES if tubular collectors are used NO MAX FLOW 0 to 20 l/min Maximum flow rate of the solar pump
¼ "MAX FLOW", page 666.7 l/mim.
(1) The menu is only displayed if the solar control system is connected and the INSTALLATION parameter is set to EXTENDED
n MAX.CIRC...
WARNING
If using underfloor heating, do not modify the factorysetting (50 °C). To install this, please consult existinglegislation.
Connect a safety thermostat to the CS contact on the pumpconnector.
n CIRC. CURVE ...
Heating curve circuit B or C
x Outside temperature (°C)y Water flow temperature (°C)
A Maximum temperature of the circuit B - C
n ANTICIP.B, ANTICIP.C
A Room temperature instruction - Comfort
Z Room temperature instruction - Low
E Time schedule
R Anticipation time = Accelerated reheating phase
The anticipation function calculates the heating restart time to reachthe desired room temperature less 0.5 K at the time programmed forswitching to comfort mode.The start time of the timed programmed corresponds to the end of theaccelerated reheating phase.The function is activated by setting a different OFF value.The value set corresponds to the time considered necessary to returnthe installation to the required temperature (outside temperature0°C), starting from a residual room temperature corresponding to thelow nocturnal instruction.Anticipation is optimised if a room sensor is connected.The regulator will automatically fine set the anticipation time.
M001678-B
1
0,5K
8801N033
1
4
2
3
5. Operating the appliance VM iSystem
63 19/03/2012 - 300028025-001-01
This function is dependent on the surplus output availablein the installation.
n SCREED DRYING
Used to force a constant flow temperature or a train to acceleratescreed drying on underfloor heating.The setting for these temperatures must follow the screed-layer'srecommendations.The activation of this parameter (setting other than OFF) forces thepermanent display of SCREED DRYING and deactivates all otherfunctions on the control unit.When floor drying is active on a circuit, all other circuits (e.g. DHW)are shut down. The use of this function is only possible on circuits Band C.
A STOP DRYING TEMP
Z START DRYING TEMP
E Today
R NB DAYS DRYING
T Normal regulation (End of drying)
Y Heating temperature setting (°C)
For example
A STOP DRYING TEMP: 47 °C
Z START DRYING TEMP: 20 °C
R NB DAYS DRYING
T Normal regulation (End of drying)
Y Heating temperature setting (°C)
Every day at midnight (00:00): the set point (STARTDRYING TEMP) is recalculated and the remaining numberof days (NB DAYS DRYING) is decremented.
n ROOM S.INFL
Used to adjust the influence of the room sensor on the watertemperature for the circuit concerned.
0 No influence (remote control fitted in a location with no influence)1 Slight influence3 Average influence (recommended)10 Room thermostat type operation
2
34
1
6
5
C002768-A
00:00 00:00 00:00
2
10 9 8 7 6 5 4 3 2 1
23
20
26
29
32
35
38
41
44
47
4
4
5
1
6
C002769-A
00:00 00:00 00:00
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 64
n NIGHT
This parameter is displayed if at least one circuit does notinclude a room sensor.
For circuits without a room sensor:
4 NIGHT :DEC. (Reduced): The reduced temperature is maintainedduring reduced periods. The circuit pump operates constantly.
4 NIGHT :STOP (Stop): Heating is shut down during reducedperiods. When installation antifreeze is active, the reducedtemperature is maintained during reduced periods.
For circuits with a room sensor:
4 When the room temperature is lower than the room sensor setpoint: The reduced temperature is maintained during reducedperiods. The circuit pump operates constantly.
4 When the room temperature is higher than the room sensor setpoint: Heating is shut down during reduced periods. Wheninstallation antifreeze is active, the reduced temperature ismaintained during reduced periods.
n Function 0-10 V
This function controls the boiler using an external system thatincludes a 0-10 V output connected to the 0-10 V input. This controlimposes an instruction set temperature on the boiler. It will benecessary to ensure that the parameter BOILER MAX is higher thanCONS.MAX 0-10V.
