Web-based Power Quality Monitoring System of Smart Transformer Substation RTP-34 MPEI for engineering education.
Real-time PQ analysis, based on remote laboratory data.
Live broadcast of monitoring.
Moscow. Russia.
P1
Currently in the field of traditional electricity there are significant changes. These changes include the active use of power electronics, IT-technologies, increased attention to energy saving, development of approaches to create a "smart grid», the integration of the traditional system of power supply of renewable energy and more. There is a mutual penetration of new concepts in energy, information and telecommunication technologies. It is planned to create the next generation of energy systems - intelligent power networks.
P2
Intellectualization of electricity poses problems:• Creating a "smart" instrumentation and devices for substations, providing accounting and energy management in conjunction with non-stop monitoring and control of quality of electric power in stationary and transient conditions.• Develop principles for the organization of intelligent distribution transformer substations of 10 / 0.4 kV.• Formation of the concept and testing of fragments of intellectual energy in the form of Micro Smart Grid on the basis of individual power grid structures, located in a small area around MPEI.• Implementation of the Smart Grid concept in the educational process.
P3
At MPEI over the past 15 years are working in the direction of energy saving and efficiency of electric power through the introduction of elements of intellectual energy at the facilities of Moscow. We transferred this research experience in electrical engineering education.
P4
Sources of power quality deterioration became institutions, homes, schools, hospitals, etc., mainly because of controlled single-phase rectifiers: compact fluorescent and LED lamps, servers, office equipment, household appliances, switching power supplies installed in the TV , computers etc.
The increase of non-linear loads since 1960
Private sector
Commercialsector
Industry
Low Voltage (0,4 кV)
Low Voltage (0,4 кV)
Medium voltage
(3-10кV)
37 % 36% 27%
Structure of energy consumption in USA
IEEE Power&Energy, volume 10, number 3, May/June 2012
Features of modern electricity.
It can be argued that the current nonsinusoidality in modern low voltage is mainly determined by the imperfection of the secondary power supply for the equipment.
P5
90 %
IEEE Power&Energy, volume 10, number 3, May/June 2012
The level of losses in the transmission and distribution of energy in the United States from 1926 to 2007. Reducing losses by 1% every 10 years
Trends in production of electric energy.
Losses on the transmission and distribution of energy in the United States account for about 7% (in Russia, according to unconfirmed reports up to 17%).
Reducing the rate of growth of production of EE.
The annual increase in production (%)
1949 – 1973 8,3 %
1973 – 2006 2,5 %
2010 – 2030 0,9 %
Development of standards use DC in the residential sector.
The basis is a well-known fact that there are additional losses in consumer electronic devices.
Losses: AC/DC – 17-35% PV/AC – 23-28%
DC in the Home
Programm «Smart Grid»:
One of the main benefits of Smart Grid is to ensure control of the consumption of EE in online mode by means of access to the real information from the supplier EE and the opportunity to receive information on energy consumption in real time (mode "dynamic tariff», “dynamic pricing”, “penalties”).
Dynamic Pricing
ELECTROSAVINGS
P6
The modern 0.4 kV power supply network is overloaded by harmonics
Single-phase rectifiers Variable Frequency Drive Phase control (dimmers)
Typical modern currents
As a result, in four-wires network with the equality of the phase currents ("load balancing") there are
extremely large currents in neutral wire.
P7
Sources of power quality deterioration become institutions, homes, schools,
hospitals, etc., due to the non-linear loads (mostly single-phase controlled rectifiers) switching power supplies installed in the
TV, computers, servers, compact fluorescent and LED lamps , office
equipment and household appliances.
P8
After Fourier analyse nonsinusoidal load current i(t) is represented as the sum of currents 1,3,5,7,9 ... harmonics.
Despite the absence of reactive elements in the circuit between the first harmonic of the current i1 (t) and the voltage u (t) phase shift occurs.
The shift can be a leading (capacitive), zero (resistive) or lagging (inductive) depending on “On-Off” moments of switching key S.
As example, the compact fluorescent lamps and LED lamps the first harmonic current leads first harmonic voltage.
In the dimming devices (thyristor) light control first harmonic of current lags behind the first harmonic of voltage.
In mentioned cases in three-phase system neutral current contains 3 times harmonics and may exceed the phase current 1.5-2 times.
load 1st harmonic Modeling results
Simulation of power quality events with 3phase simmetrical non-linear loadThe emergence of higher harmonics at the phase control.
P9
The neutral currents in three-phase network with the single-phase non-linear loads.
