72
TICEL BIO PARK- II ACMV WORKS ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM TICEL BIO PARK II INTERNATIONAL COMPETITIVE TECHNO COMMERCIAL TENDER VOLUME 4 BILL OF QUATITIES PROVIDING SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF ACMV WORKS IN CONSTRUCTION OF LABORATORY COMPLEX – TICEL BIO PARK – II AT TARAMANI, CHENNAI (3 BASEMENTS+G+12 UPPER FLOORS) DUE DATE FOR SUBMISSION: ON OR BEFORE 28 th July, 2011 at 15.00 Hours TO BE SUBMITTED TO: M/s.TICEL BIO PARK LTD (First Floor) CSIR Road, Taramani, Chennai - 600 113. Telephone No.: +91 44 22542061 Fax No: 91-44-2254 2055 E-Mail:[email protected] ENGINEERING CONSULTANTS: M/s .TAAMAESEK ENGINEERING CONSORTIUM Architects & Engineers No 5, 1 st Floor, Bishop Wallers Avenue West. Off TTK Road, Mylapore, Chennai- 600 004 – INDIA. Tel No: 044-24671139 / 57 Fax No: 044-24672237 E-Mail: [email protected] OWNERS ENGINEERS: M/s.SPECTRAL SERVICES CONSULTANTS PVT LTD No.51, R.K.Mutt Road, Mylapore, Chennai - 600 004. TEL : +91 44 2461 3006 / 2461 8050 FAX : +91 44 2461 7956 TENDER SUBMITTED BY: M/s._________________________ Address_____________________ ____________________________ ____________________________ JUNE- 2011

Volume - 4

Embed Size (px)

Citation preview

Page 1: Volume - 4

TICEL BIO PARK- II ACMV WORKS

ENGINEERING CONSULTANT: TAAMAESEK ENGINEERING CONSORTIUM

TICEL BIO PARK II

INTERNATIONAL COMPETITIVE TECHNO COMMERCIAL TENDER VOLUME 4

BILL OF QUATITIES

PROVIDING SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF ACMV WORKS IN CONSTRUCTION OF LABORATORY COMPLEX – TICEL BIO PARK – II

AT TARAMANI, CHENNAI (3 BASEMENTS+G+12 UPPER FLOORS)

DUE DATE FOR SUBMISSION: ON OR BEFORE 28th July, 2011 at 15.00 Hours

TO BE SUBMITTED TO: M/s.TICEL BIO PARK LTD

(First Floor) CSIR Road, Taramani, Chennai - 600 113. Telephone No.: +91 44 22542061 Fax No: 91-44-2254 2055 E-Mail:[email protected]

ENGINEERING CONSULTANTS: M/s .TAAMAESEK ENGINEERING CONSORTIUM

Architects & Engineers No 5, 1 st Floor, Bishop Wallers Avenue West. Off TTK Road, Mylapore, Chennai- 600 004 – INDIA. Tel No: 044-24671139 / 57 Fax No: 044-24672237 E-Mail: [email protected]

OWNERS ENGINEERS: M/s.SPECTRAL SERVICES CONSULTANTS PVT LTD No.51, R.K.Mutt Road, Mylapore, Chennai - 600 004. TEL : +91 44 2461 3006 / 2461 8050 FAX : +91 44 2461 7956 TENDER SUBMITTED BY:

M/s._________________________ Address_____________________ ____________________________ ____________________________

JUNE- 2011

Page 2: Volume - 4

TICEL BIO PARK II ACMV WORKS

S.NO DESCRIPTION AMOUNT REMARKS

1 Cost of capital works ( Vide abstract -II)

2 Cost of Operation

3 Cost of non comprehensive maintenance

GRAND TOTAL

Signature of Tenderer

ABSTRACT - I

SUMMARY OF PRICES

ACMV WORKS AND OPERATION AND MAINTENANCE

TICEL BIO PARK-II

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM

Page 3: Volume - 4

TICEL BIO PARK II ACMV WORKS

S.NO DESCRIPTION AMOUNT REMARKS

1 A Service block plant room

2 B Trench header line for Phase 2&3

3 C Ticel Bio Park-II-Main Building

4 D Car park ventilation system

5 E Fumigation system

6 F Façade ventilation system

7 G Ground floor and common area AHUs

8 H Lab typical floor

9 I BTCIF LAB AHUS

10 J Interior

GRAND TOTAL C/o ABSTRACT-I

Signature of Tenderer / Contractor

TICEL BIO PARK-II

ACMV WORKS -ABSTRACT-II

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM

Page 4: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply ErectionA SERVICE BLOCK-PLANT ROOM1 Supply, installation, testing and commissioning of (imported) Act.cap. of 340TR Brine Air

cooled screw chillers, temp: 4 deg C leaving and 9 deg C entering condition, at normal mode and charging mode at - 5 deg C leaving and 0 deg C entering, chiller should able to run variable flow, VFD ( BMS compatible ), vibration Isolator and required adapotor box for cable termination, main disconect switch, Plant manager integerator (consider provision for five chillers), addtional pressure diff.sensor,.incoming adaptor box, flow swtich, grooved coupling coupling for inlet and outlet connection, Black Epoxy coated fins, Condensor fins covered with 12 guage SS316 mesh. compressor sound jacket using Armosound material required thickness with 22G Al cladding with suitable vibration isolator.

1 nos

2 Supply,installtion, testing and commissioning of 4500TRH Thermal staorge tank cooling capacity, with necessary isolation valves, comprising of BMS compatible ice inventory metering system with BTU meters, Sizing of tank as per manufacturer standard, Available space 1.8m height at first basement & second basement , Selection of tank as per site requirment with inclusives of required civil foundations.

1 set

3 Supply,installation testing and commisioing of Plated type heatexchangers with extended stub flange and 12Gauge SS try,Transfering of heat from mono ethyline glycol 30% water solution to water for the following condition 1500TR, Brine side flow temp. 4 and 9deg C and water side flow temp 14 and 6 deg C selection of heatexchanger pressure difference 0.5bar

2 nos

4 Supply,installation, testing and commissioning of (imported) Endsuction long coupled base mounted for primay Brine air cooled chiller pumps with bronze impeller, capacity of 1020gpm@22m head with suitable insulation and 24g AL cladding.

2 nos

5Supply and installation of commissioning of suitable VFDs with indoor panel(cubical) with individual Isolator and required adapotor box for cable termination and each pump having a dp sensor and releated cabling between sensor to vfd - Brine primary pump(2 nos vfd + 2nos space provision )

1 set

6 Supply,installation testing and commissioning of (imported)Endsuction long coupled base mounted with bronze impeller for PHE brine side pumps, capcity of 3225 gpm@26m head with suitable insulation and 24g AL cladding.

3 nos

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 1 of 64

Page 5: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

7 Supply, installation and commissioning of comprising of suitable VFDs with indoor panel(cubical) with individual Isolator and required adapotor box for cable termination,each pump having a dp sensor/tempreature sensor and cabling between sensor to vfd - Phe brine side pump(3nos vfd+1No space provision)

1 set

8 Supply, installation and commissioning of (imported) Endsuction long coupled base mounted with Bronze impeller for PHE water side pumps, capacity of 3202 gpm@26m head with suitable insulation and 24g AL cladding.

3 nos

9Supply, installation and commissioning of comprising of suitable VFDs with indoor panel(cubical) with indoor panel,each pumps is having pressure cum temprature sensor based vfd operation and related cabling between sensor to vfd - PHE water side pumps (3nos vfd + 1No Space provision)

1 set

10 Supply,installation and commissioning of (imported) double suction top discharge, long coupled base mounted for Secondary pumps with bronze impeller with , capacity of 3800 gpm@36m head with suitable insulation and 24g AL cladding.

3 nos

11 Supply,installation and commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination (3nos vfd+1No space provision) and pump prgram logic controller for pump operation, 3 nos of dp sensor and appx.1560 rmt related cabling and GI conduits

1 set

12 Supply,installation and commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination for 7.5 kw (3nos vfd ) each VFD having 1no of dp sensor and related cabling from sensor to vfd, for existing chilled primary pumps & removal of existing starter panel & related cables and refixing of same cables for new VFD.

1 set

13 Supply, installation and commissioning of commissioning of suitable VFD with indoor panel (cubical) with invidual Isolator and required adapotor box for cable termination for 7.5 kw (3nos vfd ) each VFD having 1no of dp sensor and related cabling sensor to vfd for existing brine primary pumps & removal of existing starter panel & related cables and refixing of same cables for new VFD.