1 Instruction set outlet temperature (°C)2 Power input signal (V) - DC3 0 V4 CONS.MIN 0-10V
5 CONS.MAX 0-10V
6 VMIN/OFF 0-10V
7 VMAX 0-10V
8 10 Vx Voltage at inputy Boiler temperature
If the input voltage is less than VMIN/OFF 0-10V, the boiler is off.The boiler temperature setting corresponds strictly to the 0-10 Vinput. The secondary boiler circuits continue to operate but have noimpact on the water temperature in the boiler. If using the 0-10 V inputand a secondary boiler circuit, the external regulator providing this0-10 V power supply must always request a temperature at leastequal to the needs of the secondary circuit.
M001679-A
5
1
4
3 6 2 7 8
5. Operating the appliance VM iSystem
65 19/03/2012 - 300028025-001-01
n MAX FLOW
In order for the regulator to calculate the quantity of heat produced bythe installation (parameter kWh), input parameter MAX FLOW. Theparameter MAX FLOW is equal to the flow in litres per minute in thesolar circuit.Establish the MAX FLOW value with the help of the table below,according to the configuration of the installation and the number orsurface area of collectors.When the flow is input incorrectly, the display kWh will also beincorrect.
The quantity of heat (kWh value) can only be used forchecks carried out for personal reasons.
Flat solar panelsSolar panelinstallation
Area (m2) Number ofpanels
Flow rate(l/h)
Flow rate(l/min)
3...5 1 or 2 400 6,76...8 3 or 4 300 5,08...10 4 or 5 250 4,18...10 2x2 750 12,512...15 2x3 670 11,216...20 2x4 450 7,512...15 3x2 850 14,218...23 3x3 800 13,424...30 3x4 650 10,916...20 4x2 1200 20,024...30 4x3 850 14,2
5.6.5. Configuring the network
1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NETWORK.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. To set the following parameters:
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 66
Installer level - Menu #NETWORK(1)
Parameter Adjustment range Description Factory setting Customer settingVM NUMBER(2) 20 to 39 Set the module's network address 20 CASCADE:(2) ON / NO ON: System in cascade NO VM NETWORK(2) Specific menu: Enlist VMs in cascade
mode¼ See chapter: "ConnectingVM iSystem in cascade", page68
MASTER CONTROLLER(3)
ON / NO Configure this control system asmaster on the bus
ON
SYSTEM NETWORK (4) Specific menu: Enlist VMs in cascademode¼ See chapter: "ConnectingVM iSystem in cascade", page68
FUNCT (4) CLASSIC Operation in cascade: Successivetriggering of the various boilers in thecascade according to requirements
CLASSIC
PARALLEL Functioning in parallel cascade: If theoutside temperature is lower than thevalue PARALLEL CASC., all of theboilers are started up at the same time
PARALLEL CASC. (5) -10 to 20 °C Outside temperature triggering allstages in parallel mode
10 °C
TIMER GENE P. CASC(3) 0 to 30 min Minimum duration of post-operation ofthe generator pump
0 mn
INTER STAGE TIMER (3) 1 to 60 min Time delay for starting up or shuttingdown generators.
4 mn
SLAVE NUMBER (6) 2 to 10 Set the network address of thesecondary generator
2
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if CASCADE: is set to ON(4) The parameter is only displayed if MASTER CONTROLLER is set to ON(5) The parameter is only displayed if FUNCT is set to PARALLEL(6) The parameter is only displayed if MASTER CONTROLLER is set to OFF
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customer settingPERMUT(1) AUTO / 1 ... 10 This parameter is used to set the master boiler.
