SECTION 15720 AIR HANDLING UNITS Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating products. . This section is based on the products of REZNOR®, which is located at: 8155 T&B Blvd. Mailcode #4C-25 Memphis, TN 38125 Toll Free Tel: 800-695-1901 Fax: 901-252-1305 Email:request info ([email protected]) Web:www.rezspec.com [Click Here ] for additional information. With over 120 years of experience in gas heating, Reznor manufactures a wide range of industrial and commercial heating products. Founded in 1888 in Pennsylvania, Reznor is a global leader, attained by being at the forefront of HVAC technology, thanks to its innovative solutions for heating, ventilation, cooling and air conditioning incorporated in its extended range of gas fired air heaters, air handling units, condensing units and rooftop units. Today Reznor is a $100 million+ division of Thomas & Betts Corp. and has manufacturing and sales facilities across the world. PART 1 GENERAL 1.1 SECTION INCLUDES ** NOTE TO SPECIFIER ** Delete items below not required for project. A. Heating/cooling makeup air systems. B. Air rotation equipment. 1.2 RELATED SECTIONS ** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required. A. Section 15050 - Basic Mechanical Materials and Methods: Rough-in and service requirements for materials and installation. B. Section 16050 - Basic Electrical Materials and Methods: Rough-in and service requirements for materials and installation. 1.3 SUBMITTALS 15720-1

  · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

SECTION 15720AIR HANDLING UNITS

Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved

** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating products..This section is based on the products of REZNOR®, which is located at:8155 T&B Blvd. Mailcode #4C-25Memphis, TN 38125Toll Free Tel: 800-695-1901Fax: 901-252-1305Email:request info ([email protected])Web:www.rezspec.com[Click Here] for additional information.With over 120 years of experience in gas heating, Reznor manufactures a wide range of industrial and commercial heating products. Founded in 1888 in Pennsylvania, Reznor is a global leader, attained by being at the forefront of HVAC technology, thanks to its innovative solutions for heating, ventilation, cooling and air conditioning incorporated in its extended range of gas fired air heaters, air handling units, condensing units and rooftop units. Today Reznor is a $100 million+ division of Thomas & Betts Corp. and has manufacturing and sales facilities across the world.

PART 1 GENERAL

1.1 SECTION INCLUDES** NOTE TO SPECIFIER ** Delete items below not required for project.

A. Heating/cooling makeup air systems.

B. Air rotation equipment.

1.2 RELATED SECTIONS** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

A. Section 15050 - Basic Mechanical Materials and Methods: Rough-in and service requirements for materials and installation.

B. Section 16050 - Basic Electrical Materials and Methods: Rough-in and service requirements for materials and installation.

1.3 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used, including:1. Preparation instructions and recommendations.2. Storage and handling requirements and recommendations.3. Installation methods.

C. Shop Drawings: Submit manufacturer/installer's shop drawings, including plans, elevations, sections, and details, indicating location of equipment, operating characteristics, loads,

15720-1

Page 2:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

dimensions, tolerances, materials, components, fabrication, fasteners, hardware, finish, options, and accessories.

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Single source for design, engineering, production, warranty and warranty service.1. Manufacturer shall have at least 20 years experience in manufacturing makeup air

equipment.

B. Installer Qualifications: Licensed and experienced with mechanical equipment installation, testing and start-up. Familiar with code and AHJ requirements and restrictions.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Store products in manufacturer's unopened packaging until ready for installation.

1.6 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: REZNOR®, which is located at: 8155 T&B Blvd. Mailcode #4C-25 ; Memphis, TN 38125; Toll Free Tel: 800-695-1901; Fax: 901-252-1305; Email:request info ([email protected]); Web:www.rezspec.com

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of Section 01600.

** NOTE TO SPECIFIER ** Delete if not required.

2.2 HEATING/COOLING MAKEUP AIR** NOTE TO SPECIFIER ** The MAPS III Series packaged rooftop units are designed to cool and heat high volumes of outside air year round for makeup air and ventilation applications. In addition, MAPSIII can provide significant capacities of space conditioning. All MAPSIII products feature the Reznor IQ digital controller to fully integrate all operation and external sensing into a stand-alone package or through native BacNet, into a building management system.Models RCB/RDB/RDCB/RDDB/RECB/REDB only. Delete if not required.

A. Packaged Rooftop Unit:** NOTE TO SPECIFIER ** Delete unit not required.

1. Unit: High Capacity DX Cooling Makeup Air Units in R410-A Refrigerant:a. Model RCB as manufactured by REZNOR.

** NOTE TO SPECIFIER ** Delete size not required.b. Size: 060. Minimum CFM - 1350. Maximum CFM - 3000.c. Size: 078. Minimum CFM - 1350. Maximum CFM - 3000.d. Size: 090. Minimum CFM - 1350. Maximum CFM - 3000.e. Size: 118. Minimum CFM - 1350. Maximum CFM - 3000.

15720-2

Page 3:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

f. Size: 136. Minimum CFM - 1350. Maximum CFM - 3000.g. Size: 160. Minimum CFM - 2200. Maximum CFM - 4840.h. Size: 186. Minimum CFM - 2200. Maximum CFM - 4840.i. Size: 190. Minimum CFM - 3600. Maximum CFM - 9000.j. Size: 200. Minimum CFM - 2200. Maximum CFM - 4840.k. Size: 216. Minimum CFM - 3600. Maximum CFM - 9000.l. Size: 298. Minimum CFM - 3600. Maximum CFM - 9000.m. Size: 360. Minimum CFM - 6000. Maximum CFM - 12500.n. Size: 410. Minimum CFM - 3600. Maximum CFM - 9000.o. Size: 480. Minimum CFM - 6000. Maximum CFM - 13000.p. Size: 600. Minimum CFM - 6000. Maximum CFM - 13000.q. Size: 720. Minimum CFM - 6000. Maximum CFM - 13000.

2. Unit: High Outside Air DX Cooling with dedicated Re-Heat Pump Makeup Air Units in R410-A Refrigerant:a. Model RDB as manufactured by REZNOR.

** NOTE TO SPECIFIER ** Delete size not required.b. Size: 084. Minimum CFM - 1350. Maximum CFM - 3000.c. Size: 102. Minimum CFM - 1350. Maximum CFM - 3000.d. Size: 114. Minimum CFM - 1350. Maximum CFM - 3000.e. Size: 142. Minimum CFM - 1350. Maximum CFM - 3000.f. Size: 162. Minimum CFM - 1350. Maximum CFM - 3000.g. Size: 184. Minimum CFM - 2000. Maximum CFM - 5000.h. Size: 210. Minimum CFM - 2000. Maximum CFM - 5000.i. Size: 222. Minimum CFM - 2000. Maximum CFM - 5000.j. Size: 224. Minimum CFM - 2000. Maximum CFM - 5000.k. Size: 236. Minimum CFM - 2000. Maximum CFM - 5000.l. Size: 248. Minimum CFM - 3600. Maximum CFM - 9000.m. Size: 262. Minimum CFM - 3600. Maximum CFM - 9000.n. Size: 272. Minimum CFM - 3600. Maximum CFM - 9000.o. Size: 288. Minimum CFM - 3600. Maximum CFM - 9000.p. Size: 354. Minimum CFM - 3600. Maximum CFM - 9000.q. Size: 370. Minimum CFM - 3600. Maximum CFM - 9000.r. Size: 418. Minimum CFM - 6000. Maximum CFM - 13000.s. Size: 444. Minimum CFM - 6000. Maximum CFM - 13000.t. Size: 468. Minimum CFM - 3600. Maximum CFM - 9000.u. Size: 482. Minimum CFM - 3600. Maximum CFM - 9000.v. Size: 602. Minimum CFM - 6000. Maximum CFM - 13000.w. Size: 722. Minimum CFM - 6000. Maximum CFM - 13000.x. Size: 842. Minimum CFM - 6000. Maximum CFM - 13000.

3. Unit: High Capacity DX Cooling/Gas Heating Makeup Air Units in R410-A Refrigerant:a. Model RDCB as manufactured by REZNOR.b. Units are 82% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.c. Size-Input MBH: 060-100. Minimum CFM - 1350. Maximum CFM - 1650.d. Size-Input MBH: 078-100. Minimum CFM - 1350. Maximum CFM - 1650.e. Size-Input MBH: 090-100. Minimum CFM - 1350. Maximum CFM - 1650.f. Size-Input MBH: 118-100. Minimum CFM - 1350. Maximum CFM - 1650.g. Size-Input MBH: 136-100. Minimum CFM - 1350. Maximum CFM - 1650.h. Size-Input MBH: 060-150. Minimum CFM - 1350. Maximum CFM - 2500.i. Size-Input MBH: 078-150. Minimum CFM - 1350. Maximum CFM - 2500.j. Size-Input MBH: 090-150. Minimum CFM - 1350. Maximum CFM - 2500.k. Size-Input MBH: 118-150. Minimum CFM - 1350. Maximum CFM - 2500.l. Size-Input MBH: 136-150. Minimum CFM - 1350. Maximum CFM - 2500.m. Size-Input MBH: 060-200. Minimum CFM - 1480. Maximum CFM - 3300.n. Size-Input MBH: 078-200. Minimum CFM - 1480. Maximum CFM - 3300.

15720-3

Page 4:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

o. Size-Input MBH: 090-200. Minimum CFM - 1480. Maximum CFM - 3300.p. Size-Input MBH: 118-200. Minimum CFM - 1480. Maximum CFM - 3300.q. Size-Input MBH: 136-200. Minimum CFM - 1480. Maximum CFM - 3300.r. Size-Input MBH: 078-250. Minimum CFM - 2220. Maximum CFM - 4940.s. Size-Input MBH: 090-250. Minimum CFM - 2220. Maximum CFM - 4940.t. Size-Input MBH: 118-250. Minimum CFM - 2220. Maximum CFM - 4940.u. Size-Input MBH: 136-250. Minimum CFM - 2220. Maximum CFM - 4940.v. Size-Input MBH: 160-250. Minimum CFM - 2220. Maximum CFM - 4940.w. Size-Input MBH: 186-250. Minimum CFM - 2220. Maximum CFM - 4940.x. Size-Input MBH: 200-250. Minimum CFM - 2220. Maximum CFM - 4940.y. Size-Input MBH: 078-300. Minimum CFM - 2220. Maximum CFM - 4940.z. Size-Input MBH: 090-300. Minimum CFM - 2220. Maximum CFM - 4940.aa. Size-Input MBH: 118-300. Minimum CFM - 2220. Maximum CFM - 4940.bb. Size-Input MBH: 136-300. Minimum CFM - 2220. Maximum CFM - 4940.cc. Size-Input MBH: 160-300. Minimum CFM - 2220. Maximum CFM - 4940.dd. Size-Input MBH: 186-300. Minimum CFM - 2220. Maximum CFM - 4940.ee. Size-Input MBH: 200-300. Minimum CFM - 2220. Maximum CFM - 4940.ff. Size-Input MBH: 190-400. Minimum CFM - 3000. Maximum CFM - 9000.gg. Size-Input MBH: 216-400. Minimum CFM - 3000. Maximum CFM - 9000.hh. Size-Input MBH: 298-400. Minimum CFM - 3000. Maximum CFM - 9000.ii. Size-Input MBH: 410-400. Minimum CFM - 3000. Maximum CFM - 9000.jj. Size-Input MBH: 190-500. Minimum CFM - 3500. Maximum CFM - 9000.kk. Size-Input MBH: 216-500. Minimum CFM - 3500. Maximum CFM - 9000.ll. Size-Input MBH: 298-500. Minimum CFM - 3500. Maximum CFM - 9000.mm. Size-Input MBH: 360-500. Minimum CFM - 6000. Maximum CFM - 13000.nn. Size-Input MBH: 410-500. Minimum CFM - 3500. Maximum CFM - 9000.oo. Size-Input MBH: 480-500. Minimum CFM - 6000. Maximum CFM - 13000.pp. Size-Input MBH: 600-500. Minimum CFM - 6000. Maximum CFM - 13000.qq. Size-Input MBH: 720-500. Minimum CFM - 6000. Maximum CFM - 13000.rr. Size-Input MBH: 190-600. Minimum CFM - 3500. Maximum CFM - 9000.ss. Size-Input MBH: 216-600. Minimum CFM - 3500. Maximum CFM - 9000.tt. Size-Input MBH: 298-600. Minimum CFM - 3500. Maximum CFM - 9000.uu. Size-Input MBH: 360-600. Minimum CFM - 6000. Maximum CFM - 13000.vv. Size-Input MBH: 410-600. Minimum CFM - 3500. Maximum CFM - 9000.ww. Size-Input MBH: 480-600. Minimum CFM - 6000. Maximum CFM - 13000.xx. Size-Input MBH: 600-600. Minimum CFM - 6000. Maximum CFM - 13000.yy. Size-Input MBH: 720-600. Minimum CFM - 6000. Maximum CFM - 13000.zz. Size-Input MBH: 190-700. Minimum CFM - 3500. Maximum CFM - 9000.aaa. Size-Input MBH: 216-700. Minimum CFM - 3500. Maximum CFM - 9000.bbb. Size-Input MBH: 298-700. Minimum CFM - 3500. Maximum CFM - 9000.ccc. Size-Input MBH: 360-700. Minimum CFM - 6000. Maximum CFM - 13000.ddd. Size-Input MBH: 410-700. Minimum CFM - 3500. Maximum CFM - 9000.eee. Size-Input MBH: 480-700. Minimum CFM - 6000. Maximum CFM - 13000.fff. Size-Input MBH: 600-700. Minimum CFM - 6000. Maximum CFM - 13000.ggg. Size-Input MBH: 720-700. Minimum CFM - 6000. Maximum CFM - 13000.hhh. Size-Input MBH: 360-800. Minimum CFM - 6000. Maximum CFM - 13000.iii. Size-Input MBH: 480-800. Minimum CFM - 6000. Maximum CFM - 13000.jjj. Size-Input MBH: 600-800. Minimum CFM - 6000. Maximum CFM - 13000.kkk. Size-Input MBH: 720-800. Minimum CFM - 6000. Maximum CFM - 13000.lll. Size-Input MBH: 360-1000. Minimum CFM - 6000. Maximum CFM - 13000.mmm. Size-Input MBH: 480-1000. Minimum CFM - 6000. Maximum CFM -

13000.nnn. Size-Input MBH: 600-1000. Minimum CFM - 6000. Maximum CFM - 13000.ooo. Size-Input MBH: 720-1000. Minimum CFM - 6000. Maximum CFM - 13000.ppp. Size-Input MBH: 360-1200. Minimum CFM - 6000. Maximum CFM - 13000.qqq. Size-Input MBH: 480-1200. Minimum CFM - 6000. Maximum CFM - 13000.

