VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24 VT25 VT26 VT27 VT28 VT29 VT30 VT31 VT32 VT32A VT32B VT33 VT33A VT33B VT34 VT35 Upstand Terminations Verge Edge Parapet Edge Internal Gutter Parapet Gutter to Metal Roof with Overflow Parapet Gutter to Membrane Roof Drip Edge Outlet / Overflow Proprietary Sump Viking Sump Dimensions Scupper Transition to Pitched Roofing Upstand to Pitched Roofing Rebated Door Threshold Plant Posts Plinth Base direction to Watershed Plinth Footing Cavity Vent Horizontal Ducting Penetration Flue Penetration Skylight Seismic Generic Diverter Kick-Out Straight Diverter Kick-Out Return Parapet Meets Wall External Corner External Cnr BASE ISO External Cnr CAP ISO Internal Corner Internal Cnr BASE ISO Internal Cnr CAP ISO Ridge Detail Substrate Expansion Ducting Penetration Membrane upstand behind Cladding VT16 Door Threshold VT21 Substrate Vent VT22 Pipe Penetration VT23 Horizontal Pipe Penetration Accessories IMR400 Sump IMR100 Sump IMR120 Sump IMR130 Sump IMT107 Scupper 200 x 80mm IMT108 Scupper 100 x 100mm VT10A VT10B VT10C 80mm Balcony Drain Side Exit Outlet / Overflow 100mm Balcony Drain VT19A Plinths Concrete and Timber VT04A Viking Arch Finishing Series Verge Edge VT04A ISO Viking Arch Finishing Series Verge Edge ISO IMT109 Overflow Scupper 200 x 80mm 26/11/2018 DRAWING STATUS ISSUE Detail Ref: INFORMATION ONLY Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz Viking DRAWING TITLE DATE Viking Viking Torch-on Systems are CodeMarked Cert # GM-CM30092- RevA Note that substrates are indicative only A Viking 2 layer Torch-on Details INDEX

VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

VT01VT02VT03VT04

VT05VT06VT07VT08VT09VT10

VT11VT11A

Membrane Important Notes

VT12VT13VT14VT15

VT17VT18VT19

VT20

VT24VT25VT26VT27VT28VT29VT30VT31VT32

VT32AVT32BVT33

VT33AVT33BVT34VT35

Upstand TerminationsVerge Edge

Parapet EdgeInternal GutterParapet Gutter to Metal Roof with OverflowParapet Gutter to Membrane RoofDrip EdgeOutlet / Overflow

Proprietary SumpViking Sump DimensionsScupperTransition to Pitched RoofingUpstand to Pitched RoofingRebated Door Threshold

Plant PostsPlinth Base direction to WatershedPlinth Footing

Cavity Vent

Horizontal Ducting PenetrationFlue PenetrationSkylightSeismic GenericDiverter Kick-Out StraightDiverter Kick-Out ReturnParapet Meets WallExternal CornerExternal Cnr BASE ISOExternal Cnr CAP ISOInternal CornerInternal Cnr BASE ISOInternal Cnr CAP ISORidge Detail Substrate Expansion

Ducting Penetration

Membrane upstand behind Cladding

VT16 Door Threshold

VT21 Substrate VentVT22 Pipe PenetrationVT23 Horizontal Pipe Penetration

Accessories IMR400 SumpIMR100 SumpIMR120 SumpIMR130 SumpIMT107 Scupper 200 x 80mm

IMT108 Scupper 100 x 100mm

VT10AVT10BVT10C

80mm Balcony DrainSide Exit Outlet / Overflow

100mm Balcony Drain

VT19A Plinths Concrete and Timber

VT04A Viking Arch Finishing Series Verge EdgeVT04A ISO Viking Arch Finishing Series Verge Edge ISO

IMT109 Overflow Scupper 200 x 80mm

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A Viking 2 layer Torch-on Details

INDEX

Page 2: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Angle Fillet 20mm min.Recommended

Viking Bitumen Fillet IMT603

IMPORTANT NOTES for all following details:Specification: These details are for use with all Viking Torch-on Membranes

Gemini APP, Lybra SBS or Phoenix Supper APAO selections.Contact Viking Roofspec to assist with the best selection for your needs.