1 set

14Supply and installation of Pump Inertia base with spring of 20mm deflection

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 2 of 64

Page 6: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a Chiller Brine primary pumps 2 nos

b Chilled water Secondary pumps 3 nos

c PHE pumps- Brine side 3 nos

d PHE pumps- water side 3 nos15 Supply,installation and commissioning of Butterfly Valve with extended stem of 100mm

length, pressure rating of PN16, Suitable for pipes - SS wafer/stem for brine application, with insulation and 24g AL cladding

a 650 mm dia qro nos

b 600 mm dia 2 nos

c 500 mm dia qro nos

d 450 mm dia 4 nos

e 400 mm dia 34 nos

f 350 mm dia 8 nos

g 300 mm dia qro nos

h 250mm dia qro nos

i 200mm dia 16 nos

j 150 mm dia qro nos

k 100 mm dai 74 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 3 of 64

Page 7: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

l 80 mm dia qro nos

16 Supply,installation and commissioning of Swing type Non return Valve suitable for the pipes, pressure rating of PN16, with insulation and 24g AL cladding

a 450 mm dia qro nos

b 400 mm dia 9 nos

c 350 mm dia qro nos

d 300 mm dia qro nos

e 250 mm dia qro nos

f 200 mm dia 2 nos

17 Supply, installation and commissioning of Metallic bellows suitable for pipes, pressure rating of PN16

a 450 mm dia qro nos

b 400 mm dia 18 nos

c 350 mm dia qro nos

d 300 mm dia qro nos

e 250 mm dia qro nos

f 200 mm dia 6 nos18 Supply, installation and commissioning of Suction Guide suitable for pipes with pressure

rating of PN16-with insulation and 24g AL claddinga 450 mm dia qro nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 4 of 64

Page 8: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b 400 mm dia 9 nos

c 350 mm dia qro nos

d 300 mm dia qro nos

e 250 mm dia qro nos

f 200 mm dia 2 nos

19 Supply,installation and commissioning of two way on/off motorised isolation valve suitable for pipes, with actuator 230v power supply,BMS compatible, pressure rating of PN16,suitable for brine application-with insulation and 24g AL cladding

a 650 mm dia qro nos

b 600 mm dia 2 nos

c 500 mm dia qro nos

d 450 mm dia 4 nos

e 400 mm dia 2 nos

f 350 mm dia 2 nos

g 300 mm dia qro nos

h 250 mm dia qro nos

i 200 mm dia 1 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 5 of 64

Page 9: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

j 150 mm dia qro nos20 Supply,installation and commissioning of Semi automatic Balancing valve suitable for pipes -

digital display, BMS compatible, suitable for 230 volt supply,pressure rating of PN16-with insulation and 24g AL cladding

a 500 mm dia qro nos

b 400 mm dia 2 nos

c 350 mm dia 2 nos

d 300 mm dia qro nos

e 250 mm dia qro nos

f 200 mm dia 1 nos

21 Supply, installation of glycol/water mixing syntex tank of 2000 lits with 100mm thick rigid Puff insulation with 24g Al clading 2 nos

22Supply,installation of glycol open expansion Steel tank of 5000 lits with related valve aux. with supports, 100mm thick rigid puff insulation with 20G GI galding with float valve arrangement 1 nos

23Supply,installation of pressurised closed expansion tank with stand by motor and bms compatible -capacity of 3000 lit. for water. 100mm thick rigid puff insulation with 20G GI galding with float valve arrangement

1 nos

24Supply and installation of small pump for mixing purpose of capcity 2m3/hr @18m head with level controller, starter panel & related power cabling between starter to motor approximately 30rmt

1 nos

25 Supply and installation of 50mm GI piping for the above 60 Rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 6 of 64

Page 10: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

26 supply,installation of MS channel works for following

a supply and instaltion of ms angle suport for plant room supports 4000 kg

b supply and instaltion of Ms Checkered platr for shaft closings etc. 1000 kg27

Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, anchors, saddles, sleeves, brackets, welding, smooth finishing, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil foundation inclusive of scope including, excavation, dewatering, brickworks, pedestals, covers, etc.,

a 600mm dia 180 Rmt

b 550mm dia qro Rmt

c 500mm dia qro Rmt

d 450 mm dia 70 Rmt

e 400 mm dia 90 Rmt

f 350 mm dia 30 Rmt

g 300 mm dia qro Rmt

h 250mm dia qro Rmt

i 200mm dia 40 Rmt

j 150mm dia qro RmtENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 7 of 64

Page 11: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

k 125mm dia qro Rmt

l 100 mm dia 200 Rmt

m 50 mm dia qro Rmt

28 Supply, charging and commissoing of mono ethylene glycol-30% concentration-App. Volume 320 cum of glycol 1 lot

29 Supply,Laying and commisioing of PVC insulated, copper conductor 1.1kv grade, Armoured copper cable

a 1C x 240 sqmm xlpe 180 Rmt

b 4C X70 sqmm xlpe 144 Rmt

c 4c X35 sqmm xlpe 152 Rmt

d 4C x 16sqmm xlpe 175 Rmt

e 4C x 10sqmm xlpe 125 Rmt

f 4c x 2.5sqmm 60 Rmt

30 Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

a 1C x 240 sqmm xlpe 10 set

b 4C X70 sqmm xlpe 12 set

c 4c X35 sqmm xlpe 10 set

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 8 of 64

Page 12: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

d 4C x 16sqmm xlpe 10 set

e 4C x 10sqmm xlpe 10 set

f 4c x 2.5sqmm 24 set

31 Supply and installation of Aluminium earth platea 50 x6mm 240 Rmt

b 40 x6mm 48 Rmt

c 25 x6mm 144 Rmt

32 Supply and installation of GI Perforated Tray with angle supportsa 600mm width 60 rmt

b 450mm width 240 rmt

c 300mm width 60 rmt

d 200mm width 48 rmt

e 150mm width 72 rmt

33 Supply and installation of Pressure gauge with SS syphons,niddle Valves,100mm dia range -0 to 15 kg/cmsq 28 nos

34 Supply and installation of Temp. gauge with SS thermowell,100mm dia, -10 to 20 deg C 10 nos

35 Supply and installation of 25mm Ball valves with flange end, pressure rating PN 16 with insulation and 24g AL cladding 24 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 9 of 64

Page 13: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

36 Supply and installation of Auto air vent size 25mm dia with 9 rmt 20mm copper piping 10 nos

37 Supply , installation , testing and commissioning of Electromagnetic Descaler for Chilled water flow suitable capacity-600 mm dia

1 nos

38 Supply , installation , testing and commissioning of Centrifugal, Side Stream Filter for Chilled water, 600mm dia-6480 gpm.

1 nos

39 Supply, installation and commissioning of trible duty valves for pumps, pressure rating of PN16 -with insulation and 24g AL cladding

a 450 mm dia qro nos

b 400 mm dia qro nos

c 350 mm dia qro nos

d 300 mm dia qro nos

e 250 mm dia 2 nos

f 200 mm dia 9 nos

Total

Note : Whereever BMS compatible shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 10 of 64

Page 14: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

B TRENCH PIPING-HEADER LINE FOR FOR PHASE 2 & 340 Supply, installation and commissioning of MS C class pipe with Regid puff, density 48

Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc.,

a 600mm dia 220 rmt

b 450mm dia 340 rmt

c 400mm dia 90 rmt

d 350mm dia qro rmt

e 250mm dia qro rmt

41Supply,installation and commissioning of Butterfly value, pressure rating of PN16

a 450 mm dia qro nos

b 400 mm dia qro nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 11 of 64

Page 15: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

c 350 mm dia qro nos

d 250 mm dia qro nos

42 Supply,installation and commissioning of Semi automatic Balancing valve with BMS compatible, pressure rating of PN16-with insulation

a 450 mm dia 1 nos

b 400 mm dia 1 nos

c 350 mm dia qro nos

d 250 mm dia 2 nos

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 12 of 64

Page 16: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

C TICEL BIO PARK - II MAIN BUILDING

43 Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.

a 450mm dia 10 rmt

b 400mm dia 24 rmt

c 350mm dia 40 rmt

d 300 mm dia 80 rmt

e 250 mm dia 80 rmt

f 200 mm dia 90 rmt

g 150 mm dia 30 rmt

h 125 mm dia 930 rmt

i 100 mm dia 360 rmt

j 80 mm dia 880 rmt

k 65 mm dia 380 rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 13 of 64

Page 17: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

l 50 mm dia 2100 rmt

m 40 mm dia 300 rmt

n 32 mm dia 4200 rmt

o 25 mm dia 350 rmt

p 20 mm dia qro rmt

44 Supply and installation of GI pipe with Insulated Condensate Drain piping-25mm thick regid puf density 48 Kg/m3, 24G AL. cladding

a 50 mm dia 900 rmt

b 40 mm dia 800 rmt

c 32 mm dia 500 rmt

d 25 mm dia 210 rmt

45 Supply,installation and commissioning of Semi automatic Balancing valve with BMS compatible, pressure rating of PN16-with insulation,suitable for 230v supply

a 125 mm dia 12 nos

b 100 mm dia 2 nos

c 80 mm dia 12 nos

d 65 mm dia 2 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 14 of 64

Page 18: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

46 Supply,installation and commissioning of CHILLED WATER MANIFOLD rating of PN16-with insulation and 24G al cladding. Chilled Water Manifold size suitable to AHU ( Includes 5 Nos butterfly valve/ ball Valve, 1 self modulating valve(auto balancing/modulating with thermostat), 1 No Y strainer, 2 Nos Pressure gauges(with ss styphon&Needle valve), 2 Nos temperature Gauges(with ss thermowell), 1 No drain valve, 1 no fo auto air vent and inclusive Flange provision for one BTU.

a 80 Dia Size Manifold qro nos

b 65 Dia Size Manifold 4 nos

c 50 Dia Size Manifold 94 nos

d 40 Dia Size Manifold 12 nos

e 32 Dia Size Manifold 104 nos

f 25 Dia Size Manifold 16 nos

g 20 Dia Size Manifold qro nos

47 Supply,installation and commissioning of Butterfly Valve with extended stem of 100mm length, pressure rating of PN16, Suitable for brine application -SS wafer/stem for brine application.-with insulation and 24g AL cladding

a 400 mm dia qro nos

b 300 mm dia qro nos

c 125 mm dia 24 nos

d 100 mm dia qro nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 15 of 64

Page 19: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

e 65 mm dia 24 nos

f 50 mm dia 2 nos

48 Supply,installation and commissioning of Self Dynamic Valve with extended stem of 100mm length, pressure rating of PN16, SS wafer/stem for brine application.-with insulation and 24g AL cladding,suitable for 230v supply power

a 65 mm dia 20 nos

b 50 mm dia 18 nos

c 40 mm dia 16 nos

d 32 mm dia 12 nos

e 25 mm dia 12 nos

49 Supply,installation and commissioning of Ball valve with flange end, pressure rating of PN25-with insulation and 24G al cladding

a 32 mm dia 12 nos

b 25 mm dia 50 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 16 of 64

Page 20: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

50 2 TR capacity, 4 row cooling coil, CHILLED WATER cassette Units. The cassete units shall be complete with f valves(ball valve with y sainer,self modulating valve and copper pipe for valve connections) - ATM