Irms=101,67AI1 =86A / 31o
THD=63%3 harm: 52 / -93o
5 harm : 18 / 79o
7 harm: 18 / -101o
9 harm: 11 / 72o
Kfactor = 4,74PF = 0,73Cos(fi) = 0,86
U(t)
Irms=101,67AI1 =86A / -31o
THD=63%3 harm : 52 / 93o
5 harm : 18 / -79o
7 harm : 18 / 101o
9 harm : 11 / -72o
Kfactor = 4,74PF = 0,73Cos(fi) = 0,86
Irms=100,03AI1 =69A / 0o
THD=100,76%3 harm: 80 / 180o
5 harm: 46 / 0o
7 harm: 12 / 180o
9 harm: 13 / 180o
Kfactor = 6,89PF = 0,69Cos(fi) = 1
i(t)
U1(t) Neutral current RMS=144A
Neutral current RMS=144A
Neutral current RMS=173A
i(t)
U(t)
U(t)
i(t)
U1(t)
U1(t)
I1(t)
I1(t)
I1(t)
PF = P / S = ( I1 / I ) * cos(φ1)
Modeling results
P10
Standard USA ANSI/IEEE C57.110Non-sinusoidal loads. Additional transformer losses.
K1 – heating loadК4 – UPS with built-in filterК13 – UPS without filterК20 – variable frequency driveК30 – laboratory equipment
P11
"Smart" meter - power quality controller "MAGISTR-430 PQ.“Primary aggregation interval = 10T (200 ms). The device provides continuous monitoring of the main task - get the Online Power Quality Parameters (OPQP). “Online parameters“ means 3 seconds aggregation intervals.
Voltages measuring:The limits of the basic reduced (the nominal value of the phase voltage) error ± 0,1%
Currents measuring:The limits of the basic reduced (to the nominal value of the phase current) error ± 0,1%
Satisfies the Standard IEC 61000-4-30.
P12
Online Power Quality Parameters (OPQP) – the base of real-time monitoring. www.magistr.tv/demo
Online Parameters appropriate aggregation interval 3 seconds in accordance with IEC 61000-4-30.
P13
Online Power Quality Parameters table (OPQP table)
L1 - Column with parameters of phase AL2 - Column with parameters of phase BL3 - Column with parameters of phase CAvg/Sum - Column with sum or avg value
Old version New version
P14
Calculator the contribution of the harmonic components of current.
Special calculator of the contribution of the harmonic components is designed to calculate the effective values of the currents in the phase and neutral conductors, the effective value of the harmonic current and harmonic distortion factor Ki (THDi). Source data for calculating values are 1,3,5,7,9 harmonics for each phase.Source data may be entered manually into the cells or copied from real-time data corresponding controller quality.The calculator may include one, two or three buttons of the data request. If the calculator is attached to a single controller, copying of the source data occurs when you press the [Request] button. If the computer is attached to two or three controllers, copying of the source data occurs when you press [1], [2] or [3] button (the numbers correspond to the number keys on the table OPQP on web-map).Pressing the [Calculate] button, the computation of the required phase currents and the neutral conductor and the coefficients is made.
Note: Calculated parameters are evaluated taking into account the 1,3,5,7,9 harmonics (in OPQP table they are calculated taking into account all the harmonics up to the 50th).
Initial state Final stateSource data state
P15
WEB-BASED POWER QUALITY MONITORING SYSTEM (WPQMS)
The aim of non-stop monitoring is information about electrical parameters of power supply basic elements. Measuring system consists of decentralized synchronized to external time standard measurement tools with remote access via the Internet to Web-technologies.
WPQMS is intelligent monitoring system
WPQMS provides technical capabilities for the analysis of voltage and current load. For these purposes the harmonic contributions calculator (Fig.6) which makes it possible not only to determine harmonic components and the currents on the neutral conductor, but also to quantify the increase of the cable losses and copper losses in the power transformer. This allows us to estimate (and provide) ELECTROSAVINGS using filters or power supplies with built-in power factor corrector.
WPQMS supports various data protocols: CAN, SNMP, ModBus, LonWork etc. In addition the system can be integrated into various devices having a data interface (energy meters, panel meters, PLC controllers, UPS units air-conditioning systems, diesel generator, etc.), which provides:• View the measured OPQP in the form of graphs, waveforms, spectra; preservation of information in graphic and text files; counting the number of voltage sags, surges and voltage pulses;• control standard and emergency events, which are displayed on a special screen forms single-line structural schemes using animation and color changes;• viewing parameters measured in real time, including forms of voltages and currents for the three phases (waveform);• Analysis of the harmonic structure of currents and voltages;• archiving (logging) of the measured parameters;• Creation of power quality indices protocol in accordance with Russian Standard RU GOST 32144-2013;• count dips and voltage pulses and their representation in the standard ANSI;• preservation of the graphs in graphic files;• e-mail alerts by e-mail, sms.