Priming: All substrates and surfaces where Torch-on membrane is being applied must beprimed with Viking SES300 Bituminous primer. All Metal flashings or Proprietary fittings such as drip-edges, drains, sumps and scuppers must be sanded then primed with Viking Solvent-based Bituminous Primer SES297.

Substrates: All Substrates are to comply with Viking Torch-on System requirements.All external corners must be min. 5mm radius , with Internal corners to have min. 20mm Angle Fillet installed. A Bitumen Fillet is best.

Detailing: All upstand transitions are to be installed as per this detail VT01Internal gutters, door thresholds, wall upstands, skylight upstands etc. Reasoning: To allow for membrane movement near fillets at substrate transition from horizontal to vertical planes

Viking Torch-onCap Sheet Membrane

Viking Water-basedBituminous Eco-Primer SES300

Viking Torch-onBase Sheet Membrane

80mm lap min. for 1st and 2nd layers

150m

m mi

n. up

stand

heigh

t for m

embr

ane

Substrate to comply with current VikingRoofspec Masterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

VT 0126/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Viking 2 layer Torch-on DetailsMembrane Important Notes VT01

Page 3: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

min.

35mm

to cl

addin

g

Specified Cladding on Cavity System

Floor Structure

Roof or Deck Structure

Memb

rane

upsta

nd M

in. 15

0mm

100m

m Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

80mm min.

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsUpstand behind Cladding VT02

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 4: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

'Z'

150m

m mi

n. up

stand

MS Sealant

'Z'

Pressure Bar

Refer

table

7 E2

/AS1

Refer

table

7 E2

/AS1

MS Sealant

20mm

30mm

35mm

Pressure Bar

*Chase termination 'A' *Chase termination 'B' *Pressure Bar termination 'C'recommended only where achase detail is not possible

*Apron Flashing termination 'D'

150m

m mi

n. up

stand

150m

m mi

n. up

stand

150m

m mi

n. up

stand

Cap sheet pushed into 45°chase cut.Seal remaining gap withbituminous compatible sealant.

Notes:- *Refer Detail VT01 for sheet transition from Horizontal to Upstand- 'Z' = Variable cover according to wind zone refer table 7 E2/AS1.- 150mm minimum membrane upstand heights where-ever possible.

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking 2 layer Torch-on DetailsUpstand Terminations VT03

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 5: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

r efer

to ta

ble 7

E2/A

S1Viking Torch-onBase Sheet Membrane

80mm min.

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsVerge-edge VT04

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 6: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

109m

m

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane

Viking 'AFS' Straight COVERITM700 Natural finish Alum1.6mm

Viking 'AFS' Straight BASEITM701 Natural finish Alum1.6mm

Note: Apply Viking Solvent-based Bituminous Primer SES297

Viking Architectural Finishing SeriesViking 2 layer Torch-on Detail for Verge-edge VT04A

17/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 7: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Note: Apply Viking Solvent-basedBituminous Primer SES297

Viking Architectural Finishing SeriesViking 2 layer Torch-on Detail for Verge-edge ISO VT04A ISO

17/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 8: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

'Z'

Metal Cap Flashing& Fixings*5° slope to cap flashing.

'Z' = variable according to wind zoning. please refer to table 7 E2/AS1

►Gutters must be constructed and sized to E2/AS1 paragraphs 8.5.6 and 8.5.10 Refer also to FIG. 64b & 64c E2/AS1►All internal corners must have minimum 20mm angle fillet, all external corners must bebeveled min. 5mm.►The membrane must extend across the top of the parapet and down the outside of theparapet.►The top of the parapet substrate, must be angled to allow water to run off the top of theparapet, *If no metal cap is to be used, then a 10° slope to the top of parapet is required. Refer

E2/AS1 6.5(a)►All fixings for the cap flashing, must be through the side of the flashing.