2 nos

a Supply and installation of isolator panel for the above 2 nos51 Supply and installation of Pressure differencial valves for rasier shaft, BMS compatibility with

insulation & 24G al cladding.- for Header line

a 450mm dia 2 nos

b 300mm dia 2 nos

c 250 mm dia 2 nos

d 200 mm dia 2 nos52 Supply, instalation and commissioning of Double skin low leakage VAVs, selection of VAV 5

to 6 m/sec, dba level less than 30db,A in built thermostart and controller, suitable size of cabling, conduiting, cat 5 cable for between thermostart to VAV, and VAV to isolater, required 5A isolator, fast activating type of VAV that is 3 to 5 seconds, interlocking arrangement between AHU to VAV for on/off operation

a 450 to 550 CFM 2 nos

b 700 to 800 CFM 178 nos

c 900 to 1000CFM 2 nos

d 1000 to 1200 CFM 1 nos

e 1800 to 2000 CFM 1 nos

f 3400 to 3600 CFM 1 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 17 of 64

Page 21: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

HEAT RECOVERY UNITS

Supply, installation, testing and commissioning of HEAT RECOVERY WHEEL UNIT with assembled condition all Sheet metal cabinet type double skin HRU, the inner and outer sheets of the double skin shall be 0.8 mm thick pre-coated and pre plasticized sheets with 50 mm thick . Backward aero foil curve fan, fan motor,fan casing insulation for accoustic, with enthalpy recovery, Filter section with Pre Filter, Bag Filter, Hepa filter ( Box type 450mm length ) & UVGI lamp on both sides, HEPA filter 450 mm box type,sound level shall be 60dbA from 1 mtr for both sides of air stream

Units shall be complete with opposed blade volume control dampers at both oulets, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, Fresh air temp DB:103F, WB: 82F, Exhaust air temp DB:76F, RH:55%, duct static pressure sensor (range 100-150pa), cabling between sensor to VFD, with neccessary conduits, 2 runs of 12gauge copper earth rod, apprx. 75-90 rmt.

53Supply,installation and commissioning fo HRUs with wheel -capacity of 21600cfm@ external static 50mm for both supply air and exhaust air, 75% of efficieny for sensibel and latent heat-LAB - TYPICAL FLOORS (2-12) - LAB 1- 8, exhaust/fresh air side consist of EU3,EU9 and and HEPA filter 0.1micron 99% efficiency, with Ultra violet germicidal irradiation Lamp on both sides

11 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 22 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 248 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 44 Set

d Supply and installation of Starter panel for the wheels 11 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 18 of 64

Page 22: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

54 Supply,installation and commissioning fo HRUs with wheel -capacity of 2080cfm@ total 50mm supply air and exhaust air cfm@ total 50mm, without hepa filter & uvgi lamp, 75% of efficieny for sensibel and latent heat- GF- FOOD COURT

1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 6 Set

d Supply and installation of Starter panel for the wheels 1 nos

55 Supply,installation and commissioning fo HRUs with wheel -capacity of 1720cfm@ total static 50mm supply air and exhaust air cfm@ total static 50mm, without hepa filter and uvgi lamp, 75% of efficieny for sensibel and latent heat- GF - RETAIL AREA

1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

56 Supply & installation of false ceiling type suitable terminal Box of double skin 25mm thick puf panel hooded type hepa filter with SS316 perforated grilles gear type vcd with insulated canvas, 450mm height

200 nos

57 Supply ,installation and commissioning of Hepa terminal filter for 600x600 with SS 316 grille 200 nos

58 Supply & installation of SS 316 pipe of 50mm dia for pressure difference 164 rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 19 of 64

Page 23: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

59 Magnahelic gauges 0-50 pascal with fixing box, complete CRA powder coated with ss304 covered sheet. 94 nos

60Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM, 500pa (foodcourt,retail,HRW,lift lobby,service corri. ), using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealent

a 18G 145 sqmt

b 20G 1900 sqmt

c 22G 6600 sqmt

d 24G 5160 sqmt

61 Supply and installation of al.powdered coated grilles with VCD and wooden frame for grille erection (atrium & corridors ) 60 sqmt

62 Supply and installation of VCD with gear operated type 22 sqmt

63 Supply and installation of S/R diffuser 96 sqmt

64 Supply and installation of UL listed fire dampers with actuator, BMS compatible, fire sensors and actuators,suitable for 230v poer supply 90 sqmt

65 Supply and installation of flexiable duct dia 300mm,25 micron poly laminated type with heavy duty type clamp 180 rmt

66 Supply and installation of flexiable duct dia 250mm with heavy duty type clamp 225 sqmt

67 Supply and installation of flexiable duct dia 200mm with heavy duty type clamp 115 sqmt

68 Supply and installation of Plenum boxes with inside 6mm thick nitrile rubber insulation (525x525x450 mm) 135 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 20 of 64

Page 24: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

69 Supply and installation of Plenum boxes with inside 6mm thick nitrile rubber insulation (1000Lx250Wx300H mm) 75 nos

70 Supply and installation of Butterfly dampers dia 300 mm 120 nos

71 Supply and installation of Butterfly dampers dia 250 mm 150 nos

72 Supply and installation of Butterfly dampers dia 200 mm 75 nos

73 Supply and installation of Duct Thermal Insulation of 19mm thick nitriyle rubber for SA duct passing through the Conditioned space, class O range, with 0.5 mm thick al. foil faced 420 sqmt

74 Supply and installation of Duct Thermal Insulation of 13mm thick nitriyle rubber for SA duct passing through the Conditioned space, class O range, with 0.5 mm thick al. foil faced 10000 sqmt

75 Supply and installation of Duct Thermal Insulation of 20mm thick nitriyle rubber with 0.5 mm thick al. foil faced for SA/RA duct passing thrugh the un Conditioned space 300 sqmt

76 Supply and installation of Duct Thermal Insulation of 13mm thick nitriyle rubber with 0.5 mm thick al. foil faced for RA duct passing through the un Conditioned space 2000 sqmt

77 Supply, installation and commissioning of Duct Accoustic(Nitrile rubber base, Open cell material 24mm thick, Thermal conductivity 0.047w/m.k@20deg C, excellent absorption, 99.9% reduction of bacterial growth, class1 fire performance, with a density of 140-180Kg/cubicmeter)

90 sqmt

78 Supply and installation of non return air dampers low leakage type with spring loaded 60 sqmt

79 Supply and installation of external curved prole and shperical inner nozzle using the mechanical principle of eye ball ( ball & sacket principle ) engineered to swivel 360deg made of high quality aluminium, jet nozzle 250 dia to 300 dia

24 nos

80 Supply and installation of low leakage bubble type damper with spring acturator 5 sqmt

81 Supply, installation of heavy duty gripples for large duct, attenuators & VAVs supports 150 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 21 of 64

Page 25: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

82 charges for air balancing for all erected ducts 25000 sqmt

83 supply and installation armasound open cell nytrile rubber material thickness of 30mm thick,wall primer paintting, including GI stips for regidity for wall acousting in AHU rooms 800 sqmt

Ventilation System84

Supply, installation and commissioning of out door mounted - cabinet type Toilet Exhaust Air Fan for exhaust(13900 CFM/ 125 mm external static) 2 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination, water proof. 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade, Armoured copper cable

3 C x 4 sqmm xlpe 50 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 4 sqmm xlpe 4 Set

85 Supply, installation and commissioning of out door mounted cabinet type Toilet Fresh Air Fan (12005 CFM/50 mm external static) 2 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 4 sqmm xlpe 50 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 4 sqmm xlpe 4 Set

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 22 of 64

Page 26: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

86 Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 440 CFM/25 mm external static-For Drivers toilet @ B1) 2 nos

a Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 20 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 4 Set

87 Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 460 CFM/25mm external static -For Mens & womens toilet @ GF) 2 nos

a Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 20 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 4 Set

88 Supply, installation and commissioning of cabinet type Toilet booster fan (inline fan 1566 CFM/25mm external static-For Mens & womens toilet @ GF) 1 nos

a Supply and installation of respective motor kw starter panel with 16A DP Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 10 rmtENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 23 of 64

Page 27: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

89 Supply, installation and commissioning of cabinet type Toilet booster fan(inline fan 900 CFM/25mm external static -For womens toilet @ Typical Floors 1-12) 12 nos

a Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination 12 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 125 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 24 Set

90 Supply, installation and commissioning of cabinet type Toilet booster fan(inline fan 1250 CFM/25mm external static -For Mens toilet @ Typical Floors 1-12) 12 nos

a Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination 12 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 125 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 24 Set

91 Supply, installation and commissioning of cabinet type Pantry booster fan(inline fan 300 CFM/30mm external static-For Pantry Room @ GF) 2 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 24 of 64

Page 28: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a Supply and installation of respective motor kw starter panel with 16A DP MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 4 Set

92 Supply, installation and commissioning of out door mounted cabinet type Stair well pressurization fan, with flexible fire proof connection at inlet & outlet. (25025 CFM/ 50 mm external static),motor tempreature rating 300 deg C 2Hrs rating

3 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 3 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 50 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 6 Set

93 Supply, installation and commissioning of out door mounted cabinet type Lift well pressurization fan, with flexible fire proof connection at inlet & outlet. (26655CFM/ 35 mm ex Static)-Temp.Rating 300 deg C 2Hrs rating.

