NFPA No.

15

WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION

1 9 6 9

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 2: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

O f f i c i a l N F P A Definitions

Adopted Jan. 23, 1964. Where variances to these definitions are found, efforts to eliminate such conflicts are in process.

S~ALL is i n t e n d e d to i n d i c a t e r e q u i r e m e n t s .

SHOULD is i n t e n d e d to i n d i c a t e r e c o n l m e n d a t i o n s or t h a t w h i c h is a d v i s e d b u t n o t r e q u i r e d .

, APPROVED m e a n s a c c e p t a b l e to the a u t h o r i t y h a v i n g ju r i sd i c t ion . T h e N a t i o n a l F i re P r o t e c t i o n Assoc ia t ion does n o t a p p r o v e , i n spec t or ce r t i fy a n y in s t a l l a t i ons , p rocedures , e q u i p m e n t or m a t e r i a l s no r does i t a p p r o v e or e v a l u a t e t e s t i ng l a b o r a - tor ies . I n d e t e r m i n i n g *~he a c c e p t a b i l i t y of i n s t a l l a t i ons or p rocedu re s , e q u i p m e n t or ma te r i a l s , t he a u t h o r i t y h a v i n g j u r i sd i c t i on m a y base a c c e p t a n c e on c o m p l i a n c e wi th N F P A or o t h e r a p p r o p r i a t e s t a n d a r d s . In t he a b s e n c e of such s t a n d a r d s , sa id a u t h o r i t y m a y r equ i r e ev idence of p r o p e r i n s t a l l a t i on , p r o c e d u r e or use . T h e a u t h o r i t y h a v i n g ju r i sd ic t ion m a y also re fe r to t he l i s t ings or l a b e l i n g p r a c t i c e s of n a t i o n a l l y recognized t e s t ing l abo ra to r i e s ,* i.e., l a b o r a t o r i e s qual i f ied a n d e q u i p p e d to c o n d u c t t he neces sa ry tests , in a pos i t i on to d e t e r m i n e c o m p l i a n c e wi th a p - p r o p r i a t e s t a n d a r d s for the c u r r e n t p r o d u c t i o n of l i s ted i t ems , a n d the s a t i s f a c t o r y p e r f o r m a n c e of such e q u i p m e n t or m a t e r i a l s in a c t u a l u sage .

*Among the laboratories nationally recognized b y the authorities having jurisdiction in the United States and Canada are the Underwriters' Laboratories, Inc., the Factory Mutual Engineering Division, the American Gas Association Laboratories, tile Underwriters' Labora- tories of Canada, the Canadian Standards Association Testing Laboratories, and the Canadian Gas Association Approvals Division.

LISTED: E q u i p m e n t or m a t e r i a l s i n c l u d e d in a l is t pub l i shed b y a n a t i o n a l l y r ecogn ized t e s t ing l a b o r a t o r y t h a t m a i n t a i n s pe r iod ic i n spec t i on of p r o d u c t i o n of l i s ted e q u i p m e n t or ma te r i a l s , a n d whose l i s t ing s t a t e s e i the r t h a t the e q u i p m e n t or m a t e r i a l m e e t s n a t i o n a l l y r ecogn ized s t a n d a r d s or h a s been t e s t ed a n d f o u n d s u i t a b l e for u se in a specif ied m a n n e r .

LABELED: E q u i p m e n t or m a t e r i a l s to w h i c h has been a t t a c h e d a label of a n a t i o n a l l y r ecogn ized t e s t ing l a b o r a t o r y t h a t m a i n t a i n s pe r iod ic i n spec t i on of p r o d u c t i o n of l abe led e q u i p m e n t or ma te r i a l s , a n d b y whose l a b e l i n g is i n d i c a t e d c o m p l i a n c e w i th n a t i o n a l l y r ecogn ized s t a n d a r d s or the c o n d u c t of t e s t s to d e t e r m i n e su i t ab l e u s a g e in a specif ied m a n n e r .

AUTHORITY HAVING JURISDICTION: T h e o r g a n i z a t i o n , office or i n d i v i d u a l re - spons ib le for " a p p r o v i n g " e q u i p m e n t , aIl i n s t a l l a t i on , or a p r o c e d u r e .

S t a t e m e n t o n N F P A Procedures This material has been developed in the interest of safety to life and property under the

published procedures of the National Fire Protection Association. These procedures are de- si~ned to assure the appointment of technically competent Committees having balanced representation from those vitally interested and active in the areas with which the Committees are concerned. These procedures provide tha t all Committee recommendations shall be pub- lished prior to action on them by the Association itself and that following this publication these recommendations shall be presented for adoption to the Annual Meeting of the Association where anyone in attendance, member or not, may present his views. While these procedures assure the highest degree of care, neither the National Fire Protection Association, its members, nor those participating in its activities accepts any liability resulting from compliance or non- compliance with the provisions given herein, for any restrictions imposed on materials or processes, or for the completeness of the text,

Copyright and Republ i shing Rights T h i s p u b l i c a t i o n is c o p y r i g h t e d © b y t h e N a t i o n a l F i re P r o t e c t i o n Asso-

c ia t ion . Pe rmi s s ion is g r a n t e d to r e p u b l i s h in full t he m a t e r i a l he re in in laws, o r d i n a n c e s , r egu la t ions , a d m i n i s t r a t i v e o r d e r s or s imi la r d o c u m e n t s i ssued b y publ ic a u t h o r i t i e s . All o the r s des i r ing pe rmi s s ion to r e p r o d u c e th i s m a t e r i a l in who le o r in p a r t sh~ll c o n s u l t t h e N a t i o n a l F i re P r o t e c t i o n Assoc ia t ion .

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 3: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

$ 6 9 0 3 2 8

Standard for / ~ , ~'. ( " : " ~'' ~J~}~_ 9 196~/Vater Spray Fixed S y ~ ; ~ o 2" /

for F,re Protect, on . . . . . -, / '

This 1969 edition of NFPA No. 15 was prepared by the Committee on Water Spray Fixed Systems and was adopted by the National Fire Protection Associa- tion at its 1969 Annual Meeting in New York, N.Y., May 12-16. It supersedes the edition of 1962.

Origin and Development of No. 15 Standards for Water Spray Systems for Fire Protection, formerly "Water

Spray Nozzles and Extinguishing Systems," first prepared by the Committee on Manufactur ing Hazards, were tentatively adopted in 1939, with final adoption in 1940. Subsequently, these standards were placed under the jurisdic- tion of the Committee on Special Extinguishing Systems and a new edition was adopted in 1947. In 1959 the committee organization was further changed to place pr imary responsibility in the hands of the Committee on Water Spray, under the general supervision of the General Committee on Special Extinguish- ing Methods. In 1966 the General Committee on Special Extinguishing Methods was discontinued and the Committee on Water Spray was constituted as an independent committee.

Committee on Water Spray Fixed Systems W. M. Horn, Chairman,

Kentucky Inspection Bureau, 940 Starks Bldg., Louisville, Ky. 40202

Joe D. Smith , Secretary, Kentucky Inspection Bureau, 940 Starks Bldg., Louisville, Ky. 40202

(Alternate to W. M. Horn.)

S. E. Auck, Underwriters' Laboratories, Inc. Wayne E. Ault, National Automatic Sprin-

kler & Fire Control Assn. George G. Blair, Edison Electric Institute. J. C. Chapman, Factory Mutual Engineer-

ing Assn. Norman E. Gatsch, Jr., Ohio Inspection

Bureau. Halk R. Kazarian, National Automatic

Sprinkler and Fire Control Assn. Benjamin E. Lingo, Department of the

Navy.

N. R, Lockwood, American Petroleum In- stitute.

H. S. Robinson, Oil Insurance Assn. R. M. L. Russell, Factory Insurance Assn. Win. P. Underwood, Pacific Fire Rating

Bureau. J. J. Walker, Union Carbide Corp. Jack A. Wood, National Automatic Sprin-

kler & Fire Control Assn. Clairmont Zook, Jr., Improved Risk Mu-

tuals.

Alternates.

R. E. Sherwood, Oil Insurance Assn. W . J . Swingler, Factory Insurance Assn. (Alternate to H. S. Robinson.) (Alternate to R. M. L. Russell.)

SCOPE: To develop minimum standards for the design, construction, installation, mainte- nance, and test of fixed water spray systems for fire protection purposes.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 4: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-2 W A T E R S P R A Y F I X E D S Y S T E M S

T A B L E O F C O N T E N T S

Page

Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 4

Chapter 1. General Provisions 1010 . S c o p e . . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 5

1020 . D e f i n i t i o n s . . . . . . . . . . . . . . . . . . . . . . 1 5 - 5

1030 . A p p l i c a b i l i t y . . . . . . . . . . . . . . . . . . . . . 1 5 - 6

1040 . L i m i t a t i o n s . . . . . . . . . . . . . . . . . . . . . 1 5 - 7

1050 . P l a n s a n d S p e c i f i c a t i o n s . . . . . . . . . . . . . . . 1 5 - 1 0

1060 . A p p r o v a l o f W a t e r S p r a y S y s t e m s . . . . . . . . . . . . 1 5 - 1 0

Chapter 2. System Components 2 0 1 0 . D e v i c e s a n d M a t e r i a l s . . . . . . . . . . . . . . . . . 1 5 - 1 1

2 0 2 0 . C o m p o n e n t P a r t s . . . . . . . . . . . . . . . . . . . 1 5 - 1 1

2 0 3 0 . C o r r o s i o n P r o t e c t i o n . . . . . . . . . . . . . . . . . 1 5 - 1 1

2 0 4 0 . S p r a y Nozz le s . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 1

2 0 5 0 . P i p i n g . . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 1

2 0 6 0 . F i t t i n g s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 2

2 0 7 0 . H a n g e r s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 3

2 0 8 0 . V a l v e s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 3

2 0 9 0 . C o n t r o l E q u i p m e n t . . . . . . . . . . . . . . . . . . 1 5 - 1 3

2 1 0 0 . P r e s s u r e G a g e s . . . . . . . . . . . . . . . . . . . . 1 5 - 1 3

2 1 1 0 . S t r a i n e r s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 3

2 1 2 0 , A l a r m s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 4

2 1 3 0 . F i r e D e p a r t m e n t C o n n e c t i o n s . . . . . . . . . . . . . . 1 5 - 1 4

2 1 4 0 . F l u s h i n g C o n n e c t i o n s . . . . . . . . . . . . . . . . . 1 5 - 1 4

Chapter 3. Water Supplies 3 0 0 0 . G e n e r a l . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 5

3 0 1 0 . V o l u m e a n d Pressure . . . . . . . . . . . . . . . . . . 1 5 - 1 5

3 0 2 0 . S o u r c e s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 1 5

Chapter 4. System Design and Installation 4 0 0 0 . W o r k m a n s h i p . . . . . . . . . . . . . . . . . . . . 1 5 - 1 7

4 0 1 0 . P l a n s , Spec i f i c a t i ons , a n d H y d r a u l i c C a l c u l a t i o n s . . . . . 1 5 - 1 7

4 0 2 0 . D e s i g n G u i d e s . . . . . . . . . . . . . . . . . . . . 1 5 - 1 7

4 0 3 0 . D e s i g n P u r p o s e . . . . . . . . . . . . . . . . . . . . 1 5 - 1 7

4 0 4 0 . D e n s i t y a n d A p p l i c a t i o n . . . . . . . . . . . . . . . . 1 5 - 1 8

4 0 5 0 . Size o f S y s t e m . . . . . . . . . . . . . . . . . . . . 1 5 - 2 5

4 0 6 0 . S e p a r a t i o n o f F i r e A r e a s . . . . . . . . . . . . . . . . 1 5 - 2 5 4 0 7 0 . V a l v e s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 2 6

4 0 8 0 . S p r a y Nozz l e s . . . . . . . . . . . . . . . . . . . . 1 5 - 2 6 4 0 9 0 . P i p i n g . . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 2 7

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 5: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

C O N T E N T S 1 5 - - 3

Page

4 1 0 0 . H a n g e r s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 2 8

4110 . S t r a i n e r s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 2 8

4120 . G a g e s . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 2 9

Chapter 5. Acceptance Tests

5000 . F l u s h i n g o f P i p i n g . . . . . . . . . . . . . . . . . . 1 5 - 3 0

5010 . H y d r o s t a t i c P r e s s u r e Tes t s . . . . . . . . . . . . . . . 1 5 - 3 0

5020 . W a t e r D i s c h a r g e Tes t s . . . . . . . . . . . . . . . . . 1 5 - 3 0

5030 . O p e r a t i n g T e s t s . . . . . . . . . . . . . . . . . . . 1 5 - 3 1

5040 . A c c e p t a n c e T e s t S u g g e s t i o n s . . . . . . . . . . . . . . 1 5 - 3 1

Chapter 6. Periodic Testing and Maintenance

6000 . G e n e r a l . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 3 2

6010 . M a i n t e n a n c e . . . . . . . . . . . . . . . . . . . . . 1 5 - 3 2

Chapter

7000 .

7010 .

7020 .

7030 .

7 0 4 0 .

7050 .

7060 .

7070 .

7080 .

7 0 9 0 .

7. Plans, Specifications and Hydraulic Calculations

P l a n s a n d S p e c i f i c a t i o n s . . . . . . . . . . . . . . . . 1 5 - 3 4

H y d r a u l i c C a l c u l a t i o n s . . . . . . . . . . . . . . . . 1 5 - 3 4

S u m m a r y S h e e t . . . . . . . . . . . . . . . . . . . 1 5 - 3 6

D e t a i l e d W o r k Shee t s . . . . . . . . . . . . . . . . . 1 5 - 3 6

G r a p h Shee t s . . . . . . . . . . . . . . . . . . . . . 1 5 - 3 7

A b b r e v i a t i o n s a n d S y m b o l s . : . . . . . . . . . . . . . 1 5 - 3 7

F o r m u l a e . . . . . . . . . . . . . . . . . . . . . . 1 5 - 3 9

V e l o c i t y P r e s s u r e . . . . . . . . . . . . . . . . . . . 1 5 - 3 9

E q u i v a l e n t P i p e L e n g t h s o f V a l v e s a n d F i t t i n g s . . . . . . 1 5 - 4 1

C a l c u l a t i n g P r o c e d u r e . . . . . . . . . . . . . . . . . 1 5 - 4 1

Chapter

8 0 0 0 .

8 0 1 0 .

8 0 2 0 .

8030 .

8 0 4 0 .

8 0 5 0 .

8. Automatic Detection Equipment

G e n e r a l . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 4 4

S e l e c t i o n . . . . . . . . . . . . . . . . . . . . . . . 1 5 - 4 4

P r o t e c t i o n . . . . . . . . . . . . . . . . . . . . . . 1 5 - 4 4

L o c a t i o n a n d S p a c i n g o f D e t e c t o r s . . . . . . . . . . . 1 5 - 4 4 A r r a n g e m e n t a n d S u p e r v i s i o n o f S y s t e m s . . . . . . . . . 1 5 - 4 6

R e s p o n s e T i m e . . . . . . . . . . . . . . . . . . . . 1 5 - 4 6

Appendix

A - 1 0 3 3 D e s i g n P u r p o s e s . . . . . . . . . . . . . . . . . . . 1 5 - 4 8 A - 1 0 4 4 C l e a r a n c e to L i v e E l e c t r i c a l A p p a r a t u s . . . . . . . . . 1 5 - 4 8

A - 4 0 4 3 ( b ) E x p o s u r e P r o t e c t i o n - - Vessels . . . . . . . . . . . 1 5 - 5 0

A - 4 0 6 0 D r a i n a g e . . . . . . . . . . . . . . . . . . . . . . 1 5 - 5 0

A - 7 0 9 0 S a m p l e C a l c u l a t i o n s . . . . . . . . . . . . . . . . . 1 5 - 5 6

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 6: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15--4 WATER SPRAY FIXED SYSTEMS

Standard for

Water Spray Fixed Systems

for Fire Protection N F P A N o . 1 5 - - 1 9 6 9

FOREWORD

The term water spray refers to the use of water in a form having a predetermined pattern, particle size, velocity, and density discharged from specially designed nozzles or devices. Water spray fixed sys- tems are usually applied to special fire protection problems, since the protection can be specifically designed to provide for effective fire control, extinguishment, prevention, or exposure protection. Water spray systems may be independent of, or supplementary to, other forms of protection.

This Standard deals with water spray protection from fixed nozzle systems only. It does not cover water spray protection from portable nozzles, sprinkler systems, monitor nozzles, or other means of application covered by other standards of the National Fire Protection Association.

Water spray fixed systems are most commonly used to protect processing structures and equipment, flammable liquid and gas vessels, piping, and equipment such as transformers, oil switches, and motors. Such protection has also been shown to be effective on many combustible solids.

The design of specific systems may vary considerably, depending on the nature of the hazard and the basic purposes of protection. Because of these variations and the wide choice in the character- istics of spray nozzles, these systems must be competently designed, installed, and maintained. Although water spray has a wide ap- plication, it is essential that its limitations be understood by the designer.

1V[uch informative material was included in earlier editions of this publication, in view of the limited knowledge about this form of protection. Over the years, however, additional test work has been done, and considerable additional field experience has become available. The present edition has been prepared as a standard rather than as a compilation of informative material.

There are several methods of hydraulic calculation which will produce satisfactory results. There is a need, however, for a uni- form method of hydraulic calculations for the sake of simplicity and consistency. For this reason a recommended method has been included in this Standard.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 7: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

GENERAL PROVISIONS 15-5

C H A P T E R 1. G E N E R A L P R O V I S I O N S

1010. S c o p e . 1011. This S t anda rd is a m i n i m u m s tandard for the design,

instal lat ion, main tenance , and test of water spray fixed systems, [ for fire protec t ion service. I

1020. D e f i n i t i o n s . AUTOMATIC DETECTION EQUIPMENT - - Equ ipmen t which will

au tomat i ca l ly detect heat, f lame, smoke, combust ib le vapor , or o ther condi t ion l ikely to p roduce fire or explosion, and cause au to- mat ic ac tua t ion of a l a rm and protec t ion equipment .

CONTROL OF BURNING - - Appl i ca t ion of water spray to equip- ment or areas where a fire may occur to control the ra te of bu rn ing and thereby l imit the hea t release from a fire unti l the fuel can be e l imina ted or ext inguishment effected.

DENSITY - - The unit ra te of water appl ica t ion to an a rea or surface expressed in gallons per minu te per square foot.

EXPOSURE PROTECTION - - Appl ica t ion of water spray to s tructures or equ ipmen t to l imit absorp t ion of hea t to a level which will min imize d a m a g e and prevent failure, whe ther source of hea t is external or internal .

IMPINGEMENT - - The str iking of a pro tec ted surface by wate r drople ts issuing direct ly from a wate r spray nozzle.

INSULATED EQUIPMENT, STRUCTURES, OR V E S S E L S - Equipment , structures, or vessels p rovided with insulat ion, which, for the ex- pected du ra t i on of exposure, will pro tec t steel from exceeding a t empera tu re of 850 ° F. for s t ructura l members , or 650 ° F. for vessels; and where the insulat ion system is:

(a) Noncombus t ib le and fire r e t a rdan t , (b) Mi ldew and wea the r resistant, (c) Resis tant to the force of hose streams, and (d) Secured by fire and corrosion resistant fastenings.

NOTE 1: Noncombustible materials affording two-hour ratings under the Standard Method of Fire Tests of Building Construction and Materials, NFPA No. 251, will usually satisfy these requirements when properly fastened and weather protected. NOTE 2: For equipment, structures and vessels of nonferrous metals, somewhat lower temperature limits may be required.

NONABSORBINO GROUND - - Ear th or fill which is not read i ly pe rmeab le or absorbent to large quant i t ies of f l ammable or com- bust ible l iquid a n d / o r water . Most soils are not considered suf- f iciently pe rmeab le or absorbent to be considered absorbing ground. Par ings , such as concrete or asphal t , are considered nonabsorb ing .

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 8: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-6 WATER SPRAY FIXED SYSTEMS

RuN-DowN - - The downward travel of water along a surface, caused by the momentum of the water or by gravity.

SLIPPAGE - - The horizontal component of the travel of water along a surface beyond the point of impact, caused by the mo- mentum of the water.

WATER SPRAY NOZZLE - - A water discharge device which, when supplied with water under pressure, will distribute the water in a special, directional pattern peculiar to the particular device.

WATER SPRAY SYSTEM - - A water spray system is a special fixed pipe system connected to a reliable source of fire protection water supply, and equipped with water spray nozzles for specific water discharge and distribution over the surface or area to be protected. The piping system is connected to the water supply through an automatically or manually actuated valve which initiates the flow of water. An automatic valve is actuated by operation of automatic detection equipment installed in the same areas as the water spray nozzles. (In special cases the automatic detection equipment may also be located in another area.)

WET WATER - - Wet water is any water to which a compatible wetting agent has been added in quantities specified by the manu- facturer.

NOTE: For definitions of combustible and flammable liquids, see N F P A No. 321, Standard for Basic Classifications of Flammable and Combustible Liquids.

1030. Applicabili ty. 1031. Water spray is applicable for protection of specific haz-

ards and equipment and may be installed independently of or supplementary to other forms of fire protection systems or equip- ment.

1032. Hazards - - Water spray protection is, in general, ac- ceptable for the protection of hazards involving:

(a) Gaseous and liquid flammable materials.

(b) Electrical hazards such as transformers, oil switches, and motors.

(e) Ordinary combustibles such as paper, wood, and textiles.

(d) Certain hazardous solids.

1033. PURPOSES - - In general, water spray may be used ef- fectively for any one or a combination of the following purposes: (See Appendix A 1033)

(a) Extinguishment of fire.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 9: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

GENERAL PROVISIONS 15--7

(b) Control of burning.

(c) Exposure protection.

(d) Preven:ion of fire.

1040. Limitations.

1041. There are limitations to the use of water spray whichshall be recognized. Such limitations involve the nature of the equip- ment to be protected, the physical and chemical properties of the materials involved and the environment of the hazard.

NOTE: Other standards also consider lirrfitations to the application of water (slop-over, frothing, electrical clearances, etc.). See Hazardous Chem- icals Data (NFPA No. 49) and Properties of Flammable Liquids (NFPA No. 325M).

1042. Materials Involved .

(a) A careful study should be made of the physical and chemical properties of the materials for which water spray protection is being considered, in order to determine the advisability of its use. The flash point, specific gravity, viscosity, miscibility and solubility of the material, temperature of the water spray and the normal temperature of the hazard to be protected are among the factors which must be given consideration.

(b) The slop-over or frothing hazard should be considered where water spray may encounter confined materials at a high tempera- ture or having a wide distillation range.

(c) Water soluble materials, such as alcohol, require special consideration. Fires involving spills of such materials may usually be controlled, until extinguished by dilution, and in some cases the surface fire may be extinguished by an adequate application rate and coverage. Each water soluble material should be tested under the conditions of use to determine the applicability of a water spray system.

(d) Water spray is generally not suitable for direct application to materials which react with water, such as metallic sodium or calcium carbide, producing violent reactions or increased hazard- ous products as a result of heated vapor emission. Liquefied gases at cryogenic temperatures, such as liquefied natural gas, also boil violently when heated by water. In special cases, where adequate safeguards have been provided, water spray systems for the pro- tection of structures, equipment, or personnel in the presence of such materials may be acceptable to the authority having juris- diction.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 10: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

| 5 - - 8 WATER SPRAY FIXED SYSTEMS

200'

u~ i,I I U Z I w 0 Z nr

ill -I U

180,

160,

140.

120.

100

80, j 60. /

4 0 /

20, j

0 0 300 600

/ /

/

/

900 1200 1500 1800 2100 2 4 0 0

BASIC INSULATION LEVEL-KILOVOLTS

Fig. ~1044(b). Clearance from Water Spray Equipment to Live Uninsulated Electrical Components.

1043. Equipment Involved.

(a) Consideration should be given to the possibility of damage, distortion, or failure of equipment operating at high surface tem- peratures.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 11: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

G E N E R A L P R O V I S I O N S 15-9

1044. Clearance to L ive Electrical Apparatus . (See Appendix A-1044.)

( a ) G E N E R A L - - The clearances given are for altitudes of 3,300 feet or less. At altitudes in excess of 3,300 feet, the clearance shall be increased at the rate of one percent for each 330-foot increase in altitude above 3,300 feet.

(b) CLEARANCE (1) Clearance between any portion of water spray equipment

and unenclosed or uninsulated live electrical components, at other than ground potential, shall not be less than that given in Table 1044(b) or Figure 1044(b).

(2) The clearances are based upon minimum general prac- tices related to design BIL (Basic Insulation Level) values. To coordinate the required clearance with the electrical design, the design BIL of the equipment being water spray protected should be used as a basis. Where the design BIL is not available, the voltage may be used as a basis. However, in either event, the clearance between uninsulated energized parts of the electrical system equip- ment and any portion of the water spray system shall not be less

TABLE 1044(b)

Clearance from Water Spray Equipment to Live Uninsulated Electrical Components

Nominal No minal Design Mini rnu m Line Voltage BIL Clearance

Voltage (KV) To Ground (KV) (KV) (Inches)

To 15 To 9 110 6 23 13 150 8

34.5 20 200 12 46 27 250 15 69 40 350 23

115 66 550 37 138 80 650 44 161 93 750 52

/ 900 63 196-230 114-132 ~, 1050 76

[1175 87 1300 98

287-380 166-220 1 1425 109 (1550 120 1"1675 131

500 290 ~1800 142 f1925 153

500-700 290-400 ~2100 168 (2300 184

NOTE: When nominal voltage to ground is used for the design criteria, the highest minimum clearance listed for this group should be used.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 12: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-10 WATER SPRAY FIXED SYSTEMS

than the minimum clearances provided elsewhere for electrical system insulation on any individual component (the minimum unshielded straight line distance from the exposed electrical parts to nearby grounded objects).

NOTE: BIL values are expressed as K V (kilovolts), the number being the crest value of the full wave impulse tes t .

1050. Plans and Specifications. 1051. Water spray system design should be entrusted only to

responsible persons fully experienced in this field.

1052. Prior to determining the purpose of the water spray system under consideration, the authority having jurisdiction shall be consulted. (See Chapter 4.) All plans and specifications perti- nent to the installation and all devices and material shall be found acceptable by the authority having jurisdiction prior to installa- tion. (See Section 7001.)

1060. Approval of Water Spray Systems. 1061. Before asking final approval of the water spray system by

the authority having jurisdiction, the applicable parts of the Sprinkler Contractor's Certificate Covering Materials and Tests (see NFPA 13) should be completed and submitted, certifying that the work has been completed and tested in accordance with ap- proved plans and specifications.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 13: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM COMPONENTS 15--11

CHAPTER 2. SYSTEM COMPONENTS

2010. Devices and Materials. 2011. The authority having jurisdiction shall be consulted as to

the acceptability of devices and materials.

2020. Component Parts. -~ 2021. All component parts shall be coordinated to provide

complete systems and should he operable by automatic means with supplementary auxiliary manual tripping means. Under certain conditions, (such as certain fire control, exposure protection, or fire prevention applications) manual operation only may be per- mitted, subject to approval by the authority having jurisdiction.

2022. Only listed new materials and devices shall be employed in the installation of systems except, when special conditions war- rant, listed devices such as special system water control valves and their accessories, circuit closers, water motor alarm devices, non- automatic pattern spray nozzles, etc., may be reused, but if reused they shall be reconditioned by the original manufacturer. On re- quest of the authority having jurisdiction, the original manufac- turer shall furnish a certificate, stating that such specified devices have been reconditioned and tested and are considered satisfactory for reuse.

2030. Corrosion Protection. 2031. System components installed out of doors, or in the

presence of a corrosive atmosphere, shall be protected from cor- rosion by the use of suitable materials of construction, or by pro- tective coatings. The threaded ends of galvanized pipe, after installation, shall be suitably protected against corrosion.

2040. Spray Nozzles. 2041. Spray nozzles shall be of approved makes and types.

2042. Care shall be taken in the selection of strainers, particu- larly where nozzle waterways are less than 1/~-inch in least di- mension. (See 2110 and 4110.)

2050. Piping. 2051. Pipe used in water spray systems shall be wrought steel

or wrought iron. The chemical and physical properties of this pipe should be at least equal to those manufactured in accordance with the Specifications of the American Society for Testing and Ma- terials for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 14: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-12 W A T E R S P R A Y F I X E D S Y S T E M S

and Seamless Steel Pipe for Ordinary Uses, ASTM Designation A-120-65 (USAS B36.20 - - 1966) or for Welded Wrought Iron Pipe, ASTM Designation A-72-64T (USAS B36.20 - - 1966). Dimen- sions for all pipe should be in accordance with the American Standard for Wrought Steel and Wrought Iron Pipe, USAS B36.10 - - 1959. Pipe should be designed to withstand a working pressure of not less than 175 psi. It is intended that this Standard permit the use of "standard wall" pipe as described in USAS B-36.10 - - 1959 for pressures up to 300 psi. Schedule 40 pipe is considered "standard wall" pipe. Schedule 30 pipe is, however, acceptable in sizes 8 inches and larger.

I 2052. Galvanized pipe shall be used except that; where cor- rosion of galvanized pipe may be caused by corrosive atmospheres or the water, or by additives to the water, other suitable coatings shall be provided.

2053. The galvanizing of galvanized pipe shall be in accordance with Specifications A120-65 of the American Society for Testing and Materials (USAS B36.20 - - 1966).

2054. Other pipe or tubing which has been investigated and listed for this service by a nationally recognized testing and in-

[ spection agency may be used where acceptable to the authority having jurisdiction. The use of such tubing should involve espe- cially careful consideration of the following factors:

1. Pressure rating.

2. Beam strength (hangers and spacing).

3. Corrosion (chemical and electrolytic).

4. Methods of joining (strength, permanence, fire endurance).

5. Availability of fittings (for water spray nozzle outlets and proper routing).

6. Resistance to limited exposure time without water and resistance to rapid temperature change and steam pressure generated upon the admittance of water.

2060. Fittings. 2061. All fittings shall be of a type specifically approved for

fire protection systems and of a design suitable for the working pressures involved, but not less than 175 psi cold water pressures. Ferrous fittings shall be of steel, malleable iron or ductile iron in dry sections of the piping exposed to possible fire or in self-sup- porting systems. Galvanized fittings shall be used where galvanized pipe is required.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 15: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

S Y S T E M C O M P O N E N T S 15-13

2062. Rubber gasketed fittings subject to direct fire exposure are generally not suitable. Where necessary for piping flexibility, or for locations subject to earthquake, explosion, or similar haz- ards, such installations may be acceptable to the authority have jurisdictiqn. In such cases special hanging or bracing may be necessary.

2070. Hangers. 2071. Hangers shall be of a type approved for use with the

piping involved. (See 4100.)

2080. Valves.

2081. All valves shall be of a type approved for the purpose.

2090. Control Equipment. 2091. Automatic valves shall be special system water control

valves approved for the use intended.

2092. Control of automatic valves shall be by means of approved accessories for special systems.

2093. Manual devices may actuate the automatic control valves by mechanical, hydraulic pneumatic, electrical, or other approved means. The manual device shall be amply strong to prevent breakage. Manual controls shall not require a pull of more than 40 pounds (force) nor a movement of more than 14 inches to se- cure operation.

2094. Automatic detection equipment shall be of a type listed by a nationally recognized testing laboratory for use with special system water control valves.