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane80mm min.

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsParapet VT05

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 9: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Minimum 300mm Gutter width. Min. 1:100 falls, though greater is recommended where it can be achieved

Refer E2/AS1 paragraphs 8.5.6 and 8.5.10 figures. 64b & 64c

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking Clamped Drain or Overflow80/100mm SDM049

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsInternal Gutter VT06

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 10: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

'Z'

'Z' = variable according to wind zoning. please refer to table 7 E2/AS1

►Gutters must be constructed and sized to E2/AS1 paragraphs 8.5.6 and 8.5.10 Refer also to FIG. 64b & 64c E2/AS1►All internal corners must have minimum 20mm angle fillet, all external corners min. 5mm arrise.►The membrane must extend across the top of the parapet and down the outside of the parapet.►The top of the parapet substrate, must be angled to allow water to run off the top of the parapet, *If no metal cap is to be used, then a 10° slope to the top of parapet is required. Refer E2/AS1 6.5(a)►All fixings for the cap flashing, must be through the side of the flashing.

Profiled Roofing

Suggest keeping Parapet heightbelow Gutter Flood line

*5° slope to cap flashing.

Viking Torch-on Base Sheet MembraneViking Torch-on Top Sheet Membrane

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

IMT107

IMT109Scupper Overflow

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsParapet Gutter to Metal Roof VT07

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 11: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane

300mm min. width Gutter

Overflow level (high-point of deck)

100mm minimum depth to floor from high-point of deck

Cladding to Overlap membrane by a minimum 50mm Membrane continues a further 100mm beyondfloor level as per E2/AS1 Fig 62(b)

Membrane continues a further 100mm beyondfloor level as per E2/AS1 Fig 62(b)

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsParapet Gutter to Membrane Roof VT08

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 12: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

2mm Alum or S/S Angle 50x50mm min.

Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Alum or S/S fixing bar to securemembrane to metal drip-edge

Viking 2 layer Torch-on DetailsDrip-edge to Spouting VT09

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 13: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Clamped Overflow80mm / 100mm SDM049150mm diameter specify SDM051

Flange width 230mm (280mm for 150mm outlet)

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

Viking Clamped Outlet80mm / 100mm SDM049150mm diameter specify SDM051

Overflow

Note:1/ Overflow to match outlet capacity.2/ Overflow to be plumbed independent of stormwater, through soffit or exterior wall3/ Viking Solvent-based Bituminous Primer to all metal andproprietary fittings

Viking Solvent-basedBituminous Primer to allmetal and proprietary fittings

Note:Refer Detail VT01

VT1026/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Viking 2 layer Torch-on DetailsClamped Outlet or Overflow

Page 14: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

230mm 230mm

Viking Clamped Drain or Overflow Side exit SDM05580mm flowrate 3.2Lts/sec

Note:1/ Overflow to match outlet capacity.2/ Overflow to be plumbed independent of stormwater, through soffit or exterior wall

Outlet

Overflow

100m

mNote:Refer Detail VT01

VT10A26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Viking 2 layer Torch-on Details80mm Side Exit Clamped Outlet or Overflow

Page 15: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

150m

mas

per E

2/AS1

5mm Gap

115mm

80mm Downpipe

Allthrough Balcony Drain 80mmSDM057

Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

Note:Refer Detail VT01

VT10B26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Viking 2 layer Torch-on Details80mm Balcony Outlet SDM057

Page 16: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

150m

mas

per E

2/AS1

5mm Gap

150mm

100mm Downpipe

Allthrough Balcony Drain100mm SDM058

Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

Note:Refer Detail VT01

VT10C26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Viking 2 layer Torch-on Details100mm Balcony Outlet SDM058