4 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 4 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 25 of 64

Page 29: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 50 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 6 Set

94Supply, installation and commissioning of out door mounted cabinet type Lift well pressurization fan, with flexible fire proof connection at inlet & outlet. (17770CFM/ 35 mm ex Static)-Temp.Rating 300 deg C rating.

1 nos

aIP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 15 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set

95 Supply, installation and commissioning of out door mounted SISW type Kitchen Exhaust fan (9000 cfm/ 200mm total static),outdoor mounted type 2 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 35 rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 26 of 64

Page 30: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 4 Set

96 Supply, installation and commissioning of out door mounted cabinet type DIDW, Kitchen Fresh fan (8000 cfm/ 50mm external static), DIDW type, with pre filter 2 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 30 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 4 Set

97 Supply, installation, testing and commissioning of out door mounted dry scrubber electrostatic type 9000 cfm for kitchen exhaust application, 230V 50HZ power supply, with BMS compatibility multi arrangement of scrubber, Outdoor type, for kitchen exhaust application, inbuilt control panel ( starter panel ) and related power cables between scrubber and panel approximately 52rmts end terminations, it capable of handling the Kitchen exhaust gases coming out of the Kitchen hoods. The scrubber shall be able to control SPM at 150 mg/ NM and 99% of SO2 removal. The scrubber shall behaving cyclonic inlet / outlet with honeycomb type impingement plates complete with FRP / epoxy lining, structural supports, water spraying arrangement, mist collection, painting etc. The srubbing system shall have an induced draught fan capacity of handling flue gases of the specified DG set with motor, base plate, vibration isolation pads, flexible inlet & outlet connection, outlet damper & V belt drive mechanism. The fan shall be designed to have an inlet to with stand for the temperature of 80-degree temperature

2 set

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 27 of 64

Page 31: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

The scrubbing system shall have a water circulating pump complete with motor, base plate, pressure gauge on delivery side, coupling etc.,The scrubbing system shall also have a dosing system consisting of a metering tank, a metering pump with adjustable capacity as required complete with motor, base plate, coupling etc., and a high speed motor mounted agitator with SS shaft / impeller and supporting arrangement. The scrubbing system shall be complete with HDPE interconnecting piping with valves, NRV, strainer etc., including pipefittings, flange nuts & bolts. Clamps, pipeline supports, painting etc., The scrubbing system shall also be provided with motorized damper. The scrubbing system shall be complete with motor control center consisting of cubicle outdoor type panel with incoming & outgoing MCCBs, starters, indicating lamps, indicating meters etc.,

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 20 rmtc Supply and Installation of cable end termination with Double brass compression gland and

Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set98

Supply, installation and commissioning of out door mounted cabinet type STP room fresh air fan (24200 cfm/ 65mm external static) 1 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 15 rmtc Supply and Installation of cable end termination with Double brass compression gland and

Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set

99Supply, installation and commissioning of out door mounted cabinet type STP room Exhaust fan (24400 cfm/ 125mm external static) 1 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 28 of 64

Page 32: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 16 sqmm xlpe 15 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 16 sqmm xlpe 2 Set

100Supply, installation and commissioning of out door mounted cabinet type Service corridor exhuast fan for exhaust(47520 CFM/150 mm external static) 5 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 5 nos

bSupply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 20 rmtc Supply and Installation of cable end termination with Double brass compression gland and

Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 4 Set

101Supply, installation and commissioning of out door mountedcabinet type fan (8400 cfm/ 50mm external static) with filter - Transformer Room 2 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 29 of 64

Page 33: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 30 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 4 Set

102 Supply, installation and commissioning of out door mountedcabinet type fan (8400 cfm/ 50mm external static) with filter - Panel Room 2 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 30 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 4 Set

103 Supply, installation and commissioning of out door mountedcabinet type fan (15800 cfm/ 50mm external static) with filter - Pump Room 2 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 30 of 64

Page 34: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 2 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 30 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 4 Set

104 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 1850 rmt

105 Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM 500pa, (Toilet ,stairwell ,liftwell,hru's,lobby smoke,sercorr ex, kit, Sdp vent.) Risers, using food grade type of sealant for leakage arresting,wall to wall duct crossing area to be sealed with fire retardant sealent.

a 18G 610 sqmt

b 20G 588 sqmt

c 22G 2900 sqmt

d 24G 1500 sqmt

106 Supply and installation of al.powdered coated exhaust / fresh air Dia 125 DISC Valve 300 nos

107 Supply and installation of al.powdered coated exhaust/ fresh air grilles with al co damper 18.0 sqmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 31 of 64

Page 35: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

107a Fresh air louvers made of 16 gauge GI sheet duly epoxy powder coated with filterfixing frame with 20 micron filter suitable to fix in wall / window. 20 Sq.m

108 Supply and installation of low leakage VCDs for fresh/exhaust air control 90 sqmt

109 Supply and installation of cabinet type smoke check lobby ventialtion fans (supply/exhaust)-1000cfm@30mm exterenal static 6 nos

110 Supply and installation of above item fan motor, starter panel with Disconect Switch 6 nos

111 PVC insulated ,copper conductor 1.1kva grade,Armoured copper cable ,brass heavy duty glands, soldering crimping type of copper sockets,app. Distance 30rmt 6 nos

112 Charges for Duct pressure testing -Ishare std. for entire ducting 17000 sqmt

113 Supply and installation of al.powdered coated grilles with wooden frame for grille erection ( staircase, lobby press., smoke check & kit. )

30 sqmt

114 Supply and insualtion of 20mm thick nitrilye Rubber with 0.5mm thick al. Foil faced for under deck insulation

2900 sqmt

115 Supply and instalation and closing of raiser shafts with 9mm thick ms plate without air leakage using fire retardant sealant

530 sqmt

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

D CAR PARK VENTILATION SYSTEM116 Supply, installation, testing and commissioning of Car aprk Jet Fans, Dual speed type with

disconect switch-1850cfm with silencer(both sides) for normal operation and 3700CFM Fire mode operation

90 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 32 of 64

Page 36: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

117 Supply erection testing and commissioning & handing over of AXIAL fresh air fans of11000 CFM @ 25 MM TOTAL STATIC, with silencer MOTOR RATING 300DEG TEMPERATURE 2Hrs rating,low sound level - Normal mode - FRESH AIR

27 nos

118 Supply & Installation of IP 55 VFD-HVAC series, VFD panel with related motor KW VFD (fresh air fan-3nos of fan) with necessary Isolators etc., as per technical specification to receive the power to the equipment. ( cubical type vfd panel with 3 mos of VFDs per room), with one incomer main Isolator and three out going isolators for vfds with required adapotor box , cables and cable termination with necessary indication lamps, ammeter,voltmeter) -BMS compatible.

9 nos

119 Supply erection testing and commissioning & handing over of AXIAL exhaust air fans of 34000 CFM @ 25 MM TOTAL STATIC- MOTOR RATING 300DEG TEMPERATURE 2Hrs rating,low sound level - same fan should be operated in Normal mode / fire mode with VFD control - EXHAUST AIR

27 nos

120 Supply & Installation of IP 55 VFD-HVAC series, VFD panel with related motor KW VFD (fresh air fan-3nos of fan) with necessary Isolators etc., as per technical specification to receive the power to the equipment. ( cubical type vfd panel with 3 mos of VFDs per room), with one incomer main Isolator and three out going isolators for vfds with required adapotor box, cables and cable termination with necessary indication lamps, ammeter,voltmeter) Incase of fire or smoke all the exhaust fans must run at maximum flow capacity and in normal mode the fan must run at required flow capacity, required control cables for the proper operation to be considered, BMS compatible.

9 nos

121 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

a 6C x 2.5 sqmm xlpe 3000 Rmt

b 3C X10 sqmm xlpe 1500 Rmt

122 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 33 of 64

Page 37: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a 6C x 2.5 sqmm xlpe 110 set

b 3C X10 sqmm xlpe 56 set

123 Supply and providing 8 SWG Copper earth bare wires clamped on the wall / run along with the cables as required 1800 Rmt

123a Supply and installation of 25x3 Copper flat 3000 Rmt

124 150 mm wide GI Perforated Cable Tray for above cables 1600 Rmt

125 300 mm wide GI Perforated Cable Tray for above cables 1450 Rmt

126 450mm wide GI Perforated Cable Tray for above cables 1100 Rmt

127 600 mm wide GI Perforated Cable Tray for above cables 750 Rmt

128 CFD (Computational Fluid Dynamics ) analysis for all 3 basements.its should cabaple and witnessesd to chech after completion works-fire mode/normal mode 3 Set

129 CO/CO2 detector head (Analog sensor-Should match the specifications),0- 250 ppm, with nessesary arrangement of suitable fixing 45 nos

130 PLC based control panel for CO detectors and control of JET Fans with starter panel for demand ventilation with a logic contoller .Should also enable auto on/off of fans for power saving BASED ON SENSING OF CO LEVEL. WITH STARTER

3 set

131 CIRCULAR ATTENUATOR FOR SUCTION/DISCHARGE SIDE OF Normal mode(fresh/exhaust) operation of main extract Fans 54 nos

132 Supply and installation of SMACNA standard, Sheet Metal Ducting as per Specification. Pressure 500 Pa, Ducting 18 G with angle Iron flange and related fire rated canvas with 300 deg C 2Hrs rating

