146
Living Environmental Systems Division 1 Welcome to our Training Centre

Welcome to our Training Centre - E-Si Ltd Design App FTC course E-Si Rev 2… · Practical COP –Space Heating Ambient Temp °C ... • Standalone system requires the Mitsubishi

Embed Size (px)

Citation preview

Living

Environmental

Systems Division

1

Welcome to our Training Centre

Living

Environmental

Systems Division

2

Green Gateway Initiative

That‟s the equivalent of removing 830,000 cars from the UK‟s roads.

The Stern Report has highlighted the catastrophic danger to businesses of ignoring

climate change and we need to recognise that this is a challenge that involves us all.

If we are to meet this challenge and get anywhere near the targets for emissions

reductions that the Government has set then we need to look at more energy efficient

ways of providing the comfort levels for our buildings that modern life (and increasing

legislation) demands.

Anyone involved in this industry- architects, developers, consultants, building services

specifiers, installers, and equipment manufacturers, needs to find ways to provide

modern, comfortable internal environments, in the most energy efficient and

sustainable way possible.

www.greengatewayinitiative.co.uk

The Green Gateway Initiative is a bold and ambitious 10-point

plan that points the way to a reduction of over 3 million tonnes

of CO2 per year, by 2016.

Living

Environmental

Systems Division

3

Low Carbon Domestic Space

and Water Heating

Design and Installation

Living

Environmental

Systems Division

4

Subjects Covered

• CO2 Reduction Targets

• What is The Ecodan Heat pump

• System Operations

• Design and Application

• Service and Maintenance

• Regulations and Legislation

Living

Environmental

Systems Division

5

CO2 Emission Reduction

• How important is it?

• Energy saving

• Cost savings

• Legal requirement

• Moral obligation

Living

Environmental

Systems Division

6

Domestic CO2 Emissions

• A major cause of climate change comes from the

energy we use to heat, light and run our homes

• The domestic sector is a critical area and is

responsible for 27% of UK CO2 emissions

• Energy demand in the sector grew 17.5% from

1990 to 2003

• All fossil fuels are finite resources and need to be

used as economically as possible.

Source: DTI 2002, DEFRA 2002

Living

Environmental

Systems Division

7

The Code for Sustainable Homes

Minimum standards for energy usage

Current Building Regulations

CO2 emission = Level 0 Target Emissions Rate

Reduction in CO2 from current building regulations (TER)

• Level 1 * -10%

• Level 2 ** -18%

• Level 3 *** -25% by 2010

• Level 4 **** -44% by 2013

• Level 51 ***** -100%

• Level 62 ****** Zero Carbon by 2016

1. Zero emissions in relation to Building Regulations issues (i.e. zero emissions from heating, hot water, ventilation and lighting).

2. A completely zero carbon home (i.e. zero net emissions of carbon dioxide (CO2) from all energy use in the home).

Living

Environmental

Systems Division

8

Fuel Type Kg CO2 per

kWh

Boiler

Efficiency

Kg CO2 per kWh of useful

heat

Coal 0.34 85% 0.40

Oil 0.28 90% 0.31

LPG 0.25 95% 0.26

Gas 0.19 95% 0.20

Electricity 0.43 250% 0.17

Coal Boiler 50 to 85%

Oil Boiler 50 to 90%

LPG Boiler 80 to 95%

Gas Boiler 80 to 95%

Heat Pump 250 to 500%

Typical Efficiencies

Worst case heat pump

vs.

Best case boiler

C02 Emission Levels

Living

Environmental

Systems Division

9

The Ecodan Heat Pump

Living

Environmental

Systems Division

10

The Ecodan Heat Pump!

• What is a Heat Pump?

• Benefits of a Heat Pump

• The Ecodan Packages

Living

Environmental

Systems Division

11

The Heat Pump System

• A heat pump harvests low grade heat energy for free and

delivers it where it is useful

• The heat is upgraded using the vapour compression cycle

• As the main heat source is free, the efficiency is excellent

~300% to 400%

annually

Living

Environmental

Systems Division

12

The Magic of a Heat Pump!

1kWElectrical

power in

2kW

3kW

High temperature

heat output

Low temperature renewable heat energy recovered from the environment

Energy from the ambient air

Living

Environmental

Systems Division

13

Compressor

Condenser

Evaporator

4 way valve

Expansion Valve -

throttling

High pressure high

temp superheated

vapour

Low pressure

superheated vapourLow pressure

saturated liquid

and vapour

Plate Heat Exchanger

The Vapour Compression Cycle: Heating

Condenser

Living

Environmental

Systems Division

14

Benefits of the Ecodan HP

• High CoPs (Coefficients of Performance)

• Reduced Carbon emissions

• Reduced Energy Consumption

• Reduced Running costs

• Electricity can be from Renewable Sources

• No Gas Supply or Fuel Tank needed

Living

Environmental

Systems Division

15

Coefficients of Performance (COP)

Coefficients of performance relate the useful heat output to the electrical energy consumed

COP = Heating output

Power consumed

Living

Environmental

Systems Division

16

Performance Factors

• The unit harvests and “upgrades” free heat energy.

• Therefore the amount of heat delivered is always greater

than the energy paid for.

• COPs in the region of 3.0 to 4.0 are achievable i.e. for every

kW of electrical energy consumed 3.0 to 4.0 kW of heat

energy can be delivered.

Living

Environmental

Systems Division

17

Performance Factors:

COP at varying conditions

• Increase in condensing temperature and decrease in

evaporating temperature reduce COP.

°C

amb

Water temp ºC

Inlet/outlet

30/35 40/45 50/55

-15 1.77 1.41 (1.37)

-7 2.41 1.89 1.46

2 2.97 2.27 1.81

7 3.96 3.05 2.28

20 5.39 3.90 2.87( ) T ambient. - 10°C

*Figures for 8.5 KW heat pump

Living

Environmental

Systems Division

18

Weather Compensation

• The weather compensation works in two ways, primarily

the main function is to reduce the heating circuit flow

temperature as the outside temperature increases.

• This allows the heating to increase to its maximum set

point temperature when the outside temperature reduces

down to -3°C outside.

Living

Environmental

Systems Division

19

Benefits of varying flow temperature

for space heating

Living

Environmental

Systems Division

20

Benefits of varying flow temperature

Living

Environmental

Systems Division

21

Standard House Application Case Study

Living

Environmental

Systems Division

22

Standard House Application Case Study

• House constructed to 2000 building regulations

• Using the existing radiator circuit for the heating

• House temperature 18oC - 21ºC.

• Ambient temperature 2oC

• Flow temperature set point 45ºC

Design conditions

Living

Environmental

Systems Division

23

The Reality of the Heat Pump - Case Study

Heat load vs. Ambient

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

-3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Ambient Temperature

Heat

load

kW

24hrs0.4%

452hrs 7.6% 2214hrs37%

3326hrs55%

This leaves 2744 hours

above 15°C for

COPs > 4.0 for space heating,

COPs > 3.0 for Hot water heating

Living

Environmental

Systems Division

24

Practical COP – Space Heating

Ambient

Temp

°C

Output

kW

COP Hrs/year Total

output

kWh

Total

input

kWh

-5 to 0 7.1 1.6 24 170 106

0 to 5 4.8 2.1 452 2170 1033

5 to 10 2.1 4.0 2214 4649 1162

10 to 15 .75 4.5 3326 2495 554

Totals 9484 2856

Living

Environmental

Systems Division

25

Practical COP

Output and time weighted COP

COP = 9484

2856

= 3.32

Living

Environmental

Systems Division

26

Run Cost and CO2 Emissions Comparison

Building

Area

(m²)

Heat

Load

(W/m²)

Building

kW

Required

(kW)

Annual

Energy

Demand

(kWh)

Efficiency

(COP)

Annual

CO2

Emissions

(Kg)

Total

Energy

Cost per

year

(£)

HPB 150 50 7.5 17460 3.50 2145 435

Gas 150 50 7.5 17460 0.90 3686 617

Night Cost

p/kWh

Day Cost

p/kWh

HPB 0.044 0.10

Gas 0.0318 0.0318

Based

on:

Percentage saving 42.0% 29.5%

150m2 house

50w/m2 heat loss

Living

Environmental

Systems Division

27

Reduced Annual Running Costs

Living

Environmental

Systems Division

28

Reduced CO2 Emissions

Living

Environmental

Systems Division

29

The Ecodan System

Living

Environmental

Systems Division

30

Ecodan™ Standalone & Packaged System

• The Ecodan heat pump can either be installed as a package or as a standalone system

• Standalone system requires the Mitsubishi Ecodan and the Mitsubishi FTC (Flow temperature controller)

• Packaged system uses 2 separate units: Mitsubishi Ecodan & Hi-Efficiency Hot Water Tank.

• The Mitsubishi unit extracts heat from the outside air and transfers it into the property in the form of „hot‟ water

Living

Environmental

Systems Division

31

1. Ecodan™ 2. FTC

Living

Environmental

Systems Division

32

Ecodan™ Heat pump Systems

The Air to Water Heat Pump is a pre-assembled self contained

unit mounted externally and incorporates:

• All refrigeration equipment assembled, tested and ready for use

• 2 x Pre-insulated 1” BSP water connections (flexible hoses)

• “Boiler Buddy” – standard water filter system.

• Inline flow setter valve

Living

Environmental

Systems Division

33

Technical Introduction to New Product Range

Ecodan - PUHZ –W50VHA – 5KW (A2 W35) heat pump boiler

950mm

74

0m

m

Maximum running Current - 13 Amps

Maximum flow rate – 14.3 L/M

Minimum flow rate – 6.5 L/M

Power supply 16 Amp – 3 core 1.5mm2 cable

Pipe diameter – 22mm

Noise level - 45dba

Living

Environmental

Systems Division

34

Technical Introduction to New Product Range

Ecodan - PUHZ –W85VHA – 8.5KW (A2 W35) heat pump boiler

Maximum running Current - 23 Amps

950mm

95

0m

m

Maximum flow rate – 25 L/M

Minimum flow rate – 10 L/M

Power supply 25 Amp – 3 core 4mm2 cable

Pipe diameter – 22mm

Note - This unit will supersede the

PUHZ-W90VHA

Noise level - 49dba

Living

Environmental

Systems Division

35

Technical Introduction to New Product Range

Zubadan - PUHZ –HW140VHA – 14KW (A2 W35) heat pump boiler

Maximum running Current - 35 Amps

Maximum flow rate – 40 L/M

Minimum flow rate – 20 L/M

Power supply 40 Amp – 3 core 6mm2 cable

Pipe diameter – *28mm

Noise level – 53 dba

1020mm

13

50

mm

*Increase in required pipe external diameter

Living

Environmental

Systems Division

36 Inverter System

• Inverter Driven Variable Speed Compressor

• No Starting Current

• Excellent Temperature Control

• Quiet Operation

• R410A refrigerant

Overview of Ecodan Key Features

Living

Environmental

Systems Division

37

Current

Time

D.O.L. Start

Inverter Start

Reduced Starting current

Living

Environmental

Systems Division

38

Set

Temperature

On/Off Control

Inverter

Control

Improved Temperature Control

Living

Environmental

Systems Division

39

Refrigerants (R410A)

• This system contains R410A which is a blend of 2 HFCs

(HydroFluoroCarbons) R32 and R125.

• R410A is a highly efficient refrigerant compared with it‟s

predecessors

• This is a sealed system that should not leak –

at the end of its life the refrigerant will be recovered and

destroyed

Living

Environmental

Systems Division

40

F-gas Regulations

• Under F-gas regulations anyone handling

refrigerants should have appropriate training

• Not required as the Ecodan™

– All units are hermetically sealed

– All contain less than 6kg of refrigerant

– Installer will not be considered to be handling

refrigerant

• System repair may need a qualified refrigerant

handler

• Analysis of system running parameters will

require an understanding of the vapour

compression cycle

Living

Environmental

Systems Division

41

Pre-charged to 1.5 bar

Un-vented store

expansion vessel

Primary sealed system kit

Inc. 3 bar relief valve

Sized (by the installer) on the total

system volume, (allow 10 litres for

the appliance pipe work)

Set at 0.5 bar

*Not supplied with package* Supplied with package

Living

Environmental

Systems Division

42

Flow setter valve

To aid in the commissioning and fault finding procedure a flow setter valve or

commissioning valve is supplied with each heat pump boiler.

It should be installed in the flow or return pipe-work for the heat pump boiler,

an arrow indicates the direction of flow.

The valve will give an indication of the

actual water flow rate which is being

circulated at a given time.

The flow rate can be adjusted by

altering the resistance screw.

Living

Environmental

Systems Division

43

Packaged System Operation

Living

Environmental

Systems Division

44

• System Operation

• System User Controls

• Operational Features

• Ambient flow temperature adjustment

Packaged System Operation

Living

Environmental

Systems Division

45

Packaged System and User Controls

Living

Environmental

Systems Division

46

Weather Compensation

• CHzone1 max flow temperature 50°C @ -3°C and

below

• CHzone1 min flow OWC applied 30°C @ 15°C and

above

• CHzone1 Temperature ΔT +/ - 5°C

– This stops the system starting and stopping

Living

Environmental

Systems Division

47

The Flow Temperature

Controller Package

Living

Environmental

Systems Division

48

Flow Temperature Controller or FTC

The FTC has been designed so that the Ecodan heat pump can be

incorporated into a conventional heating system.

Key Features

All system components e.g. Time clock, thermostats, pumps can be

either reused in retrofit situations or supplied & installed in a more

conventional manner.

Living

Environmental

Systems Division

49

Flow Temperature Controller or FTC

The FTC Package

Flow Temperature

Controller

PAR-W21MAA

(Remote Controller)

TH1

(Flow Temperature

Sensor)

Living

Environmental

Systems Division

50

Flow temperature Controller

System Application & Operation

Living

Environmental

Systems Division

51

• System Control Chain

• Single System Piping and Wiring Schematics

• Complete System Piping and Wiring Schematics

• Boost Heating Switch Option

• PAR-W21MAA remote controller initial setting

Standalone (FTC) System Operation

Living

Environmental

Systems Division

52

Flow Temperature Controller or FTC

The FTC is controlled and switched like a conventional gas boiler by

240V signals sent by the system components i.e. Time clock,

thermostats, zone valves and pumps.

Ecodan HPFTC

PAR-W21MAA

Remote Controller Target flow

temperature

Operation mode

ON/OFF

System controls (240V)

E.G Stats/Time clock

(End user interface)

A PAR-W21MAA remote controller is supplied with the FTC, this is only used to set the target

flow temperatures at the commissioning stage.

Living

Environmental

Systems Division

53

Single System

Space heating only or Hot water heating only

Complete System (S - Plan)

Both space heating and hot water heating combined

There are 2 ways of interlocking the FTC with heating systems, this

is dependant on how many heating mediums are incorporated into

the installation

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

The “Single system” pipe work schematic

Internal System

Either

radiators/underfloor OR

hot water

Ecodan HP

FTC

TH1 sensor (supplied with FTC) must

be strapped and insulated to the

water FLOW pipe from the Ecodan.

Boiler

Buddy

Flow

setter

From our initial findings two 15-50 pumps

should be installed in series to achieve the

required flow rates stated earlier.

Pumps

At least 150mm pipe work between

pump and setter

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

55

The “Single system” wiring schematic

Ecodan HP

FTC

PAR-W21MAA

remote controller

Time clockThermostat

Pumps

L

N

E3 core

1.5mm

2 core cable

supplied with FTC

To internal

system

230V

50HZ

Honeywell

command centre

(Optional)

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

56

The “Single system” wiring termination schematic

TH1

1 2

Rem. Con.

1 2 S1 S2 S3

Heat pumpFTC

Relay

PCB

S1 S2 S3

Ecodan HP

TH1 Sensor PAR-W21MAA

Remote controller

TB145

Pumps

Time clock

Thermostat

N L

1 2 3 4 5

Site

2 = Heating

3 = Hot water

230V / 50HZ

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

57

The “Complete system” wiring termination schematic

TH1

1 2

Rem. Con.

1 2 S1 S2 S3

Heat pumpFTC

Relay

PCB

S1 S2 S3

Ecodan HP

TH1 Sensor PAR-W21MAA

Remote controller

TB145

1 2 3 4 5

Site

Honeywell command

centre

To system components

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

58

The “Complete system” wiring termination schematic (S-Plan)

Time clock Room

ThermostatPumps Cylinder

Thermostat CH ZV HW ZV

Honeywell

command

centre

HTG

HW

1 2 3 4 5 6 7 8 9 10

L

N

L

N

L N E

1 2

1 2

4 6 2 47 1023 863

52 1 10 82 1 10

1 2 3 4 5FTC TB145

LNEL NN

75852

230V

50HZ

L L

L

Only difference from

Standard S Plan wiring

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

59

Weather compensation & Boost switch

S1 S2 S3

Heat pumpFTC

Relay

PCB

Site

1 2 3

Heating boost switch

(Optional)TH1

1 2

Rem. Con.

1 2

TH1 Sensor PAR-

W21MAA

Remote

controller

Factory fitted loop wire

between terminal 1 & 3

This will provide weather compensated

flow temperature or “Eco Heat” during

heating mode

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

60

Weather compensation & Boost switch

S1 S2 S3

Heat pumpFTC

Relay

PCB

Site

1 2 3

Heating boost switch

(Optional)TH1

1 2

Rem. Con.

1 2

TH1 Sensor PAR-

W21MAA

Remote

controller

The loop wire should be positioned between

terminal 1 & 2 if a constant heating flow

temperature regardless of the ambient

temperature is required.

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

61

Weather compensation & Boost switch

S1 S2 S3

Heat pumpFTC

Relay

PCB

Site

1 2 3

Heating boost switch

(Option)TH1

1 2

Rem. Con.

1 2

TH1 Sensor PAR-

W21MAA

Remote

controller

A standard 2-way switch can be installed to

give the option of boosting the target flow

temperature during higher ambient

temperatures.

*Terminal 1 must be common

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

62

“DIP” switch settings

SW1 SW2 SW3 SW6ON

OFF

1 8 1 8 1 8 1 2

FTCSet tempLiqud Input signal settingInput signal setting

Switches on the FTC control board must be set to the following combinations, this is the factory

default setting but should be checked during the commissioning stage

1 8 1 8 1 8 1 2

Off ON

Flow Temperature Controller or FTC

Living

Environmental

Systems Division

63

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

64

When the power supply is initially switched onto the system the remote

controller will flash “Please wait” in the left hand corner before showing the

language setting screen, this is defaulted to “English” and just needs to be

entered by pressing and holding the BACK button 2 and the

button 4 . for 2 seconds

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

65

The following settings have to be programmed into the controller after the initial

power up at the commissioning stage.

• Setting day & time

• Setting TH1 target flow temperatures

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

66

Setting the day and time

After initial power ON the time and day of the week need to be set

To set the time use the arrows.

The day of the week

can be changed using

the

*Each press advances the day

Sun Mon … Fri Sat

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

67

Setting target flow temperatures

(1) Press the for 3 seconds to activate the initial setting mode.

To set the target flow temperatures for all modes (HEATING/HEATING ECO/HOT WATER)

the following procedure should be followed

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

68

Setting target flow temperatures

Press to switch to the next

parameter setting

* Disregard these settings

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

69

Setting target flow temperatures

Set the target temperature for both “HEATING” and

“HOTWATER” heating with the Temp buttons

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

70

Setting target flow temperatures

4 parameters have to be set for the target temperature in “HEATING ECO” or weather

compensation mode (Target flow temp depends on outdoor temp).

WATER TEMP

HEATING ECO

Display C shows target flow temp

Display D shows outdoor temp

No.1

WATER TEMP

HEATING ECO

Display C shows target flow temp

Display D shows outdoor temp

No.2

Press to switch between C and D - The blinking figure can be changed using Temp

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

71

Factory settings and recommended flow temperatures (Standard application)

Hot water heating

Factory setting – 500C

Recommended setting – 580C

Heating

Factory setting – 400C

Recommended setting – 550C

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

72

Factory settings and recommended flow temperatures (Standard application)

Eco Heating

No.1 (lower ambient temp)

Factory setting – C = -100C D = 380C

Recommended setting – C = 2C D = 550C

No.2 (High ambient temp)

Factory setting – C = 170C D = 250C

Recommended setting – C = 170C D = 300C

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

73

Setting target flow temperatures

To enter the settings and enable the PCB to memorise the settings the

must be pressed.

The ON/OFF button 6 can then be pressed to exit the setup mode.

Once this stage is reached all the ON/OFF and

mode controls will be operated by the time

clock/stats etc, the PAR-W21MAA will only be

useful to monitor the system operation

If required the remote controller can then be

removed from the system and the FTC PCB

will remember the settings.

PAR-W21MAA remote controller initial setting

Living

Environmental

Systems Division

74

• Fault code indication

• System operating parameters

• System operating parameters at the time of error

PAR-W21MAA remote controller Key Features

Living

Environmental

Systems Division

75

Heat Pump System Design

Living

Environmental

Systems Division

76

Heat Pump System Design

• Heat loss calculations

• Radiator / heat emitter sizing

• Domestic hot water storage volume

• Flow rates

• Under floor heating systems

Living

Environmental

Systems Division

77

Heat Loss Calculation

• Mitsubishi Electric do not carry design liability insurance

• General size guidance only

• Design responsibility of specifier to size unit correctly.

• Gledhill Water Storage have design service for larger

projects

Living

Environmental

Systems Division

78

Heat Loss Calculation

• All buildings are suitable for a heat pump!

• Buildings should be well insulated

• Old buildings with solid walls have high heat losses

• Heat loss calculations are required for SAP on new

build properties.

• Mitsubishi BS5449:1990 Heat Loss Calculator

available for retrofit properties

• E-Si performs heat loss calcs for you.

Living

Environmental

Systems Division

79

Building Heat Loss Calculation

Insert

Dimensions

Select figures

from the

Tables sheet

The required

boiler size is

displayed

Complete

information in

yellow shaded

boxes

Living

Environmental

Systems Division

80

Heat Loss Calculation

Available Ecodan heat pump boiler duties

PUHZ-W50VHA (5KW Heating Duty)

PUHZ-W85VHA (8.5KW Heating Duty)

PUHZ-HW140VHA (14KW Heating Duty)

Living

Environmental

Systems Division

81

Heat Loss Calculation

Please note with the W50 and W85 boilers as the ambient temperature

drops the available output also drops they will still provide heat energy at

-150C ambient.

This is not applicable for the 14KW model.

Living

Environmental

Systems Division

82

Radiator Guidance

Insert

Dimensions

Room type

Insert

Dimensions

Room heat

loss is

displayed for

radiator

sizing

Complete

information in

yellow shaded

boxes

Living

Environmental

Systems Division

83

Radiator Guidance

• Heat pumps produce water at 30°C to 60°C

• Ideal for underfloor heating

• Average underfloor heating circuit 35°C

• Fossil fuel boilers heat water to 80°C

• Flow temp in rads design temp approx 70°C or more

recently for condensing boilers 50C.

• Heat pumps can be used with radiators.

• Sometimes larger surface area to emit heat from

lower temp water is required.

Living

Environmental

Systems Division

84

Radiator Sizing

• Due to lower flow temperatures provided by a heat

pump boiler additional care must be taken when

sizing the surface area of a radiator

• As the temperature difference between the primary

and secondary mediums decrease, the heat

exchangers surface area must increase to emit the

same amount of heat energy

Living

Environmental

Systems Division

85

Radiator Sizing Tool

• Available from Mitsubishi

• Allows rad outputs at variable flow temperatures to

be calculated

• Rule of thumb only

Living

Environmental

Systems Division

86

Radiator Sizing Comparison

High flow temperatureLarge ΔT

Radiator

Dimensions and

duties

0.56m² = 1.6KW

Living

Environmental

Systems Division

87

Low flow temperatureSmall ΔT

1.4m² = 1.6KW

Radiator

Dimensions and

duties

Radiator Sizing Comparison

Living

Environmental

Systems Division

88

Retrofit Radiators

• Actual surface area currently designed on appearance

– e.g. under a window, along length of wall

– Radiator under an average window = 1 – 1.5 m2

– Average property likely to significantly oversized

– Perception is small radiator = cold room

Living

Environmental

Systems Division

89

Radiator Sizing Case Study

• 3 bed semi detached house built to 2006 regs

– Heat loss of 5.4kW (20°C/-3°C)

– Design flow temp of 70°C (normal boiler)

– Each bedrooms radiator sizes should only be approx 0.5m² at this

flow temperature

– In reality the installed radiators were on average 1.15m²

– Design flow at 50°C would require radiators to be approx 1.0m²

Living

Environmental

Systems Division

90

DHW hot water usage patterns

Calculations set out in the CIBSE guide should be carried

out to decide the amount of DHW storage required for a

building.

The table below can be used as a rough guide

Living

Environmental

Systems Division

91

Domestic Hot Water Storage Cylinders and FTC

DHW Cylinder Specifications

Indirect type (with coil type heat exchanger)

5KW heat pump – At least 2m2 surface area coil should be used

9KW &14KW – At least 3m2 surface area coil should be used

(Smaller heat exchangers can be used with Ecodan but please be aware that as the area reduces

the performance and storage temperature achievable of the system is reduced)

Copper construction

We will have recommended specifications for stainless steel vessels after further testing

High density injection or spray on foam to current building regulations

Connection point for either strap-on or immersed thermostat

Living

Environmental

Systems Division

92

Domestic Hot Water Storage Cylinders and FTC

Cylinder specification sheet

This sheet can be completed and sent to a cylinder supplier for a quotation

Living

Environmental

Systems Division

93

Cylinder thermostat

Care should be taken when selecting a cylinder thermostat.

If the stat can be set higher than the achievable storage temperature of 550C then

space heating will be held off due to hot water priority.

It is recommended that a thermostat on which the maximum temperature can be

locked is used and is of an electronic type rather than mechanical. This will prevent it

asking for a temperature that cannot be achieved and preventing space heating from

occurring.

A Potterton PTT2 cylinder thermostat is

used on our demonstration system.

This also gives an indication when the set

temp is achieved.

Domestic Hot Water Storage Cylinders and FTC

Living

Environmental

Systems Division

94

The Hot & Cold Supply Flow Rates

• The hot water flow rate achievable from the HP-DEM is directly related to the adequacy of the cold mains serving the property.

• The cold supply must be capable of providing the total simultaneous demand, this should be calculated and could be up to 60 litres/minute in some properties.

• The minimum flow rate recommended for an adequate mains pressure system in any property is 30 litres/minute, this should be checked before the product is applied.

Living

Environmental

Systems Division

95

Under Floor Heating Systems

The BoilerMate contains a pre-fitted pump for the heating

circuit (s). When using an underfloor heating system, if

the manifold does NOT contain a blending valve it should

be of the non-pumped type.

The blending valve should be set at the design

temperature of the underfloor circuit.

Living

Environmental

Systems Division

96

Summary

• Careful consideration must be given to appropriate

application of this technology to maximise its benefits – it

will not suit all properties, especially many retrofits

• Heat emitters may need to be larger

• Remember – lower flow temperatures maximise COP

• Various regulations apply to the design and installation of

such systems

Living

Environmental

Systems Division

97

Application

Living

Environmental

Systems Division

98

Application

• Ecodan location and installation considerations

• Gledhill location, installation and DHW supply

considerations

• Interconnecting pipe work and wiring

Living

Environmental

Systems Division

99

Location Considerations

• Weight

• Space requirement

• Anti Vibration/Noise requirements

• Electrical details

• Drainage

Living

Environmental

Systems Division

100

Space requirements

Space is required around the a heat pump to allow air flow.

Below is the required space for the 8.5KW heat pump, these vary for

other models and can be found in the relevant installation manuals.

Living

Environmental

Systems Division

101

Space requirements

Air outlet grille for each model are available to divert airflow and reduce minimum

dimensions (PAC-SF08SG-E).

(Figures in brackets are for 14KW model)

Living

Environmental

Systems Division

102

Space requirements

• As Ecodan recovers heat from the environment, the

exhaust air from the fan can be uncomfortably cold,

deflectors are available if the units are to be installed in a

pedestrian area e.g. Patio

• Considerations should be made so that the area in front of

the Ecodan is not going to cause to much disruption to

occupants

Living

Environmental

Systems Division

103

Noise / vibration nuisance

• Flexible hoses (2 x 600mm 1” bore steel braided rubber flexible hose, one for flow and one for return, supplied loose with the unit. (Supplied with package)

• Anti- Vibration mountings i.e Tico pad (NOT supplied with package)

Care should be taken to prevent any vibration transfer into buildings

Noise considerations should be taken into account when locating in close

proximities with other residences

Living

Environmental

Systems Division

104

General Ecodan Electrical Installation

• A qualified part P certified Electrician is required to install the power supply

• Care should be taken to ensure the power supply is weather proof

• Supply cable should be either armoured cable, or twin + earth protected in conduit

• Power should be isolated locally within 1.5 metres, minimum 3mm contact gap in isolator

• An RCD (residual current device) should fitted in the supply to the Ecodan this should have a tolerance of 30mA

Living

Environmental

Systems Division

105

Defrost Cycle & Drainage

As the Ecodan extracts heat from the air at low

temperatures the heat exchanger may accumulate a

slight build up of frost/ice.

The unit will detect this and automatically reverse its

cycle sending hot gas (up to 600C) around the coil as

a defrost strategy.

This usually last for less than 4 minutes.

Living

Environmental

Systems Division

106

• When the unit is providing water heating the refrigerant to

air heat exchanger will cool, and therefore condense

moisture from the air.

• This condensate will drain from the unit and provision for its

disposal may be needed i.e gravel pit.

• Up to ~ 8L/hr

Defrost Cycle & Drainage

Living

Environmental

Systems Division

107

Summary and additional

external considerations

• Clearances around unit and provision for condensate disposal

• Noise, visual impact on property and neighbours. e.g. avoid

sitting near windows, anti vibration pads available

• