VTXSupervision Relay
AREVA T&D
Customer Benefits
• High stability on external faults• Tuned to rated frequency• 25ms operating time at 5 times current setting
VTX relay is used for the continuous supervision of CT secondary wiring and connections of busbar protection schemes. A built in delay of 3 seconds is provided to avoid unwanted alarm during external/internal faults.The relay after operation will short the CT bus wires.
Features • Consistentaccuracy. • Reliability. • Lowburden. • Reducedmaintenance. • Immunitytotransientsandsurges, withstands5KVimpulsevoltagetest.
Application
Thisrelayisusedforthecontinuoussupervisionof CT secondary wiring and connections ofbusbar protection schemes. Each protectedzoneofthebusbarinstallationisequippedwithanalarmrelay,shouldtheCTsecondarywiringdevelopafaultwhileloadcurrentisflowing,analarmisgivenafteratimedelayof3seconds.The delay is given to prevent an alarm in thecaseofgenuinebusbar faultwhen thebusbarprotectionisrequiredtooperateandisolatethefaultysection.Further,duetoitssensitivesettingrequirement, the relay may be unstable underheavy external fault conditions, the time delayallowsthefaulttobeclearedbytheappropriateprotectionthuspreventingunwantedalarms.
Therearetwotypes:SinglephaseVTX11andthreephaseVTX31.ThefollowingTablegivesthefunctionaldetailsofboththetypes.
PROTECTION
DescriptionThe relay consists of three stages, pick-upvoltagecontrol stage, timingstageandoutputstage.TheblockdiagramofVTX11isshowninFigure1.ThethreephaseversionVTX31issameas VTX 11 except that a three phase rectifierbridgeisusedtoconvertacinputquantitiestodcsignal.
UnderhealthyconditionsoftheprotectedcircuitthereisnoacinputtotherelayandtheauxiliarydcsupplycausestransistorT1toconduct,shortingout thecapacitor in the timingcircuit.Whenavoltageappearsacross theac input terminals,the rectified dc output of the bridge tends tobiasoffthetransistorT1,incasetheacinputishigherthanthevoltagesetting.WithT1off,thetimingcircuitcapacitorbeginstochargeupfromthestabiliseddcsupply.Afteratimedelayof3seconds, the capacitor voltage reaches a pre-determinedvalueandtriggersthetransistorT2which inturnswitchesontheoutputtransistorT3.Theinternalelectromechanicalauxiliaryunit,being in the load circuit of transistor T3 picksup and initiates alarm and other functions.Continuous adjustment of the relay voltagesetting is provided by a potentiometer in thebridge output circuit. Protective devices havebeenincludedinthecircuitrytopreventdamagedue to spikes in the input voltages or reverseconnectionofthedcauxiliarysupply.
Singlephaseusedwithearthfaultschemes
Threephaseusedwithphaseandearthfaultschemes
Will detect open circuit ofcurrenttransformers.
Will detect open circuit ofcurrenttransformers
WilldetectbrokenorcrossedCTpilots
VTXrelaywithdrawnfromcase
Technical dataVoltage setting
2to14Vcontinuouslyadjustableat50Hz.
Thermal rating • Singlephaserelay: 600Vacrmsat50Hzbetweenthe inputterminalscontinuouslyonanysetting. • Threephaserelay: 300Vacrmsat50Hzbetweenany phaseandneutraloftheinputterminals continuouslyonanysetting.Therelay willalsowithstand2kVacrms50Hz forthreesecondsonanysetting.
Auxiliary supply
Therelaycanbesuppliedsuitableforoperationat30V,110Vand220Vdc.Forvoltagesabove30V, an external dropping resistor is used.Satisfactory operation is maintained over arangeof75%-120%.
Accuracy
• Atratedauxiliarysupplyandrated frequency,therelayhasanaccuracyof ±5%ofthesettingvalueonanysetting.
• Operatingtemperaturerange-5ºCto +50ºC.
Operating time
Nominal3seconds.
Figure1:BlockdiagramforVTX11relay
2>3
BurdenContinuousburdenimposedondcauxiliarysupplyisasshowninthetablebelow:
AuxiliAry voltAge 30V
relAy unoperAted (W)
110V 220V
1.0 3.5 7.0
relAy operAted (W) 1.7 4.0 7.7
Approximateacburdenperphaseforbothtypesofrelaysonanysettingisasfollows:
Applied voltAge 10V
Burden (vA)
300V 1414V
0.002 4.2 86
ContactsTwopairsofnormallyopen,selfresetcontactsareprovidedontheoutputattractedarmatureunit.
Contact ratings
MAke And cArry continuously
AC
MAke And cArry for 0.5 second
BreAk
1250VAwithmaximaof5Aand660V
7500VAwithmaximaof30Aand660V
1250VAwithmaximaof5Aand660V
DC 1250Wwithmaximaof5Aand660V
7500Wwithmaximaof30Aand660V
100W(resisitive)50W(inductive)withmaximaof5Aand660V
Operation indicator
A hand reset mechanical operation indicatoris fitted as standard on the output attractedarmatureunit.
Insulation
The relay will withstand 2.5 kV rms 50 Hz for1secondbetweenall livepartsandearth,andbetweenallcircuitsnotintendedtobeconnectedtogether.Itwillalsowithstand1.25kVrms50Hzfor1sacrossopencontacts.
Impulse withstand level
The relay will withstand 5 kV impulse voltagetestinaccordancewithIECrecommendations.
High frequency disturbance
The relay meets the IEC test recommendationfor the high frequency disturbance test. Therelay accuracy is unaffected by repetitive 1MHz bursts having an initial peak of 1.0 KVsuper-imposedacrossinputcircuitsand2.5KVbetweenindependentcircuitsandearth,withatimedelayof3to6microseconds,withtherelayenergised.
Case
Singlephaseandthreephaserelaysaresuppliedin size 1 drawout (1D) cases suitable for flushmounting and are finished eggshell black andtropicalised. The drawout feature considerablysimplifiesmaintenanceandpermitstestingtobecarriedouteasilyandquickly.Acradlemountedisolatingswitchisprovidedwhichautomaticallyisolatesthetripcircuitwhenthecradleassemblyis withdrawn from the case for maintenance.This prevents any inadvertent tripping of thecircuit breaker. A filter breather is fitted whichequalises the pressure inside and outside thecasewithoutadmittingdust.
Information required with order
1.Typeofrelay
2.Auxiliarydcvoltage
Figure2:Typical connection diagram ofVTX 31 relay in 3 phase buszone protection scheme forphaseandearthfaults.
4>5
Dimensions and weights
relAy cAse size
MAxiMuM overAll diMensions
VTX31
ApproxiMAte gross Weight
kgheightMM
WidthMM
depth* MM
1Dvert. 233 170 203 4.5
* Add76mmformaximumlengthofterminalstuds,alternatively,29mmforterminalscrews. Theapproximategrossweightsgivenaboveisinclusiveofcartons,mountingappendages andterminaldetails. TherelayscomplyfullywiththerequirementsofIS3231andaresuitableforuseinnormal tropicalenvironments.
AREVA T&D
Pallavaram Works19/1, G.S.T. Road,Pallavaram, Chennai - 600 043Tel: 91-44-2264 8000
Fax: 91-44-2264 0040
AREVA T&D Worldwide Contact Centre:http://www.areva-td.com/contactcentre/Tel.: +44 (0) 1785 250 070
www.areva-td.com
Our policy is one of continuous development. Accordingly thedesignofourproductsmaychangeatanytime.Whilsteveryeffortismadetoproduceuptodateliterature.Thisbrochureshouldonlybe regardedasaguideand is intended for informationpurposesonly. Itscontentsdonotconstituteanoffer forsaleoradviseontheapplicationofanyproductreferredtoinit.Wecannotbeheldresponsibleforanyrelianceonanydecisionstakenonitscontentswithoutspecificadvice.
AR
EVA
,the
AR
EVA
logo
and
any
alte
rnat
ive
vers
ion
ther
eofa
ret
rad
emar
ksa
nds
ervi
cem
arks
ofA
RE
VA
MiC
OM
isa
reg
iste
red
tra
dem
ark
ofA
RE
VA.A
lltr
ade
nam
eso
rtr
adem
arks
men
tione
dh
erei
nw
heth
err
egis
tere
do
rno
t,a
ret
hep
rop
erty
oft
heir
owne
rs.