170 Sqmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 34 of 64

Page 38: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

133 2 Runs of copper armoud 3C 1.5 Sqmm power cable for jet fans with end termination and at the fan posistion required isolation for maintanance aux. 3900 rmt

134 2C 1.0 Sqmm FRLS Communication cable in 19 mm MS Contuit between PLC Panel to co sensors 1800 rmt

135 Supply and installation of Smoke damper with BMS compatible actuator for fire mode fresh air fan,suitable for 230v power supply 27 sqmt

136Supply and installation of UL listed Firedamper cum smoke damper with BMS compatible actuator and related cabling betwenn actuator to plc panel , including supply of smoke/fire sensor , its is controlled by PLC panel

54 sqmt

137 Supply and instalation of MS Grating for raiser shaft- service acces 88 sqmt

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

E FUMIGATION SYSTEM138 Supply, installation, testing and commissioning of outdoor mounted Cabinet type, fan

(outdoor) at terrace open mounted type a 18000CFM@130mm external static 2 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 35 of 64

Page 39: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

139 IP 55 VFD-HVAC series with 63A TPN Isolator and required adapotor box for cable termination 2 nos

140 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

a 3 C x 6 sqmm xlpe 50 rmt

141 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

a 3 C x 6 sqmm xlpe 2 Set

142 Supply, installation, testing and commissioning of outdoor mounted Cabinet type, fan (outdoor ) at terrace open mounted type

a 12000CFM @ 130mm external static 1 nos

143 IP 55 VFD-HVAC series with 63A TPN Isolator and required adapotor box for cable termination 1 nos

144 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

a 3 C x 6 sqmm xlpe 25 rmt

145 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

a 3 C x 6 sqmm xlpe 1 Set

146 Supply, instalation and commissioning of Double skin low leakage VAVs, selection of VAV 5 to 6 m/sec, dba level less than 30db,A iDiauilt thermostart and controller, suitable size of cabling, conduit, earth between thermostart to VAV, and VAV to isolater, required 5A isolator, fast activating type of VAV that is 3 to 5 seconds, interlocking arrangement between AHU to VAV for on/off operation

a 1800 to 2000 CFM 90 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 36 of 64

Page 40: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

147Supply and installation of SMACNA standard, factory fabricated, flanged GI ducting,180GSM, 500pa, using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealent

a 20G 50 sqmt

b 22G 1800 sqmt

c 24G 200 sqmt

148Supply and installation of Low leakage bubble type damper with BMS compatible actuator 30 sqmt

149 Charges for Duct pressure testing -ishrae std. 2250 sqmt

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

F FAÇADE VENTILATION SYSTEM150

Supply, installation, testing and commissioning of axial type fan at Ground/terrace open mounted type -2700cfm@25mm ex Static,low speed less than 450 rpm ,less than 40 dba 24 nos

151 Supply and installation of cubical panel for the above , ( cubical type starter panel with 6starters per floor ,with one incomer isolator and six outgoing isolator , with necessary indication lamps, ammeter,voltmeter -3nos)

3 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 37 of 64

Page 41: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

152Supply and installation of cubical panel for the above ,( cubical type starter panel with 2starters per floor ,with one incomer isolator and two outgoing isolator , with necessary indication lamps, ammeter,voltmeter -3nos)

3 nos

153 Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

a 3 C x 2.5 sqmm xlpe 600 rmt

154 Supply and Installation of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of 1.1KV grade complete as required..

a 3 C x 2.5 sqmm xlpe 48 Set

155 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 950 rmt

156 Supply and installation of GI ducting,180GSM ,24G 20 sqmt

157 Supply and installation of Non Vision louvers 20 sqmt

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

G GROUND FLOOR & COMMON AREA AHUSDOUBLE SKIN AIR HANDLING UNITS

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 38 of 64

Page 42: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Supply, installation, testing and commissioning of AHUs with assembled condition All Sheet metal cabinet type double skin air handling units, with 50mm thickness RPUF panels complete with Fan section with DIDW centrifugal Backward aero foil curve fan, water inlet temp 6deg C & water outlet temp 14deg C, outer and inner skin0.8mm thick pre-coated and pre plasticized sheets, fan motor, fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 10kw heater strip bank section with thyrister control type, Filter section with Pre Filter & Bag Filter, two pass SS316 18Gauge eliminator , sound level shall be 60dbA from 1 mtr.

Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve, return air plenum sections of 910mm length with top entry provided with SS316 12Gauge mesh, magnolic gauges, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator cabling and termination and duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD with neccessary conduits apprx. 45-55rmt

1584 TR capacity, 2261 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- LIFT LOBBY TYPICAL FLOORS (2-12)

12 nos

aIP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination and required adapotor box for cable termination 12 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 840 Rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 24 Set

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 39 of 64

Page 43: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

159 3 TR capacity, 2261 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- LIFT LOBBY GROUND FLOOR

1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 70 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

1603 TR capacity, 1568 Dcfm, 25 mmwg fan external static, 6row cooling coil, Chilled water Ceiling suspended Unit with isolation valves and self dynamic valves- BASEMENTS 3 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 3 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 310 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 6 Set

161 5TR capacity, 2671 Dcfm, 25 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - IBMS ROOM @ B1 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 40 of 64

Page 44: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 4 sqmm xlpe 20 rmtc Supply and Installation of cable end termination with Double brass compression gland and

Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 4 sqmm xlpe 2 Set

162 22TR capacity, 13147 Dcfm, 50 mmwg fan external static, 6 row cooling coil, ceiling suspended unit - ATTRIUM 3 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 3 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 75 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 6 Set

163 31 TR capacity,9636 Dcfm, ext.static 30 mmwg fan static, 8 row cooling coil, floor mounted unit - FOOD COURT AHU 1 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 25 rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 41 of 64

Page 45: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set

16434 TR capacity,13090 Dcfm, 30 mmwg fan external static, 6 row cooling coil, floor mounted unit - RETAIL AREA AHU 1 nos

a IP 55 VFD-HVAC series with 63 A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set

165 6TR capacity, 3150 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - GF LOBBY&CORRIDOR 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 42 of 64

Page 46: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

3 C x 2.5 sqmm xlpe 2 Set

166 8TR capacity, 4275 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - GF CORRIDOR 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

167 6TR capacity, 2612 Dcfm, 25 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - GF.BUISINESS CENTER 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

168 22TR capacity, 5286 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended Units - GF CONVENTION CENTER 1 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 43 of 64

Page 47: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a IP 55 VFD-HVAC series with 63 A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 10 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 2 Set

169 9TR capacity, 4575 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - TYPICAL FLOORS CORRIDOR (1-11) 11 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 11 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 250 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 22 Set

170 6TR capacity, 3705 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - TYPICAL FLOORS CORRIDOR (1-11) 11 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 11 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 44 of 64

Page 48: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

3 C x 2.5 sqmm xlpe 250 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 22 Set

171 9TR capacity, 3947 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended / floor mounted Units - 12TH FLOOR CORRIDOR 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

172 6TR capacity, 3705 Dcfm, 40 mmwg fan external static, 6 row cooling coil, ceiling Suspended/floor mounted Units - 12TH FLOOR CORRIDOR 1 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator and required adapotor box for cable termination 1 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armoured copper cable

3 C x 2.5 sqmm xlpe 25 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 2 Set

Total

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 45 of 64

Page 49: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

H LAB TYPICAL FLOORDOUBLE SKIN AIR HANDLING UNITS ( 100% FRESH AIR )

Supply, installation, testing and commissioning of clean room type, AHUs with assembled condition All Sheet metal cabinet type double skin air handling units with 50mm thickness RPUF panels complete with Fan section with high efficient type PLUG FAN, water inlet temp 6deg C & water outlet temp 14deg C, outer skin 0.8mm GI, inner skin SS316 0.8mm, above 95% efficiency motor,fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 7.5kw heater strip bank section with thyrister control, RH cum Temp sensor, required controller for RH and heater, power control panel, interlocking arrangement for heater and VFD, return air plenum of 910mm length, Filter section with Pre Filter & Bag Filter filter, Hepa filter( Box type 450mm length ), run around 6row deep heatpipes, two pass 18g SS 316 eliminator , sound level shall be 60dbA from 1 mtr.

Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve. Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator, cabling and termination ,duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD, heater to VFD, RH sensor to controller with neccessary conduits apprx. 75-90 rmt.

17318TR capacity, 3200 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 20 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator 20 nos

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 46 of 64

Page 50: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable

3 C x 10 sqmm xlpe 400 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 20 Set

17412TR capacity, 2200 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 70 nos

a IP 55 VFD-HVAC series with 63A TPN MCB Isolator 70 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable

3 C x 10 sqmm xlpe 1400 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 10 sqmm xlpe 70 Set

DOUBLE SKIN AIR HANDLING UNITS ( RECIRCULATORY )

Supply, installation, testing and commissioning of AHUs with assembled condition All Sheet metal cabinet type double skin air handling units with 50mm thickness RPUF panels complete with Fan section with DIDW centrifugal Backward aero foil curve fan, water inlet temp 6deg C & water outlet temp 14deg C, outer and inner skin0.8mm thick pre-coated and pre plasticized sheets, fan motor, fan casing insulation for accoustic, SS316 18Gauge Stainless drain pan with double side insulation, 5kw heater strip bank section, with thyrister control type, Filter section with Pre Filter & Bag Filter, two pass SS316 18Gauge eliminator 20G, sound level shall be 60dbA from 1 mtr.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 47 of 64

Page 51: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Units shall be complete with opposed blade volume control dampers at its oulet and necessary drain valve, return air plenum sections of 910mm length with top entry provided with SS316 12Gauge mesh, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, heater bank isolator cabling and termination and duct static pressure sensor ( range 100-150pa), cabling between sensor to VFD with neccessary conduits apprx. 45-55 , apprx. 75-90 rmt.

