2
A PICV replaces a traditional control valve and water pressure balancing set. It automatically limits the water flow rate, irrespective of pressure and allows the flow to be modulated to match the load. Once the maximum flow setting is pre-set using the graduated scale, the flow will be modulated by means of the control valve and actuator - independent of the system pressure. This results in stable flow and energy efficiency, regardless of what is happening elsewhere in the system. PIC Valves are particularly well suited to use with inverter driven pumps and variable load circuits. Dynamic curve Provides constant flow at any pump head Full Stroke Separate pressure control and flow chambers allow for full stroke accuracy at any reduced flow setting. Pressure Independent Control Valves ON-OFF ZONE MODULATING ZONE Equal percentage curve n(eq) = 3.9 CONTROL SIGNAL % Knob Opening ΔP 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Actuator / Valve Stroke % 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% Kv % 100% 70% 50% 20 kPa Start-up Adjustment Knob The maximum flow setting can be set without removing the actuator. Cartridge The single piece cartridge gives easier maintenance and flushing. Manual Shut Off For easy maintenance … integral isolation feature. Flushing Mode Control valve rotated by 180°, profiled opening outside flow path. The valve has now full port passage, allowing twice maximum flow, for proper flushing and cleaning. Actuator Assembly Assemblies with 8Nm Non Spring Return on Spring Return Rotary Actuators. Equipercentage Characterised Profile The S-shape design of the valve body flow path minimises internal resistance and turbulence. Pressure measuring connector can provide convenience for customers to test flow at site. Actuators Offer: High Accuracy of Flow Control Four different input/output Display for function information on 3000N model 110,00% 100,00% 90,00% 80,00% 70,00% 60,00% 50,00% 40,00% 30,00% 20,00% 10,00% 0,00% 0 100 200 300 400 Q(m^3/h) PΔ (kPa) 100% Open 80% Open 50% Open 100 90 80 70 60 50 40 30 20 10 0 0 % of max. Flow Angle of rotation [°] 5 10 15 20 25 30 35 40 45 50 55 60 65 70 Theoretical 75 80 85 90 12000 l/h - Equip 9000 l/h - Equip 18000 l/h - Equip VP1000 Series Pressure Independent Control Valves and Actuators Control curve Changes design flow according to control logic of BMS Johnson Controls Building Efficiency UK limited 72 Buckingham Avenue Slough Berkshire SL1 4PN United Kingdom Tel: 01753 870300 Fax: 0870 889 5664 Email: [email protected] Web: www.johnsoncontrols.co.uk & www.johnsoncontrols.com Your stockist: Johnson Controls Limited, a company registered in England & Wales. Registered office: Johnson Controls Limited, 2 The Briars, Waterberry Drive, Waterlooville, Hants, PO7 7YH, United Kingdom. Registered number: 661449. © 2014-2015 Johnson Controls Limited. All rights reserved. Printed in England Manufacturer reserves the right to change specifications without prior notice. E & OE VP1000 – Valves Axial Model VPA – Flanged Axial Model VP1000 – Valves Ball Model

VP1000 Series Pressure Dynamic curve Manual Shut Off ...Berkshire SL1 4PN United Kingdom Tel: 01753 870300 Fax: 0870 889 5664 Email: [email protected] Web: & Your stockist: Johnson

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: VP1000 Series Pressure Dynamic curve Manual Shut Off ...Berkshire SL1 4PN United Kingdom Tel: 01753 870300 Fax: 0870 889 5664 Email: oducts.uk@jci.compr Web: & Your stockist: Johnson

A PICV replaces a traditional control valve and water pressure balancing set. It automatically limits the water flow rate, irrespective of pressure and allows the flow to be modulated to match the load.

Once the maximum flow setting is pre-set using the graduated scale, the flow will be modulated by means of the control valve and actuator - independent of the system pressure. This results in stable flow and energy efficiency, regardless of what is happening elsewhere in the system.

PIC Valves are particularly well suited to use with inverter driven pumps and variable load circuits.

Dynamic curveProvides constant flow at any pump head

Full StrokeSeparate pressure control and flow chambers allow for full stroke accuracy at any reduced flow setting.

Pressure Independent Control Valves

ON-OFF ZONE

MODULATING ZONE

Equal percentage curve n(eq) = 3.9

CONTROL SIGNAL

% Knob Opening

ΔP

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%Actuator /

Valve Stroke %

100%

90%

80%

70%

60%

50%

40%

30%

20%

10%

0%

Kv %

100%

70%

50%

20 kPa Start-up

Adjustment KnobThe maximum flow setting can be set without removing the actuator.

CartridgeThe single piece cartridge gives easier maintenance and flushing.

Manual Shut OffFor easy maintenance … integral isolation feature.

Flushing ModeControl valve rotated by 180°, profiled opening outside flow path. The valve has now full port passage, allowing twice maximum flow, for proper flushing and cleaning.

Actuator AssemblyAssemblies with 8Nm Non Spring Return on Spring Return Rotary Actuators.