Page 17: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Screw fixing of Sumpinto recessed substrate

Overflow insert Viking Torch-onBase Sheet Membrane

Notes:Refer Detail VT11A for Sump DimensionsSumps to be plumbed with flexible hose-clamped couplings such as Dux or PlumbQwik

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Overflow

IMR120

Leaf GratesIMT302 60-200mmIMT303 60 - 110mmIMT304 75 - 125mm

Install extra strip of Base Sheetmembrane to inside of Sump.Install Gussets at corners

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsViking Proprietary Sump VT11

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 18: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

'E''D''C''B'

'G''F'

MODEL

100 / 150mm100 / 150mm 150 / 200mm250mm30mm

170mm30mm

185mm40mm

IMR130Viking Torch-on Sump Dimensions

150 / 200mm275mm580mm

IMR100 IMR120

100 / 150mm200mm450mm

IMR400

475mm70mm

100 / 150mm

Made NZNZ NZ

'A' 380mm300mm 300mm 292mm450mm

75 / 100mm164mm

150mm30mm

75 / 100mm

NZ

'B''A'

'C'

'D'

'D''E'

'E'

'F'

'G' 'G'

Note:Sumps to be plumbed with flexible hose-clamped couplingssuch as Dux or PlumbQwik

Viking 2 layer Torch-on DetailsViking Proprietary Sump Dimensions VT11A

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 19: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Install a strip of Base Sheet membrane into substraterebate to seal scupper into

Screw fixing of scupper

Viking SilCoat over leading edgeBottom and 2 sides

Viking Scupper IMT107

with Drip edge installedand cut back to cladding

Rain-head with Overflowby others

30mm

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsViking Proprietary Scupper VT12

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 20: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Pitched Roofing

Pitched Roofing Underlay

150m

m

2° fall

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

80mm min.

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsTransition to Pitched Roof VT13

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 21: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

150m

m mi

n. he

ight fo

r mem

bran

e

Pitched Roofing

Pitched Roofing Underlay

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane80mm min.Note:

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsMembrane to Pitched Roofing VT14

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 22: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

5mm Gap

Alum joinery as per specific manufacturers requirements.This drawing shows a seperate Sill Support Bar with sealed fixings.Pre-fill fixing holes with silicone sealant.

Finish Membrane 100mm min. up framing at ends.Width to suit joinery and cladding.Refer E2/AS1 FIG62(b)(d)

Interior floor levelMi

n. 10

0mm

as pe

r E2/A

S1 Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane80mm min.

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsRebated Door Threshold VT15

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 23: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

100m

mas

per E

2/AS1

Finish Membrane 100mm min. up framing at ends.Width to suit joinery and cladding.Refer E2/AS1 FIG62(b)(d)

Refer E2/AS1 Fig62(b)Sill Tray to paragraph 9.1.10.5(c) and Fig17D

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane

5mm Gap

80mm min.

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsDoor Threshold VT16

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 24: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Beam to span frompost supports

Wall Mounted Steel Bracketto support beam

Viking Torch-on 2 LayerWaterproofing Membrane System

NOTE:Brackets to be manufactured specific to requirements andspaced according to Plant weight and beam spanning abilities

Engineered Plant Mount support Bracketsfixed to round posts above waterproofing.

Engineered Round Support Posts and Plates.Fixed to Main Structure.

Beam to span frompost supports

Wall Mounted BracketRound Support post brackets

Viking Torch-on 2 LayerWaterproofing Membrane System

Min.

100m

m

Min. 100mm

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsPlant support Posts and Beams 'WITHOUT PLINTHS' VT17

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 25: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Direction of Watershed

Plinth

Vent or PipePenetration

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsPlinth direction to Watershed for following details VT18

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 26: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Timber or ply plinth fixed throughmain membrane into solid blocking

Sealed fixings by other trades

Viking Bitumen Sealant SES015

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

80mm min.