4 AUTO: The master boiler switches automaticallyevery 7 days
4 1 ... 10: The master boiler is always the onedefined by this value
AUTO
(1) The parameter is only displayed if CASCADE: is on ON and MASTER CONTROLLER on ON
n Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/orVM iSystem as slaves. Proceed as follows:
1. Set parameter CASCADE: to ON.
5. Operating the appliance VM iSystem
67 19/03/2012 - 300028025-001-01
2. Select SYSTEM NETWORK and press the rotary button to go tothe specific menu.
3. To add a slave appliance to the network, select ADD SLAVE.
4. The screen displayed allows you to choose numbers for the slaveboilers to be added to the network. Numbers 2 to 10 are dedicatedto the generators and numbers 20 to 39 to the VM iSystem. Turnthe rotary button to scroll through the numbers and press toconfirm the number chosen. Press j to go back to the previouslist.
5. To remove a slave appliance from the network, select ERASENETWORK.
6. The screen displayed allows you to choose the numbers of theslave boilers to be removed from the network. Turn the rotarybutton to scroll through the numbers and press to remove thenumber chosen. Press j to go back to the previous list.
7. Select NB. ELEMENTS.NETWORK. This screen summarises theelements in the network recognised by the system. Press j to goback to the previous list.
n Connecting VM iSystem in cascade
It is possible to assign VMs only as slaves. Proceed as follows:
1. Set parameter CASCADE: to NO.
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CASCADE
MASTER CONTROLER
SYSTEM NETWORK
FUNCT
INTER STAGE TIMER
ON
ON
TRADITIONAL
4'a
C002409-C-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
NB.NETWORK ELEMENTS
ADD SLAVE
ERASE NETWORK
4
a
C002410-C-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
ADD SLAVEGENE: 2, 5,VM: 29,
4
a
C002412-B-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
ERASE NETWORKGENE: 2, 5,VM: 29,
4
a
C002413-B-04
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
NB.NETWORK ELEMENTSGENE: 2, 5,VM: 29,
4
a
C002411-C-04
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 68
2. Select VM NETWORK and press the rotary button to go to thespecific menu.
3. The screen displayed is used to select the numbers of the slaveVMs to be added to the network. Numbers 20 to 39 are dedicatedto the VMs. Turn the rotary button to scroll through the numbersand press to confirm the number chosen. Press j to go back tothe previous list.
4. To remove a slave VM from the network, select DELETE VM.5. The screen displayed is used to select the numbers of the slave
VMs to be removed from the network. Turn the rotary button toscroll through the numbers and press to remove the numberchosen. Press j to go back to the previous list.
6. Select NB. ELEMENTS.NETWORK. This screen summarises theelements in the network recognised by the system. Press j to goback to the previous list.
5.6.6. Return to the factory settings
To reset the appliance, proceed as follows:
1. Press key C, > and j simultaneously for 4 seconds. The menu#RESET is displayed.
2. To set the following parameters:
Menu #RESETChoice of generator Parameter DescriptionGENERATOR RESET TOTAL Performs a TOTAL RESET of all parameters
EXCEPT PROG. Performs a parameter RESET but retains the timer programmesPROG. Performs a RESET on the timer programmes but retains the parametersSENSOR SCU Performs a RESET of the generator sensors connectedROOM SENSOR Performs a RESET of the room sensors connected
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
MODE
SUNDAY 11:45
C002296-B-04
4"
+ +
5. Operating the appliance VM iSystem
69 19/03/2012 - 300028025-001-01
After reset (TOTAL RESET and RESET EXCEPT PROG.), thecontrol system goes back to the display of the language choice aftera few seconds.
1. Select the desired language by turning the rotary button.2. To confirm, press the rotary button.
Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
ÿLANGUE FRANCAIS
C002286-C
VM iSystem 5. Operating the appliance
19/03/2012 - 300028025-001-01 70
6 Switching off the appliance
6.1 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance. If thecentral heating system is not used for a long period, werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump).
6.2 Frost protection
CAUTION
4 The antifreeze protection does not function if theappliance is switched off.
4 To protect the installation, set the appliance toHOLIDAYS mode.
The HOLIDAYS mode protects:
4 The installation if the outside temperature is lower than 3°C(factory setting).
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 °C (factory setting).