2100. Pressure Gages. 2101. Required pressure gages shall be of approved type and

shall have a maximum limit not less than twice the normal work- ing pressure when installed. They shall be so installed as to permit easy removal, and shall be located where they will not be subject to freezing.

2110. Strainers. 2111. Pipe line strainers shall be specifically approved for use in

water supply connections. Strainers shall be capable of removing from the water all solids of sufficient size to obstruct the spray nozzles. In addition, the strainers shall be capable of continued operation without serious increase in head loss, for a period esti- mated to be ample when considering the type of protection pro- vided, the condition of the water, and similar local circumstances.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 16: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-14 W A T E R SPRAY F I X E D SYSTEMS

2112. Pipe line strainer designs shall incorporate a flushout connection.

2113. Individual strainers for spray nozzles, where required, shall be of approved type capable of removing from the water all solids of sufficient size to obstruct the spray nozzle they serve.

2120. Alarms.

2121. The authority having jurisdiction shall be consulted re- garding the alarm service to be provided and regarding the need for electrical fittings designed for use in hazardous locations in electric-alarm installations (see National Electrical Code, NFPA No. 70, Article 500 and other Articles in Chapter 5 thereof).

2122. A local alarm, actuated independently of water flow, to indicate operation of the heat-responsive system should be pro- vided on each system.

2123. Outdoor water-motor or electric-alarm gongs, respon- sive to system water flow, may be required by the inspection au- thority having jurisdiction.

2124. Central station or proprietary station water-flow alarm service is desirable, but where not available, it may be advisable to connect electrical alarm units to the public fire department alarm headquarters, or other suitable place where aid may be readily secured.

2125. A suitable alarm shall be provided for each system to indicate failure of automatic detection equipment (including elec- tric supervisory circuits) or other such devices or equipment upon which system actuation is dependent. If system operation will result from such failure, the trouble alarm, in some cases, may be waived by the authority having jurisdiction.

2130 . Fire Department Connections. 2131. Fire department connections may be required by the au-

thority having jurisdiction (see 3025).

2140. Flushing Connections.

2141. A suitable flushing connection shall be incorporated in the design of the system to facilitate routine flushing as required by 6019. This connection may be incorporated in the design of the strainer or provided below the automatic special system con- trol valve.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 17: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

W A T E R S U P P L I E S 15-15

CHAPTER 3. WATER SUPPLIES

3000. Genera l . 3001. The authority having jurisdiction shall be consulted con-

cerning water supplies. I t is of vital importance that water supplies be selected which provide water as free as possible from foreign ma- te1 ials.

3010. Volume and Pressure. 3011. The water supply flow rate and pressure shall be capable

of maintaining water discharge at the design rate for the required period of discharge for all systems designed to operate simul- taneously.

3012. The authority having jurisdiction shall be consulted as to the water flow rate required for hydrant systems for hose stream protection. Unless water supplies and distribution systems for water spray systems are separate from hydrant systems, thus in- suring adequate hose protection in the event of the disruption of water spray equipment by explosion or otherwise, supplies should contemplate additional water for hose streams. Where the distri- bution system is not separate, sectional control shutoff valves shall be located with particular care so that they will be accessible during an emergency.

3013. When only a limited water source is available, it is con- sidered good practice to provide sufficient water for a second oper- ation of the system so that the protection can be re-established without waiting for the supply to be replenished. In estimating the period of time sufficient for duration of operation of water spray systems for a particular hazard, an ample factor of safety should be included. (See Chapter 4.)

3020. Sources. 3021. The water supply for water spray systems shall be from

reliable fire protection water supplies, such as:

(a) Connections to waterworks systems,

(b) Gravity tanks (in special cases pressure tanks, see 3023), and /o r

(c) Fire pumps and suction supply.

3022. Cycle Systems. Where the quantity of water supply is extremely limited, a cycle water system may be acceptable in some instances. For such an arrangement water could be collected by means of a fire drainage trench and interceptor system. Suction

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 18: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-16 WATER SPRAY FIXED SYSTEMS

would then be taken from the last pass in the interceptor (or sep- arator). However, caution should be observed when designing such a system and full consideration should be given to such items as type of flammables involved, foreign materials which may be present in the drainage system, and valving arrangements.

3023. Pressure Tanks. Pressure tanks generally are of in- adequate volume to serve as a water supply for water spray systems. In special cases, however, such as remotely located transformers, where pressure tanks can furnish an adequate volume and pressure, they may be acceptable.

3024. Auxiliary Supplies. Readily available sources of water supply should be made accessible as auxiliary supplies for water spray systems. Cross connections from service water systems in industrial plants should, where permissible, be made to fire main systems. Where connections are made from public waterworks systems it is necessary to guard against possible contamination of the public supply. The requirements of the public health au- thority should be determined and followed. The effect of reducing water pressures when large quantities of water are drawn for fire fighting must be carefully studied to prevent potentially dangerous operating situations. Manual operation of auxiliary sources may be acceptable.

3025. Fire D e p a r t m e n t Connections. To provide an auxiliary supply, one or more fire department connections shall be provided when required by the authority having jurisdiction. Careful con- sideration should be given to such factors as the purpose of the system, reliability, and capacity and pressure of the water system. The possibility of serious exposure fires and similar local conditions may also be important factors. A pipe line strainer in the fire depar tment connection may be required.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 19: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

S Y S T E M D E S I G N A N D I N S T A L L A T I O N 15-17

C H A P T E R 4. S Y S T E M D E S I G N A N D I N S T A L L A T I O N

4000. W o r k m a n s h i p . 4001. Water spray system design, layout, and installation should

be entrusted to none but fully experienced and responsible parties. Water spray system installation is a specialized field of sprinkler system installation which is a t rade in itself.

4010. Plans, Specifications, and Hydraulic Calculations. 4011. Before a water spray system is installed or existing equip-

ment remodeled, complete working plans, specifications and hy- draulic calculations shall be submitted to the authori ty having jurisdiction. For details concerning plans, specifications and hy- draulic calculations, see Chapter 7.

4020. Design Guides. 4021. Wate r spray system designs shall conform to the ap-

plicable requirements of the following Standards of the Nat ional Fire Protection Association, except where otherwise specified herein :

NFPA Standard Number

13 14 18 2O 22 24 26

70 71 72A 72B 72C 72D

Title

Sprinkler Systems Standpipe and Hose Systems Wetting Agents Centrifugal Fire Pumps Water Tanks for Private Fire Protection Outside Protection Supervision and Care of Valves Controlling Water

Supplies for Fire Protection National Electrical Code Central Station Protective Signaling Systems Local Protective Signaling Systems Auxiliary Protective Signaling Systems Remote Station Protective Signaling Systems Proprietary Protective Signaling Systems

NOTE: Components of the electrical portions of these protective systems, where installed in locations subject to hazardous vapors or dusts, shall be of types approved for use therein.

4030. Design Purpose. 4031. The authori ty having jurisdiction shall be consulted as to

the purpose of the water spray system under consideration. (See Section 1033.)

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 20: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-18 W A T E R SPRAY F I X E D SYSTEMS

4040. Density and Application. 4041. Extinguishment. (a) Extinguishment of fires by water spray may be accomplished

by surface cooling, by smothering from steam produced, by emulsi- fication, by dilution, or by various combinations thereof. Systems shall be designed so that, within a reasonable period of time, ex- tinguishment shall be accomplished and all surfaces shall be cooled sufficiently to prevent "flashback" occurring after the system is shut off.

(b) Where systems are designed for extinguishment of fires in- volving solids, consideration should be given to such factors as penetrating ability of the water, and the configuration and state of the material.

(c) Where extinguishment of f lammable or combustible liquids is contemplated the rate of water application necessary will de- pend on such characteristics of the fuel as vapor pressure, flash point, viscosity, water solubility, and specific gravity. Care must be observed with very viscous heated materials, such as asphalt, be- cause of the potential slop-over or froth-over hazard. When water spray extinguishment systems are designed for material of this type, the use of nonfoaming agents, special containment capacity, drains, or extensions of the spray system beyond the immediate area of the initial containment, should be contemplated. Care must also be observed with materials having a hazardous chemical reaction with water.

(d) In all cases, the positioning of nozzles with respect to burning surfaces to be extinguished shall be guided by the particular nozzle design, the water pressure available, and the character of water spray produced. The effect of wind and fire draft on very small drop sizes or on larger drop sizes with little initial nozzle velocity will limit the distance between nozzle and surface.

(e) The design density for extinguishment shall be based upon test data or knowledge concerning conditions similar to those that will: apply in the actual installation. A general range of water spray application rates that will apply to most ordinary com- bustible solids or flammable liquids is from 0.2 gpm per sq. ft. to 0.5 gpm per sq. ft. of protected surface.

NOTE: T h e r e a re some d a t a a v a i l a b l e on w a t e r a p p l i c a t i o n ra tes n e e d e d for e x t i n g u i s h m e n t of c e r t a i n c o m b u s t i b l e s or f l a m m a b l e s ; h o w e v e r , m u c h a d d i t i o n a l tes t w o r k is n e e d e d before m i n i m u m r a t e s c a n be e s t ab l i shed .

(f) Each of the following methods or a combination of them should be considered when designing a water spray system for extinguishment purposes:

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 21: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM DESIGN AND INSTALLATION 15-19

1. SURFACE COOLING - - W h e r e extinguishment by su r face cooling is contemplated, the design shall provide complete water spray coverage over the entire surface. Surface cooling is not effective on gaseous products or flammable liquids having a flash point below the temperature of the applied water and is not gen- erally satisfactory for flammable liquids having flash points below ] 140 ° F. I

2. SMOTHERING BY STEAM PRODUCED - - W h e r e this ef fect is contemplated the intensity of the expected fire shall be sufficient to generate adequate steam from the applied water spray and conditions shall be otherwise favorable for the smothering effect. The water spray shall be applied to essentially all the areas of ex- pected fire. This effect shall not be contemplated where the ma- terial protected may generate oxygen when heated.

3. EMULSIFICATION - - This effect shall be contemplated only for liquids not miscible with water. The water spray shall be ap- plied over the entire area of flammable liquids. For those having low viscosities the coverage shall be uniform and the minimum rate required shall be applied and the nozzle pressure shall not be less than the minimum on which approval is based. For more viscous materials the coverage should be complete but need not be so uniform and the unit rate of application may be lower. Wet water may be considered where the effect of emulsification is contem- ] plated. I

4. DILUTION - - The material shall be miscible with water where this effect is contemplated. The application rate shall be adequate to effect extinguishment within the required period of time based upon the expected volume of material and the per- centage of dilution necessary to make it nonflammable, but not less than that required for control and cooling.

5. OTHER FACTORS - - The system design may contemplate other extinguishing factors, in some cases, such as a continuous film of water over the surface where the material is not miscible with water and has a density much greater than 1.0 (such as asphalt, tar, carbon disulfide, and some nitrocellulose solutions). Water spray may also be used on some materials to produce extinguish- ment as a result of rapid cooling below the temperature at which the material will decompose chemically at a self-sustaining rate.

NOTE: For the effect of droplet size, see N.B.F.U. Research Report No. 10, "The Mechanism of Extinguishment of Fire by Finely Divided Water", published by the American Insurance Association.

4042. Control of Burning. (a) A system for the control of burning shall function at full

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 22: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

1 5 - 2 0 WATER SPRAY FIXED SYSTEMS

effectiveness until there has been time for the flammable materials to be consumed, for steps to be taken to shut off the flow of leaking material, for the assembly of repair forces, etc. System operation for hours may be required.

(b) Nozzles shall be installed to impinge on the areas of the source of fire, and where spills may travel or accumulate. The water ap- plication rate on the probable surface of the spill should be at the rate of not less than 0.50 gpm per sq. ft.

(c) Pumps or other devices which handle flammable liquids or gases shall have the shafts, packing glands, connections, and other critical parts enveloped in directed water spray at a density of not less than 0.50 gpm per square foot of projected surface area.

4043. Exposure Protection. (a) GENERAL:

(I) The system shall be able to function effectively for the duration of the exposure fire which is estimated from a knowledge of the nature and quantities of the combustibles and the probable effect of fire-fighting equipment and materials. System operation for hours may be required.

(2) Automatic water spray systems for exposure protection should be designed to operate before the formation of carbon de- posits on the surfaces to be protected and before the possible failure of any containers of flammable liquids or gases because of the tem- perature rise. The system and water supplies should, therefore, be designed to discharge effective water spray from all nozzles within 30 seconds following operation of the detection system.

(3) The densities specified for exposure protection contem- plate minimal wastage of 0.05 gpm per square foot. In some cases additional wastage should be contemplated to insure proper appli- cation on the surfaces. (See 4080.)

(4) Generally, the upper portions of equipment and the upper levels of supporting structures are less severely exposed by fire than are tthe lower portions or levels due to the accumulation at grade level of fuel from spillage or equipment rupture. Consideration may thus be given to reducing the degree of (or eliminating) water spray protection for the upper portions of high equipment or levels of structures, provided a serious accumulation of fuel, or torch action from broken process piping or equipment, cannot occur at these elevations, and serious exposure does not exist. Examples are some steel columns, above the 30- or 40- foot level, and above the third or fourth level of muhi-level open structures.

(5) Where equipment, structures, or vessels are provided with insulation systems which are considered of some value, but which do

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 23: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM D E S I G N AND I N S T A L L A T I O N 15-21

not fully meet the requirements for the definition of "Insulated" (see 1020), consideration may be given to the reduction of water application rates specified for exposure protection.

(b) VESSELS: (1) These rules for exposure protection contemplate adequate

emergency relieving capacity for vessels, based upon a maximum allowable heat input of 6,000 Btu per hour per square foot of ex- posed surface area. The density shall be increased to limit the heat absorption to a safe level in the event adequate emergency relieving capacity is not provided. (See Appendix A-4043(b).)

(2) Where the temperature of a vessel or its contents must be limited, higher densities than called for under (4) or (7) will be required.

(3) Internally insulated or lined vessels require special con- sideration to determine necessary water spray requirements.

(4) Water shall be applied to vertical or inclined vessel sur- faces at a net rate of not less than 0.25 gallons per minute per square foot of exposed uninsulated surface. Individual nozzle water ap- plication rates shall be increased to provide for any run-down or slippage allowances. Where rundown is contemplated, the vertical distance between nozzles shall not exceed twelve feet. The hori- zontal extremities of spray patterns shall at least meet.

(5) In most cases spherical or horizontal cylindrical surfaces below the vessel equator cannot be considered wettable from rundown.

(6) Where projections (manhole flanges, pipe flanges, support brackets, etc.) will obstruct water spray coverage, including run- down or slippage on vertical surfaces, additional nozzles shall be installed around the projections to maintain the wetting pattern which otherwise would be seriously interrupted.

(7) Bottom and top surfaces of vertical vessels shall be com- pletely covered by directed water spray at an average rate of not less than 0.25 gallons per minute per square foot of exposed unin- sulated surface. Consideration may be given to slippage but on the bottom surfaces the horizontal extremities of spray patterns shall at least meet.

(8) Special attention shall be given to distribution of water spray around relief valves and around supply piping and valve connection projections.

(9) Uninsulated skirts shall have water spray applied on one I exposed (uninsulated) side, either inside or outside, at a net rate of not less than 0.10 gpm per square foot.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 24: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

1 ~ - 2 2 WATER SPRAY FIXED SYSTEMS

~ WETTED SURFACE

Fig. 4 0 4 3 ( c ) . The wetted surface of structural member q beam or column is defined as one side of the web and the inside surface of one side of the f langes as shown above .

/ / / / / / / / / / /

6" ~ 8~DIA, PIPES 0 0 0 0 0 0 N O Z Z L E S S H O U L D BE S E L E C T E D A N D P O S I T I O N E D SO AS TO S P R A Y A T L E A S T ONE S I D E OF T H E P I P I N G A T A T O T A L D I S C H A R G E R A T E OF 1.47 G P M

R E Q U I R E D P E R F ~ L E N G T H OF

P I P E R A C K

/ / / / / / / / / / / / / / / / / / / * / . / / / / , I /

N O T E : A D D I T I O N A L N O Z Z L E S M A Y BE R E Q U I R E D FOR P R O T E C T I O N OF V E R T I C A L C O L U M N S

r / / / / / * / / *

Fig. 4 0 4 3 ( c - 4 - 1 ) . Calculat ion of water spray density requirement for typical pipe rack.

The sum (~) of the total number (N) of pipes multiplied by ~ times the diameter (d) of the pipe in feet multiplied by a unit length (L) of pipe of I foot, times the density rate (q) equals total gpm required per ft. length of pipe rack.

~N~dLq = 71r (8 /12 ) (1) (0.1) = 1.47 g pm required per ft. length of pipe rack.

To determine density in gprn per square foot, divide the total discharge per foot of length of pipe rack by the width of the pipe rack in feet: 1.47 ÷ 6 = 0 . 2 4 5 gpm/ f t 2 of projected grade area.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 25: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM D E S I G N A N D I N S T A L L A T I O N 15-23

/ / / / / / / / / / / /

0 0 0 0 0 I0~ DIA. P I Pt:'$

/ 0 0 0 0 0 0 0

12" DIA. P IPES /

0 0 0 0 0 0 NOZZLES SHOULD BE SELECTED ANO POSIT IONED SO AS TO SPRAY AT LEAST ONE SIDE OFALL (EACR LEVEL) THE P IP ING AT A TOTAL DISCHARGE RATE OF 554 GPM REQUIRED PER FT LENGTH OF PIPE RACK

/ / ' / / / / / / / / / / / / / / / . f / / / / / / / / / / / / / / / / / / / / / / /

N O T E : ADDIT IONAL NOZZLES MAY BE REQUIRED FOR PROTECTION OF VERTICAL COLUMNS

Fig. 4 0 4 3 ( c - 4 - 2 ) . Calculation of water spray density requirement for typical pipe rack.

The (~ ) of the total number (N) of pipes multiplied by lr times the diameter (d) of the pipe in feet multiplied by a unit length (L) of pipe of 1 foot, times the density rate (q) equals total gpm required per ft. length of pipe rack.

~N~rdLq ± 14~r ( 1 0 / 1 2 ) (1) (0.1) + 6 ~ ' ( 1 2 / 1 2 ) (1) (0.1) = 3.66 + 1.88 = 5 . 5 4 gpm required per ft. length of pipe rack.

To determine density in gpm per square foot, divide the total discharge per foot of length of pipe rack by the width of the pipe rack in feet: 5 . 5 4 - 10 = 0 . 5 5 gpm/f t ~ of projected grade area. Reduce to not more than 0.,50 gpm/ft 2 of pro- jected grade area. [See 4043 (c) (4)]

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 26: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-24 WATER SPRAY FIXED SYSTEMS

(C) STRUCTURES AND MISCELLANEOUS EQUIPMENT:

(1) Horizontal, stressed (primary) structural steel members shall be protected by nozzles spaced not greater than ten feet on centers (preferably on alternate sides) and of such size and ar- rangement as to discharge not less than 0.10 gpm per square foot over the wetted area. See Figure 4043(c).

(2) Vertical structural steel members shall be protected by nozzles spaced not greater than ten feet on centers (preferably on alternate sides) and of such size and arrangement as to discharge not less than 0.25 gpm per square foot over the wetted area. See Figure 4043(c).

(3) Pipe, tubing, conduit, and cable runs shall be protected by water spray at a basic rate of 0.10 gpm per square foot of the aggregate pipe wall area. In the interest of conserving water, this rate should be limited to maintain a cumulative projected grade area rate of not more than 0.50 gpm per square foot. Factors to be considered when designing water spray protection for pipe racks include the number of levels of pipe, the spacing between pipes, and the general configurations of the pipe rack. See Figures 4043(c-4-1) and 4043(c-4-2) for typical water spray application rate calculations. Nozzle arrangement will depend upon char- acteristics of nozzles chosen and the design selected to meet the requirements.

(d) TRANSFORMERS.

(1) Transformer protection shall contemplate essentially com- plete impingement on all exterior surfaces, except underneath surfaces which in lieu thereof may be protected by horizontal projection. The water shall be applied at a rate not less than 0.25 gpm per square foot of projected area of rectangular prism en- velope for the transformer and its appurtenances and not less than 0.15 gpm per square foot on the expected nonabsorbing ground surface area of exposure. Additional application may be needed for special configurations, conservator tanks, pumps, etc. Spaces greater than twelve inches in width between radiators, etc., should be individually protected.

(2) Water spray piping should not be carried across the top of the transformer tank.

(3) In order to prevent damage to energized bushings or lightning arrestors, water spray should not envelop this equipment by direct impingement. If it is desired to envelop this equipment, the manufacturer, or his literature, and the owner should be consulted.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 27: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

S Y S T E M D E S I G N A N D I N S T A L L A T I O N 15-25

4044. Fire Prevention. (a) The system shall be able to function effectively for a suf-

ficient time to dissolve, dilute, disperse, or cool flammable or haz- ardous materials. The possible duration of release of the materials shall be considered in the selection of duration times.

(b) The rate of application for fire prevention shall be based upon experience with the product or upon test. The authority having jurisdiction shall be consulted concerning rates of ap- plication.

4050. Size of System. 4051. Separate fire areas should be protected by separate sys-

tems. Single systems should be kept as small as practicable, giving consideration to the water supplies and other factors affecting re- liability of the protection. A design discharge rate of 3,000 gpm should not be exceeded for a single system. (See Chapter 3.)

4060. Separation of Fire Areas. 4061. Fire areas may be properly subdivided by space, fire

barriers, diking, special drainage, or by combination of these. In the separation of fire areas consideration must be given to the pos- sible flow of burning liquids before or during operation of the water spray systems.

4062. Area Drainage. (a) Adequate provisions shall be made to promptly and ef-

fectively dispose of all liquids from the fire area during operation of all systems in the fire area. Such provisions shall be adequate for:

(1) Water discharged from fixed fire protection systems at maximum flow conditions.

(2) Water likely to be discharged by hose streams. (3) Surface water. (4) Cooling water normally discharged to the system.

(b) There are four methods of disposal or containment: (1) Grading. (2) Diking. (3) Trenching. (4) Underground or enclosed drains.

The method used shall be determined by: (1) The extent of the hazard. (2) The clear space available. (3) The protection required.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 28: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-26 WATER SPRAY FIXED SYSTEMS

Where the hazard is low, the clear space is adequate, and the degree of protection required is not great, grading should be ac- ceptable. Where these conditions are not present consideration shall be given to dikes, trenching, or underground or enclosed drains.

(c) For the methods of drainage or diking, see Standard for Flam- mable and Combustible Liquids (NFPA No. 30) and Appendix A-4060.

4070. Valves. 4071. Shutoff Valves - - Each system shall be provided with

a shutoff valve so located as to be readily accessible during a fire in the area the system protects or adjacent areas, or, for systems installed for fire prevention, during the existence of the contingency for which the system is installed.

4072. Automatically Controlled Valves. (a) Automatically controlled valves shall be as close to the haz-

ard protected as accessibility during the emergency will permit, so that a minimum of piping is required between the automatic valve and the spray nozzles.

(b) Remote manual tripping devices, where required, shall be conspicuously located where readily accessible during the emer- gency and adequately identified as to the system controlled.

4073. Dra in Valves. (a) Readily accessible drains shall be provided for low points

in underground and aboveground piping. (b) Where feasible automatic drain may be acceptable.

4080. Spray Nozzles. 4081. Selection - - The selection of the type of spray nozzles

shall be made with proper consideration given to such factors as physical character of the hazard involved, draft or wind conditions, material likely to be burning, and the general purpose of the system.

4082. Size - - A test of the water supply is recommended before the size of spray nozzle orifices is selected, unless full information concerning the water supply is readily available. I t is required that piping be hydraulically calculated and sized, and, if necessary, that spray nozzle orifices be varied in size in order to obtain desired water distribution and to allow for loss of head in water supply piping. Where nozzle waterways are less than l~-inch in least dimension, particular care shall be taken in the selection of strainers. (See 2110 and 4110.)

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 29: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM D E S I G N AND I N S T A L L A T I O N 15-27

4083. P o s i t i o n - Spray nozzles may be placed in any position necessary to obtain proper coverage of the protected area. Po- sitioning of nozzles with respect to surfaces to be protected, or to fires to be controlled or extinguished shall be guided by the par- ticular nozzle design and the character of water spray produced. The effect of wind and fire draft on very small drop sizes or on larger [ drop sizes with little initial nozzle velocity shall be considered, since these factors will limit the distance between nozzle and sugface. Care should be exercised in placement of spray nozzles protecting pipe lines handling flammable liquids under pressure, where such protection is intended to extinguish or control fires resulting from leaks or ruptures.

4090. Piping. 4091. Size - - As effective protection is dependent on having

adequate pressure and quantity of water available at all spray nozzles, each system requires individual consideration as to the size of the piping. This requires that the size of the piping be based upon hydraulic computations (see Chapter 7). However, piping in gen- eral should not be less than one-inch nominal diameter.

4092. Installation.

(a) The installation standards for water spray system piping shall be applicable sections of the Standard for the Installation of Sprinkler Systems (NFPA 13), except as herein modified.

(b) Welding is permissible. The authority having jurisdiction should be consulted to assure safe welding or cutting practices. Welding should preferably be done in the shop. When done in the field, the fire hazard of the process shall be suitably safeguarded. Welding shall be conducted in accordance with the USA Standard Code for Pressure Piping, USAS B31.1 where applicable. This may require galvanizing of sections involving welded parts after fabri- cation. Special care shall be taken to insure that the openings are fully cut out and that no obstructions remain in the waterway.

(c) All underground supply piping after the automatic control valve shall be pitched ~ inch in ten feet to drain in the same manner as the above mentioned Standards specify for aboveground piping. Provision shall be made to drain underground and overhead piping.

(d) Main headers should be installed underground or at least as near as possible to ground level as protection against the effects of possible fire, explosion, or mechanical injury. Where overhead piping is necessary, it should not pass over another hazard. Piping may be looped if desired.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 30: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-28 W A T E R SPRAY F I X E D SYSTEMS

(e) Gage connections shall be provided for test gages near the highest or most remote nozzle on each major separate section of the system or where indicated by the authority having jurisdic- tion. In any event, one gage connection shall be provided near the nozzle calculated as having the least pressure under normal flow conditions.

(f) Unions, flanges, or other approved couplings may be used to assemble closed loops of piping or to assemble prefabricated piping. (See 2062.)

4100. Hangers. 4101. System piping shall be adequately supported. All sup-

ports in the fire area should be protected by the system. In any area where possibility of explosion may be recognized, special care shall be taken to support the piping from portions of the struc- ture least liable to disruption.

4102. Tapping or drilling of load bearing structural members generally is not permitted. Attachments may be made to existing steel or concrete structures and in some cases to equipment and its supports. Where welding of supports directly to vessels or equip- ment is necessary, it shall be done in a safe manner in conformance with the provisions of all safety, structural, and fire codes and standards.

4103. Where the usual methods of supporting piping for fire protection purposes cannot be used, the piping shall be supported in such a manner as to produce the strength equivalent to that afforded by such usual means of support. In such cases, piping ar- rangements which are essentially self-supporting may be employed together with such hangers as are necessary.

4110. Strainers. 41Jl . Main pipeline strainers shall be provided for all systems

utilizing nozzles with waterways less than ~ inch and for any system where the water is likely to contain obstructive material.

4112. Pipeline strainers should be installed so as to be accessible for cleaning during the emergency. Dual type strainers or equivalent may be necessary if water supplies are badly contaminated.

I 4113. Individual strainers shall be provided for nozzles having water passageways smaller than ~ inch.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 31: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

SYSTEM D E S I G N AND I N S T A L L A T I O N 15-29

4120. Gages. 4121. Gages shall be installed as follows: (a) Below the seat of the automatic valve and arranged so as

to indicate the residual pressure in the riser with the test pipe valve wide open.

(b) At each independent pipe from an air supply to an auto- [ matic valve.

(c) On the water supply connection to hydraulically controlled [ automatic valves.

At the air pump supplying an air receiver. [ (d) v

(e) At an air receiver. J

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 32: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-30 W A T E R S P R A Y F I X E D S Y S T E M S

CHAPTER 5. ACCEPTANCE TESTS

5000. Flushing of Piping. 5001. Supply Piping. - - Underground mains and lead-in

connections to system risers shall be flushed thoroughly before con- nection is made to system piping, in order to remove foreign ma- terials which may have entered the underground during the course of the installation or which may have been present in existing piping. The minimum rate of flow should be not less than the water demand rate of the system which is determined by the system design; in any case, it should not be less than that necessary to provide a velocity of ten feet per second. For all systems the flushing op- erations should be continued for a sufficient time to insure thor- ough cleaning. When planning the flushing operations considera- tion shall be given to disposal of the water issuing from the test outlets.

Flow Required to Produce a Ve loc i t y of Ten Feet per Second in Pipes

Pipe Size F low (Inches) (Gal lons per Minute)

4 3 9 0 6 880 8 1560

10 2440 12 3520

5002. System Piping - - All system piping shall be flushed where practicable; otherwise, cleanliness shall be determined by visual examination.

5010. Hydrostatic Pressure Tests. 5011. Hydrostatic Tests - - All new system piping shall be

hydr"ostatically tested in accordance with the provisions of the Standard for Installation of Sprinkler Systems (NFPA No. 13).

5020. Water Discharge Test. 5021. When practicable, full flow tests with water should be

made of system piping as a means of checking the nozzle layout, discharge pattern, any obstructions and determination of relation between design criteria and actual performance, and to insure against clogging of the smaller piping and the discharge devices by foreign matter carried by the water.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 33: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

A C C E P T A N C E T E S T S 15-31

5022. The maximum number of systems that may be expected to operate in case of fire should be in full operation simultaneously in order to check as to adequacy and condition of the water supply.

5023. The discharge pressure at the highest, most remote nozzle, shall be at least that for which the system was designed.

5030. Operating Tests. 5031. All operating parts of the system shall be fully tested to

assure they are in operating condition.

5032. The operating tests shall include a test of automatic de- tection equipment.

5040. Acceptance Test Suggestions. 5041. All tests should be made by the contractor in the presence

of the inspector for the authority having jurisdiction. When an inspector is not available, and permission is granted by the au- thority having jurisdiction, tests may be witnessed by, and the test certificate signed by the owner or his representative.

5042. Before asking for final approval of the protective equip- ment by the authority having jurisdiction, installing companies should furnish a written statement to the effect that the work cov- ered by its contract has been completed and all specified flushing of underground, lead-in, and system piping has been successfully completed, together with specified hydrostatic pressure tests.

5043. The applicable parts of the Sprinkler Contractor's Cer- tificate Covering Materials and Tests (see NFPA 13) should be completed and submitted, certifying that the work has been com- pleted and tested in accordance with approved plans and speci- fications.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 34: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-32 W A T E R S P R A Y F I X E D S Y S T E M S

C H A P T E R 6. P E R I O D I C T E S T I N G A N D M A I N T E N A N C E

6000. Genera l . 6001. Water spray systems require competent and effective care

and maintenance to assure that they will perform their purpose ef- fectively at the time of fire. Systems should be serviced and tested periodically by men experienced in this work. An inspection con- tract with a qualified agency acceptable to the authority having jurisdiction for service, test, and operation at regular intervals is recommended and may be required.

6002. Operating and maintenance instructions and layouts shall be posted at control equipment and at the plant fire head- quarters. Selected plant personnel should be trained and assigned to the task of operating and maintaining the equipment.

6003. At weekly, or other frequent routine plant inspections, equipment should be checked visually for obvious defects, such as broken or missing parts, nozzle loading, or other evidence of im- paired protection.

6010. M a i n t e n a n c e . 6011. Water Supp l i e s - - Proper precautions should be taken

to insure that water supplies are kept turned on and are in full op- erating condition at all times.

6012. Strainers - - Strainers, except individual nozzle strainers (see 6018), shall be thoroughly inspected after each operation or flow test and cleaned if necessary. Routine inspection and cleaning should be performed at intervals of not more than six months and shall be performed annually.

6013. P i p i n g - - All piping shall be examined at regular in- tervals to determine condition. Frequency of inspections will be de- pendent upon local conditions and should be at intervals of not more:than one year. This should include tests to determine that proper drainage is maintained for piping.

6014. Flow tests of open head spray systems shall be made at such intervals as are deemed necessary by the authority having juris- diction, wherever such tests are practicable.

6015. Control V a l v e s a n d D e v i c e s - - Control valves and auto- matic detection equipment shall be tested at least annually and more often if conditions warrant, by qualified inspectors acceptable to the authority having jurisdiction.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 35: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

P E R I O D I C T E S T I N G 15-33

6016. Manual tripping devices and valves, including O. S. & Y. gate and post indicator valves, shall be operated at least annually.

6017. Where normally opened valves are closed following sys- tem operation or test, suitable procedures should be instituted to insure that they are reopened and that the system is promptly and properly restored to full normal operating condition. Main drain flow tests should be made after valves are reopene d (see NFPA No. 13A - - Flow Tests).

6018. S p r a y Nozzles - - All spray nozzles shall be inspected for proper positioning, external loading, a n d corrosion, and cleaned if necessary at intervals of not more than six months. Local con- ditions may require such inspection and cleaning more frequently and may require internal inspection. After each operation open spray nozzles equipped with individual screens shall be removed and the spray nozzle and screen cleaned, unless observation under flow conditions indicates this is not necessary.

6019. Flushing - - Underground lead-in connections to system risers shall be flushed at least annually, in accordance with 5001. This may be accomplished by:

(a) A flow test of the system, or

(b) Flowing water from a suitable flushing connection of ade- quate size.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 36: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-34 WATEI~ S P R & Y F I X E D S Y S T E M S

CHAPTER 7. PLANS, SPECIFICATIONS, AND HYDRAULIC CALCULATIONS

7000. Plans and Specifications. 7001. Working plans, including elevations, shall be drawn to

an indicated scale, show all essential details, and the following data: Date. Name of owner and occupant. Location, including street address. Point of compass. Structural features. Relative elevations of nozzles, junction points and supply or

reference points. Full information concerning water supplies, including pumps,

underground mains, etc., and flow test results. Make, type, size, location, position, and direction of spray nozzles. Make, type, model, and size of special system valve. Types of alarms to be provided. Number of each size and type of spray nozzles on each system. Lengths of pipe and whether center to center or cutting lengths

are shown. Size of all pipe and fittings. Heat responsive equipment, including type, arrangement and

location. Hydraulic reference points. Design purpose of system. Make and type of hangers and inserts. All control and check valves, strainers, drain pipes, and test pipes. Small hand hose and hose equipment. The weight or class, lining and size of underground pipe and the

depth that the top of the pipe is to be laid below grade. Provisions for flushing underground pipe. Accurate and complete layout of the hazard being protected. When the equipment to be installed is an addition or change,

enough of the old system should be indicated on the plans to make all conditions clear.

Name and address of contractor.

7010. Hydraulic Calculations. 7011. Genera l - - Hydraulic calculations should be prepared

on forms that include a summary sheet, detailed work sheets, and a graph sheet. (See Figures 7020, A-7090b. and A-7090d. for typical forms.)

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 37: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

H Y D R A U L I C C A L C U L A T I O N S 15-35

- - S U M M A R Y S H E E T - - H Y D R A U L I C C A L C U L A T I O N - -

N A M E A N D A D D R E S S O F C O N T R A C T O R ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C O N T R A C T N O ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C A L C U L A T O R ........................ D A T E ....................

N A M E O F O W N E R A N D O C C U P A N T ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A D D R E S S ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B U I L D I N G O R P L A N T U N I T N U M B E R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D E S C R I P T I O N O F H A Z A R D ..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A U T H O R I T Y H A V I N G J U R I S D I C T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

- - S Y S T E M R E Q U I R E M E N T S - -

D E S I G N P U R P O S E : E X T I N G U I S H M E N T ................ E X P O S U R E P R O T E C T I O N ............

C O N T R O L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F I R E P R O T E C T I O N ............................

T Y P E S Y S T E M : A U T O M A T I C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M A N U A L ............................................

D E N S I T Y ( G . P . M . P E R S Q . F T . ) ............ T O T A L N O Z Z L E F L O W R E Q U I R E D ........ G . P . M .

A L L O ' W A N C E F O R I N S I D E H O S E S T A T I O N S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G . P . M .

A L L O W A N C E F O R O U T S I D E H Y D R A N T S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G . P . M .

T O T A L W A T E R R E Q U I R E D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G . P . M . A T .................................... P . S . I .

R E M A R K S : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

- - W A T E R S U P P L Y I N F O R M A T I O N -

T Y P E O F W A T E R S U P P L Y : P U B L I C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P R I V A T E ....................................

S T A T I C P R E S S U R E I N P . S . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

R E S I D U A L P R E S S U R E :

G . P . M . F L O W I N G . . . . . . . . . . . . . . . . . . . . . . A T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P . S . I .

E L E V A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . L O C A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P U M P D A T A :

R A T E D C A P A C I T Y . . . . . . . . . . . . . . . . . . . . . . G . P . M . A T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P . S . I .

E L E V A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L O C A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T A N K D A T A :

C A P A C I T Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G A L S . - E L E V A T I O N .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

L O C A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

R E M A R K S : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fig. 7020. Sample Summary Sheet

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 38: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-36 W A T E R SPRAY F I X E D SYSTEMS

7020. Summary Sheet. The summary sheet (for sample summary sheet see Figure 7020)

should contain the following information: (a) Date. (b) Location. (c) Name of owner and occupant. (d) Building or plant unit number. (e) Description of hazard. (f) Name and address of contractor. (g) Authority having jurisdiction. (h) Design purpose. (i) Minimum rate of water application (density) . . . gpm per

square foot. (j) Total water requirements as calculated including allowance

for inside hose and outside hydrants. (k) Water supply information.

7030. Detailed Work Sheets. Detailed work sheets or computer print-out sheets (for sample

work sheet, see Fig. A-7090b.) should contain the following in- formation:

(a) Sheet number, date, job number, and identification of cal- culations covered.

(b) Description and discharge constant (K) (or provide the discharge curve or tabulation) for each nozzle type.

(c) Hydraulic reference points. (d) Flow in gpm. (e) Pipe size. (f) Pipe lengths, center to center of fittings. (g) Equivalent pipe lengths for fittings and devices. (h) Friction loss in psi per foot of pipe. (i) Total friction loss in psi between reference points. (j) Elevation head in psi between reference points. (k) Required pressure in psi at each reference point. (1) Velocity pressure and normal pressure if included in calcu-

lations. (m) Notes to indicate starting points, reference to other sheets

or to clarify data shown. (n) When extending existing equipment hydraulic calculations

are to be furnished indicating the previous design, volume, and

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 39: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

HYDRAULIC CALCULATIONS 15-37

pressure at points of connection, and adequate additional calcula- tions to indicate effect on existing systems.

7040. Graph Sheets. 7041. The graph sheet should be made to n TM. Water supply

curves and system requirements plus hose demand should be plotted so as to present a graphic summary of the complete hydraulic calculation. (For sample graph sheet, see Fig. A-7090d.)

7050. Abbreviations and Symbols. 7051. The following standard abbreviations and symbols should

be used. Symbol or Abbreviation

P gpm q

O

Pt PI

P,

Pv P, E EE Lt E Cr T GV Del V DPV AL V CV St psig V

g

K C P d

/gem Pressure in psig. Flow rate in U. S. Gallons per minute. Flow increment in gpm to be added at a specific location. Summation of flow in gpm at a specific lo- cation. Total pressure at a point in a pipe. Pressure loss due to friction between points indicated in location column. Pressure due to elevation difference between indicated points. This can be a plus value or a minus value. Where minus, the symbol ( - - ) shall be used; where plus, no sign need be indicated. Velocity pressure at a point in a pipe. Normal pressure at a point in a pipe. 90 ° Elbow 45 ° Elbow Long Turn Elbow. Cross. Tee, flow turned 90 ° . Gate Valve. Deluge Valve. Dry-Pipe Valve. Alarm Valve. Swing Check Valve. Strainer. Pounds per square inch gage. Velocity of water in pipe in feet per second. Acceleration due to gravity in feet per second per second (generally 32. or 32.16 is used). A constant. Hazen and Williams friction loss coefficient. Frictional resistance per foot of pipe in psi per ft. Actual internal diameter of pipe used, in inches.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 40: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-38 W A T E R S P R A Y F I X E D S Y S T E M S

,00

O0

O0

O0

O0

~0 ~0 ~0 =~

~0 O_

~0 ' 0

)0 Z

~o ~ ©

0 - J tl_

0

I ) )

)

)

o ~ l ~ ~ ~1" r,1 al -- ~ ) ~ ~ ~ ~ ~ 0 ; • . . . . . o o o . o. o. o. o

LOSS I N P S I G PER FT.

Fig. 7 0 6 0 . a . Friction loss in schedule 40 steel pipe. Hazen & Wil l iams C-120.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 41: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

HYDRAULIC CALCULATIONS 15-39

7060. F o r m u l a e .

a. Pipe friction losses should be de te rmined on the basis of Hazen and Wil l iams formula . (See Fig. 7060a.)

4.52 Q1.85 p =

C 1.85 d 4.87

b. The veloci ty pressure should be de te rmined on the basis of

/)2' P~ = 0 . 4 3 3 - - -

2g

Where v is the u p s t r e a m velocity.

c. Norma l pressure should be de t e rmined on the basis of

P , ~ P t - - P v

d. H y d r a u l i c j unc t ion po in t ca lcula t ions except for loops should be ba lanced to the h igher pressure by the formula*

_~_ Q' - P ~ p P ~ (corrected for Q = KV'-P- or K = % / or Q,2 elevations)

e. T h e discharge of a nozzle m a y be ca lcu la ted by the formula*

q = ~c%/g--

*NOTE: (|) P may be the total or normal pressure according to whether or not the velocity pressure is being included.

(2) Piping may be looped to divide the total water flowing to the design area.

7070. V e l o c i t y P re s su re . a. T h e veloci ty pressure Pv m a y or may not be included in the

ca lcula t ions a t the discret ion of the designer.

NOTE: The omission of the velocity pressure from the calculations in- troduces an error that is generally on the safe side. However, under some conditions with high velocity, the velocity pressures should be considered.

b. The veloci ty pressure Pv is a measure of the energy requi red to keep the water in a pipe in motion. At the end of the nozzle or end section of system (when consider ing junc t ion of sections of sys- tems) the to ta l pressure ava i lab le in the pipe at tha t point should

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 42: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-40 W A T E R S P R A Y F I X E D S Y S T E M S

o

m 0.

Ld

m m bJ a: 0.(

F- C Uq 0 ,d( bl

(

I0 20 30 40 50 I00 200 :300 600 I000 2000 5000

FLOW- GPM

Fig. 7070 .b . Graph for the determinat ion of velocity pressure.

be considered as causing flow. However, at other nozzles or junc- tion points the pressure causing flow will be the normal pressure which is the total pressure minus the velocity pressure. Figure 7070.b. may be used for determining velocity pressures, or velocity pressure may be determined by dividing the flow in gpm squared by the proper constant from Table 7070.b.

' TABLE 7 0 7 0 . b .

Pipe Constant Schedule Pipe Size Based on Actua l h D.

40 I 1,080 40 11/4 3,230 40 1 I/2 5 , 9 8 0 40 2 16,200 40 21/2 3 3 , 1 0 0 40 3 7 8 , 8 0 0 40 31/2 141 ,000 40 4 2 3 4 , 0 0 0 40 5 577,000 40 6 1 ,204 ,000 30 8 3 , 7 8 0 , 0 0 0 40 8 3 , 6 2 0 , 0 0 0

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 43: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

H Y D R A U L I C C A L C U L A T I O N S 15-41

c. T h e following assumptions are to be used in app ly ing veloci ty pressure to the calculat ions.

1. At any nozzle a long a pipe, except the end nozzle, only the no rma l pressure can act on the nozzle. At the end nozzle, the total pressure can act.

2. At any nozzle a long a pipe, except the end nozzle, the pres- sure ac t ing to cause flow from the nozzle is equal to the total pres- sure minus the velocity pressure on the ups t ream side.

3. To find the normal pressure at any nozzle except the end nozzle, assume a flow from the nozzle in question, and de te rmine the veloci ty pressure for the total flow on the ups t r eam side. Be- cause no rma l pressure = total pressure - - velocity pressure, the value of the no rma l pressure so found should result in a nozzle flow a p p r o x i m a t e l y equal to the assumed flow. If not, a new value should be assumed and the ca lcula t ion repeated .

7080. Equivalent Pipe Lengths of Valves and Fittings. a. T a b l e 7080 should be used to de te rmine equivalent lengths of

pipe for fittings. b. Specific friction loss values or equiva len t pipe lengths for

deluge valves, strainers, and o ther devices shall be m a d e ava i lab le to the au thor i ty having jur isdic t ion.

7090. Calculating Procedure. 7090. In o rder to main ta in consistency in hydraul ic calculat ions,

whe the r done by hand or by compute r , the following rules should I be followed. Experience has shown tha t good results are ob ta ined if the calcula t ions are m a d e in accordance with these rules. I t is recognized tha t satisfactory results m a y be ob ta ined by using other methods . However , in order to simplify the checking of ca lcula- t ions and to ob ta in more consistent corre la t ion between ca lcu la ted system character is t ics and ac tua l system character is t ics it is de- s irable to use a s tandard me thod .

a. T h e first work sheet should start a t a remote nozzle and pro- ceed direct ly to a point of known or proposed water supply. Branch calculat ions should be made on subsequent sheets.

b. Inc lude the friction loss on all p ipe and devices such as valves, meters, and strainers.

c. Inc lude all fittings where a change in direct ion of the flow occurs, as follows:

1. Calcula te the loss for a tee or a cross where flow direct ion change occurs, based on the equiva lent pipe length for the smal ler size of the tee or cross in the pa th of the turn. Do not include any loss for that por t ion of the flow which passes s t raight th rough the run of a tee or a cross.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 44: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

Fittings and Va lves 3/~ in. I in.

4,5 ° Elbow 1 1

90 ° Standard Elbow 2 2

90 ° Long Turn Elbow 1 2

Tee or Cross 4 5 (Flow Turned 90 ° )

Gate Valve - -

Swing Check* 4 .5

TABLE 7 0 8 0

EQUIVALENT PIPE LENGTH CHART

Fittings and Va lves Expressed in Equivalent Feet of Pipe. 11~in. 1~2in. 2 in. 2Y2in. 3 in. 3V2in. 4 in. 5 in. 6 in. 8 in. l O i n . 12 in .

I 2 2 3 3 3 4 5 7 9 11 13

3 4 5 6 7 8 10 12 14 18 22 27

2 2 3 4 5 5 6 8 9 13 16 18

6 8 10 12 15 17 20 25 30 35 50 60

- - I I I I 2 2 3 4 5 6

7 9 11 14 16 19 22 27 32 45 55 65

Use with Hazen and Williams C = 120 only. For other values of C, the figures in Table 7080 should be multiplied~by the factors indicated below:

Value of C 100 120 130 140

Multiplying factor 0.7 13 1.00 1.16 1.32

(This is based upon the friction loss through the fitting being independent of the C factor applicable to the piping.)

Specific friction loss values or equivalent pipe lengths for alarm valves, dry-pipe valves, deluge valves, strainers and other devices shall be made available to the authority having jurisdiction.

~'Due to the variations in design of swing check valves, the pipe equivalents indicated in the above chart to be considered average.

L~

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 45: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

H Y D R A U L I C C A L C U L A T I O N S 15-43

2. Calculate the loss of reducing elbows based on the equivalent feet value of the smallest outlet. Use the equivalent feet value for the "standard elbow" on any abrupt ninety degree turn, such as the screw type pattern. Use the equivalent feet value for the " long turn elbow" on any sweeping ninety degree turn, such as a flanged, welded, or mechanical joint type elbow.

3. Friction loss should be excluded for tapered reducers and for the fitting directly supplying the spray nozzle.

d. Include all elevation changes affecting the discharge and /o r the total required pressure where it occurs.

e. Piping may be looped to divide the total water flowing to the design area.

f. The water allowance for outside hydrants when served from the same underground mains may be added to the system require- ment at the system connection to the underground main. The total water requirement should then be calculated through the under- ground main to the point of supply.

g. Orifice plates should not be used for balancing the system.

h. Calculate pipe friction loss in accordance with the Hazen and Williams formula using " C " value of 120 for black or galvanized steel pipe, C-140 for cement lined cast iron pipe or copper tubing, and C-100 for unlined cast iron pipe. The authority having juris- diction may recommend other C values. These coefficients con- template the use of the actual pipe internal diameter in the formula.

NOTE: See Appendix for sample calculatiom.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 46: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-44 WATER SPRAY FIXED SYSTEMS

CHAPTER 8. A U T O M A T I C D E T E C T I O N E Q U I P M E N T

8000. General. 8001. The arrangements of automatic detection equipment for

water spray systems requires careful engineering, and a different arrangement from that required for other types of systems. The provisions of this Chapter are based upon the type of equipment presently available for use with special systems. Other types shall give at least equivalent performance.

8010. Selection. 8011. Care should be exercised in the selection and adjustment

of detection equipment to assure proper operation and to guard against premature operation of the system from normally fluctu- ating conditions. For example, particular care should be taken to compensate for normal temperature fluctuations in installations such as transformer protection involving heat exchangers having automatic fans, and installations involving industrial ovens and furnaces.

8020. Protection. 8021. Corrosion Protection. Detection equipment installed

out of doors or in the presence of possible corrosive vapors or at- mospheres shall be protected from corrosion by suitable materials of construction or by suitable protective coatings applied by the equipment manufacturer.

8022. Protect ive Canopy, Detection equipment requiring pro- tection from the weather shall be provided with a canopy, hood, or other suitable protection.

8023. Mechanical Damage. Detection equipment shall be lo- cated so as to be protected from mechanical damage.

8024. Mount ing. Detectors shall, in all cases, be supported independently of their attachment to wires or tubing.

8030. Location and Spacing of Detectors. 8031. Automatic detection equipment shall be so located and

adjusted as to operate reliably. The location of detectors should be based upon data obtained from field experience, tests, engineer- ing surveys, the manufacturer's recommendations, and recognized laboratory listings, insofar as these are applicable. In addition, location should take into consideration such factors as the nature of the hazard being protected, air velocity, temperature variations,

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 47: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

AUTOMATIC DETECTION EQUIPMENT 15-45

number and height of structural levels, shielding, indoors or out- doors, open or closed structures, and other variable conditions where the exercise of judgment based upon experience with such detection equipment in actual tests and service, is needed.

8032. Location and spacing of detectors may be in accordance with the manufacturer's recommendations where such recom- mendations are based upon tests satisfactory to the authority having jurisdiction. In the absence of such recommendations the follow- ing rules apply.

8033. Outdoor Installations.

(a) Detectors used outdoors should be installed with a markedly reduced spacing from that shown by tests to be satisfactory for indoor installation.

NOTE: Presently, fire detectors for special systems have been investigated and identified by Underwriters' Laboratories, Inc., Underwriters' Labora- tories of Canada, and the Factory Mutual Engineering Corporation; how- ever, the spacing limitations specified are for indoor installations, prin- cipally under smooth ceilings.

(b) Detectors should be located around the perimeter of the I hazard and within the area enclosed by the perimeter detectors. The ! uppermost complement, vertically, of detectors, should be a mini- mum of one foot above the general level of the top of the equipment.

8034. Unenc losed Structures.

(a) Detectors should be located in a manner similar to those for outdoor installations.

(b) Beneath solid floors or ceilings the detectors, except for the perimeter, may be installed under the rules for indoor installations.

(c) Installations beneath floors or ceilings which are not solid should be considered as outdoor installations.

8035. Indoor Installations.

(a) CEILING HEIGHTS. The ceiling height and nature of the ex- pected fire shall be given consideration in the selection and spacing of detectors. Where ceiling heights exceed 35 feet detectors should be so spaced that the area covered by each detector will not exceed 75 percent of the area normally covered.

(b) SPACING. Detector spacings shall not exceed the linear maximums indicated by tests of Underwriters' Laboratories, Inc., Underwriters' Laboratories of Canada, or Factory Mutual Engi-

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 48: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-46 WATER SPRAY FIXED SYSTEMS

neering Corporation for the particular device used. Closer spacing may be required due to structural characteristics of the protected area, possible drafts, or other conditions affecting detector op- eration.

(C) DISTANCE BETWEEN DETECTORS AND WALLS.

(1.) Where ceilings are level, the distance between the wall and the nearest detector shall not exceed one-half the distance allowed between detectors.

(2) With sloping ceilings, (slope more than 1~'~ inches per foot) the distance to the lowest detector shall not exceed two-thirds the distance allowed between detectors. Distance may be measured horizontally for both level and sloping ceilings.

(3) In areas requiring only a single row of detectors the dis- tance between the end detector and the end wall shall not exceed one-third the distance allowed between detectors.

8036. Two or More Systems, Where there are two or more systems in one area controlled by separate systems of fire detectors, those on each system shall be spaced at least up to the dividing line between systems, as to a wall or partition or draft stop.

8040. Arrangement and Supervision of Systems. 8041. Supervision. Central station, remote station, or pro-

prietary supervision of detection equipment may be required by the authority having jurisdiction.

NOTE: For the applicable standards, see N F P A 71, 72C and 72D.

8042. Electric Systems. Water spray systems which depend for operation on electric thermostats, relay circuits, or other similar equipment shall be so arranged that such equipment is normally energized, or completely supervised in a manner that will result in positive notifications of an abnormal condition unless failure of the detection system results in the operation of the water spray syste m .

8043. Pneumatic and Hydraulic Systems. Pneumatically and hydraulically operated systems shall be supervised in a manner such that failure will result in positive notification of the abnormal condition, unless the failure shall result in operation of the water spray system.

8050. Response Time. 8051. The heat detection system should be designed to cause

actuation of the special system water control valve within 20

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 49: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

AUTOMATIC DETECTION EQUIPMENT 15- -47

s e c o n d s u n d e r e x p e c t e d f i r e c o n d i t i o n s . U n d e r t e s t c o n d i t i o n s w h e n e x p o s e d to a s t a n d a r d h e a t s o u r c e , t h e s y s t e m s h o u l d o p e r a t e w i t h i n 4 0 s e c o n d s .

NOTE: (1) Some detection circuits m a y be deliberately desensitized in order to override unusua l ambien t conditions, In such cases the above response m a y be exceeded subject to the au thor i ty hav ing jurisdict ion. (2) Tes t ing of integrat ing tub ing systems m a y be related to this test by means of a s t anda rd pressure impulse test specified by the listing lab- oratory. (3) O n e me thod of testing hea t detection uses a r ad ian t hea t surface at a t empera tu re of 300 ° F. and a capaci ty of 350 watts at a dis tance of one but not more t h a n two inches f rom the nearest par t of the detector. Th i s me thod of testing wi th electric test set should not be used in haza rdous locations. O t h e r test methods m a y be employed but the results shall be related to the results obta ined unde r these conditions. [See 4043 (a) (2).]

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 50: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-48 WATER SPRAY FIXED SYSTEMS

A P P E N D I X

A-1033. Design Purposes. (a) Ex t ingu i shment of fire by water spray is accomFlished by cooling,

smother ing f rom s team produced, emulsif icat ion of some liquids, di lut ion in some cases, or a combina t ion of these factors.

(b) Control of fires is accomplished by an appl icat ion of water spray to the bu rn ing mater ia ls producing controlled burn ing . T h e principle of control m a y be appl ied where combust ib le mater ia ls are not susceptible to comple te ex- t i ngu i shmen t by water spray, or where comple te ex t ingu i shment is not con- sidered desirable.

(c) Effective exposure protect ion is accompl ished by appl icat ion of water sp ray directly to the exposed s t ructures or equ i pmen t to r emove or reduce the hea t t ransferred to t h e m f rom the exposing fire. W a t e r spray curta ins are less effective t h a n direct appl icat ion but may, u n d e r favorable condit ions, pro- vide some protect ion against fire exposure t h rough subdivision of fire areas. Unfavorab le condit ions m a y include such factors as windage, t he rma l updraf ts , and inadequa te drainage.

(d) Start of fire is prevented by the use of water sprays to dissolve, dilute, disperse, or cool f l ammable materials .

A-1044. Clearance to Live Electrical Apparatus. Possible design variations in the c learance required at h igher voltages are

evident on Tab le 1044(b) where a range of voltages is indicated opposite the var ious BIL test values in the h igh voltage por t ion of the Table .

z

Q se

g

/ o

/ /

. / /

j J

/

Al l ItOXl~A'r = t P i i

. / , I

I / / /

i . , "

/ I /

/ . . /

L 7 / - -

/

I t [ m ~ _ Estlrnate~ time [or volatile liquid contents of at-

mospheric storage tanks to reach I00 degrees Fahren- heit when absorbing heat at 20,O0O Btu per sq. ft. pe~ ;3our f rom a start ing temperature of 70 u F. for tank contents and 60" F. for tank steel.

mt ' ao )s ~ 4~ Ro mo

Fig. A - 4 0 4 3 ( b - 1 )

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 51: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

A P P E N D I X 1 5 - 4 9

IP

\ T I M E e IN M I N U T [ S

\

G~.L \ \ " ~ T'l lO 12)00< GLI.

I v r _~ o . ~ ~ . _ . ~ ~ ~.-~

~ = " ' ~ ' ~

~.~ ~ ~ -

-t - 0 • o c ~ O ~ . ~

:o='~ ~.~o

- - - - - - - - ~ m - -

I I I o ~' ~ ~ ~ ~ ~ I o ~

T I M E e IN M I N U T E S

z~,.ac~ i GAl.

\ \

\

Fig. A - 4 Q 4 3 ( b - 2 )

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 52: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15--50 WATER SPRAY FIXED SYSTEMS

Up to system voltages of 161 kv the design BIL kv and corresponding mini- mum clearances, phase to ground, have been established through long usage. At the higher voltages, the relationship between design BIL kv and the various system voltages has not been established in practice and is dependent upon several variables, so that the required clearance to ground should be based upon the design BIL used, rather than on the nominal line voltage or voltage to ground.

A - 4 0 4 3 ( b ) E x p o s u r e P r o t e c t i o n - - Vesse ls . It has been established that uninsulated vessels, under average plant con-

ditions, when enveloped with flame, may be expected to absorb heat at a rate of at least 20,000 B.T.U. per square foot per hour, of exposed surface wetted by the contents, Unwetted, uninsulated steel equipment absorbs heat rapidly, and failure occurs from overpressure and/or overheating when such equip- ment is exposed to fire. Figure A-4043(b-1) is a time-temperature curve show- ing the lengths of time required for vessels of different sizes containing volatile materials to have their contents heated to 100 ° F. from a starting temperature of 70 ° F. for tank contents and 60 ° F. for the tank steel. (See "Requirements for Relief of Overpressure in Vesssels Exposed to Fire", J. J. Duggan, C. H. Gilmour, P. F. Fisher; Transactions of the A.S.M.E., January, 1944, Pages 1-53; "Venting of Tanks Exposed to Fire", NFPA Quarterly, October, 1943; and Rubber Reserve Company Memorandum 89, "Heat Input to Vessels".)

The application of water spray to a vessel enveloped by fire will reduce the heat input rate to a value on the order of 6,000 B.T.U. per square foot per hour of exposed surface wetted by the contents when the unit rate of water ap- plication is 0.2 gallons per minute per square foot of exposed surface. The 6,000 B.T.U. rate was also established in Rubber Reserve Co. Memorandum 123, "Protection of Vessels Exposed to Fire". Figure A-4043(b-2) shows the esti- mated time for volatile liquid contents of atmospheric storage tanks to reach the boiling point when absorbing heat at 6,000 B.T.U. per hour per square foot. This may be compared with the figure shown in Figure A-4043(b-1) to show the benefits derived from water spray systems.

A - 4 0 6 0 . D r a i n a g e . As stated, there are four methods of drainage (1) grading, (2) diking, (3)

trenching, and (4) underground or enclosed drains, the application of which must be determined by the extent of the hazard and the degree of protection desired.

GRADING - - Where grading is employed a slope of not less than 1 percent should be provided. Concrete surfacing is most desirable. However, other hard surfacing or crushed rock is acceptable.

DIKING - - Where diking is employed dikes should be in accordance with the requirements of NFPA No. 30. Figure A-4060(1) is based on NFPA re- quirements and will serve to illustrate the necessary features of adequate diking.

TRENCmNG - - General specifications for drainage trench and recovery systems installation, which is a desirable drainage arrangement for storage and equipment areas, are as follows:

A. PURPOSE OF DRAINAGE TRENCH.

(a) To remove from the area and promptly and effectively dispose of all accidentally spilled liquids and water discharged from fixed spray systems and/or hose streams.

(b) To provide, by means of partial closure of trench top, a basin within which ignited flammable liquids may be safely consumed by controlled burning without seriously exposing adjacent equipment.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 53: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

A P P E N D I X 15-51

TYPI U I

f l ~ 5 I~t<~'L~"t'l!D .5'-O*M~I W~'~ TOP I-4~COMPACTBD wn'H ~,OD OR / ~ TO eE U~eD A~, | IND~R~, ¢ l k l D ~ : J RO,a3DV4AY" I=OR |

r-~-'-~T~oo~p~crE D - ~ ' - ' n I "~i:[

"- (~V14EN ~'-O~AT 'TOF) I

SECTION "A-A"

~ ~RllklffOeCE

• :. ~..: . : .~ " , ' : .o'. ~. ~: ; . . , ~ : . ' . , . , ; :.4".: , o . " . ~ " ~ . . . ' . . . : # , ' . : . ~ ' . : ~ :

.....;~.... ,.. : ~ . ' . . . . . . , . ~,:.~.~ • ; . . ; ~ . . . : ~ . . . , ; ~ : ~ , ' . . ' ~ ' : : ...-.

SECTION "C-C"

dl: C

i I r ~ ,~ l ¢ E . . ~ Ir'~'~

i l r m m m m a l - ~

ImL"~m I R l l BL '~

i i m t n l ~ l i ~

TABLE OF DIMENSIONS, S04L PR[SSUR[S AND CONCRETE QUANTITIES

Fig. A - 4 0 6 0 ( ! ) . Standard dikes for field storage tanks.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 54: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

1 5 - 5 2 WATER SPRAY FIXED SYSTEMS

(c) To act as a container for retention of accidentally spilled, unignited high value liquids for salvage purposes.

B. CONSTRUCTION OF DRAINAGE TRENCH. (a) Drainage trench should be constructed of reinforced concrete, except

that expanded blast furnace slag aggregate should be used in precast trench cover.

(b) The minimum size of any drainage trench should be 3 ft. wide and 1 ft. 6 in. deep. In no case should the depth exceed the width.