15720-4

Page 5:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

rrr. Size-Input MBH: 600-1200. Minimum CFM - 6000. Maximum CFM - 13000.sss. Size-Input MBH: 720-1200. Minimum CFM - 6000. Maximum CFM - 13000.ttt. Size-Input MBH: 360-1400. Minimum CFM - 6000. Maximum CFM - 13000.uuu. Size-Input MBH: 480-1400. Minimum CFM - 6000. Maximum CFM - 13000.vvv. Size-Input MBH: 600-1400. Minimum CFM - 6000. Maximum CFM - 13000.www. Size-Input MBH: 720-1400. Minimum CFM - 6000. Maximum CFM - 13000.xxx. Size-Input MBH: 360-1600. Minimum CFM - 6000. Maximum CFM - 13000.yyy. Size-Input MBH: 480-1600. Minimum CFM - 6000. Maximum CFM - 13000.zzz. Size-Input MBH: 600-1600. Minimum CFM - 6000. Maximum CFM - 13000.

1) aaaa.Size-Input MBH: 720-1600. Minimum CFM - . Maximum CFM - 13000.

4. Unit: High Capacity DX Cooling with dedicated Re-Heat Pump/Gas Heating Makeup Air Units in R410-A Refrigerant:a. Model RDDB as manufactured by REZNOR.b. Units are 82% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.c. Size-Input MBH: 084-100. Minimum CFM - 1350. Maximum CFM - 1650.d. Size-Input MBH: 102-100. Minimum CFM - 1350. Maximum CFM - 1650.e. Size-Input MBH: 114-100. Minimum CFM - 1350. Maximum CFM - 1650.f. Size-Input MBH: 142-100. Minimum CFM - 1350. Maximum CFM - 1650.g. Size-Input MBH: 084-150. Minimum CFM - 1350. Maximum CFM - 2500.h. Size-Input MBH: 102-150. Minimum CFM - 1350. Maximum CFM - 2500.i. Size-Input MBH: 114-150. Minimum CFM - 1350. Maximum CFM - 2500.j. Size-Input MBH: 142-150. Minimum CFM - 1350. Maximum CFM - 2500.k. Size-Input MBH: 162-150. Minimum CFM - 1350. Maximum CFM - 2500.l. Size-Input MBH: 084-200. Minimum CFM - 1480. Maximum CFM - 3300.m. Size-Input MBH: 102-200. Minimum CFM - 1480. Maximum CFM - 3300.n. Size-Input MBH: 114-200. Minimum CFM - 1480. Maximum CFM - 3300.o. Size-Input MBH: 142-200. Minimum CFM - 1480. Maximum CFM - 3300.p. Size-Input MBH: 162-200. Minimum CFM - 1480. Maximum CFM - 3300.q. Size-Input MBH: 102-250. Minimum CFM - 2220. Maximum CFM - 4940.r. Size-Input MBH: 114-250. Minimum CFM - 2220. Maximum CFM - 4940.s. Size-Input MBH: 142-250. Minimum CFM - 2220. Maximum CFM - 4940.t. Size-Input MBH: 162-250. Minimum CFM - 2220. Maximum CFM - 4940.u. Size-Input MBH: 184-250. Minimum CFM - 2220. Maximum CFM - 4940.v. Size-Input MBH: 210-250. Minimum CFM - 2220. Maximum CFM - 4940.w. Size-Input MBH: 222-250. Minimum CFM - 2220. Maximum CFM - 4940.x. Size-Input MBH: 224-250. Minimum CFM - 2220. Maximum CFM - 4940.y. Size-Input MBH: 236-250. Minimum CFM - 2220. Maximum CFM - 4940.z. Size-Input MBH: 102-300. Minimum CFM - 2220. Maximum CFM - 4940.aa. Size-Input MBH: 114-300. Minimum CFM - 2220. Maximum CFM - 4940.bb. Size-Input MBH: 142-300. Minimum CFM - 2220. Maximum CFM - 4940.cc. Size-Input MBH: 162-300. Minimum CFM - 2220. Maximum CFM - 4940.dd. Size-Input MBH: 184-300. Minimum CFM - 2220. Maximum CFM - 4940.ee. Size-Input MBH: 210-300. Minimum CFM - 2220. Maximum CFM - 4940.ff. Size-Input MBH: 222-300. Minimum CFM - 2220. Maximum CFM - 4940.gg. Size-Input MBH: 224-300. Minimum CFM - 2220. Maximum CFM - 4940.hh. Size-Input MBH: 236-300. Minimum CFM - 2220. Maximum CFM - 4940.ii. Size-Input MBH: 248-400. Minimum CFM - 3000. Maximum CFM - 9000.jj. Size-Input MBH: 262-400. Minimum CFM - 3000. Maximum CFM - 9000.kk. Size-Input MBH: 272-400. Minimum CFM - 3000. Maximum CFM - 9000.ll. Size-Input MBH: 288-400. Minimum CFM - 3000. Maximum CFM - 9000.mm. Size-Input MBH: 354-400. Minimum CFM - 3000. Maximum CFM - 9000.nn. Size-Input MBH: 370-400. Minimum CFM - 3000. Maximum CFM - 9000.oo. Size-Input MBH: 468-400. Minimum CFM - 3000. Maximum CFM - 9000.pp. Size-Input MBH: 482-400. Minimum CFM - 3000. Maximum CFM - 9000.

15720-5

Page 6:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

qq. Size-Input MBH: 248-500. Minimum CFM - 3500. Maximum CFM - 9000.rr. Size-Input MBH: 262-500. Minimum CFM - 3500. Maximum CFM - 9000.ss. Size-Input MBH: 272-500. Minimum CFM - 3500. Maximum CFM - 9000.tt. Size-Input MBH: 288-500. Minimum CFM - 3500. Maximum CFM - 9000.uu. Size-Input MBH: 354-500. Minimum CFM - 3500. Maximum CFM - 9000.vv. Size-Input MBH: 370-500. Minimum CFM - 3500. Maximum CFM - 9000.ww. Size-Input MBH: 418-500. Minimum CFM - 6000. Maximum CFM - 13000.xx. Size-Input MBH: 444-500. Minimum CFM - 6000. Maximum CFM - 13000.yy. Size-Input MBH: 468-500. Minimum CFM - 3500. Maximum CFM - 9000.zz. Size-Input MBH: 482-500. Minimum CFM - 3500. Maximum CFM - 9000.aaa. Size-Input MBH: 602-500. Minimum CFM - 6000. Maximum CFM - 13000.bbb. Size-Input MBH: 722-500. Minimum CFM - 6000. Maximum CFM - 13000.ccc. Size-Input MBH: 842-500. Minimum CFM - 6000. Maximum CFM - 13000.ddd. Size-Input MBH: 248-600. Minimum CFM - 3500. Maximum CFM - 9000.eee. Size-Input MBH: 262-600. Minimum CFM - 3500. Maximum CFM - 9000.fff. Size-Input MBH: 272-600. Minimum CFM - 3500. Maximum CFM - 9000.ggg. Size-Input MBH: 288-600. Minimum CFM - 3500. Maximum CFM - 9000.hhh. Size-Input MBH: 354-600. Minimum CFM - 3500. Maximum CFM - 9000.iii. Size-Input MBH: 370-600. Minimum CFM - 3500. Maximum CFM - 9000.jjj. Size-Input MBH: 418-600. Minimum CFM - 6000. Maximum CFM - 13000.kkk. Size-Input MBH: 444-600. Minimum CFM - 6000. Maximum CFM - 13000.lll. Size-Input MBH: 468-600. Minimum CFM - 3500. Maximum CFM - 9000.mmm. Size-Input MBH: 482-600. Minimum CFM - 3500. Maximum CFM - 9000.nnn. Size-Input MBH: 602-600. Minimum CFM - 6000. Maximum CFM - 13000.ooo. Size-Input MBH: 722-600. Minimum CFM - 6000. Maximum CFM - 13000.ppp. Size-Input MBH: 842-600. Minimum CFM - 6000. Maximum CFM - 13000.qqq. Size-Input MBH: 248-700. Minimum CFM - 3500. Maximum CFM - 9000.rrr. Size-Input MBH: 262-700. Minimum CFM - 3500. Maximum CFM - 9000.sss. Size-Input MBH: 272-700. Minimum CFM - 3500. Maximum CFM - 9000.ttt. Size-Input MBH: 288-700. Minimum CFM - 3500. Maximum CFM - 9000.uuu. Size-Input MBH: 354-700. Minimum CFM - 3500. Maximum CFM - 9000.vvv. Size-Input MBH: 370-700. Minimum CFM - 3500. Maximum CFM - 9000.www. Size-Input MBH: 418-700. Minimum CFM - 6000. Maximum CFM - 13000.xxx. Size-Input MBH: 444-700. Minimum CFM - 6000. Maximum CFM - 13000.yyy. Size-Input MBH: 468-700. Minimum CFM - 3500. Maximum CFM - 9000.zzz. Size-Input MBH: 482-700. Minimum CFM - 3500. Maximum CFM - 9000.

1) aaaa.Size-Input MBH: 602-700. Minimum CFM - . Maximum CFM - 13000.

2) bbbb.Size-Input MBH: 722-700. Minimum CFM - . Maximum CFM - 13000.

3) cccc.Size-Input MBH: 842-700. Minimum CFM - . Maximum CFM - 13000.

4) dddd.Size-Input MBH: 418-800. Minimum CFM - . Maximum CFM - 13000.

5) eeee.Size-Input MBH: 444-800. Minimum CFM - . Maximum CFM - 13000.

6) ffff.Size-Input MBH: 602-800. Minimum CFM - . Maximum CFM - 13000.7) gggg.Size-Input MBH: 722-800. Minimum CFM - . Maximum CFM -

13000.8) hhhh.Size-Input MBH: 842-800. Minimum CFM - . Maximum CFM -

13000.9) iiii.Size-Input MBH: 418-1000. Minimum CFM - . Maximum CFM - 13000.10) jjjj.Size-Input MBH: 444-1000. Minimum CFM - . Maximum CFM - 13000.11) kkkk.Size-Input MBH: 602-1000. Minimum CFM - . Maximum CFM -

13000.12) llll.Size-Input MBH: 722-1000. Minimum CFM - . Maximum CFM - 13000.

15720-6

Page 7:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

13) mmmm.Size-Input MBH: 842-1000. Minimum CFM - . Maximum CFM - 13000.

14) nnnn.Size-Input MBH: 418-1200. Minimum CFM - . Maximum CFM - 13000.

15) oooo.Size-Input MBH: 444-1200. Minimum CFM - . Maximum CFM - 13000.

16) pppp.Size-Input MBH: 602-1200. Minimum CFM - . Maximum CFM - 13000.

17) qqqq.Size-Input MBH: 722-1200. Minimum CFM - . Maximum CFM - 13000.

18) rrrr.Size-Input MBH: 842-1200. Minimum CFM - . Maximum CFM - 13000.

19) ssss.Size-Input MBH: 418-1400. Minimum CFM - . Maximum CFM - 13000.

20) tttt.Size-Input MBH: 444-1400. Minimum CFM - . Maximum CFM - 13000.21) uuuu.Size-Input MBH: 602-1400. Minimum CFM - . Maximum CFM -

13000.22) vvvv.Size-Input MBH: 722-1400. Minimum CFM - . Maximum CFM -

13000.23) wwww.Size-Input MBH: 842-1400. Minimum CFM - . Maximum CFM -

13000.24) xxxx.Size-Input MBH: 418-1600. Minimum CFM - . Maximum CFM -

13000.25) yyyy.Size-Input MBH: 444-1600. Minimum CFM - . Maximum CFM -

13000.26) zzzz.Size-Input MBH: 602-1600. Minimum CFM - . Maximum CFM -

13000.27) aaaaa.Size-Input MBH: 722-1600. Minimum CFM - . Maximum CFM -

13000.28) bbbbb.Size-Input MBH: 842-1600. Minimum CFM - . Maximum CFM -

13000.5. Unit: Packaged Rooftop, Electric Heat, DX Cooling Makeup Air System for

Commercial / Industrial Use, R410-A Refrigerant:a. Model RECB as manufactured by REZNOR.b. Units are 100% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.c. Size (Input MBH): 060-10S (34). Minimum CFM - 1350. Maximum CFM - 3000.d. Size (Input MBH): 060-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.e. Size (Input MBH): 060-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.f. Size (Input MBH): 078-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.g. Size (Input MBH): 078-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.h. Size (Input MBH): 090-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.i. Size (Input MBH): 090-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.j. Size (Input MBH): 118-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.k. Size (Input MBH): 118-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.l. Size (Input MBH): 136-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.m. Size (Input MBH): 136-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.n. Size (Input MBH): 160-15 (51). Minimum CFM - 2000. Maximum CFM - 5000.o. Size (Input MBH): 186-15 (51). Minimum CFM - 2000. Maximum CFM - 5000.p. Size (Input MBH): 060-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.q. Size (Input MBH): 060-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.r. Size (Input MBH): 078-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.s. Size (Input MBH): 078-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.t. Size (Input MBH): 090-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.u. Size (Input MBH): 090-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.v. Size (Input MBH): 118-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.

15720-7

Page 8:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

w. Size (Input MBH): 118-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.x. Size (Input MBH): 136-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.y. Size (Input MBH): 136-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.z. Size (Input MBH): 160-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.aa. Size (Input MBH): 186-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.bb. Size (Input MBH): 200-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.cc. Size (Input MBH): 060-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.dd. Size (Input MBH): 078-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.ee. Size (Input MBH): 090-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.ff. Size (Input MBH): 118-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.gg. Size (Input MBH): 136-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.hh. Size (Input MBH): 060-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.ii. Size (Input MBH): 078-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.jj. Size (Input MBH): 090-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.kk. Size (Input MBH): 118-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.ll. Size (Input MBH): 136-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.mm. Size (Input MBH): 160-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.nn. Size (Input MBH): 186-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.oo. Size (Input MBH): 200-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.pp. Size (Input MBH): 060-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.qq. Size (Input MBH): 078-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.rr. Size (Input MBH): 090-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.ss. Size (Input MBH): 118-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.tt. Size (Input MBH): 136-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.uu. Size (Input MBH): 160-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.vv. Size (Input MBH): 186-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.ww. Size (Input MBH): 200-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.xx. Size (Input MBH): 060-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.yy. Size (Input MBH): 078-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.zz. Size (Input MBH): 090-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.aaa. Size (Input MBH): 118-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.bbb. Size (Input MBH): 136-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.ccc. Size (Input MBH): 160-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.ddd. Size (Input MBH): 186-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.eee. Size (Input MBH): 200-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.fff. Size (Input MBH): 060-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.ggg. Size (Input MBH): 078-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.hhh. Size (Input MBH): 090-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.iii. Size (Input MBH): 118-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.jjj. Size (Input MBH): 136-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.kkk. Size (Input MBH): 160-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.lll. Size (Input MBH): 186-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.mmm. Size (Input MBH): 190-39 (133). Minimum CFM - 3600. Maximum CFM -

7500.nnn. Size (Input MBH): 200-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.ooo. Size (Input MBH): 216-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.ppp. Size (Input MBH): 298-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.qqq. Size (Input MBH): 410-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.rrr. Size (Input MBH): 078-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.sss. Size (Input MBH): 090-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.ttt. Size (Input MBH): 118-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.uuu. Size (Input MBH): 136-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.vvv. Size (Input MBH): 160-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.www. Size (Input MBH): 186-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.xxx. Size (Input MBH): 190-50 (171). Minimum CFM - 3600. Maximum CFM - 7500.yyy. Size (Input MBH): 200-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.