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsPlinth Footing VT19

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 27: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Note:Substrates to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Use this detail if plinth is already formed in the substrateE.G. Concrete

Viking Bitumen Sealant SES015

Plinths fixed through to the main structure below Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsPlinths Concrete OR Timber VT19A

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 28: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

100m

m

Ensure cross-ventilation within the roof structureEG use of a Castellated Batten directly under the Ply substrate or drill 20mm holes attop of timber supports

Refer VT18 for Direction of Plinth to watershed

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Airflow

Viking Proprietary Vent IMV111Allow 1 vent per 50M2 area

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

min. 100mm

Airflow

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsCavity Vent on Plinth VTM20

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 29: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

100m

m

Viking Proprietary Vent IMV111Allow 1 vent per 50M2 area

Refer VT18 for Direction of Plinth to watershed

AirflowViking Torch-on

Cap Sheet Membrane

Viking Torch-onVented Base Sheet Membrane

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

min. 100mm

Airflow

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsSubstrate Vent on Plinth VT21

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 30: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Pipe Over-flashingby Plumber

Min. 80mm

Refer VT18 for Direction of Plinth to watershed

Min. 100mm

Min.

100m

m

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsPipe Penetration with Plinth VT22

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 31: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane

Stainless Steel Hose Clamp

Viking SES015 Elastigum Bitumen Sealant

Min.

100m

m

Min. 100mm

Substrate to comply with current Viking RoofspecMasterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsHorizontal Penetration VT23

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 32: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Pipe Over-flashingby Plumber

Goose-neck by Plumber or electricianallowing Wiring or Conduit to be passed through

Polystyrene Plug

Cable or Conduit

Min. 80mm

Min. 100mm

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsGoose-Neck Pipe Penetration for Ducting Cables VT24

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 33: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Min.

100m

m

Goose-neck by Plumber or electricianallowing Wiring or Conduit to bepassed through

Polystyrene PlugCable or Conduit

Stainless Steel Hose Clamp

Bitumen compatible Sealant

Min. 100mm

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane

Substrate to comply with current Viking RoofspecMasterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsHorizontal Cable or Conduit Penetration VT25

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 34: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

150m

m up

stand

min.

80mm

Dektite Aluminium Over Flashingsuitable for 115°refer Decktite for specific flashing.

Viking Torch-onBase Sheet Membrane

50mm

Flue and cover flashing

Viking Torch-onCap Sheet Membrane

Refer Table 7 E2/AS1

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsFlue Penetration VT26

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 35: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Minim

um15

0mm

Over Flashing from Skylight, Vent, etc.

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet MembraneSkylight

Divert watershedaway from Skylight

80mm min.

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsSkylight upstand VTM27

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 36: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Minim

um10

0mm

Metal Cap Flashing to allow for movementspecific site details by Designer

Specific Seismic Joint by Designer

80mm

Site specificSeismic Gap determined by Designer.

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Viking Torch-onCap Sheet Membrane

Viking Torch-onBase Sheet Membrane

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsGeneric Seismic Joint VT28

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 37: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-on2 Layer Membrane System

Sealant bead to membranebehind metal Kick-out diverter

Use Viking Proprietary S/S Kick-out DivertersIMT604 R/H or IMT605 L/H

Substrate to comply with current VikingRoofspec Masterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsMembrane Kick-out Diverter VT29

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 38: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Viking Torch-on2 Layer Membrane System

*MetalKick-out Diverter

►◄

*Kick-out diverterUse Viking Proprietary S/S Kick-out DivertersIMT604 R/H or IMT605 L/H

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsMembrane Kick-out Diverter VT30

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 39: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 5. Metal Cap flashing to seal to saddle flashing

50mm

50mm

*NOTE:refer E2/AS1 fig12 for saddle detail

Sealant Bead x 2for Parapet Cap

Viking Torch-on Membrane Systemto detail over cladding

50x50mm Internal-corner Flashing by cladding supplierBehind saddle flashing extended to bottom of cladding.

