VT01VT02VT03VT04
VT05VT06VT07VT08VT09VT10
VT11VT11A
Membrane Important Notes
VT12VT13VT14VT15
VT17VT18VT19
VT20
VT24VT25VT26VT27VT28VT29VT30VT31VT32
VT32AVT32BVT33
VT33AVT33BVT34VT35
Upstand TerminationsVerge Edge
Parapet EdgeInternal GutterParapet Gutter to Metal Roof with OverflowParapet Gutter to Membrane RoofDrip EdgeOutlet / Overflow
Proprietary SumpViking Sump DimensionsScupperTransition to Pitched RoofingUpstand to Pitched RoofingRebated Door Threshold
Plant PostsPlinth Base direction to WatershedPlinth Footing
Cavity Vent
Horizontal Ducting PenetrationFlue PenetrationSkylightSeismic GenericDiverter Kick-Out StraightDiverter Kick-Out ReturnParapet Meets WallExternal CornerExternal Cnr BASE ISOExternal Cnr CAP ISOInternal CornerInternal Cnr BASE ISOInternal Cnr CAP ISORidge Detail Substrate Expansion
Ducting Penetration
Membrane upstand behind Cladding
VT16 Door Threshold
VT21 Substrate VentVT22 Pipe PenetrationVT23 Horizontal Pipe Penetration
Accessories IMR400 SumpIMR100 SumpIMR120 SumpIMR130 SumpIMT107 Scupper 200 x 80mm
IMT108 Scupper 100 x 100mm
VT10AVT10BVT10C
80mm Balcony DrainSide Exit Outlet / Overflow
100mm Balcony Drain
VT19A Plinths Concrete and Timber
VT04A Viking Arch Finishing Series Verge EdgeVT04A ISO Viking Arch Finishing Series Verge Edge ISO
IMT109 Overflow Scupper 200 x 80mm
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A Viking 2 layer Torch-on Details
INDEX
Angle Fillet 20mm min.Recommended
Viking Bitumen Fillet IMT603
IMPORTANT NOTES for all following details:Specification: These details are for use with all Viking Torch-on Membranes
Gemini APP, Lybra SBS or Phoenix Supper APAO selections.Contact Viking Roofspec to assist with the best selection for your needs.
Priming: All substrates and surfaces where Torch-on membrane is being applied must beprimed with Viking SES300 Bituminous primer. All Metal flashings or Proprietary fittings such as drip-edges, drains, sumps and scuppers must be sanded then primed with Viking Solvent-based Bituminous Primer SES297.
Substrates: All Substrates are to comply with Viking Torch-on System requirements.All external corners must be min. 5mm radius , with Internal corners to have min. 20mm Angle Fillet installed. A Bitumen Fillet is best.
Detailing: All upstand transitions are to be installed as per this detail VT01Internal gutters, door thresholds, wall upstands, skylight upstands etc. Reasoning: To allow for membrane movement near fillets at substrate transition from horizontal to vertical planes
Viking Torch-onCap Sheet Membrane
Viking Water-basedBituminous Eco-Primer SES300
Viking Torch-onBase Sheet Membrane
80mm lap min. for 1st and 2nd layers
150m
m mi
n. up
stand
heigh
t for m
embr
ane
Substrate to comply with current VikingRoofspec Masterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
VT 0126/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking 2 layer Torch-on DetailsMembrane Important Notes VT01
min.
35mm
to cl
addin
g
Specified Cladding on Cavity System
Floor Structure
Roof or Deck Structure
Memb
rane
upsta
nd M
in. 15
0mm
100m
m Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
80mm min.
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsUpstand behind Cladding VT02
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
'Z'
150m
m mi
n. up
stand
MS Sealant
'Z'
Pressure Bar
Refer
table
7 E2
/AS1
Refer
table
7 E2
/AS1
MS Sealant
20mm
30mm
35mm
Pressure Bar
*Chase termination 'A' *Chase termination 'B' *Pressure Bar termination 'C'recommended only where achase detail is not possible
*Apron Flashing termination 'D'
150m
m mi
n. up
stand
150m
m mi
n. up
stand
150m
m mi
n. up
stand
Cap sheet pushed into 45°chase cut.Seal remaining gap withbituminous compatible sealant.
Notes:- *Refer Detail VT01 for sheet transition from Horizontal to Upstand- 'Z' = Variable cover according to wind zone refer table 7 E2/AS1.- 150mm minimum membrane upstand heights where-ever possible.
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking 2 layer Torch-on DetailsUpstand Terminations VT03
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
r efer
to ta
ble 7
E2/A
S1Viking Torch-onBase Sheet Membrane
80mm min.
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsVerge-edge VT04
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
109m
m
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane
Viking 'AFS' Straight COVERITM700 Natural finish Alum1.6mm
Viking 'AFS' Straight BASEITM701 Natural finish Alum1.6mm
Note: Apply Viking Solvent-based Bituminous Primer SES297
Viking Architectural Finishing SeriesViking 2 layer Torch-on Detail for Verge-edge VT04A
17/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
Note: Apply Viking Solvent-basedBituminous Primer SES297
Viking Architectural Finishing SeriesViking 2 layer Torch-on Detail for Verge-edge ISO VT04A ISO
17/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
'Z'
Metal Cap Flashing& Fixings*5° slope to cap flashing.
'Z' = variable according to wind zoning. please refer to table 7 E2/AS1
►Gutters must be constructed and sized to E2/AS1 paragraphs 8.5.6 and 8.5.10 Refer also to FIG. 64b & 64c E2/AS1►All internal corners must have minimum 20mm angle fillet, all external corners must bebeveled min. 5mm.►The membrane must extend across the top of the parapet and down the outside of theparapet.►The top of the parapet substrate, must be angled to allow water to run off the top of theparapet, *If no metal cap is to be used, then a 10° slope to the top of parapet is required. Refer
E2/AS1 6.5(a)►All fixings for the cap flashing, must be through the side of the flashing.
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane80mm min.
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsParapet VT05
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Minimum 300mm Gutter width. Min. 1:100 falls, though greater is recommended where it can be achieved
Refer E2/AS1 paragraphs 8.5.6 and 8.5.10 figures. 64b & 64c
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking Clamped Drain or Overflow80/100mm SDM049
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsInternal Gutter VT06
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
'Z'
'Z' = variable according to wind zoning. please refer to table 7 E2/AS1
►Gutters must be constructed and sized to E2/AS1 paragraphs 8.5.6 and 8.5.10 Refer also to FIG. 64b & 64c E2/AS1►All internal corners must have minimum 20mm angle fillet, all external corners min. 5mm arrise.►The membrane must extend across the top of the parapet and down the outside of the parapet.►The top of the parapet substrate, must be angled to allow water to run off the top of the parapet, *If no metal cap is to be used, then a 10° slope to the top of parapet is required. Refer E2/AS1 6.5(a)►All fixings for the cap flashing, must be through the side of the flashing.
Profiled Roofing
Suggest keeping Parapet heightbelow Gutter Flood line
*5° slope to cap flashing.
Viking Torch-on Base Sheet MembraneViking Torch-on Top Sheet Membrane
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
IMT107
IMT109Scupper Overflow
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsParapet Gutter to Metal Roof VT07
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane
300mm min. width Gutter
Overflow level (high-point of deck)
100mm minimum depth to floor from high-point of deck
Cladding to Overlap membrane by a minimum 50mm Membrane continues a further 100mm beyondfloor level as per E2/AS1 Fig 62(b)
Membrane continues a further 100mm beyondfloor level as per E2/AS1 Fig 62(b)
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsParapet Gutter to Membrane Roof VT08
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
2mm Alum or S/S Angle 50x50mm min.
Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Alum or S/S fixing bar to securemembrane to metal drip-edge
Viking 2 layer Torch-on DetailsDrip-edge to Spouting VT09
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Clamped Overflow80mm / 100mm SDM049150mm diameter specify SDM051
Flange width 230mm (280mm for 150mm outlet)
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
Viking Clamped Outlet80mm / 100mm SDM049150mm diameter specify SDM051
Overflow
Note:1/ Overflow to match outlet capacity.2/ Overflow to be plumbed independent of stormwater, through soffit or exterior wall3/ Viking Solvent-based Bituminous Primer to all metal andproprietary fittings
Viking Solvent-basedBituminous Primer to allmetal and proprietary fittings
Note:Refer Detail VT01
VT1026/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking 2 layer Torch-on DetailsClamped Outlet or Overflow
230mm 230mm
Viking Clamped Drain or Overflow Side exit SDM05580mm flowrate 3.2Lts/sec
Note:1/ Overflow to match outlet capacity.2/ Overflow to be plumbed independent of stormwater, through soffit or exterior wall
Outlet
Overflow
100m
mNote:Refer Detail VT01
VT10A26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking 2 layer Torch-on Details80mm Side Exit Clamped Outlet or Overflow
Min.
150m
mas
per E
2/AS1
5mm Gap
115mm
80mm Downpipe
Allthrough Balcony Drain 80mmSDM057
Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
Note:Refer Detail VT01
VT10B26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking 2 layer Torch-on Details80mm Balcony Outlet SDM057
Min.
150m
mas
per E
2/AS1
5mm Gap
150mm
100mm Downpipe
Allthrough Balcony Drain100mm SDM058
Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
Note:Refer Detail VT01
VT10C26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking 2 layer Torch-on Details100mm Balcony Outlet SDM058
Viking Torch-onCap Sheet Membrane
Screw fixing of Sumpinto recessed substrate
Overflow insert Viking Torch-onBase Sheet Membrane
Notes:Refer Detail VT11A for Sump DimensionsSumps to be plumbed with flexible hose-clamped couplings such as Dux or PlumbQwik
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Overflow
IMR120
Leaf GratesIMT302 60-200mmIMT303 60 - 110mmIMT304 75 - 125mm
Install extra strip of Base Sheetmembrane to inside of Sump.Install Gussets at corners
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsViking Proprietary Sump VT11
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
'E''D''C''B'
'G''F'
MODEL
100 / 150mm100 / 150mm 150 / 200mm250mm30mm
170mm30mm
185mm40mm
IMR130Viking Torch-on Sump Dimensions
150 / 200mm275mm580mm
IMR100 IMR120
100 / 150mm200mm450mm
IMR400
475mm70mm
100 / 150mm
Made NZNZ NZ
'A' 380mm300mm 300mm 292mm450mm
75 / 100mm164mm
150mm30mm
75 / 100mm
NZ
'B''A'
'C'
'D'
'D''E'
'E'
'F'
'G' 'G'
Note:Sumps to be plumbed with flexible hose-clamped couplingssuch as Dux or PlumbQwik
Viking 2 layer Torch-on DetailsViking Proprietary Sump Dimensions VT11A
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Install a strip of Base Sheet membrane into substraterebate to seal scupper into
Screw fixing of scupper
Viking SilCoat over leading edgeBottom and 2 sides
Viking Scupper IMT107
with Drip edge installedand cut back to cladding
Rain-head with Overflowby others
30mm
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsViking Proprietary Scupper VT12
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
Pitched Roofing
Pitched Roofing Underlay
150m
m
2° fall
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
80mm min.
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsTransition to Pitched Roof VT13
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
150m
m mi
n. he
ight fo
r mem
bran
e
Pitched Roofing
Pitched Roofing Underlay
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane80mm min.Note:
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsMembrane to Pitched Roofing VT14
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
5mm Gap
Alum joinery as per specific manufacturers requirements.This drawing shows a seperate Sill Support Bar with sealed fixings.Pre-fill fixing holes with silicone sealant.
Finish Membrane 100mm min. up framing at ends.Width to suit joinery and cladding.Refer E2/AS1 FIG62(b)(d)
Interior floor levelMi
n. 10
0mm
as pe
r E2/A
S1 Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane80mm min.
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsRebated Door Threshold VT15
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Min.
100m
mas
per E
2/AS1
Finish Membrane 100mm min. up framing at ends.Width to suit joinery and cladding.Refer E2/AS1 FIG62(b)(d)
Refer E2/AS1 Fig62(b)Sill Tray to paragraph 9.1.10.5(c) and Fig17D
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane
5mm Gap
80mm min.
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsDoor Threshold VT16
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Beam to span frompost supports
Wall Mounted Steel Bracketto support beam
Viking Torch-on 2 LayerWaterproofing Membrane System
NOTE:Brackets to be manufactured specific to requirements andspaced according to Plant weight and beam spanning abilities
Engineered Plant Mount support Bracketsfixed to round posts above waterproofing.
Engineered Round Support Posts and Plates.Fixed to Main Structure.
Beam to span frompost supports
Wall Mounted BracketRound Support post brackets
Viking Torch-on 2 LayerWaterproofing Membrane System
Min.
100m
m
Min. 100mm
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsPlant support Posts and Beams 'WITHOUT PLINTHS' VT17
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Direction of Watershed
Plinth
Vent or PipePenetration
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsPlinth direction to Watershed for following details VT18
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Timber or ply plinth fixed throughmain membrane into solid blocking
Sealed fixings by other trades
Viking Bitumen Sealant SES015
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
80mm min.
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsPlinth Footing VT19
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Note:Substrates to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Use this detail if plinth is already formed in the substrateE.G. Concrete
Viking Bitumen Sealant SES015
Plinths fixed through to the main structure below Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsPlinths Concrete OR Timber VT19A
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Min.
100m
m
Ensure cross-ventilation within the roof structureEG use of a Castellated Batten directly under the Ply substrate or drill 20mm holes attop of timber supports
Refer VT18 for Direction of Plinth to watershed
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Airflow
Viking Proprietary Vent IMV111Allow 1 vent per 50M2 area
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
min. 100mm
Airflow
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsCavity Vent on Plinth VTM20
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Min.
100m
m
Viking Proprietary Vent IMV111Allow 1 vent per 50M2 area
Refer VT18 for Direction of Plinth to watershed
AirflowViking Torch-on
Cap Sheet Membrane
Viking Torch-onVented Base Sheet Membrane
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
min. 100mm
Airflow
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsSubstrate Vent on Plinth VT21
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Pipe Over-flashingby Plumber
Min. 80mm
Refer VT18 for Direction of Plinth to watershed
Min. 100mm
Min.
100m
m
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsPipe Penetration with Plinth VT22
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane
Stainless Steel Hose Clamp
Viking SES015 Elastigum Bitumen Sealant
Min.
100m
m
Min. 100mm
Substrate to comply with current Viking RoofspecMasterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsHorizontal Penetration VT23
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Pipe Over-flashingby Plumber
Goose-neck by Plumber or electricianallowing Wiring or Conduit to be passed through
Polystyrene Plug
Cable or Conduit
Min. 80mm
Min. 100mm
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsGoose-Neck Pipe Penetration for Ducting Cables VT24
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Min.
100m
m
Goose-neck by Plumber or electricianallowing Wiring or Conduit to bepassed through
Polystyrene PlugCable or Conduit
Stainless Steel Hose Clamp
Bitumen compatible Sealant
Min. 100mm
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane
Substrate to comply with current Viking RoofspecMasterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsHorizontal Cable or Conduit Penetration VT25
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
150m
m up
stand
min.
80mm
Dektite Aluminium Over Flashingsuitable for 115°refer Decktite for specific flashing.
Viking Torch-onBase Sheet Membrane
50mm
Flue and cover flashing
Viking Torch-onCap Sheet Membrane
Refer Table 7 E2/AS1
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsFlue Penetration VT26
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Minim
um15
0mm
Over Flashing from Skylight, Vent, etc.
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet MembraneSkylight
Divert watershedaway from Skylight
80mm min.
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsSkylight upstand VTM27
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Minim
um10
0mm
Metal Cap Flashing to allow for movementspecific site details by Designer
Specific Seismic Joint by Designer
80mm
Site specificSeismic Gap determined by Designer.
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Viking Torch-onCap Sheet Membrane
Viking Torch-onBase Sheet Membrane
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsGeneric Seismic Joint VT28
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-on2 Layer Membrane System
Sealant bead to membranebehind metal Kick-out diverter
Use Viking Proprietary S/S Kick-out DivertersIMT604 R/H or IMT605 L/H
Substrate to comply with current VikingRoofspec Masterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsMembrane Kick-out Diverter VT29
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Viking Torch-on2 Layer Membrane System
*MetalKick-out Diverter
►◄
*Kick-out diverterUse Viking Proprietary S/S Kick-out DivertersIMT604 R/H or IMT605 L/H
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsMembrane Kick-out Diverter VT30
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 5. Metal Cap flashing to seal to saddle flashing
50mm
50mm
*NOTE:refer E2/AS1 fig12 for saddle detail
Sealant Bead x 2for Parapet Cap
Viking Torch-on Membrane Systemto detail over cladding
50x50mm Internal-corner Flashing by cladding supplierBehind saddle flashing extended to bottom of cladding.
STEP 4.Cladding to seal to saddle flashing
STEP 1. NOTE: Must be installed as part of the roof membrane systemViking Torch-on 2 Layer Torch-on System behind cavity battenis to be fully supported by substrate ply or timber.Finish 150mm min. cover over & beyond the parapet junction
Viking GM Torchon 2 Layer Membrane System
STEP 3. *Saddle Flashing over cavity batten,directly behind cladding, refer Fig12 E2/AS1
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsISO Parapet Meets Wall Junction VT31
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 2.
1
STEP 1. STEP 3.
NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.
STEP 1.
STEP 2.
STEP 3.
2
1
Note: Fillets at Upstand transitions are required.
Also refer VT32A and VT32B for External Corner detailing
Note:Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsExternal Corner VT32
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
External Corner Detail BASE SHEET LAYER
STEP 1.Lay Viking Torch-on Base
sheet to fillets
STEP 2. Base Sheet LayerInstall 140mm Gusset
STEP 3. Viking Torch-on Base Sheet LayerInstall Double on the vertical planewith a min. 80mm lap onto base sheetand over onto the opposite corner
STEP 4. Viking Torch-on Base Sheet LayerInstall 2nd Double from theopposite direction also witha min. 80mm lap onto base sheet.Mitre to corner over 1st Double
NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.
STEP 3.
STEP 2.STEP 1.
STEP 4.
Substrate to comply with current VikingRoofspec Masterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsISO External Corner Base Layer VT32A
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 1.Lay Viking Torch-on Cap
sheet to fillets
STEP 2. Viking Torch-on Cap Sheet layer.Install Double on the vertical planewith a min. 80mm lap onto theMain Feild-sheet and overonto the opposite corner
STEP 3. Viking Torch-on Cap Sheet Layer.Install Double from the opposite direction alsowith a min. 80mm lap onto Main Feild sheet.Mitre Butt join to 1st Double at bottom.
*Important Note:Cap sheet external corner tabs must beinstalled in the opposite direction to the
1st layer Base sheet
NOTE: Particular care should be taken to ensure Overlaps do not leave holes or cuts exposed.
*STEP 2.
STEP 1.
*STEP 3.
External Corner Detail CAP SHEET LAYER refer VT32A for 1st layer
Substrate to comply with current VikingRoofspec Masterspec specification
Substrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsISO External Corner Cap Sheet Layer VT32B
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 1. STEP 2. STEP 3.
STEP 4. STEP 5. STEP 6.
Note: Fillets at Upstand transitions are required.
Form a 140mm round Gusset toInternal corner
Also
refer
VT3
3A an
d VT3
3B fo
r Inte
rnal
Corn
er de
tailin
g
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsInternal Corner VT33
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 1.Lay Base sheet to fillets
STEP 3. Viking Torch-on Base Sheet LayerInstall Double on the vertical plane with a min. 80mm laponto base sheet and over onto the opposite corner
STEP 2. Base Sheet LayerInstall 140mm round Gusset
STEP 4. Viking Torch-on Base Sheet LayerInstall 2nd Double from the opposite direction also witha min. 80mm lap onto base sheet. Mitre to corner over1st Double
Internal Corner Detail BASE SHEET LAYER Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsISO Internal Corner Base Layer VT33A
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
STEP 1.Lay Cap sheet to fillets
STEP 2. Viking Torch-on Cap Sheet layer.Install Double on the vertical plane with a min. 80mm laponto the Main Feild-sheet and over onto the opposite corner
STEP 3. Viking Torch-on Cap Sheet Layer.Install Double from the opposite direction alsowith a min. 80mm lap onto Main Feild-sheet.Mitre Butt join to 1st Double at bottom.
Important Note:Cap sheet layer internal corner
tabs must be installed in theopposite direction to *Base sheet
*Important Note:Cap sheet Internal corner tabs must beinstalled in the opposite direction to the
1st layer *Base sheet
Internal Corner Detail CAP SHEET LAYER refer VT33A for 1st layerSubstrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsISO Internal CornerTop Layer VT33B
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Base Sheet 150mm bond-break stripfixed to one side only either pinned, welded, or spot welded
to allow for expansion / contraction of plywood at ridge junction.
Viking Torch-on Cap Sheet Membrane
Viking Torch-on Base Sheet Membrane80mm min.
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsRidge Detail VT34
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
5mm expansion gap in plywood
Torch-on Base Sheet, 150mm bond-break stripfixed to high-side of watershed, one side only.
Either pinned, welded, or spot welded to allow forexpansion / contraction of plywood.
All Plywood sheet edges to be fully supported
Viking Torch-on Base Sheet Membrane
Viking Torch-on Cap Sheet Membrane
Substrate to comply with current Viking RoofspecMasterspec specificationSubstrate Checksheet available fromwww.vikingroofspec.co.nz
Note:Refer Detail VT01
Viking 2 layer Torch-on DetailsExpansion Detail VT35
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
450mm
300m
m
150mm
239mm211mm95mm70mm
164m
m
300mm
Plumber to connect to Downpipe with Flexible Pipe couplings
30
IMR100
Over
flow IMR100
Viking 2 layer Torch-on DetailsIMR100 Sump with Overflow 75/100mm IMR100
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
Plumber to connect to Downpipe with Flexible Pipe couplings
450mm
300m
m33
5mm 20
0mm
240mm
205mm
145mm
95mm
170mm
IMR120
IMR120
IMR120
Overflow
IMR120
Viking 2 layer Torch-on DetailsIMR120 Sump with Overflow 100/150mm IMR120
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
580mm380mm
580m
m
249m
m
390m
m
Rubber O Ring
Plumber to connect to Downpipe with Flexible Pipe couplings
300mm265mm190mm145mm
250mm
510mm
IMR130
Over
flowIMR130 IMR130
Viking 2 layer Torch-on DetailsIMR130 Sump with Overflow 150/200mm IMR130
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
292m
m
475mm
242mm186mm145mm95mm185mm
220m
m
70mm
Plumber to connect to Downpipe with Flexible Pipe couplings
475mm
40
IMR400
Overflow IMR400 IMR400
Viking 2 layer Torch-on DetailsIMR400 Sump with Overflow 100/150mm IMR400
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
95°
400
135
88207
119
135
389
IMT107E2/AS1 size compliant
IMT107E2/AS1 size compliant
IMT107
Viking 2 layer Torch-on DetailsIMT107 200x80mm 1.6mm S/S Scupper
E2/AS1 Compliant Scupper Flowrate 7.7 Lts / Sec IMT10726/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
389
IMT109 200 x 80 Scupper OverflowE2/AS1 size compliant
Viking 2 layer Torch-on DetailsIMT109 200x80mm 1.6mm S/S Overflow-ScupperE2/AS1 Compliant Scupper Flowrate 7.7 Lts / Sec IMT109
26/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only
A
95°
300
100
100
IMT108
IMT108IMT108
108
180
260
Viking 2 layer Torch-on DetailsIMT108 100x100 1.6mm S/S Scupper
Flowrate 5.9 Lts / Sec IMT10826/11/2018
DRAWING STATUS
ISSUEDetail Ref:
INFORMATION ONLY
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
Viking
DRAWING TITLE
DATE
Viking
Viking Torch-on Systems areCodeMarkedCert # GM-CM30092- RevA
Note that substrates are indicative only