175 6TR capacity, 2628 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 20 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator 20 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable

3 C x 2.5 sqmm xlpe 400 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

3 C x 2.5 sqmm xlpe 20 Set

176 9TR capacity, 3947 Dcfm, 180 mmwg fan total static, 6 row cooling coil,run around heat pipes,two pass SS eleminator, ceiling Suspended Units / Floor Mounted Units - LAB 70 nos

a IP 55 VFD-HVAC series with 32A TPN MCB Isolator 70 nos

b Supply,Laying and commisioing of PVC insulated ,copper conductor 1.1kv grade,Armored copper cable

3 C x 2.5 sqmm xlpe 1400 rmt

c Supply and Installation of cable end termination with Double brass compression gland andCopper lugs for the following sizes of PVC Insulated XLPE armoured conductor cable of1.1KV grade complete as required..

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 48 of 64

Page 52: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

3 C x 2.5 sqmm xlpe 70 Set

177 Supply and providing 8 SWG CU earth bare wires clamped on the wall / run along with the cables as required for all euipments. 1000 rmt

178Supply, installation and commissioning of Hepa filter module for AHUs 1015 sqft

Total

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

I BTCIF LAB AHUSAir Handling Units (AHU) (Classified Areas) (Recirculatory)

179 Pharma grade stericlean double skin Air handling unit with Thermal Break Profile internallycoved 43 mm thk PUF insulated Air handling Unit made out of 24G GI Plain inside and 24GGI outside pre coated sheet, with cold bridge free door on discharge side of fan, water inlettemp 6deg C & water outlet temp 14deg C, return air plenum with provision to fix G4 filter,Coil section with 6 row deep chilled water coil, 5 to 7.5kw heater strip bank section, thyristercontrol type/RH cum Temp sensor, required controller for RH and heater, power controlpanel, interlocking arrangement for heater and VFD, velocity across coil not to exceed 2.5m/s. Bypass damper for 20% capacity of AHU. All coils to be sized for full supply air capacityof AHU. SS insulated drain tray, fan section with DIDW backward curved centrifugal fan,suitable TEFC squirrel cage induction motor (NFLP), drive set consisting of taper lock pulleys& V-belts,

Inspection window, filter section after the fan to fix F6 filter. Fresh air, return air, supply airdamper & bleed of damper of aluminium extruded construction with provision for fixing H13HEPA filter in bleed off module. Provision for fixing Magnehelic guages across F6 filter.(Excluding filters). (AHU height should not exceed 1100mm)

a AHU-01: 6000 CFM @ 125 mm ext. Static Pressure 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 49 of 64

Page 53: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b AHU-02A: 3600 CFM @ 125 mm ext. Static Pressure 1 nos.

c AHU-02B: 2900 CFM @ 125 mm ext. Static Pressure 1 nos.

d AHU-03: 1850 CFM @ 125 mm ext. Static Pressure 1 nos.

e AHU-04: 4250 CFM @ 125 mm ext. Static Pressure 1 nos.

f AHU-05: 1700 CFM @ 125 mm ext. Static Pressure 1 nos.

g AHU-06: 1000 CFM @ 125 mm ext. Static Pressure 1 nos.

h AHU-08: 3600 CFM @ 125 mm ext. Static Pressure 1 nos.

i AHU-09: 3800 CFM @ 125 mm ext. Static Pressure 1 nos.

j AHU-10: 4000 CFM @ 125 mm ext. Static Pressure 1 nos.

k AHU-11: 4000 CFM @ 125 mm ext. Static Pressure 1 nos.

l AHU-12: 1150 CFM @ 125 mm ext. Static Pressure 1 nos.

m AHU-13: 5700 CFM @ 125 mm ext. Static Pressure 1 nos.

n AHU-14: 3250 CFM @ 125 mm ext. Static Pressure 1 nos.

o AHU-15: 2900 CFM @ 125 mm ext. Static Pressure 1 nos.

p AHU-16: 4400 CFM @ 125 mm ext. Static Pressure 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 50 of 64

Page 54: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

q AHU-17: 3600 CFM @ 125 mm ext. Static Pressure 1 nos.

Air Handling Units (AHU) (Classified Areas) (100% fresh air)180 Pharma grade stericlean double skin Air handling unit with Thermal Break Profile internally

coved 43 mm thk PUF insulated Air handling Unit made out of 24G GI Plain inside and 24GGI outside pre coated sheet, with cold bridge free door on discharge side of fan, fres airplenum with provision to fix G2 filter(20micron, 85% efficiency), G4 filter, Coil section with 8 row deep chilled water coil and 15kw heater strip bank section, thyrister controltype/RH cum Temp sensor, required controller for RH and heater, power controlpanel, interlocking arrangement for heater and VFD, velocity across coil not toexceed 2.5 m/s. Bypass damper for 20% capacity of AHU. All coils to be sized forfull supply air capacity of AHU. SS insulated drain tray, fan section with DIDWbackward curved centrifugal fan, suitable TEFC squirrel cage induction motor(NFLP), drive set consisting of

taper lock pulleys & V-belts, Inspection window, filter section after the fan to fix F6 filter(5micron, 95% efficiency). Fres air inlet with GI Powder coated louvers, Supply air damper.Provision for fixing Magnehelic guages across F6 filter. (Excluding filters). (AHU heightshould not exceed 1100mm)

a AHU-07: 5700 CFM @ 100 mmWC ex.Static Pressure 1 nos.

181 Treated Fresh Air UnitDouble Skin type Pre-cooling unit made out of 24G GI inside plain & 24 G GI powder coatedsheet with 25mm thick PUF insulation, comprising of Pre filter section with provision to fix G4filters(10micron, 90% efficiency), 8 row deep chilled water coil, fan section with centrifugal fanwith suitable Non flame proof motor with anti vibration mounts, out let connections completewith service doors, outlet damper. (Including filters). (TFA height should not exceed1100mm)

TFA-17 : 2100 cfm @ 25 mm ex.Static pressure (For AHU-17)1 nos.

182 Fan Coil Unit

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 51 of 64

Page 55: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Double Skin type Fan Coil unit made out of 24G GI inside plain & 24 G GI powder coatedsheet with 25mm thick PUF insulation, comprising of Pre filter section with provision to fix G4filters (10micron, 90% efficiency), 4 row deep chilled water coil, fan section with centrifugalfan with suitable Non flame proof motor with anti vibration mounts, out let connectionscomplete with service doors, outlet damper. (Including filters).

a FCU-01 : 3000 cfm @ 40 mm To.Static pressure 2 nos.

TotalJ INTERIOR

183 Ventilation UnitSingle skin Ventilation Unit made out of 18G pre-painted GI sheet and essentially comprisingof Pre filter section with provision for fixing G2 filter, G4 filters (10micron, 90% efficiency), fansection with DIDW forward curved centrifugal fan, Non flame proof TEFC squirrel cageinduction motor and complete with anti vibration mounts, provision for magnehelic gaugeacross F6 filters (5micron 95% efficiency), Filter section with provision for fixing F6 filters, outlet connection complete with service doors / inspection windows with fire retardent canvasconnection supply air damper in G.I. construction. (Excluding filters). (VENT height shouldnot exceed 1100mm)

a VENT-01 : 1000 CFM @ 65 mm ext.Static Pressure 1 nos.

b VENT-02 : 1150 CFM @ 65 mm ext.Static Pressure 1 nos.

184 Exhaust UnitSingle skin Exhaust Unit made out of 18G pre-painted GI sheet and essentially comprising offilter section with provision to fix G4 filters (10micron, 90% efficiency), fan section with DIDWcentrifugal fan belt driven by suitable Non flame proof motor and complete with anti vibrationmounts, inlet and out let connections complete with service doors/inspection windows andwith outlet damper. Single skin rexin flexible connection for fan outlet. (Excluding filters).(EXU height should not exceed 1100mm)

aEXU-01 : 1100 CFM @ 40 mm ext. Static Pressure (For VENT-01) 1 nos.

bEXU-02 : 1400 CFM @ 40 mm ext.Static Pressure (For VENT-02) 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 52 of 64

Page 56: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

cEXU-03 : 1500 CFM @ 40 mm ext.Static Pressure (For Media Room of AHU-07) 1 nos.

dEXU-04 : 1250 CFM @ 40 mmext.Static Pressure (For Wash Room of AHU-07) 1 nos.

eEXU-05 : 700 CFM @ 40 mm ex Static Pressure (For Discard Room of AHU-07) 1 nos.

f EXU-06 : 3250 CFM @ 40 mm ext. Static Pressure (For Discard Corridor of AHU-07) 1 nos.

gEXU-07 : 2000 CFM @ 40 mm ext. Static Pressure (For Wash room of AHU-17) 1 nos.

185 Bleed off module Bleed Off module consisting of H13 super flow HEPA Filter with GI powder coated perforated Grill for the following sizes

a 670 x 365 mm (Double flange type) qro nos.

b 365 x 365 mm (Double flange type) 7 nos.