15720-8

Page 9:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

zzz. Size (Input MBH): 216-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.1) aaaa.Size (Input MBH): 298-50 (). Minimum CFM - 3600. Maximum CFM

- 9000.2) bbbb.Size (Input MBH): 410-50 (). Minimum CFM - 3600. Maximum CFM

- 9000.3) cccc.Size (Input MBH): 078-60 (). Minimum CFM - 1350. Maximum CFM

- 3000.4) dddd.Size (Input MBH): 090-60 (). Minimum CFM - 1350. Maximum CFM

- 3000.5) eeee.Size (Input MBH): 118-60 (). Minimum CFM - 1350. Maximum CFM

- 3000.6) ffff.Size (Input MBH): 136-60 (). Minimum CFM - 1350. Maximum CFM -

3000.7) gggg.Size (Input MBH): 160-60 (). Minimum CFM - 2000. Maximum CFM

- 5000.8) hhhh.Size (Input MBH): 186-60 (). Minimum CFM - 2000. Maximum CFM

- 5000.9) iiii.Size (Input MBH): 190-60 (). Minimum CFM - 3600. Maximum CFM -

7500.10) jjjj.Size (Input MBH): 200-60 (). Minimum CFM - 2000. Maximum CFM -

5000.11) kkkk.Size (Input MBH): 216-60 (). Minimum CFM - 3600. Maximum CFM

- 9000.12) llll.Size (Input MBH): 298-60 (). Minimum CFM - 3600 9000.13) mmmm.Size (Input MBH): 410-60 (). Minimum CFM - 3600. Maximum

CFM - 9000.14) nnnn.Size (Input MBH): 078-75 (). Minimum CFM - 1350. Maximum CFM

- 3000.15) oooo.Size (Input MBH): 090-75 (). Minimum CFM - 1350. Maximum CFM

- 3000.16) pppp.Size (Input MBH): 118-75 (). Minimum CFM - 1350. Maximum CFM

- 3000.17) qqqq.Size (Input MBH): 136-75 (). Minimum CFM - 1350. Maximum CFM

- 3000.18) rrrr.Size (Input MBH): 160-75 (). Minimum CFM - 2000. Maximum CFM -

5000.19) ssss.Size (Input MBH): 186-75 (). Minimum CFM - 2000. Maximum CFM

- 5000.20) tttt.Size (Input MBH): 200-75 (). Minimum CFM - 2000. Maximum CFM -

5000.21) uuuu.Size (Input MBH): 190-75 (). Minimum CFM - 3600. Maximum CFM

- 7500.22) vvvv.Size (Input MBH): 216-75 (). Minimum CFM - 3600. Maximum CFM

- 9000.23) wwww.Size (Input MBH): 298-75 (). Minimum CFM - 3600. Maximum

CFM - 9000.24) xxxx.Size (Input MBH): 410-75 (). Minimum CFM - 3600. Maximum CFM

- 9000.25) yyyy.Size (Input MBH): 190-88 (). Minimum CFM - 3600. Maximum CFM

- 7500.26) zzzz.Size (Input MBH): 216-88 (). Minimum CFM - 3600. Maximum CFM

- 9000.27) aaaaa.Size (Input MBH): 298-88 (). Minimum CFM - 3600. Maximum

CFM - 9000.28) bbbbb.Size (Input MBH): 410-88 (). Minimum CFM - 3600. Maximum

CFM - 9000.

15720-9

Page 10:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

29) ccccc.Size (Input MBH): 090-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

30) ddddd.Size (Input MBH): 118-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

31) eeeee.Size (Input MBH): 136-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

32) fffff.Size (Input MBH): 160-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

33) ggggg.Size (Input MBH): 186-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

34) hhhhh.Size (Input MBH): 200-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

6. Unit: Packaged rooftop makeup air unit, DX Cooling/ Dehumidification, Electric Heat, R-410A Refrigerant:a. Units are 100% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.b. Model REDB as manufactured by REZNOR.c. Size (Input MBH): 084-10S (34). Minimum CFM - 1350. Maximum CFM - 3000.d. Size (Input MBH): 084-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.e. Size (Input MBH): 084-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.f. Size (Input MBH): 102-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.g. Size (Input MBH): 102-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.h. Size (Input MBH): 114-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.i. Size (Input MBH): 114-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.j. Size (Input MBH): 142-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.k. Size (Input MBH): 142-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.l. Size (Input MBH): 162-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.m. Size (Input MBH): 184-15 (51). Minimum CFM - 2000. Maximum CFM - 5000.n. Size (Input MBH): 084-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.o. Size (Input MBH): 084-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.p. Size (Input MBH): 102-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.q. Size (Input MBH): 102-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.r. Size (Input MBH): 114-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.s. Size (Input MBH): 114-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.t. Size (Input MBH): 142-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.u. Size (Input MBH): 142-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.v. Size (Input MBH): 162-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.w. Size (Input MBH): 184-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.x. Size (Input MBH): 210-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.y. Size (Input MBH): 222-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.z. Size (Input MBH): 224-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.aa. Size (Input MBH): 236-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.bb. Size (Input MBH): 084-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.cc. Size (Input MBH): 102-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.dd. Size (Input MBH): 114-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.ee. Size (Input MBH): 142-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.ff. Size (Input MBH): 084-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.gg. Size (Input MBH): 102-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.hh. Size (Input MBH): 114-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.ii. Size (Input MBH): 142-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.jj. Size (Input MBH): 162-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.kk. Size (Input MBH): 184-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.ll. Size (Input MBH): 210-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.mm. Size (Input MBH): 222-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.nn. Size (Input MBH): 224-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.oo. Size (Input MBH): 236-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.

15720-10

Page 11:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

pp. Size (Input MBH): 084-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.qq. Size (Input MBH): 102-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.rr. Size (Input MBH): 114-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.ss. Size (Input MBH): 142-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.tt. Size (Input MBH): 162-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.uu. Size (Input MBH): 184-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.vv. Size (Input MBH): 210-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.ww. Size (Input MBH): 222-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.xx. Size (Input MBH): 224-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.yy. Size (Input MBH): 236-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.zz. Size (Input MBH): 084-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.aaa. Size (Input MBH): 102-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.bbb. Size (Input MBH): 114-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.ccc. Size (Input MBH): 142-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.ddd. Size (Input MBH): 162-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.eee. Size (Input MBH): 184-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.fff. Size (Input MBH): 210-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.ggg. Size (Input MBH): 222-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.hhh. Size (Input MBH): 224-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.iii. Size (Input MBH): 236-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.jjj. Size (Input MBH): 084-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.kkk. Size (Input MBH): 102-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.lll. Size (Input MBH): 114-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.mmm. Size (Input MBH): 142-39 (133). Minimum CFM - 1350. Maximum CFM -

3000.nnn. Size (Input MBH): 162-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.ooo. Size (Input MBH): 184-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.ppp. Size (Input MBH): 210-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.qqq. Size (Input MBH): 222-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.rrr. Size (Input MBH): 224-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.sss. Size (Input MBH): 236-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.ttt. Size (Input MBH): 248-39 (133). Minimum CFM - 3600. Maximum CFM - 7500.uuu. Size (Input MBH): 262-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.vvv. Size (Input MBH): 272-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.www. Size (Input MBH): 288-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.xxx. Size (Input MBH): 354-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.yyy. Size (Input MBH): 370-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.zzz. Size (Input MBH): 468-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.

1) aaaa.Size (Input MBH): 482-39 (). Minimum CFM - 3600. Maximum CFM - 9000.

2) bbbb.Size (Input MBH): 102-50 (). Minimum CFM - 1350. Maximum CFM - 3000.

3) cccc.Size (Input MBH): 114-50 (). Minimum CFM - 1350. Maximum CFM - 3000.

4) dddd.Size (Input MBH): 142-50 (). Minimum CFM - 1350. Maximum CFM - 3000.

5) eeee.Size (Input MBH): 162-50 (). Minimum CFM - 1350. Maximum CFM - 3000.

6) ffff.Size (Input MBH): 184-50 (). Minimum CFM - 2000. Maximum CFM - 5000.

7) gggg.Size (Input MBH): 210-50 (). Minimum CFM - 2000. Maximum CFM - 5000.

8) hhhh.Size (Input MBH): 222-50 (). Minimum CFM - 2000. Maximum CFM - 5000.

9) iiii.Size (Input MBH): 224-50 (). Minimum CFM - 2000. Maximum CFM - 5000.

15720-11

Page 12:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

10) jjjj.Size (Input MBH): 236-50 (). Minimum CFM - 2000. Maximum CFM - 5000.

11) kkkk.Size (Input MBH): 248-50 (). Minimum CFM - 3600. Maximum CFM - 7500.

12) llll.Size (Input MBH): 262-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

13) mmmm.Size (Input MBH): 272-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

14) nnnn.Size (Input MBH): 288-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

15) oooo.Size (Input MBH): 354-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

16) pppp.Size (Input MBH): 370-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

17) qqqq.Size (Input MBH): 468-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

18) rrrr.Size (Input MBH): 482-50 (). Minimum CFM - 3600. Maximum CFM - 9000.

19) ssss.Size (Input MBH): 102-60 (). Minimum CFM - 1350. Maximum CFM - 3000.

20) tttt.Size (Input MBH): 114-60 (). Minimum CFM - 1350. Maximum CFM - 3000.

21) uuuu.Size (Input MBH): 142-60 (). Minimum CFM - 1350. Maximum CFM - 3000.

22) vvvv.Size (Input MBH): 162-60 (). Minimum CFM - 1350. Maximum CFM - 3000.

23) wwww.Size (Input MBH): 184-60 (). Minimum CFM - 2000. Maximum CFM - 5000.

24) xxxx.Size (Input MBH): 210-60 (). Minimum CFM - 2000. Maximum CFM - 5000.

25) yyyy.Size (Input MBH): 222-60 (). Minimum CFM - 2000. Maximum CFM - 5000.

26) zzzz.Size (Input MBH): 224-60 (). Minimum CFM - 2000. Maximum CFM - 5000.

27) aaaaa.Size (Input MBH): 236-60 (). Minimum CFM - 2000. Maximum CFM - 5000.

28) bbbbb.Size (Input MBH): 248-60 (). Minimum CFM - 3600. Maximum CFM - 7500.

29) ccccc.Size (Input MBH): 262-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

30) ddddd.Size (Input MBH): 272-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

31) eeeee.Size (Input MBH): 288-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

32) fffff.Size (Input MBH): 354-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

33) ggggg.Size (Input MBH): 370-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

34) hhhhh.Size (Input MBH): 468-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

35) iiiii.Size (Input MBH): 482-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

36) jjjjj.Size (Input MBH): 102-75 (). Minimum CFM - 1350. Maximum CFM - 3000.

37) kkkkk.Size (Input MBH): 114-75 (). Minimum CFM - 1350. Maximum CFM - 3000.

15720-12

Page 13:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

38) lllll.Size (Input MBH): 142-75 (). Minimum CFM - 1350. Maximum CFM - 3000.

39) mmmmm.Size (Input MBH): 162-75 (). Minimum CFM - 1350. Maximum CFM - 3000.

40) nnnnn.Size (Input MBH): 184-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

41) ooooo.Size (Input MBH): 210-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

42) ppppp.Size (Input MBH): 222-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

43) qqqqq.Size (Input MBH): 224-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

44) rrrrr.Size (Input MBH): 236-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

45) sssss.Size (Input MBH): 248-75 (). Minimum CFM - 3600. Maximum CFM - 7500.

46) ttttt.Size (Input MBH): 262-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

47) uuuuu.Size (Input MBH): 272-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

48) vvvvv.Size (Input MBH): 288-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

49) wwwww.Size (Input MBH): 354-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

50) xxxxx.Size (Input MBH): 370-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

51) yyyyy.Size (Input MBH): 468-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

52) zzzzz.Size (Input MBH): 482-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

53) aaaaaa.Size (Input MBH): 248-88 (). Minimum CFM - 3600. Maximum CFM - 7500.

54) bbbbbb.Size (Input MBH): 262-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

55) cccccc.Size (Input MBH): 272-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

56) dddddd.Size (Input MBH): 288-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

57) eeeeee.Size (Input MBH): 354-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

58) ffffff.Size (Input MBH): 370-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

59) gggggg.Size (Input MBH): 468-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

60) hhhhhh.Size (Input MBH): 482-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

61) iiiiii.Size (Input MBH): 114-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

62) jjjjjj.Size (Input MBH): 142-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

63) kkkkkk.Size (Input MBH): 162-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

64) llllll.Size (Input MBH): 184-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

65) mmmmmm.Size (Input MBH): 210-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

15720-13

Page 14:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

66) nnnnnn.Size (Input MBH): 222-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

67) oooooo.Size (Input MBH): 224-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

68) pppppp.Size (Input MBH): 236-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

7. Construction - General:a. Furnish and install Modular Air Processing System for treatment of up to 100%

constant outside air per plans and specifications. Unit shall be completely factory assembled, tested, internally wired, fully charged with Refrigerant R410A, and shipped in one piece. Unit shall consist of insulated weather-tight casing with optional field installed outdoor intake hood, compressors, air-cooled condenser coils, condenser fans, evaporator coils, supply fan, motors and drives, and unit controls. Packaged Cooling and Heating Units shall carry an ETL listing.

8. Refrigerant System:a. Compressor systems shall be designed to provide 3 to 8-stage capacity

increment for treatment of up to 100% outside air with up to 80 degree F (27 degree C) dewpoint entering the unit. Hermetic compressors shall include a scroll design with internal pressure relief and motor temperature winding protection. Units shall be equipped with reversal rotation protection. Refrigeration protection shall include low and high pressure switches, refrigerant circuit frost protection, liquid line filters/dryers and service gage ports. Refrigeration control shall include thermal expansion valves, external equalizers and distributors for each compressor. Hot gas bypass options shall be available on all refrigerant stages in addition to multiple steps of capacity modulation to supplement discharge air control. The refrigerant system shall have an adjustable 5 minute minimum ON and minimum OFF timer circuit protection. The refrigerant circuit shall have an anti-cycle time in addition to the minimum ON/OFF timer that prevents the compressors from cycle on the minimum timer circuit.

** NOTE TO SPECIFIER ** Models RDB/RDDB/REDB only. Delete if not required.9. Reheat Systems:

a. Unit shall include a dedicated compressor and refrigeration circuit using full condenser reheat or total heat of rejection in the supply airstream. The circuit shall be capable of delivering a nominal 13 degree F to 17 degree F (-11 degree C to -8 degree C) temperature rise from the main evaporator temperature without the need for modulating the capacity for all entering outside air conditions. The method of reheat shall comply with ASHRAE 90.1 requirements. Dual compressor systems shall be designed to provide 4 to 8 stage capacity increment using integrated DDC control. The refrigerant circuits shall include thermal expansion valves with external equalizers. Service gage ports and refrigerant line filter dryers are factory installed as standard. Pre-cooling coils shall be two row depth with 6 fin per inch to minimize air pressure drop. The reheat coil position shall include a minimum separation of 4 inches (102 mm) from the cooling coil to eliminate re-evaporation of cooling coil condensate.