(c) Whether the closed portion of the trench top is precast or constructed of grating and steel plate, the open section should be equal to one-third the width of the trench, located centrally. Distance from either edge of the open area of the top to either inside wall should not be less than 12 inches. Open section should be covered with 1 ~ in. steel walkway grating.

(d) Sumps should be poured monolithically with trench. Watertight bonds should be provided for joining concrete tank pad to trench.

(e) Where piling is required in the construction of concrete pad it should also be used for support of trench and sump.

(f) Slope of trench floor to sump should be a minimum of one per cent.

C. DRAINAGE TRENCH CAPACITY REQUIREMENTS. (a) Flowing: (Surface area served by the trench).

1. 750 gpm per 2,400 sq. ft. - - drainage from fire hose discharge, plus 2. 1,500 gpm per 2,400 sq. ft. (maximum) - - drainage where fixed water

spray systems are installed, plus

3. Normal surface drainage.

(b) Holding: (Total trench volume). 1. Should be equal to the total capacity of largest vessel in the area,

served by the trench.

2. Holding capacity may be disregarded for water insoluble liquids where individual drains are provided to an interceptor where such insolubles may be separated and retained.

3. Where individual drains, separators, or interceptors are not used, shut- off valves should be provided for each trench system to prevent accidentally spilled materials from polluting public waterways.

D. TANK PADS AND CURBS. (a) Tank pads, ff used, should be constructed of concrete and sloped toward

trench with at least a two percent grade.

(b) Concrete curbs should be provided around the perimeter of the tank pad or process area and between groups served by a common trench, to confine accidental liquid spillages to their respective areas.

(c) Curbs should be formed in a concave manner to throw back sudden wash of flammable liquid from a large spill.

E. SEPARATORS AND INTERCEPTORS. Separators and interceptors should be designed to remove from drainage

systems water insoluble liquids which may be either reclaimed or destroyed. In any event, these materials which are usually flammable and/or toxic are thus prevented from entering public waterways. Separators should be installed in locations sufficiently remote from processing and storage areas to be beyond the range of fire exposure.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 55: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

APPENDIX 1 5 - 5 3

F. UNDERGROUND OR ENCLOSED DRAINS. The capacity of the system should be equivalent to required flowing ca-

pacities of the drainage trenches connected to it, plus any additional drains on the system, plus drainage for any anticipated future developments which may be required. All points of connection should be sealed (see detail of sump, Figure A-4060(2), to prevent propagation of flame through the drainage system. A skimming device is useful for removing objectionable materials from the water surface in the sump.

G. GENERAL. (See Figs. A-4060(2) and A-4060(3).) (a) Drainage trenches should be installed to serve to divide two rows of

tanks or equipment, one row on each side, so that run-off from any vessel will enter directly into trench without exposing adjacent vessels.

(b) Where holding capacity is not a factor, small quantities of water may be directed into trench continuously to keep it clean and to assure a positive seal in the sump at all times.

(c) The installation of piping in drainage trenches should be avoided. Where it is necessary for pipe to enter or leave a drainage trench, passage should be through the grating; if through walls, the openings should be vapor- tight.

(d) The drainage system and grating shall he kept clean and free of debris.

+,. , . . .

DRAINA61 T~ENCH ',WITH IwRICAIT ¢ONCJI['TIL AND STSr.k 6RATINO COVER

. , . , . + . ,.+

Oi~IAI~AGL TRENCH ~VITN &TEL l . PLATiL AND aNAT IN I I COVER

¢ l Ja l~

T RAPP |O QUl4p

r . -

3

Fig. A - 4 0 6 0 ( 2 ) . Drainage system details for tank areas containing f lammable liquids.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 56: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

. * ~PCT ION A 'A

9-

. . . . . . . . . . . . . . . . . . . . . . -~ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . r ~ _ _-*_, ._~_-_~_._._~_ . . . . . . . . . . .

PLAN OF TANK PAD d~

I I

, , . , ,, ,,

TRA~PeO "SUMP

WH ER. I S~PA~ATOFL OK INTERCtPTOK i~ NOT IN~TALLF -D .

C~

Ii

SUGS~TS~ O E S t ~ FO~ OR~tHA~t S ~ S T ~ FO~ T ~ a ~ ~ S c o m ' ~ , t m ~ m.A~M~.W-W, u Q u m s

Fig. A . 4 0 6 0 (3)

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 57: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

A P P E N D I X 15-55

N ° I

®

®

NOTE

PIPING AT ELEV IO-O'

SIMILAR TO THAT AT

ELEV. 2 0 " 0 ' j ¢~.o'"

Fig. A-7O90.a. Drawing of Water Spray System Used for Sample Calculat ion shown in Figs. A-7090.b. and A-7090.c.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 58: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15-56 WATER SPRAY FIXED SYSTEMS

A-7090. Sample Calculations. Figure A - 7 0 9 0 ( a ) shows a hypothetical water spray system layout. Figure

A-7090(b) shows a sample calculation for this system using pipe sizing and noz- zles with constants such that the velocity pressures generally exceed 5 percent of the total pressures, and the designer elected to include velocity pressures. Figure A-7090(c) shows a sample calculation for this system, using pipe sizing and nozzles with constants such that velocity pressures are less than 5 percent of the total pressures, and the velocity pressures were not included in the cal- culation.

FOR

HYDRAULIC CALCULATIONS

[ N ~ S , ~ O~o~A~t e.O~

Ne~tle F~ w i Pipe r. P*'e Equiv. Fr,¢t.e. ] ~r'$sure Ner..l CQcat;o~ G* P, M. p.~ I Lesttk ~ e~*4t SummsrY Pr~ure

~ . ~ w ) 0 ~ 4 ~ . ~ . . ~ - ~ . - ~ L G T H 0 ~ PT 20.0 :T

(~ Q 40.Z ~ TOT. ~,S ~F I .~

_ _ _ _ E ® 4o.z I T~. ,o.o ,, 4.~ , ,

t - N ~ 0 ~ ~0 b ~ c~t . . ~ 0 ~T ~S.e , t ZS

T : 8 . 0 L G T N ~ , O ~ T ~ O 0 ~t ~O 0

_ _ ~ . s.o .SO ~ o~ ~v

_ _ L ~ T K . 4.0 ~T 4 0 . Z ~t

(~ ~ 4Ze ~i Z~/Z TOT, f.O PF ~ ~ ~N

- - _ _ F I G , "/.0 , ~ 0 P E ~ ~ V ~ ) O g l~ G ~ TOT J~,O PF 4 B =N

- - _ _ c G t w , , O , O e t ' t . ~ . ~ ~x q" _ _ F T ~ - " . 40 ~E T.~ "v

~ r - ~ L ~ ¶ ~ 0 ' 0 )~IV:IO.O FTG. ~ 1 0 . 0 S 4 ~E ~..~_~_.~PV

_ _ C G T N . _ _ P T _ ( L ? ~ P T ~ ¶ ' ~ " _ _ F T G . _ _ P E - - = V

_ _ L G I N , _ _ P t _ _ PT - - ¶ - - _ _ F T G . _ _ P E _ _ P¥

q TeT. PF ~N _ _ L G T H . _ _ P t _ _ ~t

- - ¶ - - STG. P [ _ _ ~v q TOT, ~r ~

_ _ L G T N . - - P T - - P T

q TgT. PW

~ J ] FTG, 1 P ( J ~ V q TOT PF ~w

- - L G T H - - P T _ _ ~ 1

~ q ~ j FT~ l i P f J =V q TOT. PF ~N

TOT, PF ~N _ _ _ L G T H . _ _ P t _ _ P T

Q TOT. Pr PN

BY J. E Q

OAT[ ~Z " } - ~8

JOBNO. I~7~

t~zl,ev. NOTES

? .10 ' : ~,0

40 Z

(or K~ Q.l.s,S~ <~>

43, S

40 ? 20,0' c1~" ~O.G "J%~-~ • 180

S4 ? M-,S Cl I : ~)O,~nl'~l :

4.8 ~88 3"1 "l

SSb tO.o' % :8&.6 ~ = G40.

o . s '

Y ~ o ~ y ~ u N t ~

Fig. A - 7 0 9 0 . b . Ca lcu la t ion of Sys tem s h o w n in Fig. A - 7 0 9 0 . a . w i t h V e l o c i t y Pressure Inc luded .

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 59: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

A P P E N D I X 15-57

H Y D R A U L I C C A L C U L A T I O M $

F O R ~,~,,d,.w, ~ou~ , , o~ ['~u. A,- ' lo ' )0- , , ~ ( T # O . ~ O ~ ~-

Au N0~,~l,~ Tvoc N~O s~ ~. E. C.

~0s No. IS7

..... F,.. I e~,, E ~,. r , t ~ . Idlest, & Im ~ I _~°J~_~ S~mwl* P•

. _ L : . m L I , * . ~ . .o . , , . . _ ~ _ , , z , . , , , , o . z ~ , 6 . _...I,L .4-7 e(~-~._-- pv I(l" . 6 . ~ f f Q 4G t I t iT. 7.S P f 3 . $ Pu _ _ . S T N . ~ PV ~ PT

O rer_ Pr Pu - - , G T H * _ _ PT _ _ PT

T I ~ rill. ~ P( _ _ Pv q roy. f ' ; Plo

1 4 0 . 2 - - LllrN. ~.O_ .4"~ n.plr ~ Pr ~-i.e"

1 3._~.i_. ~ .ova. ~.s p'r ~ ev tt.',- r:c,. I . .0 . 4 - 4 - P t _ _ ~ _ _ Pv. I . O

(8") q 79 .8 IY4 w r . ~ pF ~.3 e , t~.o, LGTll. I.O Pr "/-4.7 Pr t-N~o 1 . 3 x L , t . m.o . ~ pt _ . . Q , ~ pv. I < • , ~14'T~'-,~: ~ . ~

q IS'~.(. Z roT. ~ pF ;.~ PN k G T N . _ _ PT ~ PT tO.Q '

Pa

~,ON[$, t~tfl L t V I L - - k t T H . - - PT _ _ PT q - - _ _ t i t . _ _ p ( _ _ PV Q rOT. e l e PN

; * T a . . _ . L . Pv ~ pv ~ . , . . c . 1 ~ r l G . 15 . 4 " 0 p | 8.0 Pv K t w ~ a: O~,O Q ~lGh~ I ~ rOT. 20 pr $G.S PN

_ _ , G I N . _ _ PT ~ PT I - - ~ ~tS. Pit ~ Pv q rOT. Pf PN

L G T N . ~ PT _ _ PT I - - ~ r iG. P [ ~ Pv q ro'r. , pf PN

kGTN PT ~ PT

elf P~ ~ G T N . ~ PT ~ PT

- - ¶ - - ~ r iG. ~ iP( PV q ~QT, PF PN

~ G T N . ~ PT ~ PT

q roT. is, ;e,, GTN PT ~ PT

q re'r. r F Pq . S I ' N . ~ PT ~ PV

- - ~ - - ~ : I L P ¢ _ _ P v q rgv. ('r e,,

~ G T N . ~ PT ~ PT - - ~ - $15 - - P ( ~ Pv . .

Q ~ ' r , T " , , Pu

F i g . A - T O 9 0 . b , C o n t i n u e d

N o t e s f o r F i g u r e A - 7 0 9 0 . b .

The velocity pressure Pv is determined by trial. It is necessary to estimate the flow Q in the pipe on the ups t ream side of the nozzle to determine a trial Pv which is used to determine a trial Pn, a trial q, and a trial Q. After determining the trial Q use this value to determine a new Pv. If the new Pv is approximately equal to the trial Pv consider the trial Q to be the actual Q and proceed with the calculations. I f the new Pv does not check with the trial Pv estimate Q again and proceed with successive corrections until an actual Pv is obtained that checks with a trial Pv.

The flow from nozzles may be obtained from discharge curves rather than

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 60: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

1 ~ - 5 8 WATER SPRAY FIXED SYSTEMS

individual calculations at the preference of the calculator. Similarly, flow characteristics of lines or sections of systems may be obtained by plotting results on charts made up to nZ.S~ or n~ rather than by calculating constants (K - - values).

Figure No. A - 7 0 9 0 . c . shows a sample ca lcu la t ion for the system shown in Figure No. A-7090.a. using pipe sizing and nozzles with constants such that velocity pressgres are less than 5 percent of the total pressures, and the velocity pressures were not included in the calculation.

HYDRAULIC CALCULATIONS

( N o ~ l ~ - "~ISC6ARG~. ~ O ~ l " t b O ~ DATE I t - 3 " 6 8

JOSNo 151Z.

Le,,~th p ~1 /Fool S u m m m r r P , tssure E l e v Lo=atJo, G P.M.

I - N S O 13.4 ~ .GTH__Sg~_O_J PT 9 = 0 . ~ ] PT ?-[*0' 91=~.00N~'6~- ~ r1G , 0 ~ P E _ _ P v

r5.4 PN

__ Z£ ; 4. 0 .~TH _ ~ PT 20.3 ~T

L~ I~ ¢ ] rOT IO 0 pc 0.~ PN

( ~ [q Z~,.9 t l /4 r0T ~ 0 or 0,S P. S ~ > f o . K~ C * i , s

~ i _ _ rTG ~ .0~ P E p P y 13.G

q ~ _ _ IVz ro'r IO.O pr o,~ ~'. Pt 29_ 0 .GTH. S,O PT

TOT, IO 0 PF 0G PN

- - :TG -- , ~ 7 P E P P Y ( ~ q L~] . l Z I /z rot ~ - P; 0.3 P~ K ~ , I t ~ .

~ E : 1 0 .GTH_ <~ 0 pT 9-~3 PT 91 : I1. ' / td-~E. ~ : s~,. S ~ 5 5f$$ _ _ FTG, 3 0 . 0 ~ P E p P y

( ~ O t93~, ~ tOT ~ P~ 0,~ P. - - - - LGTB [0 0 PT ~L3.~ PT

_ _ F T G ~ .OS pE 4 3 P v q {~3.G ~ xe% t~ 0 P~ O S PN

~4~ N~0 9 ~ l l . 0 D~I Y : 100 FT G ~ . 0 0 7 pE ~1 pv ( '~ Q 4 0 4 4 G ~v . : 3 .o t o t {,00 P~ 04- ,~N K9 CAle.-~

- - LGT~ - - PT ~ L ~ P T O,S' 9 - - Fr~ P( i ~v

~J Cl 404 G / - - ~o~ - - P~ 'N - - L G Z H _ PT _ _ PT Note. %~t F i l , ~,-7090"d

- - ~ - - FTG ' PE _ _ PV ( a t W i t e . t ~ V P P l Y q TOt Pr ~

- - LGTH - - PT _ _ =t

q TOT Pr DN

- - LGTH _ _ PT - - ~T - - 9 - - r t ¢ P( _ _ ~v

q TOT PF ='w - - L G T H , _ _ PT _ _ P t

q TOT PF )N - - LQTH - - P T - PT _ _ rTG, - - Pi _ _ =v

q TOt PF ;~N

- - LGTH _ _ PT - - ~T

q TOT, ) F :~N

~ FTG, P[ Pv TOt P r P .

Fig, A - 7 0 9 0 . ¢ . Cnlcu lut ion of Sys tem s h o w n in Fig. A - 7 0 9 0 . o . w i f h V e l o , ' i t y Pressure not Inc luded .

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 61: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

APPENDIX 15- -59

H Y D R A U L I C C A L C U L A T I O N S

SHEET N0. ~ . . ~0F z-

OAE { Z - 3 - & 8

JOe NO, I$7 ~-

Fr;¢t;*. Noxzle Flow Pipe F; Pipe Equiv. Pressure Normel

......... ,,,, g;:':." :'41 .... Lecafion G, P. M, L h p.|, i . / feot Svmml ry Peesture

~ 15.4- E=z.0 L~T. 6,5 PT f-O.I 'T

- - LGTH _ _ PT ~ )T FTG ~ - - )V - - - - _ _ _ _ E TaT =r ~U

- - LGTH.__ PT _ ~t

T q - - FTG. Pz _ _ ' v q TOT PF ~N

LGTH ~ -0 PT ~ ~T _ L ~ _ 1134 _ _ F T ~ . - - - ,0(~ PIE ~ Pv

Q 4 ~ 4 - I TOT, Z.0 Pr 0 z , .

~ " - - FTG /o ,0 . O(P PE ~ " )V 2(~.e [J/4 TQT. "] , ~ - - -~ - - p~" O,S :*:~

LGTN I ,O p t ~__L~ t

q S'~ S Z TO* II o Pr O J ~. _ _ ;£GTH _ _ PT ~.1 . ~ PT

- - I ' - - :FTG, P t - - F~V g TOT. PF PH

L~m~K PiPe L~VgL LGTH,__ PT _ _ Px - ~ 1 , - - _ _ FTG _ _ P£ - - Pv

_ q 'ro~. PF PN

I ¢ - N 50 'I ~ L~,T. S 0 P t ~ PT - - - - - - E r r ; , I S . O . O S P [ - ' - Pv

q 193.(p ~ roT, 2.0.0 p r 1 .0 PN - - . G T M , _ _ P T ~ PT

- - 1 - - - - : t 6 , - - PiE - - Pv q rOT. P r PN

rOT. Or PN _ _ ,GTH _ _ PT - - PT

- - I - - _ _ :TG, _ _ p ~ _ _ Pv q rOT. p r PN

- - - - p ~ _ _

q rOT Pr P~ - - .GTH ,_ PT PT

- - I - - _ _ : T O - - P ~ _ Pv q ro t Pe P .

- - . G T H . - - P T _ _ PT - - q - - _ _ : T 6 . _ _ P [ _ _ PV

rOT. PF PN - - .GTH _ _ _ P~ _ _ PT

- - q - - _ _ : r ; _ _ P ( _ _ Pv q rOT. P r PN

- - .GTH,__ PT _ _ _ P1 - - q - - _ _ : t ~ , _ _ P [ _ _ Pv

q rOT. P r P .

F i g . A - 7 0 9 0 . c . C o n t i n u e d

Nezzle NOTES EI ,v

K - - ~/~ - z . e s

~(. S ~ . 8 , 1 1 . 7 - ~ , ~ , ~

K9 = ~ = 30L$

Note for F i g u r e A-7090.e . T h e flow f rom nozzles m a y be obta ined f rom discharge curves ra ther t h a n

indiv idual calculat ions at the preference of the calculator. Similarly, flow characteris t ics of lines or sections of systems m a y be obta ined by plott ing results on char ts m a d e up to nt.s5 or ns r a the r t h a n by calculat ing cons tants (K - - values) .

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 62: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

15--~0 WATER SPRAY FIXED SYSTEMS

t.9

¢/)

I

W

W

12o

41o

IOO

9 0

80- ,0

TO-

60-

50-

40-

30-

10-

0

Q 1.85 F L O W - C, P M

Fig. A -7090 .d . Sample Graph Sheet

Graphic summary of hydraulic calculations shown in Figure A-7090.c., and assuming 250 gpm outside hydrant flow requirements and 4.0 psi underground friction loss.

System requirements = 404.6 gpm at 33.21 psi

Hose Stream requirements = 250 gpm; additional 4.0 psi required

TOTAL WATER REQUIREMENTS = 654.6 gpm at 37.21 psi Pe = 8.8 psi

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 63: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 64: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

National Fire Protection Association International

60 Batterymarch Street, Boston, Mass. 02110

The National Fire Protection Association was organized in 1896 to promote the science and improve the methods of fire protection. Anyone interested may become an Associate Member; the annual dues are 830.00. National and regional societies and associations are eligible to be Organiza- tion Members; annual dues are $225. Full nlembership information is available on request.

This is one of a large number of publications on fire safety issued by the Association. All NFPA codes, standards, and reeolnmended practices are prepared by XFPA Technical Committees and adopted at an Annual Meeting of the Association. They are intended to prescribe reasonable measures for minimizing losses of life and property by fire.

This and other NFPA codes, standards, and recommended practices are published in the Nat iona l Fire Codes, a ten-volume compilation of NFPA's official technical material. Following are the titles of the ten- volume set:

Vol. 1

Vol. 2

Vol. 3

Vol. 4

Vol. 5

Vol. 6

Vol. 7

Voh S

Vol. 9

Vol. 10

Write

Flammable Liquids

Gases, Ovens and Boiler-Furnaces

Combustible Solids, Dusts and Explosives

Building Construction and Facilities

Electrical

Sprinklers, Fire Pumps and Water Tanks

Alarm and Special Extinguishing Systems

Portable and Manual Fire Control Equipment

Occupancy Standards and Process Hazards

Transportation

the Association for full information.

Discount Prices on this P a m p h l e t

The following schedule of discount prices for multiple copies of this pamphlet have been established:

1 to 4 copies: Unit price 25 copies and over: 25~ 5 copies and over: 15~ 50 copies and over: 30~

10 copies and over: 20% 75 copies and over: 35~ 100 and over: Special quote

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 65: WATER SPRAY FIXED SYSTEMS handbook/NFPA 15 1969.pdfNFPA No. 15 WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION 1969 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only

TYPICAL POCKET EDITIONS OF NFPA STANDARDS List revised as of June. i969. Most of these standards also appear, with identical text, in the National Fire Codes, republished annually. Titles are abbreviated. For complete list of publications wr i t e NFPA.

2M Model Legislation '57 . . . . 50 4h Fire Dept. Organization '69 . .75 48 Fire Dept. Management '68 . 2.50 6 Industrial Loss Prevent. '67 . .50 7 Controlling Fire Emerg. ' 67 . . .50 8 Gen. Management Responsibility

' 67 . . . . . . . . . . SO

t0 Extinguishers, Instal. '69 . . 1.00 iDA Extinguishers, Maint. '69 . . 1.00 IOL Model Enabling Act '69 . . .SO 11 Foam Ext. Systems '69 . . . 1.75 12 Carbon Dioxide Systems '68 . 1.50 13 Sprinkler Systems '69 . . . 2.00 13A Sprinkler Maintenance '69 . .75 13E Sorinklered Pron. F.D.

Ooerations at '66 . . . . 60 14 Standpipe, Hose Systems '69 . .75 15 Water Spray Fixed Systems

'69 . . . . . . . . 1.25 16 Foam-Water Systems '68 . . 1.00 17 Dry Chem. Ext. Systems '69 . .75 18 Wetting Agencs '66 . . . . . 50 182M Vaporizing Liouid '65 . . .40 19 Fire Apparatus Soecs. ' 69 . . 1.50 ]91 Portable Pump. Units ~59 . . .35 193 Ladders. Ground-Aerial '59 . .50 194 Hose Coupling Threads '68 . .75 196 Fire Hose "69 . . . . . 50 197 Init ial Fire Attack '66 . . .50 198 Fire Rose, Care of '69 . . . 1.00

20 Centrifugal Fire Pumps ' 69 . 2.00 21 Steam Fire Pump Ma[nt. '63 . .60 22 Water Tanks ' 67 . . . . . 1.50 24 Outside Protection '69 . . . 1.00 25 Rural Water Systems ' 69 . . .75 26 Suoervision Valves '58 . . . . 40 27 Private Fire Brigades '67 . . .50 292M Water Charges, Private '61 . .40 295 Forest Fire Control "65 . . .75

30 Flare, Liquids Code "69 . 1,00 31 Oil Burning Equipment '68 . 1.25 32 Dry Cleaning Plants '64 . . .60 321 Class. Flam. Liquids '69 . . .50 325A Flashooint Index of Trade

~/ame Liouids '68 . . . 2.50 325M Prop. Flare. Liquids ' 69 . 3.00 326 Warning Labels "Sf . . . . 25 327 Cleaning Small Tanks '64 . . .50 328 Manholes, Sewers, Flare

Liquids and Gases in '64 . . ,50 329 Leakage, Underground

Flam. Liquid Tanks "65 , .50 33 Spray Finishing '69 . . . 1.25 34 DIp Tanks ' 66 . . . . . . . 50 35 Mfg. Organic Coatings '64 . . . . 60 36 Solvent Extraction '67 . . . . 60 37 Combustion Engines '67 . . .50 385 Tank Vehicles %6 . . .60 393 Gasoline 8low Torches '69 .50 395 Farm Storage Flare. Lio, '65 .40

40 Motion Picture Film '67 . .60 41L. Model Rocketry Code '68 . .50 42 Pyroxylin Plastic Factories ~67 .60 • 3 Pyroxylin Warehouses "67 . .40 46 Timber, Outdoor Storage '61 . .SO 46A Wood Chips, Storage "65 .40 47 Lumber Storage Yards '61 . . ,50 48 Magnesium r67 . . . . . . 60 481 Titanium '61 . . . . . . . 60 482M Zirconium '61 . . . . . 50 49 Hazardous Chem. Data '69 . . 2.50 490 Ammonium Nitrate '69 . . .75

491M Chem. Reactions ' 6 8 . . . 2.50 492 Ammon. Nitrate, Sep. Dist. '68 30 493 Process ControY Equip. '69 . .75 494L State Fireworks Law '64 . ,40 495 Explosives, Stge., Use ~69 . 1.25 496 Purged Enclosures '67 . . . . 50

5OA Gaseous Hydrogen Syst. '69 . .50 51 Welding and Cutting '69 . . .75 5OB LH-Syst,, Consumer Sites '68 ,SO S] 8 Welding Processes ' 62 . . . . 40 54 Gas Appliances, Piping ' 69 . . 1.25 5dA Indus*=. Gas Piping '69 . . 1.00 56 Flare. Anesthetics Code '68 : 1.25 56B Inhalation Therapy '68 . .75 56C ffosoital Laboratories '69 . . .75 565 Nonffam. Med. Gases ~67 . . .50 566 Bulk Oxygen Systems ' 65 . . 50 57 Fumigation '68 . . . . . 75 58 LP-Gas Storage, Use '69 . . 1.25 59 LP-Gas, Ut i l i ty Plants '68 . 1.25 59A LN-Gas, Ut i l i ty Plants ' 67 .60

60 Pulverizod Fuel Systs. "61 .60 61A Starch Factories "62 . .50 61B Terminal Elevators "59 .SO 61C Flour and Feed Mil ls '62 .60 62 Sugar anu Cocoa '67 . . .50 63 Explosions Indus. Plants "64 .50 64 Country Grain Elevators '59 .40 65 Aluminum Processing '63 . .50 651 Aluminum Powder '67 . . .50 652 Magnesium Powder '68 . .50 653 Coal Preparation Plants ' 59 .50 654 Plastics, Expl. Prevent. '63 .75 655 Sulfur Fires '68 " .75 656 Spice Grinding Plants "59 . . .40 657 Confectionery Plants '67 . . .50 66 Pneumatic Conveying '64 . . .60 664 Woodworking, Wood Flour '62 .60 68 Explosion Venting '54 . . . . 75 69 Inerting for Fire Prey. ' 56 . . .50

70 Natq Electrlcal Code "68 . . 2.00 70A Dwelling Electrical Code '69 1.75 71 Central Station Sig. ' 69 . . 1.00 72A Local Protective Syst. ~67 . .60 72B Auxil iary SIg. Syst. '67 . .60 72C Remote Station System ' 67 . .60 72D Proprietary 5ig. Syst. '67 . .60 73 MuniciPal Alarm Syst. '67 .60 74 Household Warning Syst. ' 67 ~ .50 75 Electronic Computer Syst, '68 . .75 76 Hosoital Elec. Systems ' 67 . .50 77 Static Electricity ' 66 . . . I .O0 78 Lightning Prot. Code '68 . . 1.25 79 Electrical Metalworking

Machine Tools '69 . . . . 1 . 0 0

80 Fire Doors~ Windows '60 . . 1.50 81 Fur Storagej Cleaning ' 69 . . . . 75 82 Incinerators, Rubbish ' 69 . . .75

85 Watertuhe Boiler-Furnaces '67 .75 85B Gas Fired Multi ale Burner

Boiler-Furnaces '69 . . . ] . 0 0 85D Fuel Oil-Fired MuItiple

Burner Belier-Furnaces ~69 . 1.25 86A Ovens and Furnaces ' 69 . . 2.00 87 Piers and Wharves "68 . . . . 75 88 Garages '68 . . . . . . . 75 BgM Heat Equip. Clearances '68 .50

9OA Ai r Conditioning Syst. ' 69 . .75 gOB Residence Warm A i r Heating .75 9 1 3lower and Exhaust Syst. ' 6 1 . .SO

96 VaPor Removal Cooking Equip- ment "69 . . . . . . . 50

97M Glossary, Heating Terms '68 .50

101 Life Safety Code ' 67 . 1.50 102 Tents, Grandstands, Air-

Supported Structures t67 . . .60

204 Smoke, Heat Venting '68 .50 206M Building Areas . /65 . . . .40 211 Chimneys, Venting SysL~ " 69 . ] . 00 2]4 Water Cooling Towers '68 . .75 220 Std, Types Bldg. Const. '61 .40 224 Homes Forest Areas '69 .75 231 indoor General Storage ' 65 . .50 231A Outdoor Gen'l. Storage '65 . ,40 23] B Cellular Rubber, Storage "68 .75 232 Protection of Records '67 1.00 24! Bldg. Constr. Operation ~d8 . .50 251 Fire Tests Bldg. Matl. ' 69 .75 252 Fire Tests Door Assem. '69 .50 255 Flamespread Tests '69 . .50 256 Tests Roof Coverings ~64 . . .50

302 Motor Craft '68 . . . ." . 1.25 303 Marinas and Boatyards ' 69 . 1.00 306 Gas Hazards on Vessels ' 69 . .75 307 Marine Terminals ' 67 . . .60 312 Vessels, Constr.-Repair '68 . .SO

402 Aircraft Rescue Proced. "69 2 .00 403 Aircraft Rescue Services ' 69 . 1.25 406M Handling Crash Fires ' 68 . 1.00 407 Aircraft Fuel Servicing '68 3 3 0 dO0 Aircraft Extinguishers '65 30 409 Aircraft Hangars ' 69 . . . 1 .25 410A Elec. Syst. Mainf. '68 . . 30 4108 Oxygen Syst. Maiot. "66 . .50 410C Fuel Syst. Maint. '68 . 1.00 410D Aircraf t Painting "66 . . .50 410E Aircraft Welding '64 . . .40 41OF Aircraft Cabin Clean. '64 . .40 411 Aircraft Ramp Hazard ' 65 ,50 412 Testing, Foam Vehicles ~69 . .75 414 Rescue Vehicles ' 69 , . 2.00 415 Fueling Ramp Drainage '66 . .50 416 Airport Terminals '67 . . . . . 50 417 Loading Walkways '68 . . . . 50 418 Roof-Top Heliports ' 68 . . .50 419 Airport Water Systems ~69 . .75

50]A Trailer Courts '64 , . . 30 501B Mobile Homes '68 . . . 2.00 505 Power Industrial Trucks '69 . ,75 512 Truck Fire Protection "55 , .25 513 Motor Freight Terminals ~59 : ~40

601 Guard Service '68 . . . . . 50 601A Guard Operations "68 . . 30 602 Community Dumps '64 . , , " .50 604 Salvaging Operations ' 64 . . . . 50

701 Fire Tests~ Textiles, Films ' 69 . . . . . . . . . 75

702 Wearing Apparel ' 6 8 , . , .75 703 Fire Retardants Bldg. M a r l . . .40 704M Identification of Materials . .75

801 Radioactive Marl. Labs. '55 . .50 802 Nuclear Reactors '60 . . . . 75

901 Fire Reporting System ' 69 . 3 .00 910 Library Collections ' 69 . . .75 911 Museum Collections '69 . . .75