Equipercentage Characterised Profile

The S-shape design of the valve body flow path minimises internal resistance and turbulence.

Pressure measuring connector can provide convenience for customers to test flow at site.

Actuators Offer: ■ High Accuracy of Flow Control

■ Four different input/output

■ Display for function information on 3000N model

110,00%100,00%

90,00%80,00%70,00%60,00%50,00%40,00%30,00%20,00%10,00%

0,00%0 100 200 300 400

Q(m

^3/h

)

PΔ (kPa)

100% Open 80% Open 50% Open

100

90

80

70

60

50

40

30

20

10

00

% o

f max

. Flo

w

Angle of rotation [°]5 10 15 20 25 30 35 40 45 50 55 60 65 70

Theoretical

75 80 85 90

12000 l/h - Equip 9000 l/h - Equip18000 l/h - Equip

VP1000 Series Pressure Independent Control Valves and Actuators

Control curveChanges design flow according to control logic of BMS

Johnson Controls Building Efficiency UK limited72 Buckingham AvenueSloughBerkshire SL1 4PNUnited Kingdom

Tel: 01753 870300Fax: 0870 889 5664Email: [email protected]: www.johnsoncontrols.co.uk & www.johnsoncontrols.com

Your stockist:

Johnson Controls Limited, a company registered in England & Wales.Registered office: Johnson Controls Limited, 2 The Briars, Waterberry Drive,Waterlooville, Hants, PO7 7YH, United Kingdom. Registered number: 661449.

© 2014-2015 Johnson Controls Limited. All rights reserved. Printed in England

Manufacturer reserves the right to change specifications without prior notice. E & OE

VP1000 – Valves Axial ModelVPA – Flanged Axial Model

VP1000 – Valves Ball Model

Page 2: VP1000 Series Pressure Dynamic curve Manual Shut Off ...Berkshire SL1 4PN United Kingdom Tel: 01753 870300 Fax: 0870 889 5664 Email: oducts.uk@jci.compr Web: & Your stockist: Johnson

Valves Actuators Benefits of Specifying Pressure Independent Control Valves

Actuators

Codes Power Supply Control Type

VA-7070-21 24 VAC/VDC ON/OFF or DAT Normally Open

(Stem Extends when energised)VA-7070-23 230 VAC

VA-7071-21 24 VAC/VDC ON/OFF or DAT Normally Closed

(Stem Retracts when energised)VA-7071-23 230 VAC

- 0550390101 Adapter must be ordered separately

Codes Power Supply Control Type

VA-7090-21 24VacProportional

Normally Open (Stem Extends when energised)

VA-7091-21 24 VACProportional

Normally Closed (Stem Retracts when energised)

- 0550390101 Adapter must be ordered separately

Flow Rate Range Codes Body Size Connection Size PN Dp Range (kPa)

0.045 ÷ 0.15 m3/hVP100AAA DN15 ½” Union Female 25 20 ÷ 400

0.013 ÷ 0.042 l/s0.060 ÷ 0.6 m3/h

VP100AAE DN15 ½” Union Female 25 25 ÷ 4000.017 ÷ 0.167 l/s0.078 ÷ 0.78 m3/h

VP100AAG DN15 ½” Union Female 25 25 ÷ 4000.022 ÷ 0.217 l/s0.1 ÷ 1 m3/h

VP100BAJ DN20 ¾” Union Female 25 30 ÷ 4000.028 ÷ 0.278 l/s0.45 ÷ 1.5 m3/h

VP101BAN DN20 ¾” Union Female 25 35 ÷ 4000.125 ÷ 0.417 l/s

Flow Rate Range Codes Body Size Connection Size PN Dp Range (kPa)

1.8 ÷ 6 m3/hVP101DBB DN40 1¼” Union Female 16 30 ÷ 600

0.5 ÷ 1.667 l/s1.8 ÷ 6 m3/h

VP101EBB DN40 1½” Union Female 16 30 ÷ 6000.5 ÷ 1.667 l/s0.9 ÷ 9 m3/h

VP101EBC DN40 1½” Union Female 16 35 ÷ 6000.25 ÷ 2.5 l/s3.3 ÷ 11 m3/h

VP101EBD DN40 2” Union Female 16 40 ÷ 6000.917 ÷ 3.056 l/s1.2 ÷ 12 m3/h

VP101FBD DN50 2” Union Female 16 30 ÷ 4000.333 ÷ 3.333 l/s1.8 ÷ 18 m3/h

VP101FBF DN50 2” Union Female 16 35 ÷ 4000.5 ÷ 5 l/s1.8 ÷ 18 m3/h

VP101GBF DN50 2½” Union Male 16 35 ÷ 4000.5 ÷ 5 l/s

Flow Rate Range Codes Body Size Connection Size PN Dp Range (kPa)

