VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING SYSTEM FOR CAST-IN-PLACE CONCRETE APPLICATIONS
PRODUCT MANUAL
www.cetco.com
PRODUCT MANUAL
- 2 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
CONTENTSWHAT IS SODIUM BENTONITE?PRODUCT DESCRIPTIONASSOCIATED SYSTEM PRODUCTSACCESSORIESLIMITATIONS
INSTALLATION GUIDELINESSECTION 1: UNDERSLAB INSTALLATION 1.1 Substrate Preparation 1.2 Installation 1.3 Pile Caps & Grade Beams 1.4 Slab Penetrations 1.5 Elevator Pits 1.6EdgeofSlab,BackfilledWalls 1.7EdgeofSlab,PropertyLineWalls SECTION 2: PROPERTY LINE CONSTRUCTION 2.1 Property Line Installation Guidelines 2.2 Soldier Pile & Lagging 2.3MetalSheetPilingRetainingWall 2.4 Earth Formed Shotcrete Retention 2.5AugerCastCaissonRetentionWall SECTION 3: BACKFILLED WALLS 3.1 Surface Preparation 3.2 Installation 3.3BackfilledWallPenetrations 3.4 Terminations 3.5MasonryBlockWalls SECTION 4: SPECIAL CONDITIONS 4.1 Precast Concrete Construction 4.2 Contaminated Conditions
THIS MANUAL CONTAINS THE INSTALLATION GUIDE-LINES FOR THE VOLTEX AND VOLTEX DS WATER-PROOFING SYSTEM FOR CAST-IN-PLACE CONCRETE APPLICATIONS, INCLUDING UNDERSLAB, PROPERTY LINE WALLS, AND BACKFILLED WALLS. THIS MANUAL DOES NOT COVER SHOTCRETE, MASONRY BLOCK, OR PRECAST CONCRETE APPLICATIONS. FOR APPLI-CATIONS NOT COVERED IN THIS MANUAL, CONTACT CETCO FOR SPECIFIC INSTALLATION GUIDELINES. BEFORE INSTALLATION, READ THIS MANUAL TO GAIN FAMILIARITY WITH SPECIFIC PROCEDURES AND AP-PLICATIONS. IN THIS MANUAL THE PRODUCT NAME “VOLTEX” IS USED GENERICALLY FOR ALL VOLTEX PRODUCT TYPES.
WHAT IS SODIUM BENTONITE?Sodium bentonite is a non-toxic mineral of volcanic origin found exten-sively in the Black Hills region of North America. Bentonite is specially processed by CETCO to achieve the highest possible performance for allofourwaterproofingproducts.CETCOalsomanufacturersacontami-nant resistant bentonite to assure optimum performance in moderate saline or contaminated water.
Bentonite prevents water intrusion by forming a dense monolithic mem-brane upon contact with water. The specially processed bentonite ex-pandsunderconfinement,forminganimperviousmembranethatwillbe maintained for the life of the structure.
PRODUCT DESCRIPTIONVOLTEX isahighly effectivewaterproofing composite comprisedof twopolypropylene geotextiles and sodium bentonite. The two geotextiles are in-terlocked by a patented needlepunching process which encapsulates and confinesthebentonite.VOLTEXDS® integrates a polymer liner bonded to the outside surface of the nonwoven geotextile. The polymer liner provides extremely low permeabilities for water vapor transmission.
Figure1–CrosssectionillustrationofVOLTEXwaterproofingmembranemechanicallybondedtoconcrete
Concrete
Needlepunched geotextilefibers
Granular sodium bentonite
Nonwoven geotextile
VOLTEX forms a continuous mechanical bond to concrete. This bond is created when VOLTEX’s strong geotextilefibersareencapsulated by poured concrete as shown in the illustration
Wovengeotextile
www.cetco.com
Installation of VOLTEX is fast and easy. Simply position the product into place and fasten. VOLTEX can be installed on green concrete, in virtu-ally any weather, without the need for primers or adhesives. VOLTEX can be easily cut on site to form around corners and penetrations. The result is always a consistent self-sealing membrane.
DURABILITYThe VOLCLAY® sodium bentonite in VOLTEX is uniformly encapsulated between two high-strength woven and non-woven geotextiles. CETCO’s state-of-the-art needlepunching process interlocks the geotextiles, preventing the displacement of bentonite prior to, during, and after in-stallation. The geotextiles provide superior protection from inclement weather and construction-related damage, without requiring to use a protection course.
SUPERIOR ADHESIONWhenconcreteispouredagainstVOLTEX,atenaciousmechanicalbondis created with VOLTEX’s high strength geotextile. Independent labora-torytestingconductedinaccordancewithASTMD903(mod.)(PeelAd-hesiontoConcrete),yieldsanaverageadhesionvalueof2.6kN/m(15lbs/in).ThemechanicalbondwillholdVOLTEXinintimatecontactwiththe concrete should any ground settlement occur, thereby preventing watermigrationbetweenthewaterproofingandtheconcrete.
COST EFFECTIVE AND TIME EFFICIENTVOLTEX is designed to be installed on a properly prepared subgrade, withouttheneedtopouraworkingslab.Theproduct’sinherentflexibil-ity allows for easy installation on irregular surfaces and rough property line forming. VOLTEX can be installed as soon as the forms are stripped; there is no waiting for the concrete to cure.
ASSOCIATED SYSTEM PRODUCTSWATERSTOP-RX® – expanding concrete joint waterstop used around penetrations and applicable concrete joints. Swells upon hydration.AQUADRAIN® – foundation drainage composite consisting of a molded profilecoreandafilterfabric.Includessheetdrainageandbasedraincollection.
ACCESSORIESBENTOSEAL® – trowel grade mastic used to detail around penetrations, corner transitions and terminations. CETSEAL – single-component polyether general sealant and adhesive. HYDROBAR TUBES®–watersolublefilmtubingfilledwithactivegranu-lar material.WATERSTOPPAGE® – active granular material used at detail areas that require additional protection.SEAMTAPE® – premium tape used to seal overlapped membrane edges ofVOLTEXDS.AKWASWELL® – caulk grade hydrophilic waterstop.
TERMINATION BAR–Min.25mm(1”)widealuminumorstainlesssteelbarwithpre-punchedholeson300mm(12”)centeringforfastening.
CEMENTITIOUS BOARD – 12 mm (1/2”) thick cementitious wallboardforprotectionofwaterproofingduringtheremovalofsteelsoldierpile cap and top lagging boards.
ENVIROSHEET – self-adheringflashingmembraneusedforgradeandthru-wallflashing.
TB-BOOT – pre-formed, single piece cover for tie-back heads and soil nails.Threesizesavailable:TB-6SN,TB-8&TB-10.
LIMITATIONSVOLTEX should only be installed after substrate preparation has been properly completed and is suitable to receive the waterproof-ing system. Concrete work should use conventional cast-in-place formsthatproduceasmoothsurface.Donotusestay-in-placecon-crete forming; use removeable forming products only.