STEP 4.Cladding to seal to saddle flashing

STEP 1. NOTE: Must be installed as part of the roof membrane systemViking Torch-on 2 Layer Torch-on System behind cavity battenis to be fully supported by substrate ply or timber.Finish 150mm min. cover over & beyond the parapet junction

Viking GM Torchon 2 Layer Membrane System

STEP 3. *Saddle Flashing over cavity batten,directly behind cladding, refer Fig12 E2/AS1

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsISO Parapet Meets Wall Junction VT31

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 40: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 2.

1

STEP 1. STEP 3.

NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.

STEP 1.

STEP 2.

STEP 3.

2

1

Note: Fillets at Upstand transitions are required.

Also refer VT32A and VT32B for External Corner detailing

Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsExternal Corner VT32

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

Page 41: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

External Corner Detail BASE SHEET LAYER

STEP 1.Lay Viking Torch-on Base

sheet to fillets

STEP 2. Base Sheet LayerInstall 140mm Gusset

STEP 3. Viking Torch-on Base Sheet LayerInstall Double on the vertical planewith a min. 80mm lap onto base sheetand over onto the opposite corner

STEP 4. Viking Torch-on Base Sheet LayerInstall 2nd Double from theopposite direction also witha min. 80mm lap onto base sheet.Mitre to corner over 1st Double

NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.

STEP 3.

STEP 2.STEP 1.

STEP 4.

Substrate to comply with current VikingRoofspec Masterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsISO External Corner Base Layer VT32A

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 42: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 1.Lay Viking Torch-on Cap

sheet to fillets

STEP 2. Viking Torch-on Cap Sheet layer.Install Double on the vertical planewith a min. 80mm lap onto theMain Feild-sheet and overonto the opposite corner

STEP 3. Viking Torch-on Cap Sheet Layer.Install Double from the opposite direction alsowith a min. 80mm lap onto Main Feild sheet.Mitre Butt join to 1st Double at bottom.

*Important Note:Cap sheet external corner tabs must beinstalled in the opposite direction to the

1st layer Base sheet

NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.

*STEP 2.

STEP 1.

*STEP 3.

External Corner Detail CAP SHEET LAYER refer VT32A for 1st layer

Substrate to comply with current VikingRoofspec Masterspec specification

Substrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsISO External Corner Cap Sheet Layer VT32B

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 43: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 1. STEP 2. STEP 3.

STEP 4. STEP 5. STEP 6.

Note: Fillets at Upstand transitions are required.

Form a 140mm round Gusset toInternal corner

Also

refer

VT3

3A an

d VT3

3B fo

r Inte

rnal

Corn

er de

tailin

g

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsInternal Corner VT33

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 44: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 1.Lay Base sheet to fillets

STEP 3. Viking Torch-on Base Sheet LayerInstall Double on the vertical plane with a min. 80mm laponto base sheet and over onto the opposite corner

STEP 2. Base Sheet LayerInstall 140mm round Gusset

STEP 4. Viking Torch-on Base Sheet LayerInstall 2nd Double from the opposite direction also witha min. 80mm lap onto base sheet. Mitre to corner over1st Double

Internal Corner Detail BASE SHEET LAYER Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsISO Internal Corner Base Layer VT33A

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 45: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

STEP 1.Lay Cap sheet to fillets

STEP 2. Viking Torch-on Cap Sheet layer.Install Double on the vertical plane with a min. 80mm laponto the Main Feild-sheet and over onto the opposite corner

STEP 3. Viking Torch-on Cap Sheet Layer.Install Double from the opposite direction alsowith a min. 80mm lap onto Main Feild-sheet.Mitre Butt join to 1st Double at bottom.