0.22 ÷ 2.2 m3/hVP100CAU DN25 1” Union Female 25 25 ÷ 400

0.061 ÷ 0.611 l/s0.27 ÷ 2.7 m3/h

VP100CAW DN25 1” Union Female 25 30 ÷ 4000.075 ÷ 0.75 l/s0.27 ÷ 2.7 m3/h

VP100DAW DN32 1¼” Union Female 25 35 ÷ 4000.075 ÷ 0.75 l/s0.3 ÷ 3 m3/h

VP100DAY DN32 1¼” Union Female 25 35 ÷ 4000.083 ÷ 0.833 l/s

Codes Power Supply Control Type

VA-7480-000124 VAC

Floating 13 sec/mm

VA-7481-0001 Floating 8 sec/mm

VA-7480-0003230 VAC

Floating 13 sec/mm

VA-7481-0003 Floating 8 sec/mm

VA-7482-8201 24 VAC Proportional Self Calibrating

Codes Power Supply Control Type

VA-7482-1001 24 VAC/DC Proportional 3.2 mm Electrical Stroke

Codes Power Supply Control Type

VA-7482-3001 24 VAC/DC Proportional 6 mm Electrical Stroke

Codes Power Supply Control Type

VAP1000-24-C 24 VAC 0(2)~10V,0(4)~20mA

VAP3000-24-C 24 VAC 0(2)~10V,0(4)~20mA

Codes Power Supply Control Type Auxiliary Switches

VA9208-GGA-1

24 VAC/VDC

Proportional---

VA9208-GGC-1 ●VA9208-AGA-1 Floating &

ON/OFF

---

VA9208-AGC-1 ●VA9208-BGA-1

ON/OFF

---

VA9208-BGC-1 ●VA9208-BDA-1

230 VAC---

VA9208-BDC-1 ●

Codes Power Supply Control Type Auxiliary Switches

M9108-AGA-524 VAC/VDC

ON/OFF and Floating

---

M9108-AGC-5 ●M9108-ADA-5

230 VAC---

M9108-ADC-5 ●M9108-GGA-5

24 VAC/VDC Proportional---

M9108-GGC-5 ●- M9000-525-5 linkage necessary

Flow Rate Range Codes Body Size Connection Size PN Dp Range (kPa)

3.9 ÷ 13 m3/hVPA050-C DN50 Flange ISO 7005-2 16 35 ÷ 400

1.092 ÷ 3.64 l/s6.3 ÷ 21 m3/h

VPA065-C DN65 Flange ISO 7005-2 16 35 ÷ 4001.74 ÷ 5.8 l/s8.4 ÷ 28 m3/h

VPA080-C DN80 Flange ISO 7005-2 16 35 ÷ 4002.34 ÷ 7.8 l/s15 ÷ 50 m3/h

VPA100-C DN100 Flange ISO 7005-2 16 35 ÷ 4004.17 ÷ 13.9 l/s27 ÷ 90 m3/h

VPA125-C DN125 Flange ISO 7005-2 16 35 ÷ 4007.5 ÷ 23 l/s43.5 ÷ 145 m3/h

VPA150-C DN150 Flange ISO 7005-2 16 35 ÷ 40012.09 ÷ 40.3 l/s

Johnson Controls delivers products, services and solutions that increase energy efficiency and lower operating costs in buildings for more than one million customers. Operating from 500 branch offices in more than 150 countries, we are a leading provider of equipment, controls and services for heating, ventilating, air-conditioning, refrigeration and security

systems. We have been involved in more than 500 renewable energy projects including solar, wind and geothermal technologies. Our solutions have reduced carbon dioxide emissions by 16 million metric tons and generated savings of $7.5 billion since 2000. Many of the world’s largest companies rely on us to manage 1.5 billion square feet of their commercial real estate.

Easy valve selectionKVs calculations are no longer necessary. The valve is simply selected according to the flow demand of the load.

Pumps cost reducedPICV guarantee the required flow to each terminal. Consequently the total flow is less and the system requires a lower pump head.

Simplified balancing PICV’s make circuits independent; decoupling them from the system. The balancing process is much simplified – just a check of the flow.

FlexibilityPlants can be commissioned zone-by-zone without the need for re-commissioning when additional plant or zones are added.

Three valves in one pieceAn immediate installation cost reduction and less pipe space required.

More comfort and additional savingThe morning start-up can easily cause system imbalance as loads boost to meet demand. Loads at circuit ends can become starved of flow and take longer to warm or cool. Eliminating this imbalance improves comfort and energy consumption.

Higher efficiency on equipmentPICVs guarantee the required flow to each load without wasting pump power with pressure reducing sets. The lower pump head pressure and flow rates needed save energy and the cost of oversized pumps.

VA-7070 – Thermal Actuator

VA-7090 – Thermal Actuator

M9108 – Non Spring Return Valve Actuator

VAP – Non Spring Return Plant Valve Actuator

VP1000 Valves – Axial Model

VP1000 Valves – Axial Model

VP1000 Valves – Ball Model

VA-7480 – Motorised Actuator

VA9208 – Spring Return Valve Actuators

VPA – Flanged Valves