VOLTEX is designed for below-grade waterproofing applicationswheretheproductisproperlyconfined.VOLTEXproductsshouldnotbe installed in standing water or over ice. If ground water contains strongacids,alkalies,orisofaconductivityof2,500μmhos/cmorgreater, water samples should be submitted to the manufacturer for compatibility testing. Ultraseal may be required if contaminated ground water or saltwater conditions exist.
VOLTEX isdesigned foruseunder reinforcedconcrete slabs100mm (4”) thickor greater ona compactedearth/gravel substrate.VOLTEXrequiresaminimum150mm(6”)thickreinforcedconcreteslab if installed over a mud slab. VOLTEX is not designed for split-slab plaza deck construction.
VOLTEX is not designed to waterproof expansion joints. Do not use VOLTEX on masonry block foundation walls. Con-sult CETCO for special installation guidelines that apply to shotcrete and precast concrete construction.
In this manual, the product name “VOLTEX” is used generi-cally in the installation and application guidelines for the applicable products: VOLTEX, VOLTEX CR, VOLTEX DS and VOLTEX DSCR. Refer to the table on the back page for prod-uct descriptions and roll sizes. Illustrations are not shown to scale.
PRODUCT MANUAL
- 4 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
INSTALLATION GUIDELINESBefore installing VOLTEX read this installation manual to gain familiarity withspecificproceduresandapplications.Forapplicationsnotcoveredinthismanual,contactCETCOforspecificinstallationguidelines.
VOLTEXisengineeredforuseunderreinforcedconcreteslabs100mm(4”) thickorgreateronacompactedearth/gravel substrate.VOLTEXrequiresaminimum150mm(6”)thickreinforcedconcreteslabifin-stalledoveramudslab.VOLTEXCRorVOLTEXDSCRisusedincontami-nated conditions as determined by a CETCO water sample test.
For hydrostatic conditions, VOLTEX should be installed under foot-ings and grade beams as shown in Figures 1.6, 1.7 and 1.8. For non-hydrostatic conditions, VOLTEX should be installed around footings and gradebeamsasshowninFigures1.9,1.10and1.11.
Prior to installing VOLTEX the substrate must be properly prepared. Complete all required elevator pit, sump pit, grade beam and piling work prior to installing VOLTEX under main slab area. These areas must becorrectlytiedintotheunderslabwaterproofingtoformamonolithicseal.
1.1 SUBSTRATE PREPARATIONSubstrate may be concrete, earth, sand, or crushed stone. Earth and sand substrates should be compacted to aminimum85%ModifiedProctordensity.Crushedstoneshouldbenolargerthan19mm(3/4”)insize.Substrateshouldbesmoothandwithoutsharpdeflectionsorpockets.
1.2 INSTALLATIONInstallVOLTEXorVOLTEXDSovertheproperlypreparedsubstratewiththedarkgray(woven)geotextilesideup.Overlapalladjoiningedgesaminimumof100mm(4”)andstaggersheetendsaminimumof300mm(12”)(Figure1.1).Nailorstapleedgestogetherasrequiredtopre-ventanydisplacementbeforeandduringconcreteplacement(Figure1.2).
Whentheslabispouredinsections,VOLTEXshouldextendaminimum300mm(12”)beyondtheslabedge(Figure1.3).ThisenablesVOLTEXto be properly overlapped for subsequent slab section pours. WATER-STOP-RX should be installed in all applicable slab construction joints (Figure1.3).
SECTION 1 UNDERSLAB INSTALLATION
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Overlap 100mm(4")min.
Figure 1.2 – Secure overlaps together with fasteners
Figure 1.3 – Extend VOLTEX a minimum 300mm(12”) beyond slab edge. Install WATERSTOP-RX in joint
Figure 1.1 – Overlap edges 100mm(4”)withseamsstaggered300mm(12”)
VOLTEX
Overlap 100mm (4")Min.
Stagger300mm(12”)
Reinforced concrete slab
300mm(12”)min VOLTEX
WATERSTOP-RX min.75mm(3”)coverage
www.cetco.com
WATERSTOP-RX 75mm(3”)min.coverage
Reinforced concrete slab a minimum100mm(4”)thick
VOLTEX
Compacted Substrate
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Figure1.4–VOLTEXinstalleddirectlyovercompactedearth/gravelsubstraterequiresaminimum100mm(4”)slab
Reinforced concrete slab a minimum150mm(6”)thick
VOLTEX
Compacted Substrate
Concrete mud slab
Figure1.5–VOLTEXinstalledoveramudslabrequiresaminimum150mm(6”)thickreinforcedslab
WATERSTOP-RX 75mm(3")min.coverage
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
PRODUCT MANUAL
- 6 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
HYDROSTATIC CONDITIONS NON-HYDROSTATIC CONDITIONS
VOLTEX
VOLTEX
Hydrobar Tube
Figure1.6–Slabonfootingdetail(hydrostatic)
VOLTEX
BENTOSEAL
Hydrobar Tube
VOLTEX
Mud slab
Figure1.7–Raisedslabdetailwithmudslab(hydrostatic)
VOLTEX
VOLTEX
Figure1.8–Flushslabdetailpropertylinewall(hydrostatic)
VOLTEX
Hydrobar Tube
Figure1.9–Slabonfootingdetail(non-hydrostatic)
VOLTEX
BENTOSEAL
VOLTEX
Mud slab
Figure1.10–Raisedslabdetailwithmudslab(non-hydrostatic)
VOLTEX
Term Bar & BENTOSEAL
300mm (12”)
Figure1.11–Flushslabdetailbackfilledwall(non-hydrostatic)
WATERSTOP-RX 75mm(3")min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage WATERSTOP-RX
75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
Term bar and BENTOSEAL
www.cetco.com
1.3 PILE CAPS AND GRADE BEAMSVOLTEX is typically not installed over pile caps but cut to fit tightlyaroundpilecaps.Thenapplyaminimum19mm(3/4”) thickfilletofBENTOSEALatintersectionofVOLTEXandthepiling(Figure1.12)withWaterstoppageunderVOLTEXat thepilingedge.BENTOSEAL should extendontoVOLTEXandpilingaminimumof50mm(2”)at19mm(3/4”)thickness.WATERSTOP-RX should be installed on top surface of pilecaparoundreinforcingsteel(Figure1.12).
Detail gradebeams thesameaspilecaps (Figure1.14)withanon-hydrostatic condition. For hydrostatic conditions, VOLTEX should be in-stalledundertheentiregradebeam(Figure1.15).Linethegradebeamformwork with VOLTEX prior to placement of reinforcing steel. Leave a minimum300mm(12”)ofVOLTEXat the topof the formto tie intobelowslabwaterproofing.
Figure1.12–PileCapDetail(Hydrostaticcondition)
Figure1.13–PileCapDetail(Non-hydrostaticcondition)
Figure1.14–GradeBeam(Non-hydrostaticcondition) Figure1.15–GradeBeam(Hydrostaticcondition)
WATERSTOP-RX
Concrete pile
BENTOSEAL
VOLTEX
Waterstoppage
WATERSTOP-RX
Metal I-beam
VOLTEX
WATERSTOP-RX
50mm(2”)thickfilletofBENTOSEAL
GranularWaterstoppage
WATERSTOP-RX Waterstoppage
VOLTEX
BENTOSEAL
Pile cap
BENTOSEAL
Pile
WATERSTOP-RX Reinforcing steel BENTOSEAL
VOLTEX
Grade beam
50mm(2”)thick filletof Waterstoppage
Grade beam
Reinforcing steelWATERSTOP-RX
VOLTEX
PRODUCT MANUAL
- 8 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
1.4 SLAB PENETRATIONSCutVOLTEX tocloselyfitaroundpenetrations (Figure1.16).Trowelaminimum19mm(3/4”)thickfilletofBENTOSEAL around the penetra-tiontocompletelyfillanyvoidareabetweenVOLTEXandthepenetra-tion(Figure1.17).TheBENTOSEAL should extend up the penetration about38mm(1–1/2”)andextendontoVOLTEX.Inareaswheremulti-ple penetrations are close together, it may be impractical to cut VOLTEX
tofitaroundeachpenetration.PourWaterstoppage,granularbenton-ite,aminimum6mm(1/4”)thickaroundthepenetrationscoveringtheentiresubstratearea.Withgravelsubstrate,installminimum200mm(8”) collar of VOLTEX around penetration prior to placing waterstop-page. Then apply a thick layer of BENTOSEAL around each penetration asdetailed(Figure1.19).
Figure 1.17 – BENTOSEAL troweled around penetrations Figure 1.18 – Slab penetration cross section detail
Figure1.19–Multiplepipepenetrations.TrowelBENTOSEAL around pipes and covering area between the pipes
VOLTEX
Pipe
BENTOSEAL
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
VOLTEX
Waterstoppage
BENTOSEAL
WATERSTOP-RX 75mm(3")min.coverage Pipe
Mud Slab Substrate Compacted Earth or Gravel Substrate
Mud slab
WATERSTOP-RX
BENTOSEAL
Continue VOLTEX between pipes VOLTEX
WaterstoppageMud slab substrate
Continue VOLTEX between pipes
WATERSTOP-RX
BENTOSEAL
Gravel substrate
VOLTEX collar Waterstoppage
www.cetco.com
1.5 ELEVATOR PITSVOLTEX should be placed on vertical surfaces and on the substrate be-lowtheslabtoformacontinuousenvelopearoundtheelevatorpit(Fig-ure1.20).Iftheverticalsoilcutissmoothandstable,VOLTEXmaybe
installed directly against the soil. Contain unstable soils with a retaining wall. InstallVOLTEXdirectlyagainsttheretainingwall.Duetovariouselevatorpistonplungerdesigns,consultCETCOforspecificinstallationand detailing for piston plungers that penetrate the pit slab.
Figure1.20–VOLTEXunderelevatorpitslabandonexcavationcutwalls
1.6 EDGE OF SLAB, BACKFILLED WALLSWhen the installation reaches the outer edge of the slab, continueVOLTEXuptothetopedgeoftheformsinsidesurface(Figure1.21)orextendtheVOLTEXsheetoutthetopoftheformaminimumof300mm(12”)(Figure1.22).Attheslabcorner,VOLTEXshouldremainincontactwith the substrate and the inside surface of the concrete form.
When the slab edge form is removed, any undamaged portion ofVOLTEX extended outside the form should be positioned and secured
tothetopoftheconcretefooting.Damagedmaterialoutsidetheformshould be cut off and disposed of. Overlap the secured VOLTEX edge ontopofthefootingaminimum150mm(6”)withthesucceedingwallwaterproofing.InstallHydrobarTubesatwall-to-footingcornerpriortoinstallingoverlappingwallwaterproofing.
WATERSTOP-RXshouldbeinstalledintheperimeterwall/slabintersec-tion joint as illustrated in Figure 1.23.
Figure 1.21 – VOLTEX turned up and secured at top of concrete form Figure 1.22 – Extra tail of VOLTEX extended out of form and later cut off after concrete pour
300mm(12”) min
VOLTEX
Compacted substrate
VOLTEX VOLTEX secured to top of form before concrete pour
Slab edge form
Compacted substrate
VOLTEX
Extra tail of VOLTEX extended out of form. Cut off damaged areas before installing VOLTEX overlap
Slab edge form
Compacted substrate
WATERSTOP-RX 75mmmin.(3”)coverage
PRODUCT MANUAL
- 10 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
1.7 EDGE OF SLAB, PROPERTY LINE CONSTRUCTIONWherepropertylineretainingwalls,suchassoldierpileandlagging,areused as the outside form, continue the underslab VOLTEX installation uptheretainingwallaminimum300mm(12”)abovethetopedgeoftheslaborfooting(Figure1.23).Theextra300mm(12”)sheetexten-sion is very important since there is no access to the outer edge of the footing after it is poured.
Slab to Wall Corner Transition:InstallVOLTEXorVOLTEXDSsheethorizontallyoriented(darkgraywovengeotextilefacinginstaller)withaminimum300mm(12”)ofthesheetextendingoutontothehorizontalsubstrate.Thetopedgeofthesheetmustextendaminimum300mm(12”)abovethefinishedslabsurface.SecureVOLTEXsheettolaggingwall with washer-head fastenermaximum 600mm (24”) on center.OverlapedgesofadjacentVOLTEXsheetsaminimum100mm(4”).
Iftheslabthicknessisgreaterthan600mm(24”),installasecondfullsheetorcutstripofVOLTEX,horizontallyoriented,tomeetthe300mm(12”)requirementabovetheslab.Overlaptopedgeofprevioussheetandedgesofadjacentsheetsaminimum100mm(4”).
Base Wall Course: InstallfirstVOLTEXsheetcourseontheshoringwallhorizontallyoriented (darkgreywovengeotextile facing installer)over the corner transition sheet, with the bottom edge extending down to the wall/slab transition corner as shown in Figure 1.23. SecureVOLTEX sheet to lagging wall with washer-head fasteners maximum 600mm(24”)oncenter.OverlapedgesofadjacentVOLTEXsheetsaminimum100mm(4”).
Install underslab VOLTEX membrane extending to corner transition, overlappingthe300mm(12”)sheettailofthecornertransitionsheetinstalledatthewallbase.Securecorneredgewithfasteners300mm(12”)oncenter.
Formetalsheetpilingshoringwalls,firstinstalltheVOLTEXcornertran-sition sheet horizontally oriented with the bottom edge extending mini-mum300mm(12”)outontothesubstrate.Cutthebottomedgeofthecorner transition sheet at piling transition angles to allow the bottom edgetolayflatontothesubstrate.Pour38mm(11/2")continuouscantofWaterstoppagealongbaseof shoringwall. Then install underslabVOLTEXsheetcuttofitcontoursofmetalsheetpiling.Finally,installthebaseshoringwallVOLTEXsheet(horizontallyoriented)overlappingthecorner transition sheet.
Figure1.23–SLAB-TO-WALLTRANSITION–VOLTEXcornertransitionsheetshouldextendpasttheheightofthetopofthefinishedslablevelaminimum300mm(12”)andextendundertheslab300mm(12”)
Figure 1.24 – AQUADRAIN100BDDISCHARGEPIPE–ConnectAQUAD-RAIN100BDtowaterdischargepipesusing100BDaccessorycon-nections
VOLTEX under slabVOLTEX transition sheet at corner in-stalled horizontally oriented
Cast-in-place concrete wall
VOLTEX base course installed horizontally oriented
Woodlagging
300mm (12”)min
VOLTEX base course installed horizontally oriented
AQUADRAIN SheetDrain
Woodlagging
300mm (12”)min
AQUADRAIN100BDbasedrainconnected to discharge pipes
VOLTEX transition sheet at corner installed horizontally oriented
VOLTEX
DischargePipe
WATERSTOP-RX 75mm(3")min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
300mm(12”)BENTOSEAL
www.cetco.com
The use of construction techniques described in this section allow the exterior building dimensions to coincide with the property line, thereby maximizinguseofavailablelandforbuilding.VOLTEX/VOLTEXDShasbeen proven to be one of the most effective and widely used means forwaterproofingpropertylineconstruction.Cast-in-placepropertylineconstruction methods include soldier pile & lagging, metal sheet piling, earth formed shotcrete retention walls, and auger cast caisson walls.
For all property line construction methods, VOLTEX is installed to the shoring wall prior to concrete placement.Install VOLTEX or VOLTEX DS with the dark grey (woven) geotextile inward, facing the installer, away from the shoring wall. Refer to each applicable construction method in Section 2 for specific sub-strate preparation and detailing installation guidelines.
AQUADRAINsheetand100BDbasedraincompositesystemshouldbeconnectedtoanoperativewaterdischargesystem(sumppumporgrav-itytodaylightdischarge).
Protectbentonitewaterproofingproductsfromhydratingbeforemate-rialiscontainedwithconcreteorbackfill.Afteranyprecipitation,stand-ingwatershouldbepumpedoffwaterproofingassoonaspossible.
Shoring Wall: Excavation work should provide shoring wall in good condition to receive waterproofing system. Wood lagging shoringshouldextendtothelowestlevelofthewaterproofinginstallationwithanyvoidsorcavitiesexteriorofthelaggingfilledwithcompactedsoilorcementitiousgrout.Voidsorcavitiesattie-backsshouldbefilledwithgrout or compacted soil prior to VOLTEX installation. Interior surface of lagging timbers should be monolithic and tight together with gaps less than25mm(1”).Gapsinexcessof25mm(1”)shouldbecompletelyfilledwithcementitiousgroutorothersolidmaterial.
Cut rock excavations and concrete auger cast caisson retaining walls must be sufficiently planar. Typically a shotcrete or grout layer is re-quired to provide acceptable surface to install VOLTEX.
Employconstructionmethodstostopwaterflowingthroughshoringwallpriortowaterproofinginstallation.Ifonlywaterseepage,installpolyeth-ylene sheeting over the seepage area prior to installing VOLTEX. Poly-ethylene sheeting should extend from seepage elevation to base of wall toprotectentirewaterproofinginstallationatthatarea.
SECTION 2 PROPERTY LINE CONSTRUCTION
Figure1.25–RAISEDSLABCONDITION–ConnectAQUADRAIN100BDtowaterdischargepipesusing100BDaccessoryconnectors
Figure 1.26 – Metal sheet piling to slab transition detail
Cast-in-place concrete wall
AQUADRAIN
VOLTEXWood lagging
Hydrobar tube
VOLTEX
Dischargepipe
AQUADRAIN100BDbasedrainconnectedtodischarge pipes
VOLTEX underslab
300mm(12”)min.
Waterstoppagecantin corner over VOLTEX corner transition sheet
Metal sheetpiling
VOLTEX base layer horizontally oriented
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
BENTOSEAL
Retained earth
VOLTEX corner transition sheet horizontally oriented(installfirst)
VOLTEX corner transition sheet horizontally oriented(slicedto contour sheet piling)
VOLTEX cut to fitcontoursofsheet pilesMud slab
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
PRODUCT MANUAL
- 12 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
2.1 PROPERTY LINE WALL INSTALLATION GUIDELINESAfter the slab-to-wall corner transition sheet and bottom wall sheet coursehavebeen installedperSection1.7Page10,VOLTEXsheetscan be installed either vertically or horizontally oriented. Fasten the VOLTEX intopositionwithwasher-head fastenersmaximum600mm(24”)oncenteraroundthesheetedge.InstallsucceedingVOLTEXsheetoverlappingtheprevioussheetedge100mm(4”). (Note:Shingle lapseams so that the bottom edge of the upper sheet is over the lower sheetstopedge).
Continueinstallationupwalluntilgradedetail,orasspecified,stagger-ingallsheetendsofadjacentrollsaminimum300mm(12”).Donotallow sheet overlap joints to occur at same elevation as concrete cold joints. Plan by chalk lining the location of construction joints.
Penetrations: Install a cut collar of VOLTEX tightly around the penetra-tion;extendingaminimum300mm(12”)radius.ApplyBENTOSEAL over VOLTEX collar around penetration; extending BENTOSEAL a minimum 75mm(3”)radiusat6mm(1/4”)thickness.TheninstallmaincourseofVOLTEX membrane tightly around the penetration. Finally, detail around penetrationwith19mm(3/4”)thickcantofBENTOSEAL.Withsleevedpipes,theconcreteworkshouldincludefillingthegapbetweenthepipeand the sleeve with non-shrink cementitious grout, mechanical seal by others and install WATERSTOP-RX to outside of sleeve.
Tie-Back Covers:SelectappropriatesizeTB-Boottofitovertie-backplate and allow proper cast-in-place concrete coverage per project re-quirements. TB-Boot should fit over entire tie-backheadwithout thetie-back plate or cables in direct contact with the TB-Boot. Prior to TB-Bootinstallation,fillvoidsinretentionwallsubstrateandtie-backheadassemblywithspray foam (min20psi)ornon-shrinkgrout.Fornon-hydrostatic conditions, install and secure AQUADRAIN drainage com-posite course per manufacturer’s guidelines to soil retention wall prior to installing TB-Boot. For hydrostatic conditions, install TB-Boot prior toVOLTEXmembrane.Withsoldierpiles,strippileswithwaterproofingmembrane prior to TB-Boot placement.
Fill pre-formed shape of TB-Boot with 2-part urethane spray foam (min20PSI)andplaceovertie-backheadbeforefoamsetsup.Se-cure TB-Boot to soil retention system using washer head fasteners alongtheoutsideedgeoftheflatbase.Apply6mm(1/4”)thickbyminimum75mm(3”)widecontinuousringofBENTOSEAL onto the flatbasejustoutsideofthe12mm(1/2”)raisedcollar.Install4-ftby4-ftpieceofVOLTEX(withprecutholeincentertofittightaroundthe12mm(1/2”)raisedcollar)overtheentireflatbasewithoutsideedges fastened to the retaining wall. Secure inside VOLTEX edge around raised collar with washer-head fasteners that pass through the BENTOSEALring;typicalfastenerspacing150mm(6”).Donotinstall fasteners or puncture TB-Boot inside of the 12mm (1/2”)raised collar. Apply counter flashing ofBENTOSEAL along VOLTEX sheet edge around raised collar. Then install VOLTEX field sheetoverlappingoutermembraneedgeminimum100mm(4”).
Figure 2.1 – WALL PENETRATION – Cut and secure VOLTEX tightlyaround penetrations and then apply BENTOSEAL 19mm (3/4”) ringaroundpenetrationandextendovermembraneaminimum75mm(3”)radiusatminimum6mm(1/4”)thickness
Figure2.2–SLEEVEDWALLPENETRATION–Cut and secure VOLTEX tightly around penetrations and then apply BENTOSEAL19mm(3/4”)ringaroundpenetrationandextendovermembraneamin.75mm(3”)
300mm (12”)min
Woodlagging
300mm(12")VOLTEXcol-lar around pipe penetration
19mm(3/4")BENTOSEAL cant
WATERSTOP-RX
Pipe
Cast-in-place concrete wall
VOLTEX
AQUADRAINSheetDrain
300mm (12”)min
Woodlagging
300mm(12")VOLTEXcol-lar around pipe penetration
19mm(3/4")BENTOSEAL cant
WATERSTOP-RX
Pipe
VOLTEX
AQUADRAIN Sheet Drain
Pipesleeve,filledwithnon-shrink grout
Cast-in-place concrete wall
BENTOSEAL ring 6mmx75mm(1/4”x3")min
BENTOSEAL ring 1/4"x3"min
Mechanical seal by others
www.cetco.com
Soldier Pile Stripping: Install a strip of VOLTEX over all soldier piles with raised lagging hanger bolts, form tie rods, or other irregular sur-face.VOLTEXstripshouldextendaminimum150mm(6”)tobothsidesof the piling. Apply BENTOSEAL6mmx50mm(1/4”x2”)toVOLTEXstripsurfacealongbothedgesofeachsoldierpile(Figure2.9).
Cementitious Board: Prior to installing VOLTEX/VOLTEXDS to fin-ishedgrade, install12mm(1/2”)thickcementitiouswallboardcen-teredoversteelsoldierpilefromfinishedgradeelevationtospecifieddepth that the top of steel soldier pile and wood lagging will be removed (Figure2.13).
Grade Termination:TerminateVOLTEXmembrane300mm(12”)be-lowfinishedgradeelevationwithwasher-headfastenersmaximum300mm(12”)oncenter.InstallENVIROSHEETflashingtoprimedconcretesubstrate with bottom edge overlapping top edge of VOLTEX membrane minimum100mm(4”).Overlapallrollendsaminimum100mm(4”)toformacontinuousflashing.Heightofflashingshallbeperprojectde-tailsandspecifications.Installarigidterminationbaralongtopedgeof
ENVIROSHEET;fastenedmaximum300mm(12”)oncenter.Completegrade termination detail with tooled bead of CETSEAL along the top edge,atallpenetrationsthroughtheflashing,andallexposedoverlapseams.
Where lagging timbers and the topendof steel soldier piles are re-moved, repair anywaterproofingdamagedby theexcavationand re-moval of the retention wall system. Secure all excavated VOLTEX over-lap seams with washer-head fastenersmaximum 600mm (24”) oncenter;withVOLTEXDSalsoapplySeamtapecenteredalongoverlapseams.Backfillshallbeplacedandcompactedtominimum85%Modi-fiedProctordensitypromptlyafterwaterproofing installation.Backfillshouldconsistofcompactablesoilorangularaggregate19mm(3/4”)or less) freeofdebris,sharpobjects,andstones larger than19mm(3/4”).Seeterminationdetailsfigures3.11and3.12,page22.
Figure2.3:TIE-BACKDETAIL–InstallTB-Bootcenteredovertie-backthen install main course of VOLTEX with BENTOSEALdetailing.Donotfasten boot inside of raised collar around center formed area
Shoring wall
VOLTEX
AQUADRAIN sheet drain
2-part urethane expanding spray foam (min.20PSI)
Soldier pile
Fastener
Use spray foamtofillall voids behind tie-back
Donotfasten boot inside of raised collar
Tie-back head with cables
CETCO pre-formed TB-Boot
BENTOSEAL 6 mm X 75 mm (1/4”x3”)min VOLTEX
Field Sheet
Concrete wall
Fastener
Raised collar
Figure2.3a:TIE-BACKDETAIL–InstallTB-Bootcenteredovertie-backthen install VOLTEX with BENTOSEALdetailing.Donotfastenbootin-side of raised collar around center formed area
Shoring wallSoldier pileFastener
VOLTEX pile strip
VOLTEX
Raised collar
TB-Boot
Fastener
Soldier pile
VOLTEXfieldsheet
Use spray foamtofillall voids behind tie-back
Donotfasten boot inside of raised collar
VOLTEX pile strip
VOLTEX pile strip
Tie-back head with cables
CETCO pre-formed TB-Boot
2-part urethane expanding spray foam (min.20PSI)
VOLTEXfieldsheet
BENTOSEAL 6 mm X 75 mm (1/4”x3”)min
NON-HYDROSTATIC CONDITIONS HYDROSTATIC CONDITIONS
BENTOSEAL
Soldier pile
AQUADRAIN
BENTOSEAL
BENTOSEAL
BENTOSEAL
PRODUCT MANUAL
- 14 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
2.2 SOLDIER PILE & LAGGING RETAINING WALLVerify the following substrate preparation work has been completed. Then install VOLTEX following the property line installation guidelines in Section 2.1 on page 12 and 13.
Preparation: Gaps between the wood lagging must be no wider than 25mm(1”).Ifthegapsbetweenlaggingareinexcessof25mm(1”),thegapsshouldbecompletelyfilledwithcementitiousgrout,wood,ex-trudedpolystyrene(40psimin.)orcompactedsoil(Figure2.7).Ifwaterisflowingthroughthelagging,athinpolyethylenesheetingcanbein-stalled over the area before VOLTEX is installed.
In areas with large gaps (up to 63 mm [2–1/2”]) between lagging,AQUADRAIN sheet drainage composite can be installed over the lagging toprovideauniformsurface tomountVOLTEX (Figure2.8).Securelyfasten AQUADRAIN to the lagging surface with washerhead nails be-foreinstallingVOLTEX.Gapslargerthan63mm(2–1/2”)betweenlag-gingshouldbecompletelyfilledwithgrout,wood,extrudedpolystyrene(40psimin.)orcompactedsoilevenifAQUADRAIN is installed prior to VOLTEX.Donotuseplywoodorothersurfacetreatmentoverlargelag-ginggapsthatleavesthecavityvoid.Details2.10through2.12onpage15 illustrate the installation of VOLTEX over the different wood lagging positions relative to the soldier piling.
Figure 2.8 – AQUADRAIN used to cover gaps in lagging less than 63 mm (2.5”). (Cast-in-placeconcretewall)
Woodlagging
VOLTEX
Grout caps larger than25mm(1”)
WATERSTOP-RX
Woodlagging
VOLTEX
AQUADRAIN
WATERSTOP-RX
Figure2.9–InstallVOLTEXontosoldierpileandwoodlaggingretainingwallpriortocast-in-placeconcretewall
BENTOSEAL troweled over surface of VOLTEX strip at both edges of the soldier pile
VOLTEX strip centered over soldier pile BENTOSEAL
TB-Boot over tie-back plate
VOLTEX corner transition sheet installed horizontally oriented
VOLTEX base wall course installed horizontally oriented
Wood lagging
Tie-back head
Soldier pile
VOLTEX section
100mm (4”)
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
Figure 2.7 – VOLTEX installed di-rectly to wood lagging with gaps filled. (Cast-in-place concretewall)
www.cetco.com
Wood lagging
Steel piling
VOLTEX main course
VOLTEX strip over pile prior to main course
WATERSTOP-RX (75mm(3”)min coverage)
BENTOSEAL
Cast-in-place concrete wall
Woodlagging
Steel piling
Retained earth
VOLTEX main course
BENTOSEAL between sheets of VOLTEX
VOLTEX strip over pile prior to main course
Fill gap with solid material
Cast-in-place concrete wall
Plate & bolts secure lagging
WATERSTOP-RX (75mm(3")min coverage)
Figure2.11– Lagging secured to inside surfaceof front pile flange.Install VOLTEX strip to cover mounting plates and bolts prior to main course(PlanView)
Figure2.10–Laggingsecuredtooutsidesurfaceof frontpileflangeprovidingsmoothsurface(PlanView)
Figure2.12–Lagging secured to insidesurfaceofbackpile flange.Install BENTOSEAL and VOLTEX strip prior to main VOLTEX course and inward BENTOSEALcant.(PlanView)
Steel piling
Woodlagging
VOLTEX main courseBENTOSEAL, apply two cants – one before VOLTEX strip and one after main course
WATERSTOP-RX to exterior of cut rebar hole in steel piling
VOLTEX strip over pile prior to main VOLTEX course
WATERSTOP-RX (75mm(3”)min coverage)
Figure2.13–WALLEXCAVATIONATGRADE–Cementitiousboardpro-tectswaterproofingduringexcavationandremovalofsteelpiletopandwood lagging
VOLTEX Cementitious board
Woodlagging
Steel H-pile, top removed with excavation work
AQUADRAIN sheet drainCast-in-place concrete wall
PRODUCT MANUAL
- 16 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure 2.14 – Sheet pile interlock detail
Figure 2.15 – Install VOLTEX onto metal sheet piling retaining wall with powder-actuated fasteners
2.3 METAL SHEET PILING RETAINING WALLVerify the following substrate preparation work has been completed. Then install VOLTEX following the property line installation guidelines in Section 2.1 on page 12 and 13. Special knurled powder-actuated fas-teners are recommended to secure VOLTEX to the metal sheet piling.
Preparation:Trowela12mm(1/2”)thicklayerofBENTOSEAL along all sheet piling knuckles. Fill voids or cavities at tieback plates with ce-mentitious grout or compacted soils. If excessive water is penetrating the sheet piling knuckles, Bentogrout can be injected to the outside of theknuckletostopwaterflow(Figure2.14).ConsultCETCOforBentogrout applications and installation guidelines.
Alternate Plywood MethodAlternatively,12mm(1/2”)plywoodmaybefastenedtothesheetpilingtocreateaflatsurfaceuponwhichVOLTEXisfastened.Allvoidspacesbetweentheplywoodandsheetpilingmustbefilledwithcompactedearth or concrete. Apply VOLTEX to plywood following “Property Line Construction”GuidelinesinSection2,Page11.
BENTOGROUT injected to exterior sideofsheetpileinterlock(perprojectrequirements)
Retained earth
Sheet piling
VOLTEXBENTOSEALSheet pile interlock
Cast-in-place concrete wall
VOLTEX vertical seams should not occur at interlocking of sheet piling
VOLTEX
WATERSTOP-RX (75mm(3”)mincoverage)
Retained earth
Metal sheet piling
Completelyfillareabehind plywood with compacted soil or concrete
Optional technique: plywood fastened to sheet piling to form flatsurfacetomountVOLTEX
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
2.4 EARTH FORMED SHOTCRETE RETAINING WALLVerify the following substrate preparation work has been completed. Then install VOLTEX following the property line installation guidelines in Section 2.1 on page 12 and 13.
Preparation: The surface of the earth formed diaphragm wall must besufficientlyplanartoprovideanadequatelysmoothsurfacetoapplyVOLTEX. VOLTEX can be applied over large, relatively shallow indenta-tions. The surface should not contain voids or sharp protrusions in ex-cessof25mm(1”).FillallvoidswithcementitiousgroutandremoveprotrusionspriortoinstallingVOLTEX(Figure2.18).
Figure 2.17 – Earth formed concrete retention wall with concrete cais-sonsupports.(PlanView)
Figure 2.18 – VOLTEX installation over an earth formed shotcrete retention wall prior to cast-in-place concrete wall
Figure 2.16 – Grout void area and remove protrusions to provide smooth surface for VOLTEX
WATERSTOP-RX 75mm(3")min-coverage)
Grout irregular areas
VOLTEX
Cast-in-place concrete wall
Shotcrete retaining wall (non-structural)
Shotcrete retaining wall (non-structural)
VOLTEX
WATERSTOP-RX
Cast-in-place concrete wall
Retained earth Concrete caisson
Retained earth
Shotcrete retaining wall (non-structural)
VOLTEX
VOLTEX corner transition sheet horizontally oriented
Grouted depressions and irregular surfaces
100mm(4”)
100mm(4”)INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
PRODUCT MANUAL
- 18 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure2.19–CutRockexcavationwithshotcreteappliedtoprovideasmoothsurfaceforwaterproofinginstallation
Figure2.20–Fillinrecessesbetweencastcaissonswithgrouttopro-videsmoothsurface(PlanView).
2.5 AUGER CAST CAISSON WALLSVerify the following substrate preparation work has been completed. Then install VOLTEX following the property line installation guidelines in Section 2.1 on page 12 and 13.
Preparation: The surface of auger cast caisson and cut rock excava-tionwallsmustbesufficientlyplanartoprovideanadequatelysmoothsurface to apply VOLTEX. VOLTEX can be applied over large, relative-ly shallow indentations where VOLTEX can conform tight against the surface. The surface should not contain voids or sharp protrusions in excessof25mm(1”).Fillalllargerecessesbetweencaissonswithce-mentitiousgroutpriortoinstallingVOLTEX(Figure2.20).Cutrockexca-vations typically require shotcrete or grout work to provide acceptable surfacetoinstallVOLTEX(Figure2.19).
Figure 2.21 – VOLTEX installation over an auger cast concrete retention wall prior to cast-in-place concrete wall
Retained earth side Concrete caisson
VOLTEX Grout recesses
Retained earth
VOLTEX
100mm(4”)
VOLTEX corner transi-tion sheet horizontally oriented
Shotcrete retaining wall (non-structural)
Grouted depressions and irregular surfaces
Cut rock formation from excavation
Shotcrete applied to cut rock surface(non-structural)
VOLTEX TB-6SNVOLTEX
WATERSTOP-RX
BENTOSEAL detailing
DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
InstallVOLTEXorVOLTEXDSwiththedarkgray(woven)geotextilesideagainst the concrete wall on cast-inplace concrete foundation walls priortobackfilling.VOLTEXmaybeappliedassoonastheformsareremoved. It is not necessary to wait for the concrete to completely cure. Use VOLTEX with concrete cast with conventional forms that produce smooth surface.
3.1 SURFACE PREPARATIONFooting should be swept clean of silt, rocks and debris to provide VOLTEX with direct contact to the concrete in the application area. The wall sur-face must be properly prepared before VOLTEX is installed. Areas of surfacehoneycombingorvoidsshouldbefilledwithcementitiousgroutor BENTOSEAL.Protrusionsofover6mm(1/4”)shouldbeknockedoffsmooth with the concrete surface. Concrete work should include com-pletelyfillingtaper-tieholeswithnon-shrinkcementitiousgroutandapiece of WATERSTOP-RXcenteredinthewall(Figure3.1).ApplyBEN-TOSEALoverexteriorgroutedsurfaceofallformtieholes(Figure3.1).
3.2 INSTALLATIONBefore installing thefirstcourseofVOLTEX,placeHydrobarTubesatthewall/footinginsidecorner(Figure3.2).“Butt”theendsofHydrobarTubes together to form a continuous line.
Beginning at the bottom corner of the wall, install VOLTEX horizontal-lyorientedwith1.5m(5’)ononewallandtheremainderaroundthecornerontheotherwallsurface(Figure3.2).CutthebottomedgeofVOLTEXatthecorneraminimumof150mm(6”)sothatVOLTEXcanbe extended onto the footing. Fasten VOLTEX into position with washer headfastenersmaximum600mm(24”)oncenter.Thencutandinstalla VOLTEX section over the uncovered footing corner area. Apply BEN-TOSEALattheVOLTEXsectiontoVOLTEXoverlaps.(Figure3.2).
Install adjacent VOLTEX rolls of the bottom course horizontally oriented. Eachrollshouldoverlaptheprecedingrollaminimum100mm(4”)andshould extend onto the footing aminimum150mm (6”). At verticalinsidecornersapplyacontinuous19mm(3/4”)filletofBENTOSEAL directlyinthecornerpriortoinstallingVOLTEX(Figure3.3).Staggerallverticaloverlapjointsaminimumof300mm(12”)(Figure3.4).Whenhydrostatic conditions exist, the vertical wall VOLTEX should cover the entirefootingandoverlaptheunderslabwaterproofingaminimum150mm(6”)(Figure3.6).TapeallVOLTEXDSmembraneoverlapseamswithCETCO Seamtape.
SECTION 3 BACKFILLED WALLS
Figure 3.2 – Start VOLTEX at the corner horizontally. Place cut section at corner and apply BENTOSEAL at overlaps
Figure 3.1 – Concrete form tie details
Figure3.3–ApplyfilletofBENTOSEAL to inside corner
Snap-Tie Taper-Tie
Non-shrink groutConcrete Tile BENTOSEAL exterior
face of form tie
Non-shrink grout
VOLTEX
Install VOLTEX around corner
Hydrobar Tube under VOLTEX
VOLTEX
BENTOSEAL
InstallVOLTEXtofitcorner
Install VOLTEX tofitcorner
19mm(3/4”)filletofBENTOSEAL
Inside corner of cast-in-place concrete wall
WATERSTOP-RX
PRODUCT MANUAL
- 20 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure3.4–VOLTEXinstalledoncast-in-placebackfilledwall,overlapedges100mm(4”)andstaggerverticalendlaps
Backfill: The excavated area should be backfilled and compactedpromptlyafterVOLTEXisinstalled.UseplacedbackfillasaplatforminapplyingsucceedingVOLTEXcourses.Thebackfillmustbecompactedtoaminimum85%ModifiedProctordensity.Backfillshouldconsistofcompactible soilsorangularaggerate (19mm (3/4") or less) freeofdebris,sharpobjects,andstonelargerthan19mm(3/4”).Whenback-fillcannotbeplacedimmediatelyprotectmembranefromprecipitationand debris by sealing edges to concrete substrate with CETCO SEAM-TAPE or tooled bead of CETSEAL. This temporary temination can be left in place covered by subsequent membrane overlap. Figure3.5–MinimumVOLTEXoverlapdetail;tapeVOLTEXDSseams
Figure3.6–Stepbystepdetailofoutsidewallbasecornerinstallation(hydrostaticcondition)
Trowel BENTOSEAL over grouted form-tie holes
VOLTEX
Hydrobar Tubes placed under VOLTEX at transition at footing
Stagger end seams a minimum 300mm(12”)
Mechanically fasten VOLTEX maximum 600 mm (24”) on center
Install CETCO Seamtape atVOLTEXDSmembraneoverlaps
100mm(4”)overlap
WATERSTOP-RX(min75mm(3”))coverage)
150mm(6”)
Min. 100mm (4”)
Cast-in-place concrete wall
Washer-headmechanicalfastener
VOLTEXDS
CETCO Seamtape
Step 1. Step 2.
Step 3. Step 4.
VOLTEX turned up from underslab
Trowel BENTOSEAL at corner
CutandfoldfirstVOLTEX section
Cut and fold second VOLTEX section
Place third VOLTEX piece over the previous two sections
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE AGAINST THE CONCRETE WALL
Term bar and BENTOSEAL
www.cetco.com
3.3 BACKFILLED WALL PENETRATIONSCutVOLTEXtocloselyfitaroundpenetrations.AfterinstallingVOLTEX,trowelaminimum19mm(3/4”)thickfilletofBENTOSEAL around the penetrationtocompletelyfillanyspacebetweenthepenetrationandthe VOLTEX edge. The BENTOSEAL should extend onto the penetration 38mm(1–1/2”)andcoverVOLTEX’sedge(Figure3.7).Inareaswheremultiple penetrations are close together, it may be impractical to cut VOLTEXtofitaroundbaseofeachpenetration.Therefore,applya19mm (3/4”) thick fillet of BENTOSEAL around each penetration and covertheentiresurfacebetweenthepenetrations(Figure3.8).ExtendBENTOSEAL38mm(1–1/2”)ontothepenetrations.
Figure 3.7 – Single penetration cast-in-place wall detail
Figure3.10–InstallVOLTEXbetweenpenetrationswithaccessibility.Trowel BENTOSEAL around penetrations
Figure3.8–CutVOLTEXtofitaroundpenetrations
Figure3.9–Closemultiplepenetrations.TrowelBENTOSEAL around and between penetrations
VOLTEX
Cast-in-place concrete wall
BENTOSEAL troweled around penetration
Pipe
WATERSTOP-RX (min.75mm(3”)coverage)
VOLTEX Apply BENTOSEAL to cut out area
VOLTEX cut out around multiple penetrations
WATERSTOP-RX
VOLTEX
BENTOSEAL
Pipe
BENTOSEAL
Pipe
VOLTEX
WATERSTOP-RX
WATERSTOP-RX
VOLTEX
BENTOSEAL
Pipe
BENTOSEAL
VOLTEX
BENTOSEAL
Pipe
VOLTEX
WATERSTOP-RX
PRODUCT MANUAL
- 22 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
3.4 GRADE TERMINATIONSTerminateVOLTEXmembrane300mm(12”)belowfinishedgradeel-evationwithwasher-headfastenersmaximum300mm(12”)oncen-ter. Install ENVIROSHEET flashing to primed concrete substratewithbottom edge overlapping top edge of VOLTEX membrane minimum 100mm(4”).Overlapallrollendsaminimum100mm(4”)toformacontinuousflashing.Heightofflashingshallbeperprojectdetailsandspecifications.InstallarigidterminationbaralongtopedgeofENVIRO-SHEET;fastenedmaximum300mm(12”)oncenter.Completegradetermination detail with tooled bead of CETSEAL along the top edge, at allpenetrationsthroughtheflashing,andallexposedoverlapseams.Grade terminations are illustrated in Figures 3.11 and 3.12.
3.5 MASONRY BLOCK WALLSVOLTEX is not recommended forwaterproofingmasonry blockwalls.Consult with CETCO regarding recommended products and installation guidelines for masonry block walls.
4.1 PRECAST CONCRETE CONSTRUCTIONConsult CETCO regarding products and special installation guidelines for precast concrete plank decks, precast earth covered roofs, and pre-cast wall construction.
4.2 CONTAMINATED CONDITIONSUseVOLTEXCR(ContaminantResistant)inconditionswheretheground-water contains high concentrations of chemicals or saline. These condi-tions are typically encountered at industrial sites and coastal regions. If groundwater contains strong acids, alkalies, or has aconductivityof2,500μmhos/cmorgreater (highsaltconcentration),water samples should be submitted to CETCO for compatibility testing.
Forcompatibility testing,provide two (2) litersofsitegroundwater ina clean, unbreakable container. Shipwater sample to:CETCO,2870ForbsAve,HoffmanEstates,IL60192,ATTN:BMGFieldServices.Uponanalysis, CETCO will provide a written report evaluating the water’s compatibilitywithVOLTEXandrecommendanyspecialproductand/orinstallation requirements
Figure3.11–Terminationatfinishedgrade
Figure 3.12 – Termination at grade with brick veneer
SECTION 4 SPECIAL CONDITIONS
IMPORTANT NOTICEFOR SHOTCRETE, PRECAST CONCRETE, EXPANSION JOINTS AND OTHER APPLICATIONS NOT COVERED IN THIS MANUAL, CONTACT CETCO FOR TECHNICAL ASSISTANCE AND INSTALLATION GUIDELINES.Brick veneer
Weephole
CETSEAL
Finished grade
ENVIROSHEET grade flashing
VOLTEX
ENVIROSHEET grade flashing
VOLTEX
100mm(4”)min
Finished grade
Tooled bead of CETSEAL
Terminationbarfastened300mm(12”)maximumoncenter
Tooled bead of CETSEAL
Terminationbarfastened300mm(12”)maximumoncenter
www.cetco.com
The information and data contained herein is believed to be accurate and reliable.Specificationsandotherinformationcontainedhereinsupersedeallpreviously printed material and are subject to change without notice. Manufacturer’s warranty of installed system is available. Contact seller for terms and sample documents including all limitations. All goods sold by seller are warranted to be free from defects in material and workmanship. The foregoing warranty is in lieu of and excludes all other warranties not ex-pressly set forth herein, whether expressed or implied by operation of law or otherwise including but not limited to any implied warranties of merchant-abilityorfitness. Seller shall not be liable for incidental or consequential losses, damages or expenses, directly or indirectly arising from the sale, handling or use of the goods, or from any other cause relating thereto, and seller’s liability hereun-derinanycaseisexpresslylimitedtothereplacement(intheformoriginally
shipped)ofgoodsnotcomplyingwiththisagreementoratseller’selection,tothe repayment of, or crediting buyer with, an amount equal to the purchase price of such goods, whether such claims are for breach of warranty or neg-ligence. Any claim by buyer with reference to the goods sold hereunder for any cause shall be deemed waived by buyer unless submitted to seller in writing within thirty(30)daysfromthedatebuyerdiscoveredorshouldofdiscovered,anyclaimed breach. Materials should be inspected and tested by purchaser prior to their use if productqualityissubjecttoverificationaftershipment.Performanceguaran-tees are normally supplied by the applicator.
Note:VOLTEXwaterproofingsystemisnotanexpansionjointmaterial.
LIMITED WARRANTY
PRODUCT TABLEPRODUCT DESCRIPTION
VOLTEX Bentonitegeotextilewaterproofingmembranewithstandardsodiumbentonite
VOLTEX CR Bentonitegeotextilewaterproofingmembranewithcontaminantresistantsodiumbentonite
VOLTEXDS Bentonitegeotextilewaterproofingmembranewithstandardsodiumbentoniteandapolyethylenelinercomponent
VOLTEXDSCR Bentonitegeotextilewaterproofingmembranewithcontaminantresistantsodiumbentoniteandapolyethylenelinercomponent
IMPORTANT NOTICEContact CETCO for verification of specification and instal-lation requirements to comply for eligibility of HydroShield Warranty.
www.cetco.com
©2015CETCO.IMPORTANT:Theinformationcontainedhereinsupersedesallpreviousprintedversions,andisbelieved to be accurate and reliable. For the most up-to-date information, please visit www.CETCO.com. CETCO accepts no responsibility for the results obtained through application of this product. CETCO reserves the right to update information without notice.
FORM:PM_VOLTEX_AM_EN_201509_V7
www.cetco.com | [email protected]
UPDATED:SEPTEMBER2015