4 The domestic hot water tank if the tank temperature is lowerthan 4 °C (the water is reheated to 10 °C).
To configure the holidays mode: ¼ Refer to the user instructions.
6. Switching off the appliance VM iSystem
71 19/03/2012 - 300028025-001-01
7 Troubleshooting
7.1 Installer's contact details
To display the installer's telephone number when an error isdisplayed, proceed as follows:
1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.
2. Select the menu #SUPPORT.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. To set the following parameters:
After Sales level - #SUPPORT menu
Parameter DescriptionNAME Input the installer's nameTELEPHONE NUM. Input the installer's telephone number
When an error is displayed, press ? to display the installer's telephonenumber.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
VM iSystem 7. Troubleshooting
19/03/2012 - 300028025-001-01 72
7.2 Messages (type code Mxx)
The module may display the following messages:
Codeno.
Messages Description Checking / solution
FL.DRY.B XX DAYS Floor drying is activeXX DAYS = Number of days'floor drying remaining.
Floor drying is underway. Heating on the circuits notconcerned is shut down.
4 Wait for the number of days shown to change to 04 Set the parameter SCREED DRYING to OFF
FL.DRY.C XX DAYS FL.DRY.B+C XX DAYS
M30 BL.COM.MODBUS No communication with themaster regulation by thenetwork MODBUS.
Check the wiring between the module and the masterappliance.
M31 BL.SYSTEMNETWORK
Incorrect configuration of thenetwork MODBUS.
4 Check that the address of the appliance is correctlyconfigured in the #NETWORK menu.
4 Check that the cascade configuration is set correctlyon the master module.
7.3 Message history
The menu (#MESSAGE HISTORIC) is used to consult the last 10messages displayed by the control panel.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu (#MESSAGE HISTORIC).
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. The list of the last 10 messages is displayed.
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
BL.HEATING SPEED
BL.WATER MIS.
BL.RL OPEN
BL.FLAME LOS
21/10
02/09
26/08
26/08 a
C002381-B-04
7. Troubleshooting VM iSystem
73 19/03/2012 - 300028025-001-01
4. Select a message to consult the information pertaining to it.
7.4 Faults
If a malfunction occurs, the module flashes and displays an errormessage and a corresponding code.
1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.
2. Press the ? key. Follow the instructions displayed to solve theproblem.
3. Consult the meaning of the codes in the table below:
Code Faults Description Checking / solutionD03D04
OUTL S.B FAIL.OUTL S.C FAIL.
Circuit B flow sensor faultCircuit C flow sensor faultRemarks:The circuit pump is running.The 3-way valve motor on the circuitis no longer powered and can beadjusted manually.
Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D05 OUTSI.S.FAIL. Outside temperature sensor faultRemarks:The set point of the appliance isequal to the maximum.The valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensured.Valves may be manually operated.Reheating the domestic hot waterremains ensured.
Bad connection
4 Check whether the sensor is connected4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
BL INPUT OPEN M21
28/08/2008 - 13h32
NUMBER OF CASE
OUTSIDE TEMP.
OUTLET TEMP.B
8
1.0 °C
12.0°Ca
C002382-B-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
VM iSystem 7. Troubleshooting
19/03/2012 - 300028025-001-01 74
Code Faults Description Checking / solutionD07 SYST.SENS.FAIL. System sensor fault Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D09 DHW S.FAILURE Domestic hot water sensor faultRemarks:Domestic hot water heating is nolonger controlled.The load pump operates.The load temperature of the dhwtank is the same as the boiler.
Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D12D13
ROOM S.B FAIL.ROOM S.C FAIL.
B room temperature sensor faultC room temperature sensor faultNote:The circuit concerned operateswithout any influence from the roomsensor.
Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D14 MC COM.FAIL Break in communication betweenthe iSystem module and the boilerradio module
Bad connection
4 Check the link and the connectorsBoiler module failure
4 Change the boiler moduleD15 ST.TANK S.FAIL Storage tank sensor fault
Note:The hot water storage tankreheating operation is no longerassured.
Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D16D16
SWIM.P.B. S.FAILSWIM.P.C. S.FAIL
Swimming pool sensor fault circuitBSwimming pool sensor fault circuitCNote:Pool reheating is independent of itstemperature.
Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
7. Troubleshooting VM iSystem
75 19/03/2012 - 300028025-001-01
Code Faults Description Checking / solutionD17 DHW 2 S.FAIL Sensor fault tank 2 Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D18 ST.TANK S.FAIL Solar tank sensor fault Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D19 SOL.COL.S.FAIL Header sensor fault Bad connection
4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76
4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault
4 Check the Ohmic value of the sensor4 Replace the sensor if necessary
D20 SOL COM.FAIL 4 Switch the boiler off and switch back on
4 Check whether the solar module is switched on. If necessary, replace the fuse ¼ Referto the installation, commissioning and service manual for the DHW tank
4 Check the connection between the SCU-C and the solar moduleD50 DEF.COM.OTH Break in communication between
the iSystem module and the boilercontrol panel.
4 Check the wiring between the iSystem module and thecontrol panel
4 Check that the CONFIGURATION parameter in the#SYSTEM menu is set to OTH+3WV
D51 DEF XX:SEE BOIL. An error is displayed on the boilercontrol panel.
4 Refer to the boiler's installation and service manual.
7.4.1. Deletion of sensors from the memory in thePCB
The configuration of the sensors is memorised by the PCB. If asensor fault appears whilst the corresponding sensor is notconnected or has been voluntarily removed, please delete the sensorfrom the PCB memory.
4 Press key ? repeatedly until Do you want to delete thissensor? is displayed.
4 Select YES by turning the rotary button and press to confirm.
VM iSystem 7. Troubleshooting
19/03/2012 - 300028025-001-01 76
7.5 Failure history
The menu #DEFAULT HISTORIC is used to consult the last 10 faultsdisplayed by the control panel.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Select the menu #DEFAULT HISTORIC.
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
3. The list of the last 10 faults is displayed.
4. Select a fault to consult the information pertaining to it.
7.6 Parameter and input/output check (mode tests)
Use the following menus to target the cause of a malfunction.
1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.
2. Check the following parameters:
4 Turn the rotary button to scroll through the menus ormodify a value.
4 Press the rotary button to access the menu selectedor confirm a value modification.
¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
aAUX1.SENS.FAIL 21/10
C002274-F-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
AUX1.SENS.FAIL D07
28/08/2008 - 13h32
NUMBER OF CASE
OUTSIDE TEMP.
OUTLET TEMP.B
8
1.0 °C
35.0°Ca
C002275-C-04
bar
1
1
2
2
rc
STD( ' t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 11:45
10"
TEMP.: _ _ _ _
C002272-C-04
7. Troubleshooting VM iSystem
77 19/03/2012 - 300028025-001-01
After Sales level - #PARAMETERS menu
Parameter DescriptionPERMUT Master boiler activeSTAGE Number of boilers requesting heatingNB.CASC.:(1) Number of boilers recognised in the cascade
NB. VM:(1) Number of VM iSystem control systems recognised in the cascadeOUTPUT SOL P. Solar pump commandMEAN OUTSIDE T Average outside temperatureCALC.T. BOILER(1) Temperature calculated by the boiler
BOILER. T. (2) Measurement of the boiler flow sensor
CALCULATED T. B (3) Calculated temperature for circuit B
CALCULATED T. C (3) Calculated temperature for circuit CDHW SETP.CORRECT(3)
DHW set point used by the boiler bearing solar back-up in mind
OUTLET TEMP. B (2) (3) Temperature of the flow water in circuit B
OUTLET TEMP. C (2) (3) Temperature of the flow water in circuit C
OUTSIDE TEMP. (2) Outside temperature
ROOMTEMP. B (2) (3) Room temperature of circuit B
ROOMTEMP. C (2) (3) Room temperature of circuit C
WATER TEMP. (2)(3) Water temperature in the DHW tank
IN 0-10V (2)(3) Voltage at input 0-10 V
STOR.TANK.TEMP (2)
(3)Water temperature in the storage tank
SYSTEM TEMP. (2)(3) Temperature of the system flow water if multi-generator
T.DHW BOTTOM (2)(3) Water temperature in the bottom of the DHW tank
TEMP.TANK AUX (2)(3) Water temperature in the second DHW tank connected to the AUX circuit
KNOB B(3) Position of temperature setting button on room sensor B
KNOB C(3) Position of temperature setting button on room sensor C
OFFSET ADAP B (3) Parallel trigger calculated for circuit B
OFFSET ADAP C (3) Parallel trigger calculated for circuit C(1) According to the configuration(2) The parameter can be displayed by pressing key f.(3) The parameter is only displayed for the options, circuits or sensors actually connected
After Sales level - #TEST OUTPUTS menu
Parameter Adjustment range DescriptionP. CIRC. B (1) ON / NO Stop/start pump circuit B
P. CIRC. C (3) ON / NO Stop/start pump circuit C
HW. PUMP (3) ON / NO Stop/start domestic hot water pump
AUX.CIRC. (3) ON / NO On/Off auxiliary outlet
SOLAR P. (3) ON / NO Solar pump On/Off
3WV B (3) REST No commandOPEN: Opening 3-way valve circuit BCLOSE: Closure 3-way valve circuit B
3WV C (3) REST No commandOPEN: Opening 3-way valve circuit CCLOSE: Closure 3-way valve circuit C
(1) The parameter is only displayed for the options, circuits or sensors actually connected
VM iSystem 7. Troubleshooting
19/03/2012 - 300028025-001-01 78
After Sales level - #TEST INPUTS menu
Parameter Status DescriptionPHONE REM.(1) 0 / 1 Status of the telephone inlet
I.SYST(2) 0 / 1 Status of the telephone inlet
R.CTRL B (3) ON Presence of a remote control BNO No remote control B
R.CTRL C (3) ON Presence of a remote control CNO No remote control C
(1) The parameter is only displayed if IN 0-10V is set to OFF(2) According to the setting of the I.SYST parameter(3) The parameter is only displayed for the options, circuits or sensors actually connected
After Sales level - #INFORMATION menu(1)
Parameter Adjustment range DescriptionS/N SCU Serial no. of the Diematic iSystem DIN control panelCTRL Control versionMC.VERSION (2) Version of the boiler radio module programmeCALIBRA.CLOCK Clock calibration(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed for the options, circuits or sensors actually connected
After Sales level - #CONFIGURATION menu
Parameter Adjustment range DescriptionMODE: MONO/ ALL.CIRC. To chose if the exemption made for one remote control applies to a single circuit (MONO) or
if it must be transmitted to a group of circuits (ALL CIRC)
7. Troubleshooting VM iSystem
79 19/03/2012 - 300028025-001-01
VM iSystem 7. Troubleshooting
19/03/2012 - 300028025-001-01 80
AD
001-
AG
DUEDI S.r.l.www.duediclima.it
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
Via Passatore, 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 [email protected]
IT
DE DIETRICH THERMIQUE Iberia S.L.U.
DE DIETRICH THERMIQUE S.A.S
www.dedietrich-calefaccion.es
Av. Princep d’Astúries 43-4508012 BARCELONA
+34 932 920 520+34 932 184 709
ES
129164, Россия, г. МоскваЗубарев переулок, д. 15/1
Бизнес-центр «Чайка Плаза», офис 309
+7 (495) 221-31-51
© CopyrightAll technical and technological information contained in these technical instructions,as well as any drawings and technical descriptions supplied, remain our propertyand shall not be multiplied without our prior consent in writing.
19/03/2012
300028025-001-01
DE DIETRICH THERMIQUE
57, rue de la Gare F- 67580 MERTZWILLER - BP 30