186 Filtersa AHU fitted G2(20 micron, 85% efficiency), prefilter sealant sealed complete with

flange type fixing gadget. (including flange). Size 50 mm thick 3 sqm

b AHU fitted G4 (20 micron, 85% efficiency), prefilter sealant sealed complete with flange type fixing gadget. (including flange). Size 150 mm thick 23 sqm

c AHU fitted F6 (5 micron, 95% efficiency), fine filter sealant sealed complete with flange type fixing gadget. (including flange). Size 300 mm thick 16 sqm

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 53 of 64

Page 57: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

187 Terminal HEPA filter Module, Filter & GrillSupply of HEPA Filter module with Volume Control damper, DOP port, made out of18 G G.I. sheet duly epoxy powder coated suitable for fixing the following sizeHEPA Filters & SS perforated grill. (Room servicable)

a 610 x 610 x 150 mm Filter size 69 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 54 of 64

Page 58: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b 610 x 305 x 150 mm Filter size 41 nos.

c 305 x 305 x 150 mm Filter size 36 nos.

188 Super flow H13 HEPA filters of following sizes

a 610 x 610 x 150 mm (1000 cfm) 69 nos.

b 610 x 305 x 150 mm (500 cfm) 41 nos.

c 305 x 350 x 150 mm (250 cfm) 36 nos.

189 16G SS 304 perforated grill suitable for HEPA Module with following filtersizes

a 610 x 610 x 150 mm Filter size 69 nos.

b 610 x 305 x 150 mm Filter size 41 nos.

c 305 x 305 x 150 mm Filter size 36 nos.

190 Return Air Grill Module (Classified area)a False ceiling suitable return air grill module (suitable to fix perforated grill) made out

of 18G GI powder coated sheet with GI collar damper and double skin flexibleconnetion.

29 sqm

b16G SS 304 perforated grill suitable for the above mentioned modules 32 sqm

191 Supply / Return Air Grill (Un-Classified area)

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 55 of 64

Page 59: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

a Aluminium linear bar grill with GI collar damper suitable fix in duct. 17 sqm

192 Return Air Riser

a Return air risers made out of 22G GI sheets suitable for fixing module & perforatedgrill - wall concealed type. 1639 sqm

b Return air riser module (suitable to fix perforated grill) made out of 18G GI powdercoated sheet with GI collar damper with filter collar 20 sqm

c G4 (10 micron, 90% efficiency), filter suitable to fix in above module 14 sqm

d SS 304 perforated grill suitable for return air riser module 25 sqm

193 Dampersa Duct mounted CRCA epoxy powder coated opposed blade Volume control damper

suitable for supply and return ducts. 10 sqm

b16G GI powder coated fusible link type fire damper at AHU inlet. 6 sqm

194 DuctingSheet Metal work comprising of G.S.S.(Min 120 GSM GI Sheet) ducting completewith all supports and as per the specification with bolts, nuts neoprene gaskets andsealed with silicon sealant & quantities are as under:

a 24 G GI 2300 sqm

b22 G GI qro sqm

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 56 of 64

Page 60: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

195 Duct InsulationAl. foil faced polyethylene insulation for ducting.

a19 mm thick for supply air duct & HEPA modules 2246 sqm

b9 mm thick for return air duct, return air risers and modules 1286 sqm

c Acoustic Insulation of Supply air duct and return air duct with 25mm thick fibre glass wrapped in cora cloth and finished with Aluminium perforated sheet for ducting catering to Auditorium

223 sqm

196 Pressure Monitering systema Magnelic gauges for rooms with epoxy coated box and SS 304 flush cover with

necessary tubings

Range : 0-6 mm WC Magnehelic guages 70 nos

b Magnehelic gauges for AHUs across F6 filters

Range : 0-50 mm Magnehelic guages 20 nos

197 Chilled Water Manifold for AHUs & TFAsChilled Water Manifold size suitable to AHU includes 5 Nos. Butterfly / Ball Valves,1 No. Balancing valve, 1 No. Y-strainer, 1 No. 3 Way mixing Valve with Actuator(Suitable for BMS integeration) (with interconnected wiring between thermostat &mixing valve), 2 Nos. Pressure gauges, 2 Nos. Temperature Gauges (withthermowell), 1 No drain valve without insulation.

a 25 Dia Size Manifold 3 nos.

b40 Dia Size Manifold 14 nos.

c 50 Dia Size Manifold 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 57 of 64

Page 61: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

d 65 Dia Size Manifold qro nos.

e 80 Dia Size Manifold 1 nos.

198 Chilled Water Manifold for FCUs

Chilled Water Manifold size suitable to FCU includes 2 Nos. Ball Valves, 1 No. 3way Solenioid Valve (with interconnected wiring between thermostat & solenoidvalve), 1 No drain valve without insulation.

a 40 Dia Size Manifold 2 nos.

199 VFD PanelsVariable frequency drive for the following AHUs with local AHU panel in 16 G G.I.powder coated construction suitable to house VFD for fan motor of AHUs, controlswithchgears with bypass starters. This panel shall be provided with ventilation fan& shall be installed near to AHU.

a AHU-01 (7.5 KW) 1 nos.

b AHU-02B (3.7 KW) 1 nos.

c AHU-02A (3.7 KW) 1 nos.

d AHU-03 (2.2 KW) 1 nos.

e AHU-04 (5.5 KW) 1 nos.

f AHU-05 (2.2 KW) 1 nos.

g AHU-06 (1.5 KW) 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 58 of 64

Page 62: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

h AHU-07 (5.5 KW) 1 nos.

i AHU-08 (3.7 KW) 1 nos.

j AHU-09 (3.7 KW) 1 nos.

k AHU-10 (5.5 KW) 1 nos.

l AHU-11 (5.5 KW) 1 nos.

m AHU-12 (1.5 KW) 1 nos.

n AHU-13 (5.5 KW) 1 nos.

o AHU-14 (3.7 KW) 1 nos.

p AHU-15 (5.5 KW) 1 nos.

q AHU-16 (5.5 KW) 1 nos.

r AHU-17 (3.7 KW) 1 nos.

200 Flow measuring station with provision for fixing Pressure sensor for following supply duct sizes.

a Duct face area 4.2 sft for AHU-01 1 nos.

b Duct face area 3.0 sft for AHU-02A 1 nos.

c Duct face area 2.4 sft for AHU-02B 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 59 of 64

Page 63: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

d Duct face area 1.7 sft for AHU-03 1 nos.

e Duct face area 3.3 sft for AHU-04 1 nos.

f Duct face area 1.5 sft for AHU-05 1 nos.

g Duct face area 1.1 sft for AHU-06 1 nos.

h Duct face area 4.2 sft for AHU-07 1 nos.

i Duct face area 3.0 sft for AHU-08 1 nos.

j Duct face area 3.0 sft for AHU-09 1 nos.

k Duct face area 3.3 sft for AHU-10 1 nos.

l Duct face area 3.3 sft for AHU-11 1 nos.

m Duct face area 1.1 sft for AHU-12 1 nos.

n Duct face area 4.2 sft for AHU-13 1 nos.

o Duct face area 2.7 sft for AHU-14 1 nos.

p Duct face area 2.4 sft for AHU-15 1 nos.

q Duct face area 3.3 sft for AHU-16 1 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 60 of 64

Page 64: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

r Duct face area 3.0 sft for AHU-17 1 nos.

201 Static pressure sensor with transmitter suitable fix in flow measuring station and suitable for integeration with above mentioned VFDs 18 nos.

202 Static Pass Boxa Supply, Installation and Commissioning of Static Pass box made out of SS 304

including interlocking of size: 500 x 600 x 600 16 nos.

203 Dynamic Pass Boxa Supply, Installation and Commissioning of Static Pass box made out of SS 304

including interlocking of size: 500 x 500 x 1000 2 nos.

204 Sterile Garment Cubiclea

Supply, Installation and Commissioning of Garment cubicle of SS 304 with pre filtersection with filters, HEPA filters and blower assembly. Size: 450 x 450 x 2000mm 4 nos.

205 Laminar Air Flow Unitsa Supply, Installation and Commissioning of Ceiling suspended Vertical Laminar Flow

Unit made of SS304 with pre filter section with filters, HEPA filters and blowerassembly and SS 304 table top of size: 1200 x 750mm

13 nos.

b Supply, Installation and Commissioning of Horizontal Laminar Flow Unit made ofSS304 with pre filter section with filters, HEPA filters and blower assembly and SS304 table top of size: 1200 x 750mm

2 nos.

206 Cross Over Bench (SS 304) in Airlock 5 nos.

207 Chilled water piping

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 61 of 64

Page 65: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

Supply,installation and commissioning of MS C class pipe with Regid puff, density 48 Kg/m3 of 75mm thick for 450 mm to 150mm and below pipe 50mm thick and 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, anchors, welding, smooth finishing, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc.,

a 150 Dia 40 Rmt

b 125 Dia 40 Rmt

c 100 Dia 40 Rmt

d 80 Dia 40 Rmt

e 65 Dia 40 Rmt

f 50 Dia 80 Rmt

g 40 Dia 80 Rmt

208 Drain piping

GI 'B' class piping, nut-bolts,supports with 25mm thick nitrile rubber / cross linkedpolyethylene insulation

a 80 Dia 80 Rmt

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 62 of 64

Page 66: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b 65 Dia 80 Rmt

c 40 Dia 80 Rmt

209 Butterfly valves

a 150 Dia 2 nos.

b 50 Dia 2 nos.

210 Y Strainer with SS internal filter

a 150 Dia 1 nos.

b 50 Dia 1 nos.

211 Automatic Air Vents valve 20 nos.

212 1/2" Ball valve 20 nos.

213 Supply of ceiling suspended type Cassette unit with chilled water coil, 3waysolenoid valve with thermostat ans ser of ball valves with strainer and 1 ball valvealong with drain pump iDiauilt.

a 2 TR 6 nos.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 63 of 64

Page 67: Volume - 4

TICEL BIO PARK II ACMV WORKS

Supply Erection Supply Erection

ACMV BILL OF QUANTITIES

DescriptionSI No Units Unit Rate AmountQty

b 1 TR 1 nos.

214 Fresh air louvers made of 16 gauge GI sheet duly epoxy powder coated with filterfixing frame with 20 micron filter suitable to fix in wall / window. 20 Sq.m

215 Testing, Commissioning, Validation & Documentation Charges

DQ/OQ documents, Maintenance manual, Test certificate for equipment (IQ formatshall be provided by us but filling will be done later).1) Smoke Test2) Air balancing and velocity profile test3) Pressure balancing test4) Temperature & RH test5) Filter integrity test6) Air Flow Pattern

1 Lot

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Total

GRAND TOTAL

Total For Supply and Erection

Note : whereever BMS compatible, VFD, shown or required, the system should be compatible for all the BMS & IBMS vendors, include the cost for the respetive item

Note : Imported items rate quoted should be including the port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes and incidentals complete till delivered at site, Customs duty and countervailing duty for the above imported equipment, Receiving at site above imported equipment, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting testing and commissioning above equipment including supplying & installing all necessary indigenous accessories as required to complete the installation.

ENGINEERING CONSULTANT:TAAMAESEK ENGINEERING CONSORTIUM 64 of 64

Page 68: Volume - 4

TICEL BIO PARK II ACMV WORKS

SI No Description Amount Remarks

I OPERATING CONTRACT FOR 5 YEARS INCLUDING 1 1/2 YEAR DEFECTS LIABLITITY PERIOD( CONSIDERED FOR TENDER EVALUATION PURPOSE )

IINON COMPREHENSIVE MAINTENANCE CONTRACT FEE FOR 3 1/2 YEARS AFTER DEFECTS LIABLILITY PERIOD FOR TICEL BIO PARK-II AND 5YEAR NON COMPREHENSIVE MAINTENANCE FOR TICEL-I ( CONSIDERED FOR TENDER EVALUATION PURPOSE )

Total

ACMV BILL OF QUANTITIES

PART - II

ENGINEERING CONSULTANT : TAAMAESEK ENGINEERING CONSORTIUM

Page 69: Volume - 4

TICEL BIO PARK II ACMV WORKS

SI No Descriptionof works Amount Remarks

Full time round the clock and year round, operation of ACMV like air cooled chiller, primary pumps, secondary pumps, phe pumps, air handling units, heat recovery wheel units, latent energy storage tanks, exhaust fans, fresh air fans, mechanical ventilation system, car park jet fans, etc., and all other items in Ticel Bio Park II and in the previous ACMV systems installed at exsiting Ticel ( Annexure B ) including, keeping log books and records of energy consumption, Details of breakdown, hours of operation, meter reading on various parameters such as BTU metering and other functional requirements required by client by providing the minimum manpower as per the details given in the Annexure A

Operation for Biopark- I & II

a. First year after handing over the installation - lumpsum fee for 1 year

b. Second year after handing over the installation - lumpsum fee for 1 year

c. Third year after handing over the installation - lumpsum fee for 1 year

d. Fourth year after handing over the installation - lumpsum fee for 1 year

e. Fifth year after handing over the installation - lumpsum fee for 1 year

TOTAL C/o to ABSTRACT-I

Station :

Date : Signature of Tenderer

I. OPERATING CONTRACT FOR 5 YEARS INCLUDING 1 1/2 YEAR DEFECTS LIABLITITY PERIOD( CONSIDERED FOR TENDER EVALUATION PURPOSE )

1

MISCELLANEOUS WORKBILL OF QUANTITIES

Note:1.The escalation for operating cost for any consecutive year should no exceed 5 % value of the lumpsum see quoted for Previous year by the tenderer.2.The tenderers have to inspect the Exisiting ACMV system in Bio Park-I before Quoting.3.The selected contractor has to operate the existing system at TICEL-I and the proposed new installations in Ticel-II

ENGINEERING CONSULTANT :TAAMAESEK ENGINEERING CONSORTIUM

Page 70: Volume - 4

TICEL BIO PARK II ACMV WORKS

SI No Descriptionof works Amount Remarks

Maintenance of the ACMV system supplied, installed commissioned by successfull tenderer for Ticel Bio Park II for a period 3 1/2 years beyond the defects liability period (DLP) and as well as the previous ACMV systems installed in existing Ticel ( Annexure B ). The above scope of maintenance includes periodical maintenance, preventive maintenance and breakdown maintenance of all the ACMV installations, Equipements and components at Ticel including Annual Maintenance / servicing of all chillers,pumps , AHUs Heat Recoverywheel units, Latent Energy storage Tanks, Exhaust fans, Fresh air fans, Mechanincal ventilation system, car park jet fans, etc., and break down repairs as and when occured, ensuring that system does not remain out of service for a period more than 8 hours in case of major breakdowns and one hour in the case of minor breakdowns due to any unforeseen circumstances by providing the minimum man power as per the details given in the Annexture A. The successful tenderer shall keep the essential spares at TICEL for Bio Park-II during the Defects Liablity period to avoid the delay in attending faults / maintenance FOR Ticel Bio Park II,no maintenance charges for one and half years shall be paid.

a. For 18months after handing over of installation for Bio Park-I ( Non comprehensive)(DLP of TICEL-II)

b. For 6 months non comprehensive maintenance for Bio Park-I & II (After DLP)(for Non comprehensive Maintenance of Bio Park-I& II )- Lumpsum Fee for six months

c. Third Year after Handing over the Installation of Bio Park-II(for Non comprehensive Maintenance of Bio Park-I& II )- Lumpsum Fee for one year

d. Fourth Year after Handing over the Installation of Bio Park-II(for Non comprehensive Maintenance of Bio Park-I& II )-Lumpsum Fee for one year

e. Fifth Year after Handing over the Installation of Bio Park-II(for Non comprehensive Maintenance of Bio Park-I& II )-Lumpsum Fee for one year

TOTAL C/o to ABSTRACT-INote:

Station :

Date : Signature of Tenderer

1.The Escalation for maintenance cost for any consecutive year should no exceed 5 % value of the lumpsum fee quoted for the Preview year by the tender

II. NON COMPREHENSIVE MAINTENANCE CONTRACT FEE FOR 3 1/2 YEARS AFTER DEFECTS LIABLILITY PERIOD FOR TICEL BIO PARK-II AND 5YEAR NON COMPREHENSIVE MAINTENANCE FOR TICEL-I ( CONSIDERED FOR BID EVALUATION PURPOSE )

1

MISCELLANEOUS WORKBILL OF QUANTITIES

ENGINEERING CONSULTANT :TAAMAESEK ENGINEERING CONSORTIUM

Page 71: Volume - 4

TICEL BIO PARK II ACMV WORKS

SI No Designation No of persons

Qualification Maximum Experience ( No of Years )

A ACMV WORKS

2 Shift Supervisor for O&M (including one Reliever) 4 Diploma in Mechanical Minimum 7 years experience in Operation and maintenance of ACMV

system in Highrise buildings like IT parks / Star Hotels

3

Technician (General shift -2 Nos.and in shift-7 Nos.including one Reliever

9 ITI Minimum 7 years experience in Operation and maintenance of ACMV system in Highrise buildings like IT parks / Star Hotels

Note:

Station :

Date :

MINIMUM MANPOWER REQUIREMENT FOR ACMV OPERATION & MAINTENANCE SERVICES

Engineering Graduate / Mechanical Engineering

Minimum 7 years experience in Operation and maintenance of ACMV system in Highrise buildings like IT parks / Star Hotels

Signature of Tenderer

The above man power is the minimum requirement for routine operation and maintenance of ACMV system. In case of any emergency major breakdowns and for annual maintenance etc., If the contractor feels that the above minimum manpower is not adequate, the contractor shall engage more manpower during those times without any additional cost. Apart from the regular O&M contract fee, no seperate labour charges or service charges will be paid for any of the maintenance / servicing of the ACMV system installations / Euipments / Components during the contract period.

ANNEXURE A

1Operation & Maintenance incharge (in General Shift)1

ENGINEERING CONSULTANT :TAAMAESEK ENGINEERING CONSORTIUM

Page 72: Volume - 4

TICEL BIO PARK II ACMV WORKS

SI No Description QTY REMARKS

A ACMV WORKS

1 200 TR Air Cooled Water Chiller 2

2 200 TR Air Cooled Brine Chiller 2

3 Primary / Secondary chilled water / Chilled brine Pumps 11

4 Primary and secondary chiller water / brine piping system with insulation

5 Duct and duct insulation works

6 Toilet Exhaust System 2

7 Terrace Exhaust Blower 2

8 Air Handling Units - 3 TR to 100 TR

a 1.5 TR 6b 3 TR 3c 5.5 TR 1d 8.3 TR 27e 10 TR 7f 15 TR 1g 16.5 TR 1h 18 TR 1i 31 TR 1j 34 TR 2k 38 TR 2l 65 TR 2

m 67 TR 2n 92 TR 1o 100 TR 1

ANNEXURE B - NON DEFFECTS LIABILITY PERIOD ITEMSEXISTING TICEL BIO PARK - I EQUIPEMENTS LIST

ENGINEERING CONSULTANT :TAAMAESEK ENGINEERING CONSORTIUM