10. Evaporator and Condenser Coils:a. The refrigerant system shall include a horizontal discharge air cooled

condenser. The copper tube-aluminum plate fin evaporator coil is 4 rows with 15 fins per inch to meet SHR values of 0.60. All multi-circuit evaporator coils are of the interlaced and split face configuration to reduce the risk of coil freezing at part load. The evaporator coils shall be protected from frosting by a low temperature cutout. The coils shall be leak tested at the factory to ensure pressure integrity.

15720-14

Page 15:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

** NOTE TO SPECIFIER ** Delete if not required.1) Coils shall have ElectroFin coating for protection from corrosion.

b. The condenser coils shall be aluminum micro-channel type condensing coil.** NOTE TO SPECIFIER ** Delete if not required.

1) A coil guard shall be installed for protecting the condensing section.c. Units will ship completely charged for immediate operation upon installation and

check-out of the unit.11. Condensate Drain Pan:

a. The condensate drain pan shall be fabricated from stainless steel. The drain outlet shall be attached to a sloped drain pan with a minimum 1/8 inch per foot (10 mm per meter) slope. The sloped drain pan shall be of a removable design. The drain pain shall collect potential condensate from all evaporator/condenser coils and distributor area in the air stream to prevent blow-off condensate reaching unprotected bottom unit surfaces.

12. Heating System:** NOTE TO SPECIFIER ** MODELS RDCB/RDDB only. Delete if not required.

a. Heating shall be provided by a gas-fired heating section designed to provide a minimum 80% thermal efficiency throughout the modulated range.

** NOTE TO SPECIFIER ** Delete modulation not required.1) Provide an 8:1 power vented modulation.2) Provide a 16:1 power vented modulation.

b. The system shall modulate the gas and combustion air to maintain temperature setpoint and thermal efficiency. The heat exchanger shall be capable of 100 degree (F) temperature rise for 100% outside air treatment. The heating system shall be factory installed and design certified to ANSI Standard Z83.8/CSA 2.6.

** NOTE TO SPECIFIER ** Delete stainless alloy not required.1) The heat exchanger shall be 4 pass serpentine, non welded, constructed

of 409 stainless steel.2) The heat exchanger shall be 4 pass serpentine, non welded, constructed

of 316 stainless steel.c. The gas burner shall be direct spark, multi-try, with a flame sensing circuit

monitored by an electronic flame supervision system with 100% lockout via an integrated circuit board that incorporates LED diagnostics. Diagnostic codes shall include:

** NOTE TO SPECIFIER ** Delete diagnostic codes not required.1) Failed ignition.2) Primary limit failure.3) Value failure.4) Air sensor.5) Gas sensor.6) Fame sensor.

d. Certifications: The gas heat sections shall be and approved to ANSI Z83.8/CSA 2.6.

** NOTE TO SPECIFIER ** MODELS RECB/REDB only. Delete if not required.e. Manufacturer to provide factory installed electric resistance heat for unit. Unit

shall include field-replaceable heat sections. All heat sections are to be sub-fused.

** NOTE TO SPECIFIER ** Delete stage not required.1) Heat sections shall feature single stage capacity.2) Heat sections shall feature three stage capacity.

f. The packaged unit shall be certified to UL-1995 - UL Standards for Safety Heating & Cooling Equipment Second Edition: CAN/CSA C22.2 NO. 236-95.

g. Safety Features: Heat sections for unit shall feature factory installed:1) Automatic discharge air limit control.

15720-15

Page 16:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

2) Air proving pressure switch.3) Color coded wiring and matching terminal blocks.4) Circuit breaker protected transformers.

13. Cabinet:a. Outer casing is fabricated from G90 galvanized steel substrate with 60 gloss

painted finish coat. Structural members shall be 18 gauge (1.3 mm) with double-wall access doors. Roof panels shall be 20 gauge (1.0 mm) with double wall 2 inches (51 mm) insulation liner. The cabinet design shall prevent condensation forming on the outside of the unit casing in operation via a dedicated thermal break. Fully gasketed, hinged doors of double-wall construction shall provide access to filters, dampers, evaporator coils section, supply fan section. Provide hinged single wall construction doors for the heater section and control section. On hinged doors frequently used for service (i.e. filter and coil access) lift and turn style door handles that do not require the use of a tool to gain access shall be installed. The unit control panel section shall be laid out to provide separation of high and low voltage components per UL standards. The control panels shall be hinged for easy access to the unit controls. For ease of service, all electrical components will be clearly identified with 1/2 inch (13 mm) diameter self adhesive labels to match the unit specific wiring diagram. The low voltage and unit controller access electrical panel shall be physically isolated from the high voltage section. The open door to the control section reveals the wiring diagrams, DDC programming instructions and all manuals and literature protected and permanently attached to the cover. Control transformers will incorporate integral, resettable circuit breaker protection.

** NOTE TO SPECIFIER ** Delete if not required.b. A weatherproof convenience outlet shall be accessible from the outside of the

unit without the removal of any doors or access panels.14. Air Side:

a. The outdoor condenser fan shall be direct drive, statically and dynamically balanced, draw through in the vertical position. The condenser fan motor(s) shall be permanently lubricated and have built-in thermal overload protection.

** NOTE TO SPECIFIER ** Cabinet A, B, & C units only. Delete if not required.b. The centrifugal supply fan(s) shall be double-width, double-inlet fan with

forward curved blades mounted with adjustable pitch sheave drive assembly. Complete fan assemblies shall be statically and dynamically balanced in accordance with the latest ARI guideline and ANSI 2.19. All fan motors shall be thermally protected.

** NOTE TO SPECIFIER ** Delete if not required.1) Provide ball bearings with a minimum L10 life of 100,000.

** NOTE TO SPECIFIER ** Delete if not required.2) Provide the centrifugal supply fan(s) with bearings, drive, and motor

combinations for high static applications.** NOTE TO SPECIFIER ** Cabinet D units only. Delete if not required.

c. The supply fan(s) shall be backward inclined suitable for AMCA Class I operation. Wheels shall be SWSI and constructed of welded steel with airfoil blades, and dynamically balanced in 2 planes. Bearings shall be self-aligning, pillow block, ball bearing with provision for re-lubrication via extended lube lines and rated for a minimum L50 (average) life of 175,000 hours. Frame and bearing support shall be constructed of heavy gauge welded angle iron.

d. Motor shall be continuous duty, thermally protected, permanently lubricated, ball bearing with a 1.15 service factor. Electrical characteristics and enclosure per schedule. Drives are to be selected for 125% of driven horsepower. Blower pulleys shall be cast iron, variable speed. The fan system shall be fully vibration isolated using springs and flexible connectors. The fan system shall be

15720-16

Page 17:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

statically and dynamically balanced in accordance with the latest ARI guideline and ANSI 2.19.

** NOTE TO SPECIFIER ** Delete discharge direction not required.1) The unit shall provide horizontal discharge per the selection.2) The unit shall provide vertical discharge per the selection.

** NOTE TO SPECIFIER ** Optional VFD. Delete if not required.e. The Variable Frequency Drive shall be unit or field installed and electrically

matched to the supply motor characteristics. The unit shall have a swing choke to reduce harmonics. The VFD shall have IP21 enclosure rating.

** NOTE TO SPECIFIER ** Delete control not required.1) The VFD shall control the supply air to maintain CO2 setpoint.2) The VFD shall control the supply air to maintain building static pressure

setpoint.3) The VFD shall control the supply air to maintain the duct static pressure

setpoint.4) The VFD shall control the supply air by a manual High/Low wall selector.

15. Controls:a. The unit control panel section shall be laid out to provide separation of high and

low voltage components per UL Standards. The primary control panel shall be hinged for easy access. Controls shall be factory configured for the design application with both the required hardware, operating parameters, and typical default control setpoints. The controller is factory mounted on the unit and is pre-wired to the unit controls. The controller shall have visual (LED) status of power, running, and errors. LED indicators for transmit/receive for networks and for each of the 12 outputs. The unit shall have battery backup to maintain control program and data for a minimum of 10,000 hours during power outages. The controller shall have unit mounted display with two line 40 alpha/numeric character per line display providing full access to all commission variables, setpoints, alarms and diagnostic functions. The controller shall have BACnet (ARC156, MS/TP, and PTP) network communication available without the need for further programming or external devices. The control system shall have the capability to communicate using LonWorks protocol.

** NOTE TO SPECIFIER ** Delete if not required.b. Customer wall-mounted controls shall be available for providing:

1) Remote temperature adjustment.2) On/off -auto control.3) Damper adjustment.

c. Each unit shall be equipped with an air-proving switch to ensure proper blower operation prior to enabling cooling and heating functions. Cooling controls shall include minimum "on/off" compressor time delays and anti-cycling program to prevent unnecessary wear of compressor.

d. Commissioning control variables shall include outdoor setpoints for heating and cooling sequencing.

** NOTE TO SPECIFIER ** Delete setpoint type not required.1) Setpoints based on outdoor dry bulb, discharge or space temperature

setpoints and low limit discharge air settings for freeze protection.2) Setpoints based on outdoor dewpoint, discharge or space temperature

setpoints and low limit discharge air settings for freeze protection.e. The alarm functionality shall include low temperature, compressor failure,

sensor failure, smoke alarm, power failure, heating failure and supply fan failure. The failures shall protect the unit and displays a code at the unit's display and the optional wall mounted display. The unit will have test and diagnostics routines for services and start-up.

f. The control system shall be able to provide neutral air and space temperature control per the sequence of operation shown.

15720-17

Page 18:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

16. Outdoor Air Section:a. Outdoor air inlet hood shall include 1 inch (25 mm) permanent filters. Units

designed for 100% outside air intake only shall include an integrated transition section (without return air opening) designed specifically for 100% outside air introduction to allow uniform coil velocity and filter loading. The motorized damper shall be spring return for closure during unit shutdown or power interruption.

** NOTE TO SPECIFIER ** Delete air section damper type not required.1) Units shall have fully integrated factory installed 100% motorized outdoor

air damper.2) Units shall be available with fully integrated factory installed 100%

motorized outdoor damper and return damper.** NOTE TO SPECIFIER ** Delete air section damper control type not required.

3) The outsider air dampers shall be controlled to maintain CO2 setpoint.4) The outsider air dampers shall be controlled to maintain building static

pressure setpoint.5) The outsider air dampers shall be controlled by a manual High/Low wall

selector.6) The outsider air dampers shall be controlled to maintain economizer

settings.7) The outsider air dampers shall be controlled to maintain occupied and

unoccupied positions.17. Filters:

a. Filters shall mount integral within unit casing and be accessible through hinged access panel.

** NOTE TO SPECIFIER ** Delete filter type not required.1) Filters shall be 2 inches (51 mm) permanent aluminum - MERV8 rating.2) Filters shall be 2 inches (51 mm) disposable pleated - MERV8 rating.3) Filters shall 4 inches (102 mm) permanent aluminum.4) Filters shall be 4 inches (102 mm) disposable pleated - MERV8.5) Filters shall 4 inches (102 mm) disposable pleated MERV13.

18. Full Perimeter Curbs:a. The curbs available from the manufacturer shall be designed to meet the

National Roofing Contractors Association August 1985 guidelines for roof mounted installations. The roof curbs shall be 12 gauge (2.8 mm) zinc coated steel with a 2 inches by 6 inches (51 mm by 152 mm) nailer. Factory curb shall be required for systems requiring vertical discharge or return air connection. The curb is shipped knocked down with assembly instructions.

** NOTE TO SPECIFIER ** The MAPS®IV Series packaged rooftop units are designed to cool high volumes of outside air year-round for makeup air and ventilation applications. In addition, MAPSIV can provide significant capacities of space conditioning. The MAPS IV series all leverage the use of modulating scroll compressor technology to maintain desired leaving conditions. All MAPSIV products feature the Reznor IQ digital controller to fully integrate all operation and external sensing into a stand-alone package or through native BacNet®, into a building management system.Model RCC/RDC/RDCC/RDDC/RECC/REDC only. Delete if not required.

B. Packaged Rooftop Unit:** NOTE TO SPECIFIER ** Delete unit not required.

1. Unit: Modulating Capacity, Packaged Cooling/ Makeup Air units, R-410A Refrigerant:a. Model RCC as manufactured by REZNOR.

** NOTE TO SPECIFIER ** Delete size not required.b. Size: 060. Minimum CFM - 1350. Maximum CFM - 3000.c. Size: 090. Minimum CFM - 1350. Maximum CFM - 3000.

15720-18

Page 19:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

d. Size: 120. Minimum CFM - 1350. Maximum CFM - 3000.e. Size: 160. Minimum CFM - 2200. Maximum CFM - 4840.f. Size: 190. Minimum CFM - 3600. Maximum CFM - 9000.g. Size: 410. Minimum CFM - 3600. Maximum CFM - 9000.h. Size: 298. Minimum CFM - 3600. Maximum CFM - 9000.i. Size: 200. Minimum CFM - 2200. Maximum CFM - 4840.

2. Unit: Modulating Capacity, Packaged Cooling/ Makeup Air units with Dedicated Reheat Pump Dehumidification, R-410A Refrigerant:a. Model RDC as manufactured by REZNOR.

** NOTE TO SPECIFIER ** Delete size not required.b. Size: 114. Minimum CFM - 1350. Maximum CFM - 3000.c. Size: 144. Minimum CFM - 1350. Maximum CFM - 3000.d. Size: 184. Minimum CFM - 2000. Maximum CFM - 5000.e. Size: 196. Minimum CFM - 2000. Maximum CFM - 5000.f. Size: 236. Minimum CFM - 2000. Maximum CFM - 5000.g. Size: 248. Minimum CFM - 3600. Maximum CFM - 9000.h. Size: 257. Minimum CFM - 2000. Maximum CFM - 5000.i. Size: 262. Minimum CFM - 3600. Maximum CFM - 9000.j. Size: 354. Minimum CFM - 3600. Maximum CFM - 9000.k. Size: 370. Minimum CFM - 3600. Maximum CFM - 9000.l. Size: 468. Minimum CFM - 3600. Maximum CFM - 9000.m. Size: 482. Minimum CFM - 3600. Maximum CFM - 9000.n. Size: 084. Minimum CFM - 1350. Maximum CFM - 3000.