Important Note:Cap sheet layer internal corner

tabs must be installed in theopposite direction to *Base sheet

*Important Note:Cap sheet Internal corner tabs must beinstalled in the opposite direction to the

1st layer *Base sheet

Internal Corner Detail CAP SHEET LAYER refer VT33A for 1st layerSubstrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsISO Internal CornerTop Layer VT33B

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 46: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Base Sheet 150mm bond-break stripfixed to one side only either pinned, welded, or spot welded

to allow for expansion / contraction of plywood at ridge junction.

Viking Torch-on Cap Sheet Membrane

Viking Torch-on Base Sheet Membrane80mm min.

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsRidge Detail VT34

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 47: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

5mm expansion gap in plywood

Torch-on Base Sheet, 150mm bond-break stripfixed to high-side of watershed, one side only.

Either pinned, welded, or spot welded to allow forexpansion / contraction of plywood.

All Plywood sheet edges to be fully supported

Viking Torch-on Base Sheet Membrane

Viking Torch-on Cap Sheet Membrane

Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz

Note:Refer Detail VT01

Viking 2 layer Torch-on DetailsExpansion Detail VT35

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 48: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

450mm

300m

m

150mm

239mm211mm95mm70mm

164m

m

300mm

Plumber to connect to Downpipe with Flexible Pipe couplings

30

IMR100

Over

flow IMR100

Viking 2 layer Torch-on DetailsIMR100 Sump with Overflow 75/100mm IMR100

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 49: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

Plumber to connect to Downpipe with Flexible Pipe couplings

450mm

300m

m33

5mm 20

0mm

240mm

205mm

145mm

95mm

170mm

IMR120

IMR120

IMR120

Overflow

IMR120

Viking 2 layer Torch-on DetailsIMR120 Sump with Overflow 100/150mm IMR120

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 50: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

580mm380mm

580m

m

249m

m

390m

m

Rubber O Ring

Plumber to connect to Downpipe with Flexible Pipe couplings

300mm265mm190mm145mm

250mm

510mm

IMR130

Over

flowIMR130 IMR130

Viking 2 layer Torch-on DetailsIMR130 Sump with Overflow 150/200mm IMR130

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 51: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

292m

m

475mm

242mm186mm145mm95mm185mm

220m

m

70mm

Plumber to connect to Downpipe with Flexible Pipe couplings

475mm

40

IMR400

Overflow IMR400 IMR400

Viking 2 layer Torch-on DetailsIMR400 Sump with Overflow 100/150mm IMR400

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 52: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

95°

400

135

88207

119

135

389

IMT107E2/AS1 size compliant

IMT107E2/AS1 size compliant

IMT107

Viking 2 layer Torch-on DetailsIMT107 200x80mm 1.6mm S/S Scupper

E2/AS1 Compliant Scupper Flowrate 7.7 Lts / Sec IMT10726/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 53: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

389

IMT109 200 x 80 Scupper OverflowE2/AS1 size compliant

Viking 2 layer Torch-on DetailsIMT109 200x80mm 1.6mm S/S Overflow-ScupperE2/AS1 Compliant Scupper Flowrate 7.7 Lts / Sec IMT109

26/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

Viking

DRAWING TITLE

DATE

Viking

Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA

Note that substrates are indicative only

A

Page 54: VT01 Membrane Important Notes VT21 Substrate Vent...VT01 VT02 VT03 VT04 VT05 VT06 VT07 VT08 VT09 VT10 VT11 VT11A Membrane Important Notes VT12 VT13 VT14 VT15 VT17 VT18 VT19 VT20 VT24

95°

300

100

100

IMT108

IMT108IMT108

108

180

260

Viking 2 layer Torch-on DetailsIMT108 100x100 1.6mm S/S Scupper

Flowrate 5.9 Lts / Sec IMT10826/11/2018

DRAWING STATUS

ISSUEDetail Ref:

INFORMATION ONLY

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz