Operation/Installation Manual - Operation/Installation Manual - Edition dated 1st November 2005 AIR-CONDITIONING - PAGE :1 AIR-CONDITIONING - PAGE :1 WEBASTO MARINE - INSTALLATION MANUAL Webasto AG - Special Products & Markets - Kraillinger Strasse 5 - 82131 Stockdorf - Germany Tel. : +49(0) 89 8 57 94 543 Fax : +49(0) 89 8 57 94 753 Website : www.webasto.de Webasto - AIR-CONDITIONING SELECT SERIES - SPLIT-AIR UNITS ELECTRICAL CONTROL BOX RETURN AIR-GRILLE CLIP-ON BEZEL WITH LOUVERS AND INDEPENDENT BLOWER SPEED CONTROL STRAINER OVER-BOARD DISCHARGE DISPLAY CABLE F U N C T I O N I N G P R I N C I P L E S COOL CYCLE LED AUTO CYCLE SWITCHING LED ROOM TEMPERATURE OR SET-POINT TEMPERATURE OR FAN SPEED READ-OUT SET-POINT MODIFICATION KEYS FUNCTION KEY INTEGRATED TEMP. SENSOR BLOWER KEY INFRA-RED REMOTE CONTROL HEAT CYCLE LED ON/OFF KEY DIGIT A L C O N T R O L P A N E L DIGITAL CONTROL PANEL AIR FL O W POWER CABLE SEA-WATER PUMP 1 2 3 4 5 5 1 = SELECT 5000 to 20000 BTU with Air Transition Box with 5 outlets 80 or 100 mm Diam. 2 = Blower Module Straight Inlet - Cabin 2 3 = Blower Module Side Inlet - Cabin 1 4 = Blower Module 90° Inlet - Cabin 1 5 = Special Smooth Bore Suction Ducting Int. Diam 80 or 100 mm with Thin High Performance Insulation ATTENTION : Unit + Blower Modules have been scaled up for better detailed viewing - Real Components are smaller as compared with interior outfitting and upholstery.

Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual -

Operation/Installation Manual -Edition dated 1st November 2005 AIR-CONDITIONING - PAGE : 1

AIR-CONDITIONING - PAGE : 1WEBASTO MARINE - INSTALLATION MANUAL

Webasto AG - Special Products & Markets - Kraillinger Strasse 5 - 82131 Stockdorf - Germany Tel. : +49(0) 89 8 57 94 543 Fax : +49(0) 89 8 57 94 753 Website : www.webasto.de

Webasto - AIR-CONDITIONING

SELECT SERIES - SPLIT-AIR UNITSELECTRICAL CONTROL BOX

RETURN AIR-GRILLE

CLIP-ON BEZEL WITH LOUVERSAND INDEPENDENT BLOWERSPEED CONTROL

STRAINER

OVER-BOARD DISCHARGE

DISPLAY CABLE

F

U

N

C

T

I

O

N

I

N

G

P

R

I

N

C

I

P

L

E

S

COOL CYCLE LED

AUTO CYCLE SWITCHINGLED

ROOM TEMPERATURE ORSET-POINT TEMPERATURE OR FAN SPEED READ-OUT

SET-POINT MODIFICATION KEYS

FUNCTION KEY

INTEGRATED TEMP.SENSOR BLOWER KEY

INFRA-RED REMOTE CONTROL

HEAT CYCLE LED

ON/OFF KEY

DIGITAL CONTROL PANEL

DIGITAL CONTROL PANEL

AIR

FL

OW

POWER CABLE

SEA-WATERPUMP

1

2

3

4

5

5

1 = SELECT 5000 to 20000 BTU with Air Transition Box with 5 outlets 80 or 100 mm Diam.

2 = Blower Module Straight Inlet - Cabin 23 = Blower Module Side Inlet - Cabin 14 = Blower Module 90° Inlet - Cabin 15 = Special Smooth Bore Suction Ducting Int. Diam 80

or 100 mm with Thin High Performance InsulationATTENTION : Unit + Blower Modules have been scaled up for better detailed viewing- Real Components are smaller as compared with interior outfitting and upholstery.

Page 2: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 2

Operation/Installation Manual - Webasto blue cool select - Page : 2

Edition dated 1st November 2005

SPLITAIR AIR-CONDITIONING UNITS - SELECT SERIES

OPERATION AND INSTALLATION MANUAL

C O N T E N T S Page

1) General Information ..................................................................................................

2) Digital Control - Operation Guidelines .....................................................................2.1 - Digital Display <AIR CONTROL> - Basic Commands ...................................

3) Secondary Commands by F/Blower key .................................................................

4) Visual Error Codes - Digital Display ........................................................................

5) Central Blower Control ...........................................................................................

6) Programmable Functions ........................................................................................... 6.1 - Digital Display <AIR CONTROL> - Programming access .............................

7) Pratical Installation Guide - Components (Pumps, accessories, etc) .......................

8) Routine Checks ........................................................................................................

8A) Trouble Shooting .....................................................................................................

9) Air-Ducting and Ventilation .......................................................................................

10) Wirings Schematics .................................................................................................10.1 - Wiring diagram - WBCS 5 to 16 - single phase - Rotary compressors ..........10.2 - Wiring diagram - WBCS 20 - single phase - Rotary compressors .................10.3 - Wiring diagram - Wiring Running Capacitor - Blowers .................................

Webasto AG - Special Products & Markets Kraillinger Strasse 5, 82131 STOCKDORF, GermanyTel. : +49(0) 89 8 57 94 543 Fax : +49(0) 89 8 57 94 753 Website : www.webasto.de

3

44

5

5

5

77

8

9

9

10

11111213

Page 3: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 3

Operation/Installation Manual - Webasto blue cool select - Page : 3Edition dated 1st November 2005

1. GENERAL INFORMATION

All Webasto air conditioning units arecontrolled by a Digital Display <AIR CONTROL> which gives access to allfunctions necessary for the normal opera-tion of the unit and attached accessories(blowers, pumps, etc).

All Webasto air conditioning units are sea-water cooled by means of an AC sea-waterpump.

In order to start the system you only needto press the <On/Off> key on the digital display.From there on the electronic control unit

takes care of the progressive starting up ofthe air conditioning unit as well as it nor-mal functioning.

The digital display will show the presentair temperature of the cabin in which thedigital display is situated or where themain temperature sensor is located (incase the optional secondary temperaturesensor is used).

After a delay of approx. 20 seconds thedisplay will indicate the cycle in whichoperation will start i.e. <COOL> or<HEAT>. The choice will depend uponthe set-point temperature and the air-tem-perature as measured by the display panel.

After a further delay of approx. 50 sec-onds the compressor(s) will start up andthe normal operation cycle will begin.

2004 SERIES DIGITAL DISPLAY

As from June 2004 all Webasto air condi-tioning units are controlled by a new DigitalDisplay <AIR CONTROL> 2004 SERIESwhich gives access to all functions necessaryfor the normal operation of the unit andattached accessories (blowers, pumps, etc).

2004 Series Electronic Controls are easilyrecognized by their special remobale bezels.

In a Split-Air system the air is drawnthrough the common evaporator byremote mounted Split-Air modules con-nected to the air-transition box by specialsmoothbore insulated ducting. This prin-ciple allows a reduction in duct diameter

to 80 and 100 mm and ducts lengths of upto 6/8 meters.In a typical Split-Air set-up 1, 2 or 3 Split-Air modules are controlled directly by themain digital panel and situated in the mainsalon or cabin. 1 or more secondary Split-

Air modules are placed in other cabins.These secondary SplitAir modules havetheir own independent blower speed con-trol which allows the occupants of thesecabins to control their own environment.

HOW DOES IT WORK ?

STANDARD ELECTRICAL ACCESSORIES

ELECTRICAL CONTROL BOX DIGITAL DISPLAY PANEL

MINIMUM STANDARD CONTROL ELEMENTS DELIVERED FOR ALL WBCS SPLITAIR UNITS Summary : 1 Alu control box + 1 display cable + 1 digital control panel (External air-sensor is optional)

DISPLAY CABLE

OPTIONAL EXTERNAL AIR SENSORPP = 125 mm

226

140

74 cut-out120 overall

55 cut-out82 overall

Grille Frame with vertical or horizontallouvers

Blower Module 150 m3/Hr - Straight Entry with Blower Control

Super-silent CrossFlow blower

Integrated Blower Speed Controlfor secondary modules

SplitAir unit identical to Blue Coolself-contained - centrifugal blowersreplaced by air-transition box

Air Transition Box with 5 or 6 exits- 80 or 100 mm - for Splitair ductingto remote Blower Modules

Page 4: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 4

Operation/Installation Manual - Webasto blue cool select - Page : 4

Edition dated 1st November 2005

The new 2004 displays are backwards com-patibel with the older TCC electronic con-troller cards. In that case however the dedi-cated Blower key is not operational.

All Webasto air conditioning units are sea-water cooled by means of an AC sea-waterpump.

In order to start the system you only need topress the On/Off key on the digital display.

From there on the electronic control unittakes care of the progressive starting up ofthe air conditioning components as well asit’s normal functioning.

The digital display will show the presentroom temperature of the cabin in which thedigital display is situated or where the maintemperature sensor is located (in case theoptional secondary temperature sensor isused).

The WEBASTO <AIR CONTROL> digitaldisplay gives access to information and con-trols at three distinct levels :

Immediate Access - Level 1 :

1) Room temperature read-out in the main 4 LED display window

2) 3 small LED’s to the left indicating the operating cycle presently active :- Cool cycle only operation.- Automatic cycle switching governed by

the end-users entered set-point tempera-ture.- Heat cycle only operation.

3) 2 set-point keys give immediate access to the thermostatic set-points for blow-er-control (“Sun” and “Snow” keys).These keys are also used to alter pro-gramming values - see here-after chapter6.

Secondary commands and info -Level 2 :

4) The F key gives immediate access to anumber of secondary commands which needto be accessed frequently for day to day oper-ation.

First access is to the blower speed control,then evaporator temperature read-out, etc.

See hereafter drawing 2.1 for complete list.

Programming Commands - Level 3 :A number of programming commands thatdo not need to be accessed for day to dayoperation are hidden and require a specialprocedure to enable access and modification.An access code can be enforced to avoidaccidental modification of programming val-ues.

See Chapter 6 - Page 7.

Start-up delay :

After pushing the On/Off key the LED’s willdisplay <On> while initializing the system.Push again to stop operation - the displaywill briefly show <Off> before extinction.

The adequate LED to the left (heat, cool , etc)will come on after approx. 15 seconds andcompressor operation will start after approx.50 seconds.

The sea-water circulation pump will come onapprox. 9 seconds before compressor start-up.

Modification of set-point tempera-ture :

The set-point temperature i.e. the tempera-ture desired by the operator for blower oper-ation directly connected to the TCC con-troller card, can be modified as following :

Press and hold one of the set-point selectorkeys and wait until the new desired set-pointtemperature is obtained. Release the set-point key.The display will return to normal room tem-perature read-out after approx. 5 seconds.See drawing 2.1 - page 4 for visual operationguide.Non-volatile memory keeps last settings.

Special New Features - 2004 Series :

A) New dedicated Blower speed key -the new 2004 Digital Display provides for adedicated blower speed key whidh allows

2 - DIGITAL WBCS/BLOWER CONTROL - GENERAL PRINCIPLES

BASIC COMMANDS :1 - Press to turn on - press again to turn off.2 - Press to read set-point temperature - hold to raise

set-point temperature.3 - Press to read set-point temperature - hold to lower

set-point temperature.4 - Led indicating system working in cool mode5 - Led indicating automatic cycle-switching is active6 - Led indicating system working in heat mode7 - Function - immediate access to :

- evaporator temperature read-out ...........................- manual cycle choice (cool, heat, auto-reverse) ....- AC voltage read-out ..............................................- manual compressor selection On/Off 1 to 4 ..........- start-up priority compressors 1 to 4 ......................- automatic dehumidification cycle during absence - time lapse <F> key read-outs before returning to

room temperature.

8 - Dedicated Blower Speed Key

9 - Access to hidden programming functions - seepage 7.

1

3

9 - Push Both Keys Simultaneouslyafter Display Extinction

DRAWING 2.1 - BASIC AND SECONDARY COMMANDS

4 8

5

6

7 2

EE1133..22*FF 33 UU223300 11CC0011 etcPP112233 etc*dd 00 *tt 11

*bb AA

*Default Values

Page 5: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 5

Operation/Installation Manual - Webasto blue cool select - Page : 5Edition dated 1st November 2005

you to cycle through the speed settings. The<F> key from 2004 onwards is only used forprogramming and setting purposes

B) New self-priming pumps :WEBASTO Marine has developped in part-nership with one of the major pump manu-facturers a new variable flow ultra-silent self-priming pump. This pump will automaticallyadjust its flow rate to the real required capac-ity i.e. during a hot sunny afternoon the pumpwill run at full speed, during the night it willslow down to minimum speed.

This new pump is referenced : WEBAS-TO200; it is basically a DC pump with a spe-cial control unit between the TCC controllercard and the pump allowing to adjust thepump speed as needed. The use of standard230V AC pumps is still possible without anyrestriction.

As from July 2004 all self-contained unitsfrom 5000 to 16000 BTU will be equippedwith these new self-priming pumps.

Installation of these pumps can be above thewater-line to 250mm approx.

Flow rate varies between 6 and 12L/min.approx.

Continued Features - 2000 Series :

C) Automatic blank/sleep mode - pro-grammable time delay. Factory default : 15minutes. While in blank/sleep mode the cycleLED flashes discretely every 20 seconds. Togo back to normal operation push any key.

D) Calibrate all blower speed settingsin real time mode.

It is now possible to calibrate all speed set-tings (1 to 5) before actually putting the sys-tem into service.

To do so entrer programming mode with set-point at 15° C.; proceed to following line i.e.line <6> = speed 5 (max). (see chapter 6)

The blower will start to function as soon asyou access code <6>.Alter value to the right of code <6> andblower speed will immediately change inreal time. When satisfied go to following line <7> = speed 4 and do the same.Proceed until lowest speed N° 1 and go backagain to speed N° 5 if not satisfied.

When all speeds are programmed accordingto need, validate by pushing On/Off key(<memo> will be displayed briefly). See alsopage 8 - programming access.

Warning : Never program speedsso low that the blower is in dangerof stopping or will not re-start atthat setting. This will inevitably entail motor-windings burn-out and will not becovered by the WEBASTO warran-ty.

E) Automatic De-Icing Control :

During intermediate seasons (spring,autumn) when moderate temperatureconditions prevail, there is a definite riskof icing the evaporator coil in cool modeand pressure safety cut-outs in heat mode.

To allow maximum blower speed varia-tion and still function within a normaloperating window, the TCC card isequipped with a second temperature sen-sor which reads the exact evaporator coiltemperature.Whenever coil temperature approachesthe danger zone, blower speed isincreased to half speed; if that is not suf-ficient the micro-processor will stop com-pressor operation for pre-determinedintervals and will resume normal opera-tion when coil temperature has movedback to within normal operating values.

This feature is completely transparent tothe end-user without an error code dis-play; in short this feature belongs to thenormal operating procedures in the sameway as the temperature set-points.

F) Infra-Red Remote Control :

Infra-red remote control can be obtained asan option. This remote control is based on thestandard protocols also used by TV and otherappliances. Although the WEBASTO con-trols have been chosen so as to avoid inter-ference with most TV models, the end-usershould be aware that in certain cases interfer-ence may occur with TV sets or other appli-ances.

In general it is therefore advisable to avoidlocating a WEBASTO Air Control panel nextto other appliances using infra-red controlunits whenever it is planned to use infra-redcontrol mode.

G) ACCESS CODE :

The end-user can deny access to all programsettings by introducing an access code (seepage 8 - code <b>). Blower speed and set-points always remain accessible.

Once an access code is validated, the digitalpanel will show <Code> if the end-user triesto access other functions then blower speedor set-point. To gain full access push the sunkey to reach the code value as programmedand push the F/Blower key again to gainaccess to full program settings.

3. SECONDARY COMMANDS :

The <F> key gives immediate access to com-mands and displays necessary for day to dayoperation. When pushing the <F> key youwill see to the left a code which indicates thetype of display or command and to the rightthe present value.

In order of appearance here-after an explana-tion of these commands/displays :

a) Blower speed control : < b A>(0,1,2,3,4,5)

This command preceeded by the letter b(blower) allows the following settings :A = automatic blower speed adjusted to tem-

perature differential.1 to 5 = manual speed controlSpeed control is in real time mode i.e.changes are effected immediately withoutany validation procedure.

Warning : All following func-tions need validation before a newvalue is accepted.Validation is obtained by pushingthe <F> key again and by going tothe next function line.Then final validation will occurautomatically when the displaygoes back to room temperatureread-out or final validation can beforced by pushing the On/Off keybriefly while still in F mode.

Validation is witnessed by the briefdisplay of the message <memo>.

b) Read out of evaporator coil temperature :<E10.2> (10.2 ° C) - example.

c) Cycle mode choice : <F 3> (1 to 4) The following cycle modes can be choosenmanually :1 = cool cycle only2 = heat cycle only3 = automatic cycle switching with reversiblecompressor4 = automatic cycle switching withoutreversible compressor

d) AC Voltage read-out : < U232>(232 Volts) - example

Page 6: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 6

Operation/Installation Manual - Webasto blue cool select - Page : 6

Edition dated 1st November 2005

e) Manual on/off Compressor 1 : <1C01><1C01> = Compressor 1 on<1C00> = Compressor 1 off

f) Manual on/off Compressor 2 : <2C01><2C01> = on<2C00> = off

Idem for compressors 3 and 4 - <3C01> and<4C01>.

g) Start-up Priority Compressors 1 to 4 :<P123> = 1,2,3,4 ; <P341>=3,4,1,2<P A> = automatic priority rotation; when

in this priority mode, the startingorder will be changed everyrestart after a thermostatic cut-out.

h) Time delay between compressor start-up :<L 9> (9 seconds) - programmable

from 1 to 9 seconds.

i) Automatic dehumidification while absent.factory default setting : <d 0>0 = non active1 = 1 cycle per 24H2 = 2 cycles per 24H etc

k) display time of secondary functions (F/Blower key) by periods of 20 seconds.<t 1> (factory default setting) = display time 20 seconds.

4. VISUAL ERROR CODES - DIGITAL DISPLAY

The following malfunctions will be dis-played directly on the digital display by acode and will be followed by a system halt.Whenever any of these codes appear the sys-tem is stopped for approx. 60 seconds andthen a re-start is attempted.

If for more than 30 minutes the same mal-function occurs, the system will be stopped completely and the error-code will becomesteady.

No more re-starts will be attempted and theuser will have to re-set the system by pushingthe On/Off switch or by temporarily cuttingout the AC supply to the system. List of error-codes and nature of malfunc-tion :

Code <AAA> :Persistent low voltage (voltage below 195V)for more than 5 seconds - (see also hereafter- Trouble-Shooting - Page 9).

Code A01 to A08 *) :

Pressure safety cut-out of compressors 1 to 4.The HP and BP (if present) safety controls

are directly controlled by the micro-proces-sor inclusing the time-delays for re-start, etc.

*) Standard TCC controllercards have only 1 outlet for 1 single com-pressor. However the embedded micro-processor program can operate up to 4WBCS units from 1 single controller card.This special controller card can be obtainedon special request but is not standard deliv-ery.

Error codes displayed and probable nature ofanomaly.

<A01> : BP (low pressure) cut out - com-pressor 1 - probable causes :- insufficient refrigerant charging

level- abnormal sea-water temperature conditions in heat cycle (sea-water temperatures under 6° C. approx.)

- first start-up in heat cycle with very low chilled water circuit tempera-tures (below 8° C approx.).

WARNING : models WBCC5 to 16 donot have a low pressure safety switch (BP);therefore if you see a A01 warning on suchmodel, it can only be an electrical connectionproblem on the grey 3 pole HP/BP connectoron the TCC controller card. Check that theconnector is properly seated and that the BPstrap is properly tightened.

<A02> : HP (high pressure) cut out - com-pressor 1 - probable causes :- insufficient or non-existent sea-

water cooling - check sea-waterpump.

- too much refrigerant in system -call specialist

- abnormal sea water temperature conditions in heat cycle (sea-watertemperatures above 17° C approx.)

<A03> : BP cut out - compressor 2 - for probable causes see <A01>

<A04> : HP cut out - compressor 2 - see<A02>

<A05> to <A08> - same as above for com-pressors 3 and 4 (if present).

If any of these error codes appear too fre-quently and no appropriate action can betaken with the available means on board, it isnecessary to call a specialist.

Do not insist with manual re-starts in suchcase as this may cause major damage to theprincipal components (compressors, pumps,etc).

<A09> - absent or defective external or inter-nal (Display Face) air sensor

<A10> - absent or defective evaporator temperature coil sensor.

<CA11> - all compressor(s) have been disac-tivated by soft - <F> procedure :<1C00>, <2C00>, etcTo re-activate, reprogram asfollows : <1C01>, etc

<EA11> - compressor stopped by de-icingcontrol - automatic restart - this code doesnot entail a complete system halt and willonly be visible when in the evaporator tem-perature read-out (F key - line E).

5. CENTRAL BLOWER CONTROL

The central <AIR CONTROL> digital dis-play also directly controls the blower(s) ofthe evaporator(s).

For all WBCS systems, there are two modesof blower control and operation :

- thermostatic interruption of blower oper-ation as soon as the desired set-point temperature has been reached.

- un-interrupted blower operation regard-less of thermostatic compressor control.

The choice between these two functioningmodes can be programmed directly by theend user - see here-after Chapter 6 - pro-gramming procedures.

The digital control is initially programmedby the manufacturer in second - i.e. un-inter-rupted blower operation.

Blower control can be manual with 5 differ-ent speed levels or automatic; in this caseblower speed will be governed by the tem-perature differential with the set-point tem-perature.

Remote blowers speed is adjusted indepen-dantly by moving the wheel ont the side ofthe bezel.

To gain access to the hidden programmingfunctions proceed as following :

Raise set-point to max. value i.e. 29° C (oralternatively to lowest value i.e. 15° C) -push Off key to extinguish digital display.

Press <snow> and <sun> key simultaneouslyfor approx. 3 seconds until you see to the leftof the display window a single number codeindicating the programming line presentlyvalid and to the right the programming value.

Page 7: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 7

Operation/Installation Manual - Webasto blue cool select - Page : 7Edition dated 1st November 2005

To go to the next programming line, push the<F> key.

If you modify the programming value of anyline, you need to validate this new value bypushing the <F> key again to move to thenext line. This step will validate and memo-rize the changes made.

1° Functions accessible by raising the set-point to 29° C. :

Code <0> - factory setting : +3° Celsius -lower set-point temperature of the evaporatorcoil temperature when in cool cycle. Thisvalue gives the compressor cut-out pointwhen the de-icing mode is activated (in coolcycle). Adjustment range : between -4°C and +15° C

Code <1> - factory setting : +8° Celsius -higher set-point temperature of de-icing pro-cedure. This value gives the re-start point ofthe compressor after a thermostatic interrup-tion when in de-icing mode.Adjustment range : between 2°C and +18° C.

Code <2> - factory setting : 40° C. higherset-point temperature of the “de-icing” pro-cedure in relation to the evap. coil temepra-ture when in heat cycle (to avoid HP cut-outs). Gives the cut-out point of the com-pressor(s) when functioning in heat cycle.Set-point temperature adjustable between30° and 50° C.

Code <3> -factory setting : 35° C. - lowerset-point temperature of coil temperature cut-in when in heat cycle. Gives the cut-in pointof the compressor after an interruption (“de-icing” procedure) when functioning in heatcycle.Set-point temperature adjustable between27° and 52°C.

Code <4> - pre-programmed value : 0 - cali-

bration of the evaporator coil temperatureread-out - correction possible between -9° to+9° Celsius.

Code <5> - factory setting : 15 - time delayin minutes before the digital display goesinto blank/sleep mode. Cycle LED flashesdiscretely to indicate system is operational.

Code <6> - factory setting : 1 - first start updelay in seconds after connecting AC supply.To stage starting of several WBCS unitswhen switching on AC supply after an inter-ruption.

Code <7> - factory setting : 0 - calibrationof room temperature read-out. Correctionbetween +9 and -9° C.

Code <8> - pre-programmed value : 0.Factory calibration of AC voltage 50 Hz asdisplayed on the digital panel when access-ing the secondary commands - F/Blower key. Correction between -20 and +20 Volt.

Code <9> - pre-programmed value : 2 - Time delay before re-start in minutes after acompressor stop when in “de-icing” proce-dure. (both for cool and heat cycle).

Code <A> - pre-programmed value : 0.Factory calibration of AC voltage 60 Hz asdisplayed on the digital panel when access-ing the secondary commands by the F key.

Correction between -30 and +20 VoltCode <b> - Program version

Re-intializing of factory default set-tings :

It is possible to force the program to re-ini-tialize all program values to factory defaultsettings by the following procedure :When reading the <b> line as above (throughthe 29° set-point), push the <sun> key until

the program version starts to flash. Keep the<sun> key pushed down until the displayshows <init>.

Leave programming mode by pushingOn/Off key - you are now back to the factorydefault settings.

Code <c> - factory setting : 0 - Pump1 out-lets on the TCC controller card non-regulatedfor standard 230V AC sea-water pump. Forthe use of the new WEBASTO200 self-prim-ing variable speed pump this code should beset to <1>. In that case the AC outlet is pulsehashed to enable variable pump speed.

Code <d> - Factory setting : 12(V) - Loweradjustment ceiling DC output for specialself-priming pump. Can de adjusted to high-er ceiling (18V) - see also Code <E> here-after.

Code <E> - Factory setting : 18 (V) - Higheradjustment ceiling DC output for specialself-priming pump. Can be adjusted down-wardsto lower ceiling - see also Code <d>here-above.

2° Functions accessible when loweringthe set-point temperature to 15° C :

Code <0> - pre-programmed value : 195 -low voltage cut-out value AC. Time delay is 5 seconds approx. i.e. the lowvoltage situation will have to persist duringmore than 5 seconds before cut-out occurs.

After cut-out the electronic controller resetsand will start a new cycle. So a renewedattempt to start the compressor will occurafter approx. 90 seconds.

During low-voltage cut-out the display panelwill show the 3 letters <AAA>.

Programming of a cut-out level below 195 Vis done at the entire risk of the operator. It

PROGRAMMING MODE :

To enter programming mode : raise or lower set-point to 29 or 15° C.Turn off system by pressing <On/Off> key - 14.

Press simultaneously keys <11>. The display will show to the left<15>, the number code of the current programming line and to the right<16> the present value.

To validate and memorize modified parameters press the <F> key (12)and proceed to the following programming line.

6 - DIGITAL DISPLAY <AIR CONTROL> - PROGRAMMING ACCESS

111214

15 16

Page 8: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 8

Operation/Installation Manual - Webasto blue cool select - Page : 8

Edition dated 1st November 2005

should be noted that almost all compressormanufacturers decline all responsibility fordefects resulting from operating the com-pressors below 195V AC.

Code <1> - factory setting : 0 - infra-red remote control :0 = infra-red remote control disabled (in thismode no interference is possible with otherinfra-red commands)1 = infra-red remote control active

Code <2> : Blower type : Centrifugal or Cross-Flow. Factory default : 10 = centrifugal blowers only1 = centrifugal + cross-flow2 = for use with OND800 inverter only.Special AC/DC self-contained units.

Code <3> - pre-programmed value : 1 -basic choice of blower control :0 - thermostatic control of blower operationi.e. blower operation will be interrupted ther-mostatically when reaching the appropriateset-point.1 - un-interrupted blower operation regard-less of the thermostatic control.

Code <4> - factory setting : 1 - Choicebetween integrated air sensor and external airsensor :1 - air sensor integrated in digital display0 - external air sensor

Code <5> - Celsius or Fahrenheit display - factory setting : 00 = Celsius read-out1 = Fahrenheit read-out

Code <6> : modification speed N° 5 (max)Code <7> : idem speed N° 4Code <8> : idem speed N° 3Code <9> : idem speed N° 2Code <A> : idem speed N° 1

Code <b> - factory setting : 0 - access codefor programming mode.0 = no access code required1 to 99 = access code/number activated

*) Factory access code : in case the system isblocked and the access code cannot be found,you can access the programming line byusing the factory code number : 64

Code <c> - factory setting : 1 - duration inminutes of heat cycle operation under thedehumidifying cycle.

Code <d> - factory setting : 1 - duration inminutes of cool cycle operation under thedehumidifying cycle.

DIPSWITCHES :

The TCC controller card has a dipswitcharrangement which should be set and main-tained according to the following settings :

1) TCC controller for single compressorwithout the secondary card for compressors 3and 4 :

Warning : if dipswitches are not setaccording to the above configurations i.e.according to the number of compressorseffectively on line, the TCC controller cardmay behave in unpredictable manner :

- the initialisation <init> can not be complet-ed - card remains locked on start-up.

- HP/BP alarms for non--existing com-pressors.

7. PRACTICAL INSTALLA-TION GUIDE

1) Sea-water cooling :

Install the pump/strainer assembly in sucha manner that a natural gentle upwardsslope exists from the sea-cock to the pumpitself. See also drawing hereabove ref. 6.1.

It is strongly recommended to install anair-bleeder system both in the suction line as well as immediately after the dischargeoutlet of the pump. The advice is especial-ly valid for pumps CLD250/350/1000.The CLD1500/2000 and Calpeda pumps0.5HP to 1 HP generally will not require ableeder system to ensure proper operation.

For ALL boats it is strongly recommend-ed to install a water-scoop at the entry of the sea-cock and directed towards the bowof the boat so that at speed positive pres-sure builds up in the supply line to the sea-water pump.

2) Sea-water cooling exits :Provide for a separate sea-water exit foreach air-conditioning unit installed even ifonly one pump provides cooling for allunits.Introduce shut-off valves for each unit if 1pump provides cooling for more than 1air-conditioning unit.

1 2 3 4

OPEN

ATT. DIPSWITCH SETTINGSBLACK = PUSHED DOWN

TO OVER-BOARD OUTLET APPROX. 10 CMS ABOVE WATER-LINE

MAY BE PLACED 25 CMS ABOVE WATERLINESPECIAL MEMBRANE SELFPRIMING PUMPS

SEA-WATER STRAINER

CLAM-SHELL TYPE THRU-HULL FITTINGWITH SLOTS DIRECTED TOWARDS BOW TO OBTAIN POSITIVE PRESSURE IN SUCTION LINE

NB - ALL PIPING AS SHORT AS POSSIBLE WITHOUTKINKS NOR SYPHONS

WATER-LINE

PUMPS TO BE MOUNTED VERTICALLY WITH PUMP HEAD FACINGS DOWNWARDS

7.1 - INSTALLATION AND POSITIONING OF NEW SELF-PRIMING SEA-WATER PUMP WB200 AND ACCES-SORIES - BLEEDING VALVES NO LONGER NECES-SARY

Page 9: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

This will allow easy priming of the circuitand also calibration of the sea-water flowfor each air-conditioning unit in case ofimbalance in the water tubing lengths.

3) Evaporator coils :

The finned coils of the evaporators and/orair-handlers are fragile. When duringinstallation the fins of these coils are dam-aged, take care to re-align the fins in orderto not impair proper air-flow.

4) Air-ducts :

Flexible air-ducts need to be of good qual-ity with sufficiently strong steel or plasticre-inforcement. Do not restrict air-flow bybending the air-ducts too tightly or byaccidental local deformation.

Do not install air-ducts of excessivelengths (+ 2.5 ml); the pressure loss andconsequent reduction of air-flow will seri-ously diminish the efficiency of the instal-lation.

8. ROUTINE CHECKS

When starting up an air conditioning unitit is advisable to carry out a certain num-ber of routine checks to ensure properfunctioning of the unit.

- always check (especially after a longabsence) the functioning of the sea watercooling system. Immediately stop the sys-tem if no sea-water comes out of the pumpexit after compressor starts up.

- periodically check the air filter in thereturn air grilles. Clean if necessay.

- check condensation drain from the evap-orator drain pan.

- take care to not damage the air-ducts. Adamaged air-duct may stop air flowthrough the evaporator, freeze up the

evaporator and subsequently damage thecompressor.

- when preparing for winter lay-up takecare to rince all sea-water circuits with afresh-water/glycol solution (25% or moredepending on local winter conditions).

8A. TROUBLE SHOOTING

1) No sign of live : check main electricalsupply, fuses, etc.2) The digital display shows 3 lettres<AAA>. This means a persistent state oflow voltage (less than 195 V AC). Thesystem will re-start as soon as the voltagelevel climbs above cut-out level and thesystem will then re-start after a time-delay of 1 minute approx.

3) The compressor will start but no sea-water circulation can be observed :- check sea-cock to sea-water pump.- check sea-water strainer- check if pump rotates- if the pump does not turn with the com-pressor working, check power-supplyfrom the main control unit box to thepump.

4) Compressor and pump work but no cor-rect operation in either cool or heat cycle :- check proper air ventilation - blowers. Ifair flow completely stops with the com-pressor working, the evaporator coils mayfreeze up completely, obstruing all air cir-culation.- during the heat cycle with too slow a sea-water circulation you may actually freezeup the sea-water in the cupro-nickel con-denser and completely block the system.- check voltage level. Do not operate asystem with a persistent voltage levelbelow 195 V AC.- check freon charge if operation is stillnot satisfactory, after having checked allthe above points.

5) The compressor works but is subject to

intermittent stops without having attained the desired set-point temperature.- the HP and BP (if present) pressure safe-ty switches stop the compressor becauseof abnormal working pressures either onthe high or on the low side. Check properfunctioning of the cooling circuit. Checkventilator/blower system for obstructions.- incorrect freon charge (over-charge orinsufficient charge level).

See also here-above : Error codes/inter-rupted system operation.

6) The heat cycle takes very long to getstarted.- normal if the sea-water temperature isvery low. If sea-water temperature dropsbelow approx. 8° C. the heat cyclebecomes much less effective and takeslong to get properly started.

* * *

Operation/Installation Manual - Webasto blue cool select - Page : 9

Operation/Installation Manual - Webasto blue cool select - Page : 9Edition dated 1st November 2005

TO OVER-BOARD OUTLET APPROX. 10 CMS ABOVE WATER-LINE

INSTALLATION OF BLEEDER ADVISABLE

CENTRIFUGAL NON-SELFPRIMING PUMPS

SITUATED MINIMUM 25 CMS BELOW WATERLINE

SEA-WATER STRAINER

SUCTION GENTLY UPWARDS TOFACILITATE PRIMING

CLAM-SHELL TYPE THRU-HULL FITTINGWITH SLOTS DIRECTED TOWARDS BOW TO OBTAIN POSITIVE PRESSURE IN SUCTION LINE

NB - ALL PIPING AS SHORT AS POSSIBLE WITHOUT

KINKS NOR SYPHONS

WATER-LINE

7.2 - INSTALLATION AND POSITIONING OF CENTRIFU-GAL SEA-WATER PUMP AND ACCESSORIES

Page 10: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 10

Operation/Installation Manual - Webasto blue cool select - Page : 10

Edition dated 1st November 2005

9 - AIR DUCTING - VENTILA-TION

1) MINIMUM AIR DUCTING

In order to obtain an acceptable air flow, theuse of 80 mm interior diameter specialsmoothbore insulated ducting is highly rec-ommended. No performance warranty willremain if other air ducts are used. If severalblowers are connected on one air outlet, thesection should begin at 100 mm before split-ing in 80 mm.

The blowers include their transition box andgrilles. The grilles may be mounted horizon-

tally or vertically, the thick side facing out-side. The grilles are not symetrical to allowair deflection.

2) BLOWER INSTALLATION

In order to ease the installation, you may usetwo circular saw (90 mm and 64 mm diame-ter). The grille is maintain on the blower with6 self threading screws. After intallation ,just clip on the bezel.

3) ELECTRICAL CONNECTION

The blowers are all connected to the elctron-ic card. The blowers of the main cabin, man-aged by the digital display, are connected on

the FAN outlet. The remote blowers withindependant speed control are connected onthe piggy card (see picture).

5) RETURN GRILLE OFFSET

It is best to avoid placing a return air grilledirectly opposite the finned coil surface ofthe cooling unit. This will inevitably allowpropagation of direct noise through the grille.Always try to offset the grille so as to chicanethe return air to the coil inlet.

This will lower direct noise propagation in asignificant manner.

template of wall cutting

Page 11: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 11

Operation/Installation Manual - Webasto blue cool select - Page : 11Edition dated 1st November 2005

WIRING SCHEMATICS - SPLIT-AIR WITH NON-SELFPRIMING SEAWATER PUMP

GR

EEN

LIN

ES :

PREC

AB

LED

WIR

ES IN

CA

BLE

HA

RN

ESS

SEAW

ATER

PU

MP

(Non

Sel

f-Prim

ing)

AC

230

/115

V Su

pply

TO A

C C

OM

PRES

SOR

GN

D

HP

SAFE

TYSW

ITC

H

DIS

PLAY

CA

BLE

EXTE

RN

AL

AIR

SEN

SOR

EVA

POR

ATO

R T

EMP.

SEN

SOR

BP

SAFE

TYSW

ITC

H -

1200

0 B

TU a

nd a

bove

REV

ERSE

D C

YCLE

VA

LVE

TO S

PLIT

-AIR

BLO

WER

MO

DU

LES

WIT

HO

UT

SPEE

D C

ON

TRO

L

TO S

PLIT

-AIR

BLO

WER

MO

DU

LES

WIT

H S

PEED

CO

NTR

OL

AD

D-O

N C

ON

TRO

LLER

CA

RD

(ON

/OFF

) FO

R R

EMO

TE S

PLIT

AIR

BLO

WER

MO

DU

LES

------

----R

ed =

pha

se---

------

-blu

e =

neut

ral

------

----b

row

n =

grou

nd---

------

-gre

en =

pre

wire

d in

fact

ory

Page 12: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 12

Operation/Installation Manual - Webasto blue cool select - Page : 12

Edition dated 1st November 2005

SEAW

ATER

PU

MP

(Sel

f-Prim

ing)

AC

230

/115

V Su

pply

TO A

C C

OM

PRES

SOR

GN

D

HP

SAFE

TYSW

ITC

H

BP

SAFE

TYSW

ITC

H12

/16/

20/2

4/30

000

Btu

REV

ERSE

D C

YCLE

VA

LVE

TO S

PLIT

-AIR

BLO

WER

MO

DU

LES

WIT

HO

UT

SPEE

D C

ON

TRO

L

TO S

PLIT

-AIR

BLO

WER

MO

DU

LES

WIT

H S

PEED

CO

NTR

OL

TCC

V3

Con

trol

ler

Car

d

In s

ame

elec

tric

al b

ox :

Self-

Prim

ing

Pum

pC

ontr

olle

r ca

rd +

pre

-w

ired

AC

sup

ply

cabl

e

AD

D-O

N C

ON

TRO

LLER

CA

RD

FOR

REM

OTE

SPL

ITA

IR B

LOW

ERM

OD

ULE

S

DIS

PLAY

CA

BLE

EXTE

RN

AL

AIR

SEN

SOR

EVA

POR

ATO

R T

EMP.

SEN

SOR

WIRING SCHEMATICS - SPLIT-AIR WITH CLD200 SELFPRIMING SEAWATER PUMP

------

----R

ed =

pha

se---

------

-blu

e =

neut

ral

------

----b

row

n =

grou

nd---

------

-gre

en =

pre

wire

d in

fact

ory

Page 13: Webasto AIR-CONDITIONING · 2015-03-11 · All Webasto air conditioning units are sea-water cooled by means of an AC sea-water pump. In order to start the system you only need to

Operation/Installation Manual - Webasto blue cool select - Page : 13

Operation/Installation Manual - Webasto blue cool select - Page : 13Edition dated 1st November 2005

WIRING SCHEMATICS - BLOWER SPEED CONTROL to CROSS-FLOW BLOWER

115/230V AC SUPPLY FROM SPLITAIR UNIT’s ELECTRICAL BOX

GND

SPLITAIR BLOWERMODULE

BLOWER ELECTRICALTERMINALS

BLOWER SPEEDCONTROLLERCARD MOUNTEDIN GRILLE BASE