P16
WEB-BASED POWER QUALITY MONITORING SYSTEM (WPQMS)
WPQMS is flexible, scalable, and easily integrated into existing control systems.
Structurally complex object is a distributed decentralized network peripheral controllers, combined or fieldbus CAN, or through RS-232, RS-485, Ethernet, through which information is exchanged between controllers and data servers. WPQMS allows the connection of devices from other manufacturers under the relevant protocols.
WPQMS is addressed to six major categories of professionals:
1. duty electricians; 2. engineering staff service; 3. scientific and engineering staff of specialized organization that helps in the analysis of
emergency situations; 4. managers (not electricians) secondary and primary level; 5. students of higher and specialized educational institutions; 6. researchers.
Technically WPQMS allows for multi-parameter analysis of modes of load and mains. Additional tool for monitoring computer is the contribution of harmonics, which allows not only to evaluate the currents in the neutral conductor, but also to quantify the increase in cable loss and copper loss of the power transformer. This allows you to define (and provide) the effectiveness of power management when using active filters or power supplies with built-in power correctors.
P17
Ethernet-GSM gateway
InterNET
The servers for the collection, analysis and storage of information.
Operator workstation at the objects, local storage
server.
Ethernet
Ethernet
Пример реализации системы мониторинга нескольких объектов через GSM.
Electrical grid of object #1
Clients
Instrumentation and software for non-stop monitoring of indicators and current power supply quality power supply systems. www.magistr.tv/demo
GRID+NET
Electrical grid of object #2Ethernet-GSM gateway
P18
The architecture of online monitoring of power quality parameters.
measurement means
Voltage measuring transformer
Current measuring transformers
Operator workstation of object
Servers gathering information
Information communication channels
Web-based Power Quality Monitoring System.
Ethernet
Servers gathering information1
29
30
The point of control.Three current, three voltages
Up to 30 control points on a single server. Removal from the server up to
1000 meters (RS232,RS485).
System operators
Optical fiber, radio channel, GPRS,
Internet.
Internet Access
energy ServiceManagers
External Audit
RS232 RS485
Meets the requirements of:
GOST 32144-2013 (from 01.07.2014)
IEC 61000-4-7:2008IEC 61000-4-30:2008
P19
Active Filter ABB
WEB-BASED POWER QUALITY MONITORING SYSTEM (WPQMS)
Web-map with active filter
P20
THDi levels before and after active filter during 29.04.2015. For demonstration filter was off from 16:00 to 18:00.
WEB-BASED POWER QUALITY MONITORING SYSTEM (WPQMS)
Web-map with active filter
P21
Active power losses in T2, MPEI RTP-34, 22.04.2015
WEB-BASED POWER QUALITY MONITORING SYSTEM (WPQMS)
Web-map with transformer losses.
P22
Fragment of RTP-34 low voltage distribution panel with power quality controllers DM-306M.
RTP-34 Low Voltage switchboard.
Smart Substation.P23
MPEI RTP-34
Live broadcast of online monitoring of current power quality parameters at
distributed transformer substation MPEI RTP-34 10/0.4kV; 7000 kVA
www.magistr.tv/demo
P24
Web-based power quality monitoring system
«MAGISTR-3M» CompanyGeneral Director
Lev Khruslov+7 (495) 362-71-92
[email protected]@mail.ru
www.magistr.tv/demo
Thank you.
P25
Additional information.
P26
P27
P28
P29
P30
Люстра 408 КЛЛ. Источники питания ламп с виртуальным корректором мощности.
При наличии корректора мощности энергопотребление и световой поток 8-ми люстр с КЛЛ не изменяются. Потери в фазных проводах снижаются в 2 раза, в нейтральном проводе - в 2000 (!) раз.Существенно улучшаются условия работы защитной и коммутационной аппаратуры.Представленный анализ влияния гармоник на системы освещения можно применить и для других источников света. Например, замена люстр с КЛЛ на традиционные газоразрядные лампы (светильники Армстронг с электронной ПРА), при равенстве коэффициента светоотдачи (лм/Вт), приводит к такому же результату.