3. Unit: Packaged Rooftop, Gas Heat, DX Cooling Makeup Air System for Commercial / Industrial Use, R410-A Refrigerant:a. Model RDCC as manufactured by REZNOR.b. Units are 82% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.c. Size-Input MBH: 060-100. Minimum CFM - 1350. Maximum CFM - 1650.d. Size-Input MBH: 090-100. Minimum CFM - 1350. Maximum CFM - 1650.e. Size-Input MBH: 120-100. Minimum CFM - 1350. Maximum CFM - 1650.f. Size-Input MBH: 060-150. Minimum CFM - 1350. Maximum CFM - 2500.g. Size-Input MBH: 090-150. Minimum CFM - 1350. Maximum CFM - 2500.h. Size-Input MBH: 120-150. Minimum CFM - 1350. Maximum CFM - 2500.i. Size-Input MBH: 060-200. Minimum CFM - 1480. Maximum CFM - 3300.j. Size-Input MBH: 090-200. Minimum CFM - 1480. Maximum CFM - 3300.k. Size-Input MBH: 120-200. Minimum CFM - 1480. Maximum CFM - 3300.l. Size-Input MBH: 090-250. Minimum CFM - 2220. Maximum CFM - 4940.m. Size-Input MBH: 120-250. Minimum CFM - 2220. Maximum CFM - 4940.n. Size-Input MBH: 160-250. Minimum CFM - 2220. Maximum CFM - 4940.o. Size-Input MBH: 200-250. Minimum CFM - 2220. Maximum CFM - 4940.p. Size-Input MBH: 090-300. Minimum CFM - 2220. Maximum CFM - 4940.q. Size-Input MBH: 120-300. Minimum CFM - 2220. Maximum CFM - 4940.r. Size-Input MBH: 160-300. Minimum CFM - 2220. Maximum CFM - 4940.s. Size-Input MBH: 200-300. Minimum CFM - 2220. Maximum CFM - 4940.t. Size-Input MBH: 190-400. Minimum CFM - 3000. Maximum CFM - 9000.u. Size-Input MBH: 298-400. Minimum CFM - 3000. Maximum CFM - 9000.v. Size-Input MBH: 410-400. Minimum CFM - 3000. Maximum CFM - 9000.w. Size-Input MBH: 190-500. Minimum CFM - 3500. Maximum CFM - 9000.x. Size-Input MBH: 298-500. Minimum CFM - 3500. Maximum CFM - 9000.y. Size-Input MBH: 410-500. Minimum CFM - 3500. Maximum CFM - 9000.z. Size-Input MBH: 190-600. Minimum CFM - 3500. Maximum CFM - 9000.aa. Size-Input MBH: 298-600. Minimum CFM - 3500. Maximum CFM - 9000.bb. Size-Input MBH: 410-600. Minimum CFM - 3500. Maximum CFM - 9000.cc. Size-Input MBH: 190-700. Minimum CFM - 3500. Maximum CFM - 9000.

15720-19

Page 20:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

dd. Size-Input MBH: 298-700. Minimum CFM - 3500. Maximum CFM - 9000.ee. Size-Input MBH: 410-700. Minimum CFM - 3500. Maximum CFM - 9000.

4. Unit: Modulating Capacity, Packaged Cooling/Gas Heating Makeup Air units with Dedicated Reheat Pump Dehumidification, R-410A Refrigerant:a. Model RDDC as manufactured by REZNOR.b. Units are 82% efficient output MBH.

** NOTE TO SPECIFIER ** Delete size not required.c. Size-Input MBH: 084-100. Minimum CFM - 1350. Maximum CFM - 1650.d. Size-Input MBH: 114-100. Minimum CFM - 1350. Maximum CFM - 1650.e. Size-Input MBH: 144-100. Minimum CFM - 1350. Maximum CFM - 1650.f. Size-Input MBH: 084-150. Minimum CFM - 1350. Maximum CFM - 2500.g. Size-Input MBH: 114-150. Minimum CFM - 1350. Maximum CFM - 2500.h. Size-Input MBH: 144-150. Minimum CFM - 1350. Maximum CFM - 2500.i. Size-Input MBH: 084-200. Minimum CFM - 1480. Maximum CFM - 3300.j. Size-Input MBH: 114-200. Minimum CFM - 1480. Maximum CFM - 3300.k. Size-Input MBH: 144-200. Minimum CFM - 1480. Maximum CFM - 3300.l. Size-Input MBH: 114-250. Minimum CFM - 2220. Maximum CFM - 4940.m. Size-Input MBH: 144-250. Minimum CFM - 2220. Maximum CFM - 4940.n. Size-Input MBH: 184-250. Minimum CFM - 2220. Maximum CFM - 4940.o. Size-Input MBH: 196-250. Minimum CFM - 2220. Maximum CFM - 4940.p. Size-Input MBH: 236-250. Minimum CFM - 2220. Maximum CFM - 4940.q. Size-Input MBH: 257-250. Minimum CFM - 2220. Maximum CFM - 4940.r. Size-Input MBH: 114-300. Minimum CFM - 2220. Maximum CFM - 4940.s. Size-Input MBH: 144-300. Minimum CFM - 2220. Maximum CFM - 4940.t. Size-Input MBH: 184-300. Minimum CFM - 2220. Maximum CFM - 4940.u. Size-Input MBH: 196-300. Minimum CFM - 2220. Maximum CFM - 4940.v. Size-Input MBH: 236-300. Minimum CFM - 2220. Maximum CFM - 4940.w. Size-Input MBH: 257-300. Minimum CFM - 2220. Maximum CFM - 4940.x. Size-Input MBH: 248-400. Minimum CFM - 3000. Maximum CFM - 9000.y. Size-Input MBH: 262-400. Minimum CFM - 3000. Maximum CFM - 9000.z. Size-Input MBH: 354-400. Minimum CFM - 3000. Maximum CFM - 9000.aa. Size-Input MBH: 370-400. Minimum CFM - 3000. Maximum CFM - 9000.bb. Size-Input MBH: 468-400. Minimum CFM - 3000. Maximum CFM - 9000.cc. Size-Input MBH: 482-400. Minimum CFM - 3000. Maximum CFM - 9000.dd. Size-Input MBH: 248-500. Minimum CFM - 3500. Maximum CFM - 9000.ee. Size-Input MBH: 262-500. Minimum CFM - 3500. Maximum CFM - 9000.ff. Size-Input MBH: 354-500. Minimum CFM - 3500. Maximum CFM - 9000.gg. Size-Input MBH: 370-500. Minimum CFM - 3500. Maximum CFM - 9000.hh. Size-Input MBH: 468-500. Minimum CFM - 3500. Maximum CFM - 9000.ii. Size-Input MBH: 482-500. Minimum CFM - 3500. Maximum CFM - 9000.jj. Size-Input MBH: 248-600. Minimum CFM - 3500. Maximum CFM - 9000.kk. Size-Input MBH: 262-600. Minimum CFM - 3500. Maximum CFM - 9000.ll. Size-Input MBH: 354-600. Minimum CFM - 3500. Maximum CFM - 9000.mm. Size-Input MBH: 370-600. Minimum CFM - 3500. Maximum CFM - 9000.nn. Size-Input MBH: 468-600. Minimum CFM - 3500. Maximum CFM - 9000.oo. Size-Input MBH: 482-600. Minimum CFM - 3500. Maximum CFM - 9000.pp. Size-Input MBH: 248-700. Minimum CFM - 3500. Maximum CFM - 9000.qq. Size-Input MBH: 262-700. Minimum CFM - 3500. Maximum CFM - 9000.rr. Size-Input MBH: 354-700. Minimum CFM - 3500. Maximum CFM - 9000.ss. Size-Input MBH: 370-700. Minimum CFM - 3500. Maximum CFM - 9000.tt. Size-Input MBH: 468-700. Minimum CFM - 3500. Maximum CFM - 9000.uu. Size-Input MBH: 482-700. Minimum CFM - 3500. Maximum CFM - 9000.

5. Unit: Modulating Capacity, Packaged Cooling/Electric Heating, Makeup Air units, R-410A Refrigerant:a. Model RECC as manufactured by REZNOR.b. Units are 100% efficient output MBH.

15720-20

Page 21:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

** NOTE TO SPECIFIER ** Delete size not required.c. Size (Input MBH): 060-10S (34). Minimum CFM - 1350. Maximum CFM - 3000.d. Size (Input MBH): 060-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.e. Size (Input MBH): 060-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.f. Size (Input MBH): 090-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.g. Size (Input MBH): 090-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.h. Size (Input MBH): 120-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.i. Size (Input MBH): 120-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.j. Size (Input MBH): 160-15 (51). Minimum CFM - 2000. Maximum CFM - 5000.k. Size (Input MBH): 060-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.l. Size (Input MBH): 060-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.m. Size (Input MBH): 090-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.n. Size (Input MBH): 090-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.o. Size (Input MBH): 120-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.p. Size (Input MBH): 120-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.q. Size (Input MBH): 160-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.r. Size (Input MBH): 200-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.s. Size (Input MBH): 060-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.t. Size (Input MBH): 090-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.u. Size (Input MBH): 120-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.v. Size (Input MBH): 060-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.w. Size (Input MBH): 090-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.x. Size (Input MBH): 120-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.y. Size (Input MBH): 160-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.z. Size (Input MBH): 200-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.aa. Size (Input MBH): 060-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.bb. Size (Input MBH): 090-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.cc. Size (Input MBH): 120-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.dd. Size (Input MBH): 160-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.ee. Size (Input MBH): 200-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.ff. Size (Input MBH): 060-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.gg. Size (Input MBH): 090-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.hh. Size (Input MBH): 120-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.ii. Size (Input MBH): 160-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.jj. Size (Input MBH): 200-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.kk. Size (Input MBH): 060-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.ll. Size (Input MBH): 090-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.mm. Size (Input MBH): 120-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.nn. Size (Input MBH): 160-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.oo. Size (Input MBH): 190-39 (133). Minimum CFM - 3600. Maximum CFM - 7500.pp. Size (Input MBH): 200-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.qq. Size (Input MBH): 298-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.rr. Size (Input MBH): 410-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.ss. Size (Input MBH): 090-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.tt. Size (Input MBH): 120-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.uu. Size (Input MBH): 160-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.vv. Size (Input MBH): 200-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.ww. Size (Input MBH): 298-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.xx. Size (Input MBH): 410-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.yy. Size (Input MBH): 090-60 (205). Minimum CFM - 1350. Maximum CFM - 3000.zz. Size (Input MBH): 120-60 (205). Minimum CFM - 1350. Maximum CFM - 3000.aaa. Size (Input MBH): 160-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.bbb. Size (Input MBH): 190-60 (205). Minimum CFM - 3600. Maximum CFM - 7500.ccc. Size (Input MBH): 200-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.ddd. Size (Input MBH): 298-60 (205). Minimum CFM - 3600. Maximum CFM - 9000.eee. Size (Input MBH): 410-60 (205). Minimum CFM - 3600. Maximum CFM - 9000.

15720-21

Page 22:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

fff. Size (Input MBH): 090-75 (256). Minimum CFM - 1350. Maximum CFM - 3000.ggg. Size (Input MBH): 120-75 (256). Minimum CFM - 1350. Maximum CFM - 3000.hhh. Size (Input MBH): 160-75 (256). Minimum CFM - 2000. Maximum CFM - 5000.iii. Size (Input MBH): 200-75 (256). Minimum CFM - 2000. Maximum CFM - 5000.jjj. Size (Input MBH): 190-75 (259). Minimum CFM - 3600. Maximum CFM - 7500.kkk. Size (Input MBH): 298-75 (259). Minimum CFM - 3600. Maximum CFM - 9000.lll. Size (Input MBH): 410-75 (259). Minimum CFM - 3600. Maximum CFM - 9000.mmm. Size (Input MBH): 190-88 (300). Minimum CFM - 3600. Maximum CFM -

7500.nnn. Size (Input MBH): 298-88 (300). Minimum CFM - 3600. Maximum CFM - 9000.ooo. Size (Input MBH): 410-88 (300). Minimum CFM - 3600. Maximum CFM - 9000.ppp. Size (Input MBH): 090-88 (301). Minimum CFM - 1350. Maximum CFM - 3000.qqq. Size (Input MBH): 120-88 (301). Minimum CFM - 1350. Maximum CFM - 3000.rrr. Size (Input MBH): 160-88 (301). Minimum CFM - 2000. Maximum CFM - 5000.sss. Size (Input MBH): 200-88 (301). Minimum CFM - 2000. Maximum CFM - 5000.

6. Unit: Modulating Capacity, Packaged Cooling/Electric Heating Makeup Air units with Dedicated Reheat Pump Dehumidification, R-410A Refrigerant:a. Model REDC as manufactured by REZNOR.b. Size (Input MBH): 084-10S (34). Minimum CFM - 1350. Maximum CFM - 3000.c. Size (Input MBH): 084-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.d. Size (Input MBH): 084-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.e. Size (Input MBH): 114-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.f. Size (Input MBH): 114-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.g. Size (Input MBH): 144-15 (51). Minimum CFM - 1350. Maximum CFM - 3000.h. Size (Input MBH): 144-15S (51). Minimum CFM - 1350. Maximum CFM - 3000.i. Size (Input MBH): 184-15 (51). Minimum CFM - 2000. Maximum CFM - 5000.j. Size (Input MBH): 084-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.k. Size (Input MBH): 084-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.l. Size (Input MBH): 114-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.m. Size (Input MBH): 114-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.n. Size (Input MBH): 144-20 (68). Minimum CFM - 1350. Maximum CFM - 3000.o. Size (Input MBH): 144-20S (68). Minimum CFM - 1350. Maximum CFM - 3000.p. Size (Input MBH): 184-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.q. Size (Input MBH): 196-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.r. Size (Input MBH): 236-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.s. Size (Input MBH): 257-20 (68). Minimum CFM - 2000. Maximum CFM - 5000.t. Size (Input MBH): 084-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.u. Size (Input MBH): 114-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.v. Size (Input MBH): 144-24S (82). Minimum CFM - 1350. Maximum CFM - 3000.w. Size (Input MBH): 084-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.x. Size (Input MBH): 114-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.y. Size (Input MBH): 144-25 (85). Minimum CFM - 1350. Maximum CFM - 3000.z. Size (Input MBH): 184-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.aa. Size (Input MBH): 196-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.bb. Size (Input MBH): 236-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.cc. Size (Input MBH): 257-25 (85). Minimum CFM - 2000. Maximum CFM - 5000.dd. Size (Input MBH): 084-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.ee. Size (Input MBH): 114-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.ff. Size (Input MBH): 144-30 (102). Minimum CFM - 1350. Maximum CFM - 3000.gg. Size (Input MBH): 184-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.hh. Size (Input MBH): 196-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.ii. Size (Input MBH): 236-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.jj. Size (Input MBH): 257-30 (102). Minimum CFM - 2000. Maximum CFM - 5000.kk. Size (Input MBH): 084-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.ll. Size (Input MBH): 114-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.mm. Size (Input MBH): 144-35 (120). Minimum CFM - 1350. Maximum CFM - 3000.

15720-22

Page 23:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

nn. Size (Input MBH): 184-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.oo. Size (Input MBH): 196-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.pp. Size (Input MBH): 236-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.qq. Size (Input MBH): 257-35 (120). Minimum CFM - 2000. Maximum CFM - 5000.rr. Size (Input MBH): 084-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.ss. Size (Input MBH): 114-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.tt. Size (Input MBH): 144-39 (133). Minimum CFM - 1350. Maximum CFM - 3000.uu. Size (Input MBH): 184-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.vv. Size (Input MBH): 196-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.ww. Size (Input MBH): 236-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.xx. Size (Input MBH): 248-39 (133). Minimum CFM - 3600. Maximum CFM - 7500.yy. Size (Input MBH): 257-39 (133). Minimum CFM - 2000. Maximum CFM - 5000.zz. Size (Input MBH): 262-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.aaa. Size (Input MBH): 354-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.bbb. Size (Input MBH): 370-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.ccc. Size (Input MBH): 468-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.ddd. Size (Input MBH): 482-39 (133). Minimum CFM - 3600. Maximum CFM - 9000.eee. Size (Input MBH): 114-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.fff. Size (Input MBH): 144-50 (171). Minimum CFM - 1350. Maximum CFM - 3000.ggg. Size (Input MBH): 184-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.hhh. Size (Input MBH): 196-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.iii. Size (Input MBH): 236-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.jjj. Size (Input MBH): 248-50 (171). Minimum CFM - 3600. Maximum CFM - 7500.kkk. Size (Input MBH): 257-50 (171). Minimum CFM - 2000. Maximum CFM - 5000.lll. Size (Input MBH): 262-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.mmm. Size (Input MBH): 354-50 (171). Minimum CFM - 3600. Maximum CFM -

9000.nnn. Size (Input MBH): 370-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.ooo. Size (Input MBH): 468-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.ppp. Size (Input MBH): 482-50 (171). Minimum CFM - 3600. Maximum CFM - 9000.qqq. Size (Input MBH): 114-60 (205). Minimum CFM - 1350. Maximum CFM - 3000.rrr. Size (Input MBH): 144-60 (205). Minimum CFM - 1350. Maximum CFM - 3000.sss. Size (Input MBH): 184-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.ttt. Size (Input MBH): 196-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.uuu. Size (Input MBH): 236-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.vvv. Size (Input MBH): 248-60 (205). Minimum CFM - 3600. Maximum CFM - 7500.www. Size (Input MBH): 257-60 (205). Minimum CFM - 2000. Maximum CFM - 5000.xxx. Size (Input MBH): 262-60 (205). Minimum CFM - 3600. Maximum CFM - 9000.yyy. Size (Input MBH): 354-60 (205). Minimum CFM - 3600. Maximum CFM - 9000.zzz. Size (Input MBH): 370-60 (205). Minimum CFM - 3600. Maximum CFM - 9000.

1) aaaa.Size (Input MBH): 468-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

2) bbbb.Size (Input MBH): 482-60 (). Minimum CFM - 3600. Maximum CFM - 9000.

3) cccc.Size (Input MBH): 114-75 (). Minimum CFM - 1350. Maximum CFM - 3000.

4) dddd.Size (Input MBH): 44-75 (256). Minimum CFM - 1350. Maximum CFM - 3000.

5) eeee.Size (Input MBH): 184-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

6) ffff.Size (Input MBH): 96-75 (256). Minimum CFM - 2000. Maximum CFM - 5000.

7) gggg.Size (Input MBH): 236-75 (). Minimum CFM - 2000. Maximum CFM - 5000.

8) hhhh.Size (Input MBH): 248-75 (). Minimum CFM - 3600. Maximum CFM - 7500.

15720-23

Page 24:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

9) iiii.Size (Input MBH): 57-75 (256). Minimum CFM - 2000. Maximum CFM - 5000.

10) jjjj.Size (Input MBH): 262-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

11) kkkk.Size (Input MBH): 354-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

12) llll.Size (Input MBH): 370-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

13) mmmm.Size (Input MBH): 468-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

14) nnnn.Size (Input MBH): 482-75 (). Minimum CFM - 3600. Maximum CFM - 9000.

15) oooo.Size (Input MBH): 248-88 (). Minimum CFM - 3600. Maximum CFM - 7500.

16) pppp.Size (Input MBH): 262-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

17) qqqq.Size (Input MBH): 354-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

18) rrrr.Size (Input MBH): 370-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

19) ssss.Size (Input MBH): 468-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

20) tttt.Size (Input MBH): 482-88 (). Minimum CFM - 3600. Maximum CFM - 9000.

21) uuuu.Size (Input MBH): 114-88 (). Minimum CFM - 1350. Maximum CFM - 3000.

22) vvvv.Size (Input MBH): 44-88 (301). Minimum CFM - 1350. Maximum CFM - 3000.

23) wwww.Size (Input MBH): 184-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

24) xxxx.Size (Input MBH): 96-88 (301). Minimum CFM - 2000. Maximum CFM - 5000.

25) yyyy.Size (Input MBH): 236-88 (). Minimum CFM - 2000. Maximum CFM - 5000.

26) zzzz.Size (Input MBH): 57-88 (301). Minimum CFM - 2000. Maximum CFM - 5000.

7. Construction - General:a. Furnish and install Modular Air Processing System for treatment of up to 100%

constant outside air per plans and specifications. Unit shall be completely factory assembled, tested, internally wired, fully charged with Refrigerant R410A, and shipped in one piece. Unit shall consist of insulated weather-tight casing with optional field installed outdoor intake hood, modulated capacity scroll compressors, air-cooled condenser coils, condenser fans, evaporator coils, supply fan, motors and drives, and unit controls. Packaged Cooling and Heating Units shall carry an ETL listing.

8. Refrigerant System:a. Compressor systems shall be designed to provide 10 to 100% capacity control

for treatment of up to 100% outside air with up to 80 degree F (27 degree C) dewpoint entering the unit. Hermetic compressors shall include a scroll design with internal pressure relief and motor temperature winding protection. Units shall be equipped with reversal rotation protection. Refrigeration protection shall include low and high pressure switches, refrigerant circuit frost protection, liquid line filters/dryers and service gage ports. Refrigeration control shall include thermal expansion valves, external equalizers and distributors for each compressor. Hot gas bypass options shall be available on all refrigerant stages in addition to multiple steps of capacity modulation to supplement discharge air

15720-24

Page 25:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

control. The refrigerant system shall have an adjustable 5 minute minimum ON and minimum OFF timer circuit protection. The refrigerant circuit shall have an anti-cycle time in addition to the minimum ON/OFF timer that prevents the compressors from cycle on the minimum timer circuit.

9. Reheat Systems:** NOTE TO SPECIFIER ** RDC/RDDC/REDC only. Delete if not required.

a. Models shall include a dedicated compressor and refrigeration circuit using full condenser reheat or total heat of rejection in the supply airstream. The circuit shall be capable of delivering a nominal 13 degree F to 17 degree F (-11 degree C to -8 degree C) temperature rise from the main evaporator temperature without the need for modulating the capacity for all entering outside air conditions. Reheat shall comply with ASHRAE 90.1 requirements.

b. Dual compressor systems shall be designed to provide 4 to 8 stage capacity increment using integrated DDC control. The refrigerant circuits shall include thermal expansion valves with external equalizers. Service gage ports and refrigerant line filter dryers are factory installed as standard. Pre-cooling coils shall be two row depth with 6 fin per inch to minimize air pressure drop. The reheat coil position shall include a minimum separation of 4 inches (102 mm) from the cooling coil to eliminate re-evaporation of cooling coil condensate.

10. Evaporator and Condenser Coils:a. The refrigerant system shall include a horizontal discharge air cooled

condenser. The copper tube-aluminum plate fin evaporator coil to be 4 rows with 15 fins per inch to meet SHR values of 0.60. All multi-circuit evaporator coils are of the interlaced and split face configuration to reduce the risk of coil freezing at part load. The evaporator coils shall be protected from frosting by a low temperature cutout. The coils shall be leak tested at the factory to ensure pressure integrity.

** NOTE TO SPECIFIER ** Delete if not required.1) Coils shall have ElectroFin coating for protection from corrosion.

b. The condenser coils shall be aluminum micro-channel type condensing coil.** NOTE TO SPECIFIER ** Delete if not required.

1) A coil guard shall be installed for protecting the condensing section.c. Units will ship completely charged for immediate operation upon installation and

check-out of the unit.11. Condensate Drain Pan:

a. The condensate drain pan shall be fabricated from stainless steel. The drain outlet shall be attached to a sloped drain pan with a minimum 1/8 inch per foot (10 mm per meter) slope. The sloped drain pan shall be of a removable design. The drain pain shall collect potential condensate from all evaporator/condenser coils and distributor area in the air stream to prevent blow-off condensate reaching unprotected bottom unit surfaces.

12. Heating System:** NOTE TO SPECIFIER ** Models RDCC/RDDC only. Delete if not required.

a. Heating shall be provided by a gas-fired heating section designed to provide a minimum 80% thermal efficiency throughout the modulated range.

** NOTE TO SPECIFIER ** Delete modulation not required.1) Provide an 8:1 power vented modulation.2) Provide a 16:1 power vented modulation.

b. The system shall modulate the gas and combustion air to maintain temperature setpoint and thermal efficiency. The heat exchanger shall be capable of 100 degree (F) temperature rise for 100% outside air treatment. The heating system shall be factory installed and design certified to ANSI Standard Z83.8/CSA 2.6.

** NOTE TO SPECIFIER ** Delete stainless alloy not required.1) The heat exchanger shall be 4 pass serpentine, non welded, constructed

15720-25

Page 26:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

of 409 stainless steel.2) The heat exchanger shall be 4 pass serpentine, non welded, constructed

of 316 stainless steel.c. The gas burner shall be direct spark, multi-try, with a flame sensing circuit

monitored by an electronic flame supervision system with 100% lockout via an integrated circuit board that incorporates LED diagnostics. Diagnostic codes shall include:

** NOTE TO SPECIFIER ** Delete diagnostic codes not required.1) Failed ignition.2) Primary limit failure.3) Value failure.4) Air sensor.5) Gas sensor.6) Fame sensor.

d. Certifications: The gas heat sections shall be and approved to ANSI Z83.8/CSA 2.6.

** NOTE TO SPECIFIER ** Models RECC/REDC only. Delete if not required.e. Manufacturer to provide factory installed electric resistance heat for unit. Unit

shall include field-replaceable heat sections. All heat sections are to be sub-fused.

** NOTE TO SPECIFIER ** Delete stage not required.1) Heat sections shall feature single stage capacity.2) Heat sections shall feature three stage capacity.

f. The packaged unit shall be certified to UL-1995 - UL Standards for Safety Heating & Cooling Equipment Second Edition: CAN/CSA C22.2 NO. 236-95.

g. Safety Features: All heat sections for said unit shall feature factory installed:1) Automatic discharge air limit Control.2) Air proving pressure switch.3) Color coded wiring and matching terminal blocks.4) Circuit breaker protected transformers.

13. Cabinet:a. Outer casing is fabricated from G90 galvanized steel substrate with 60 gloss

painted finish coat. Structural members shall be 18 gauge (1.3 mm) with double-wall access doors. Roof panels shall be 20 gauge (1.0 mm) with double wall 2 inches (51 mm) insulation liner. The cabinet design shall prevent condensation forming on the outside of the unit casing in operation via a dedicated thermal break. Fully-gasketed, hinged doors of double-wall construction shall provide access to filters, dampers, evaporator coils section, supply fan section. Provide hinged single wall construction doors for the heater section and control section. On hinged doors frequently used for service (i.e. filter and coil access) lift and turn style door handles that do not require the use of a tool to gain access will be used. The unit control panel section shall be laid out to provide separation of high and low voltage components per UL standards. The control panels shall be hinged for easy access to the unit controls. For ease of service, electrical components will be clearly identified with 1/2 inch (13 mm) diameter self adhesive labels to match the unit specific wiring diagram. The low voltage and unit controller access electrical panel shall be physically isolated from the high voltage section. The open door to the control section reveals the wiring diagrams, DDC programming instructions and manuals and literature protected and permanently attached to the cover. Control transformers will incorporate integral, resettable circuit breaker protection.

** NOTE TO SPECIFIER ** Delete if not required.b. A weatherproof convenience outlet shall be accessible from the outside of the

unit without the removal of any doors or access panels.

15720-26

Page 27:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

14. Air Side:a. The outdoor condenser fan shall be direct drive, statically and dynamically

balanced, draw through in the vertical position. The condenser fan motor(s) shall be permanently lubricated and have built-in thermal overload protection.

** NOTE TO SPECIFIER ** Cabinet A, B, & C Units only. Delete if not required.b. The centrifugal supply fan(s) shall be double-width, double-inlet fan with

forward curved blades mounted with adjustable pitch sheave drive assembly. Complete fan assemblies shall be statically and dynamically balanced in accordance with the latest ARI guideline and ANSI 2.19. All fan motors shall be thermally protected.

** NOTE TO SPECIFIER ** Delete if not required.1) Provide ball bearings with a minimum L10 life of 100,000.

** NOTE TO SPECIFIER ** Delete if not required.2) Provide the centrifugal supply fan(s) with bearings, drive, and motor

combinations for high static applications.** NOTE TO SPECIFIER ** Cabinet D Units only. Delete if not required.

c. The supply fan(s) shall be backward inclined suitable for AMCA Class I operation. Wheels shall be SWSI and constructed of welded steel with airfoil blades, and dynamically balanced in 2 planes. Bearings shall be self-aligning, pillow block, ball bearing with provision for re-lubrication via extended lube lines and rated for a minimum L50 (average) life of 175,000 hours. Frame and bearing support shall be constructed of heavy gauge welded angle iron.

d. Motor shall be continuous duty, thermally protected, permanently lubricated, ball bearing with a 1.15 service factor. Electrical characteristics and enclosure per schedule. Drives are to be selected for 125% of driven horsepower. Blower pulleys shall be cast iron, variable speed. The fan system shall be fully vibration isolated using springs and flexible connectors. The fan system shall be statically and dynamically balanced in accordance with the latest ARI guideline and ANSI 2.19.

** NOTE TO SPECIFIER ** Delete discharge direction not required.1) The unit shall provide horizontal discharge per the selection.2) The unit shall provide vertical discharge per the selection.

** NOTE TO SPECIFIER ** Optional VFD : Delete if not required.e. The Variable frequency drive shall be unit or field installed and electrically

matched to the supply motor characteristics. The unit shall have a swing choke to reduce harmonics. The VFD shall have IP21 enclosure rating.

** NOTE TO SPECIFIER ** Delete control not required.1) The VFD shall control the supply air to maintain CO2 setpoint.2) The VFD shall control the supply air to maintain building static pressure

setpoint.3) The VFD shall control the supply air to maintain the duct static pressure

setpoint.4) The VFD shall control the supply air by a manual High/Low wall selector.

15. Controls:a. The unit control panel section shall be laid out to provide separation of high and

low voltage components per UL Standards. The primary control panel shall be hinged for easy access. Controls shall be factory configured for the design application with both the required hardware, operating parameters, and typical default control setpoints. The controller is factory mounted on the unit and is pre-wired to the unit controls. The controller shall have visual (LED) status of power, running, and errors. LED indicators for transmit/receive for networks and for each of the 12 outputs. The unit shall have battery backup to maintain control program and data for a minimum of 10,000 hours during power outages. The controller shall have unit mounted display with two line 40 alpha/numeric

15720-27

Page 28:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

character per line display providing full access to all commission variables, setpoints, alarms and diagnostic functions. The controller shall have BACnet (ARC156, MS/TP, and PTP) network communication available without the need for further programming or external devices. The control system shall have the capability to communicate using LonWorks protocol.

** NOTE TO SPECIFIER ** Delete if not required.b. Customer wall-mounted controls shall be available for providing:

1) Remote temperature adjustment.2) On/off -auto control.3) Damper adjustment.

c. Each unit shall be equipped with an air-proving switch to ensure proper blower operation prior to enabling cooling and heating functions. Cooling controls shall include minimum "on/off" compressor time delays and anti-cycling program to prevent unnecessary wear of compressor.

d. Commissioning control variables shall include outdoor setpoints for heating and cooling sequencing.

** NOTE TO SPECIFIER ** Delete setpoint type not required.1) Setpoints based on outdoor dry bulb, discharge or space temperature

setpoints and low limit discharge air settings for freeze protection.2) Setpoints based on outdoor dewpoint, discharge or space temperature

setpoints and low limit discharge air settings for freeze protection.e. The alarm functionality shall include low temperature, compressor failure,

sensor failure, smoke alarm, power failure, heating failure and supply fan failure. The failures shall protect the unit and displays a code at the unit's display and the optional wall mounted display. The unit will have test and diagnostics routines for services and start-up.

f. The control system shall be able to provide neutral air and space temperature control per the sequence of operation shown.

16. Outdoor Air Section:a. Outdoor air inlet hood shall include 1 inch (25 mm) permanent filters. Units

designed for 100% outside air intake only shall include an integrated transition section (without return air opening) designed specifically for 100% outside air introduction to allow uniform coil velocity and filter loading. The motorized damper shall be spring return for closure during unit shutdown or power interruption.

** NOTE TO SPECIFIER ** Delete air section damper type not required.1) Units shall have fully integrated factory installed 100% motorized outdoor

air damper.2) Units shall be available with fully integrated factory installed 100%

motorized outdoor damper and return damper.** NOTE TO SPECIFIER ** Delete air section damper control type not required.

3) The outsider air dampers shall be controlled to maintain CO2 setpoint.4) The outsider air dampers shall be controlled to maintain building static

pressure setpoint.5) The outsider air dampers shall be controlled by a manual High/Low wall

selector.6) The outsider air dampers shall be controlled to maintain economizer

settings.7) The outsider air dampers shall be controlled to maintain occupied and

unoccupied positions.17. Filters:

a. Filters shall mount integral within unit casing and be accessible through hinged access panel.

** NOTE TO SPECIFIER ** Delete filter type not required.1) Filters shall be 2 inches (51 mm) permanent aluminum - MERV8 rating.

15720-28

Page 29:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

2) Filters shall be 2 inches (51 mm) disposable pleated - MERV8 rating.3) Filters shall 4 inches (102 mm) permanent aluminum.4) Filters shall be 4 inches (102 mm) disposable pleated - MERV8.5) Filters shall 4 inches (102 mm) disposable pleated MERV13.

18. Full Perimeter Curbs:a. The curbs available from the manufacturer shall be designed to meet the

National Roofing Contractors Association August 1985 guidelines for roof mounted installations. The roof curbs shall be 12 gauge (2.8 mm) zinc coated steel with a 2 inches by 6 inches (51 mm by 152 mm) nailer. Factory curb shall be required for systems requiring vertical discharge or return air connection. The curb is shipped knocked down with assembly instructions.

** NOTE TO SPECIFIER ** Air Rotation equipment can lower heating costs by de-stratifying the air in: Warehouses. Factories. Covered Recreational Areas (Tennis Courts, etc.) Delete if not required.

2.3 AIR TURNOVER

A. Vertical Air Turnover Unit:1. Unit: Reznor Model AEB indirect fired units.2. Construction - General:

a. Provide an indirect fired air turnover unit with power burner. The configuration shall be as detailed on the drawings. The heater shall be in accordance to ANSI requirements. The entire unit shall be ETL certified, listed and labeled.

** NOTE TO SPECIFIER ** Delete installation not required.1) Unit shall be designed for indoor installation.2) Unit shall be designed for outdoor installation.

b. Unit shall be completely factory run tested. An instantaneous flow meter shall be used to confirm the firing rate. A full combustion test is to be conducted complete with analyzer computer print out. A detailed test report and installation and maintenance manual shall be sent with the unit.

3. Cabinet Construction:a. Unit exterior casing shall be constructed of heavy gauge galvaneal steel. The

unit shall incorporate a minimum two inch (51 mm) structural iron welded support frame. The entire structural iron frame shall be primed with a high build epoxy rust inhibitor.

b. The propeller fan section shall be insulated with 1 inch (25 mm) 2 lb (0.9 kg) density fiberglass insulation for sound attenuation. The insulation shall be placed in perforated liners. All fans shall be secured on two inch (51 mm) wide 1/4 inch (6 mm) thick full perimeter neoprene isolation. To ensure the casing is airtight all panels shall overlap and be caulked.

** NOTE TO SPECIFIER ** Delete if not required.c. Units without heating section have 48 inches (1219 mm) tall transition section

with 2 inches (51 mm) insulation and perforated metal liner between fan deck and discharge plenum as standard for sound attenuation. Refer to drawings for extensions required to increase unit height as indicated.

d. Each section of the unit shall have pre-punched structural angle mating flanges for final assembly. All hardware and gasket shall to be provided by the factory and sent with each unit.

e. A minimum 3 mil (0.08 mm) coat of chain stop alkyd enamel paint shall be cured on at a minimum temperature of 140 degrees F (60 degrees C). Units shall be finished machinery grey color unless indicated otherwise.

4. Blower/Motor Section:a. Unit shall be supplied with two, low noise propeller fans. Each propeller fan

shall have a minimum of six airfoil blades. The unit shall be statically and dynamically balanced at the factory.

15720-29

Page 30:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

b. The fan wheel shall be mounted on a heavy duty machined and polished solid steel shaft. The shafts maximum operating speed is not to exceed 75% of its first critical speed. The propeller motors shall be T-frame, ODP type with a 1.15 sf (0.11 sq m). The motors shall be mounted on a fully adjustable base.

c. The bearings shall be heavy duty pillow block type. Fan bearings shall have an L-10 bearing life base of 100,000 hours. The propellers are to be driven with adjustable 1.5 sf (0.14 sq m) V-Belt drives.

d. Unit shall have a hinged and gasketed fan access door with heavy duty roller action, full compression latches to provide easy access to maintain and inspect motors, belts and bearings. Each door shall be equipped with electric safety door switches.

5. Heat Exchanger Section:a. The heat exchanger shall be a four pass design. Minimum efficiency shall be

ETL certified to be no less than 80% at full firing rate. The heat exchanger manufacturer shall have a minimum of ten years experience fabricating and producing furnaces.

b. Internal baffling of the secondary tubes is not acceptable. The heat exchangers primary and secondary heat transfer surfaces shall be constructed of 409 series stainless steel. Units shall be provided with multiple condensate drains when modulating. The heat exchanger section shall have an internal radiation shield to maintain a jacket loss of less than 2% of the rated output.

c. All heat transfer surfaces, including headers and the front collector box, shall be inside the casing and in the air stream. The construction of the heat exchanger shall permit free, unrestricted lateral, vertical and peripheral expansion during the heating and cooling cycle without damage or strain to any part.

** NOTE TO SPECIFIER ** Delete if not required.d. The heater shall be equipped with a direct drive radial blade induced draft

blower. The combustion chamber is to operate under a negative pressure. The fan shall be adequately sized to insure proper draft conditions. A discharge damper on the induced draft fan shall be mechanically interlocked to the main gas actuator to proportion exhaust with intake. The induced draft fan shall be directly connected to an air tight collar and collector box header located inside the heat exchanger casing.

e. The burner shall be equipped with a combustion air proving switch, removable pilot assembly and positive pilot combustion air supply. The combustion air damper shall be interlocked with the main gas valve to insure a proper air/gas mixture.

** NOTE TO SPECIFIER ** Delete burner unit not required.1) The burner unit shall be equipped with a on/off power burner.2) The burner unit shall be equipped with a 2 stage power burner.3) The burner unit shall be equipped with a full modulation power burner.

On modulating units the main firing rate shall be factory adjusted and certified for a minimum turndown ratio of 15:1.

** NOTE TO SPECIFIER ** Delete relay unit not required.f. A solid state programmable safeguard relay with flamerod and purge card shall

continuously monitor main and pilot flame.g. A solid state programmable safeguard relay with ultra violet scanner and purge

card shall continuously monitor main and pilot flame.h. The main and pilot valve train to the burner shall be completely factory pre-

piped This assembly shall be wired and include the following minimum components; main and pilot manual shut-off valves, main and pilot pressure regulators, main and pilot automatic shut-off valves and adequate unions and test ports for unconstrained service.

** NOTE TO SPECIFIER ** Delete if not required.i. The heater shall be equipped with a direct drive radial blade induced draft

15720-30

Page 31:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

blower. The combustion chamber is to operate under a negative pressure. The fan is to be adequately sized to insure proper draft conditions. A manual locking discharge damper quadrant is to be provided for adjusting furnace pressure. When full modulation is required the discharge damper is to be electronically interlocked to the main gas valve to control draft from low to high fire.

** NOTE TO SPECIFIER ** Delete if not required.j. A duct sleeve shall be provided directly on the burner to mount an outdoor

combustion duct. The burner shall draw all air for combustion from outside.** NOTE TO SPECIFIER ** Delete unit heat source not required.

k. Unit shall include an electric heating coil.l. Unit shall include a hot water heating coil.

6. Controls:a. Unit controls shall be contained within a hinged enclosure. Control enclosure

shall have a dead front fused disconnect switch. Terminal strip, components and all wiring shall be labeled and/or numbered. Wiring in the control panel shall be run in wiring duct. The controls for the heater shall include:1) Blower motor starter with ambient compensated overloads and auxiliary

contact(s).2) Primary to 120v control transformer.3) 6,000 volt ignition transformer.4) Control fuse block w/ slow blow fuse.5) Fireye flame safeguard relay with LED status, ultra-violet flame detection

& pre-purge cycle.6) Discharge and/or return air temperature control sensor.7) Solid state temperature control circuit with space proportional adjustable

thermostat.8) Manual reset temperature high limit safety switch.9) Differential air proving safety switch.10) High and low gas pressure safety switches.11) Fan switch.

b. Wiring shall be in compliance to the latest N.E.C. standard. External wiring to control enclosure shall be run in conduit. The gas manifold shall be approved by ANSI and include;1) High gas pressure regulator.2) Manual shutoff and test firing lubricated valves.3) Main gas motorized automatic shutoff valve with proof of closure switch.4) Auxiliary main gas motorized automatic shutoff valve.5) Pressure regulating valve.6) Modulating control valve.7) Pilot pressure regulator.8) Pilot automatic shutoff valve.9) Pilot manual shutoff valve.10) Pilot needle valve.11) Multiple test ports.

c. Manifold pipe shall be painted with a rust inhibitor. Units shall be complete with a 10 point diagnostic center. The lights include; power, control fuse, blower, burner, burner airflow switch, ignition, pilot gas valve, main gas valve, safety limits and flame failure.

d. Control panel shall consist of an enclosure with lamacoid identification labels, control switches. Control panel shall include:1) Blower light.2) Burner light.3) Flame failure light.4) System on-off switch.5) Summer/winter switch.

15720-31

Page 32:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

6) Temperature selector.** NOTE TO SPECIFIER ** Delete if not required.

7. Filter Section:** NOTE TO SPECIFIER ** Delete filter type not required.

a. V-Bank filter section shall be provided with hinged access doors on both sides. Access doors are to be fully gasketed and supplied with the same industrial compression latches used with the rest of the unit. Angular racks shall hold 2 inch (51 mm) thick 30% efficient pleated type filters. Filters shall have an average arrestance of 76.4% in accordance with ASHRAE standard 52.1. Filter velocities not to exceed 500 FPM (152 MPM). The filter section shall be an integral section of the unit finished with the same casings. A complete additional set of construction filters shall be provided for each unit.

b. A flat filter section shall be provided with lift out filter tracks. Flat filter sections are utilized only when the unit height is a concern. The flat filter section reduces overall height of a unit when provided with filters. Filters shall have an average arrestance of 76.4% in accordance with ASHRAE standard 52.1. Filter velocities not to exceed 500 FPM (152 MPM). Expanded metal shall be supplied around the perimeter of the unit to provide support to all filters and eliminate the possibility of a filter being pulled in to the fan section. A complete additional set of construction filters shall be provided for each unit.

** NOTE TO SPECIFIER ** Delete if not required.8. Inlet Air Section:

a. An inlet damper shall provide up to twenty percent outdoor air. The damper shall be provided with a flanged duct connection. The direct drive spring return actuator is provided with an adjustable clutch to balance the percentage of outdoor air required.

b. A mixing box integral section shall support the unit and provide access to the dampers. Return air and inlet dampers of galvanized steel construction. A minimum of six breaks per blade shall be provided to strengthen the blades. Maximum leakage rate not to exceed 20 cfm per square foot at 4 in. w.c. differential pressure. Dampers are to be operated with direct drive spring return actuators.

** NOTE TO SPECIFIER ** Delete airfoil damper not required.c. Low leak aluminum airfoil dampers are to be provided. Dampers are to be

complete with blade and jam seals. Maximum leakage rate not to exceed 5 cfm per square foot at 4 in. w.c. differential pressure. Dampers are to be operated with direct drive actuators.

d. Low leak insulated aluminum airfoil dampers recommended when outdoor design is below 0 degrees F (-18 degrees C). Maximum leakage rate not to exceed 5 cfm per square foot at 4 in. w.c. differential pressure. Dampers operated with direct drive actuators. Standard air leakage data is certified under the AMCA ratings program. Dampers designed for operation down to -40 degrees F (-38 degrees C).

e. Blades are to be internally insulated with expanded polyurethane foam and thermally broken. The complete blade shall have an insulating factor of R-2.29 and temperature index of 55.

** NOTE TO SPECIFIER ** Delete if not required.9. Cooling Coil Section:

a. Cooling coil plenum shall consist of double wall construction. Single wall coil sections are not acceptable.

** NOTE TO SPECIFIER ** Delete insulation thickness not required.1) The coil section shall be insulated with 1 inch (25 mm) thick fiberglass

insulation.2) The coil section shall be insulated with 2 inches (51 mm) thick fiberglass

15720-32

Page 33:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

insulation.b. The plenum shall feature a double sloped 304 stainless steel condensate pan

with drain. All pans shall be minimum 18 gauge 304 stainless steel continuously TIG welded. Multiple coils shall be stacked horizontally and include intermediate drain pans to reduce refrigerant pressure drop and possibility of water carry over. Coils shall feature 0.020 inch (0.5 mm) minimum copper tube wall thickness. The fins shall be rippled and made of a minimum of 0.006 inch (0.15 mm) aluminum sheet.

c. Coils shall be pressure tested to 250 psig to ensure no refrigerant leaks. Coils designed around 400 CFM per ton. Coil bypass with manual adjustment damper shall be provided to prevent CFM per ton ratio exceeding 500. The differential air pressure drop over the coil shall not exceed 0.33 in. w.c.

** NOTE TO SPECIFIER ** Delete coil not required.1) Coils shall feature direct expansion interlaced multi-circuit design.2) Coils shall feature chilled water.

** NOTE TO SPECIFIER ** Delete if not required.d. Discharge section with cooling coil top shall be double lined with two inch (51

mm) thick insulation and perforated liner. Discharge section shall acoustically attenuate airborne noise. Minimum 2 inch (51 mm) thick steel blades shall be painted with industrial paint to match unit. Each blade shall be individually adjustable. When a dual bank of airfoil type blades are provided they will provide vertical and horizontal air diffusion control.

** NOTE TO SPECIFIER ** Delete control direction not required.1) Discharge section shall provide single directional control.2) Discharge section shall provide dual directional control.

** NOTE TO SPECIFIER ** Delete if not required.10. Outside Air Plenum

a. An integral plenum shall be included with the unit to introduce outside air prior to the filters. The plenum casings shall be constructed the same as the unit and finished to match. Inlet plenum shall be designed to prevent water from entering the unit. Exterior wall mounted plenum shall match building exterior color. A wall mount flange with gasket will run the perimeter of the inlet plenum. The inlet velocity in to the louvered plenum is to be less than 500 FPM (152 MPM) free area. The louvered inlet plenum shall be equipped with expanded metal where necessary.

** NOTE TO SPECIFIER ** Delete if not required.11. Integral Service Platform with Ladder:

a. A full OSHA approved service platform shall be provided for complete access to burner and gas manifold. The service platform is to feature 12 gauge expanded metal screen and a welded 3 inches (152 mm) structural iron frame. The service platform is to be equipped with a four inches (102 mm) high kick plate and locking chains.

** NOTE TO SPECIFIER ** Delete if not required.1) OSHA approved ladder shall include hand guide rails and concrete

securing feet.** NOTE TO SPECIFIER ** Delete if not required.

12. Discharge Air Section:a. For outdoor units an interior trapezoidal shaped discharge section shall be

provided to distribute air inside the building. The discharge shall be double lined with two inches (51 mm) thick insulation and perforated liner. Discharge section shall acoustically attenuate airborne noise. Diffuser screens located on the front of the discharge.

** NOTE TO SPECIFIER ** Delete blade type not required.1) The discharge plenum shall be equipped with single adjustable air

15720-33

Page 34:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

double deflection airfoil type blades.2) The discharge plenum shall be equipped with double adjustable air

double deflection airfoil type blades.** NOTE TO SPECIFIER ** Delete if not required.

13. Automatic Greasing Canister:a. Bearings are to be equipped with automatic greasing canisters. Microprocessor

controlled greasing canisters shall deliver 350 psig lubrication on a precision cycle to increase bearing longevity and practically eliminate bearing maintenance.

** NOTE TO SPECIFIER ** Delete bearing unit not required.1) All four unit bearings are to be automatically lubricated every second day

from a 240 cc lubrication canister.2) All six unit bearings are to be automatically lubricated every second day

from a 240 cc lubrication canister.3) All eight unit bearings are to be automatically lubricated every second

day from a 240 cc lubrication canister.b. The greasing canisters with pump driven microprocessor are to be located in

the main control panel for ease of adjustment. The grease canister shall contain a minimum quantity of grease to ensure two year supply prior to canister tank replacement.

** NOTE TO SPECIFIER ** Delete if not required.14. Humidification Plenum:

a. G90 galvanized steel. The unit shall include the humidifier mounted, wired and tested from the factory. Gas to steam microprocessor controlled humidifier. The humidifier is to automatically cool discharged hot water to 140 degree F (60 degree C) to meet governing code requirements and to prevent damage to PVC drain piping.1) Control to ±3% RH.2) Steam output rangeability up to 40 to 1 closely tracks humidity set point.3) Low nitrogen oxide (NOx) emissions of less than 20 ppm.4) Diagnostic test at unit start-up verifies system performance.5) 82% burner efficiency rating.6) Variable speed blowers and modulating gas valves provide consistent

humidity output.7) Full burner modulation and PID control provide accurate, responsive, and

adjustable RH control.8) The temperature sensor enables the controller to hold water at a preset

temperature allowing rapid response to a call for humidity, enables freeze protection, and allows rapid warm up.

** NOTE TO SPECIFIER ** Delete if not required.15. "Oil Mist" Filtration:

a. The unit will be complete with two stages of filtration. The primary filtration will be specifically designed to capture "oil mist" particulate. Farr ECO filters four inches (102 mm) thick media will be installed in a flat bank filter rack around the unit. The ECO filters will be equipped with a drain trough and these are to be connected to a common drain pipe from the unit. The secondary level of filtration will consist of two inches (51 mm) thick 30% efficient pleated filters.

16. Unit Efficiency Ouput: 80% of input (MBH).** NOTE TO SPECIFIER ** Delete model not required.

17. Model 124-30H as manufactured by REZNOR.a. Input (MBH): 250.b. # of Blowers: 1.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 5001.e. Maximum CFM: 7000.

15720-34

Page 35:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

18. Model 124-30L as manufactured by REZNOR.a. Input (MBH): 250.b. # of Blowers: 1.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 3250.e. Maximum CFM: 4000.

19. Model 224-20L as manufactured by REZNOR.a. Input (MBH): 250.b. # of Blowers: 2.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 8000.e. Maximum CFM: 8000.

20. Model 124-30S as manufactured by REZNOR.a. Input (MBH): 375.b. # of Blowers: 1.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 4001.e. Maximum CFM: 5000.

21. Model 224-30S as manufactured by REZNOR.a. Input (MBH): 375.b. # of Blowers: 2.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 8000.e. Maximum CFM: 8000.

22. Model 224-40S as manufactured by REZNOR.a. Input (MBH): 500.b. # of Blowers: 2.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 8000.e. Maximum CFM: 8000.

23. Model 130-40L as manufactured by REZNOR.a. Input (MBH): 625.b. # of Blowers: 1.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 4501.e. Maximum CFM: 6000.

24. Model 230-50L as manufactured by REZNOR.a. Input (MBH): 625.b. # of Blowers: 2.c. Blower Fan Size: 24 inches (610 mm).d. Minimum CFM: 12000.e. Maximum CFM: 12000.

25. Model 130-40S as manufactured by REZNOR.a. Input (MBH): 813.b. # of Blowers: 1.c. Blower Fan Size: 30 inches (762 mm).d. Minimum CFM: 6001.e. Maximum CFM: 7500.

26. Model 230-65S as manufactured by REZNOR.a. Input (MBH): 813.b. # of Blowers: 2.c. Blower Fan Size: 30 inches (762 mm).d. Minimum CFM: 15000.e. Maximum CFM: 15000.

27. Model 130-40H as manufactured by REZNOR.a. Input (MBH): 938.

15720-35

Page 36:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

b. # of Blowers: 1.c. Blower Fan Size: 30 inches (762 mm).d. Minimum CFM: 7501.e. Maximum CFM: 9000.

28. Model 230-75H as manufactured by REZNOR.a. Input (MBH): 938.b. # of Blowers: 2.c. Blower Fan Size: 30 inches (762 mm).d. Minimum CFM: 18000.e. Maximum CFM: 18000.

29. Model 142-50L as manufactured by REZNOR.a. Input (MBH): 1063.b. # of Blowers: 1.c. Blower Fan Size: 36 inches (914 mm).d. Minimum CFM: 9001.e. Maximum CFM: 11000.

30. Model 242-85L as manufactured by REZNOR.a. Input (MBH): 1063.b. # of Blowers: 2.c. Blower Fan Size: 36 inches (914 mm).d. Minimum CFM: 22000.e. Maximum CFM: 22000.

31. Model 142-50S as manufactured by REZNOR.a. Input (MBH): 1250.b. # of Blowers: 1.c. Blower Fan Size: 42 inches (1067 mm).d. Minimum CFM: 11001.e. Maximum CFM: 15000.

32. Model 242-100S as manufactured by REZNOR.a. Input (MBH): 1250.b. # of Blowers: 2.c. Blower Fan Size: 42 inches (1067 mm).d. Minimum CFM: 30000.e. Maximum CFM: 30000.

33. Model 142-50H as manufactured by REZNOR.a. Input (MBH): 1563.b. # of Blowers: 1.c. Blower Fan Size: 42 inches (1067 mm).d. Minimum CFM: 15001.e. Maximum CFM: 18000.

34. Model 160-175L as manufactured by REZNOR.a. Input (MBH): 1563.b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 32001.e. Maximum CFM: 36000.

35. Model 242-125H as manufactured by REZNOR.a. Input (MBH): 1563.b. # of Blowers: 2.c. Blower Fan Size: 42 inches (1067 mm).d. Minimum CFM: 36000.e. Maximum CFM: 36000.

36. Model 148-75L as manufactured by REZNOR.a. Input (MBH): 1875.b. # of Blowers: 1.c. Blower Fan Size: 48 inches (1219 mm).

15720-36

Page 37:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

d. Minimum CFM: 18001.e. Maximum CFM: 20000.

37. Model 160-175S as manufactured by REZNOR.a. Input (MBH): 1875.b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 36001.e. Maximum CFM: 42500.

38. Model 248-150L as manufactured by REZNOR.a. Input (MBH): 1875.b. # of Blowers: 2.c. Blower Fan Size: 48 inches (1219 mm).d. Minimum CFM: 40000.e. Maximum CFM: 40000.

39. Model 148-75S as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 1.c. Blower Fan Size: 48 inches (1219 mm).d. Minimum CFM: 20001.e. Maximum CFM: 22500.

40. Model 160-175H as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 42501.e. Maximum CFM: 50000.

41. Model 248-175S as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 2.c. Blower Fan Size: 48 inches (1219 mm).d. Minimum CFM: 45000.e. Maximum CFM: 45000.

42. Model 260-175H as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 10000.e. Maximum CFM: 10000.

43. Model 260-175L as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 72000.e. Maximum CFM: 72000.

44. Model 260-175S as manufactured by REZNOR.a. Input (MBH): 2188.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 85000.e. Maximum CFM: 85000.

45. Model 148-75H as manufactured by REZNOR.a. Input (MBH): 2500.b. # of Blowers: 1.c. Blower Fan Size: 48 inches (1219 mm).d. Minimum CFM: 22501.e. Maximum CFM: 24500.

15720-37

Page 38:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

46. Model 248-200H as manufactured by REZNOR.a. Input (MBH): 2500.b. # of Blowers: 2.c. Blower Fan Size: 48 inches (1219 mm).d. Minimum CFM: 50000.e. Maximum CFM: 50000.

47. Model 260-200H as manufactured by REZNOR.a. Input (MBH): 2500.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 100000.e. Maximum CFM: 100000.

48. Model 260-200L as manufactured by REZNOR.a. Input (MBH): 2500.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 72000.e. Maximum CFM: 72000.

49. Model 260-200S as manufactured by REZNOR.a. Input (MBH): 2500.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 85000.e. Maximum CFM: 85000.

50. Model 154-100L as manufactured by REZNOR.a. Input (MBH): 2813.b. # of Blowers: 1.c. Blower Fan Size: 54 inches (610 mm).d. Minimum CFM: 24501.e. Maximum CFM: 26000.

51. Model 254-225L as manufactured by REZNOR.a. Input (MBH): 2813.b. # of Blowers: 2.c. Blower Fan Size: 54 inches (1372 mm).d. Minimum CFM: 65000.e. Maximum CFM: 65000.

52. Model 254-225L as manufactured by REZNOR.a. Input (MBH): 2813.b. # of Blowers: 2.c. Blower Fan Size: 54 inches (1372 mm).d. Minimum CFM: 50000.e. Maximum CFM: 50000.

53. Model 154-100S as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 1.c. Blower Fan Size: 54 inches (1372 mm).d. Minimum CFM: 26001.e. Maximum CFM: 29000.

54. Model 160-250L as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 42500.e. Maximum CFM: 42500.

55. Model 160-250L as manufactured by REZNOR.a. Input (MBH): 3125.

15720-38

Page 39:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 36000.e. Maximum CFM: 36000.

56. Model 160-250L as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 1.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 50000.e. Maximum CFM: 50000.

57. Model 254-250S as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 2.c. Blower Fan Size: 54 inches (1372 mm).d. Minimum CFM: 60000.e. Maximum CFM: 60000.

58. Model 260-250H as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 10000.e. Maximum CFM: 10000.

59. Model 260-250L as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 72000.e. Maximum CFM: 72000.

60. Model 260-250S as manufactured by REZNOR.a. Input (MBH): 3125.b. # of Blowers: 2.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 85000.e. Maximum CFM: 85000.

61. Model 154-100H as manufactured by REZNOR.a. Input (MBH): 3428.b. # of Blowers: 1.c. Blower Fan Size: 54 inches (1372 mm).d. Minimum CFM: 29001.e. Maximum CFM: 32000.

62. Model 360-175H as manufactured by REZNOR.a. Input (MBH): 4063.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 150000.e. Maximum CFM: 150000.

63. Model 360-175L as manufactured by REZNOR.a. Input (MBH): 4063.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 92000.e. Maximum CFM: 92000.

64. Model 360-175S as manufactured by REZNOR.a. Input (MBH): 4063.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).

15720-39

Page 40:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

d. Minimum CFM: 130000.e. Maximum CFM: 130000.

65. Model 360-200H as manufactured by REZNOR.a. Input (MBH): 5000.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 150000.e. Maximum CFM: 150000.

66. Model 360-200L as manufactured by REZNOR.a. Input (MBH): 5000.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 92000.e. Maximum CFM: 92000.

67. Model 360-200S as manufactured by REZNOR.a. Input (MBH): 5000.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 130000.e. Maximum CFM: 130000.

68. Model 360-250H as manufactured by REZNOR.a. Input (MBH): 7500.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 150000.e. Maximum CFM: 150000.

69. Model 360-250L as manufactured by REZNOR.a. Input (MBH): 7500.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 92000.e. Maximum CFM: 92000.

70. Model 360-250S as manufactured by REZNOR.a. Input (MBH): 7500.b. # of Blowers: 3.c. Blower Fan Size: 60 inches (1524 mm).d. Minimum CFM: 130000.e. Maximum CFM: 130000.

PART 3 EXECUTION

3.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

B. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

A. Clean surfaces thoroughly prior to installation. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

A. Install in accordance with manufacturer's instructions. Test for proper operation. Adjust and

15720-40

Page 41:   · Web viewSECTION 15720. AIR HANDLING UNITS. Copyright 2013 - 2014 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** REZNOR®; industrial and commercial heating

retest until proper operation is achieved.

B. When installed, the unit shall be electrically wired and grounded in accordance with local codes or, in absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70.

3.4 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION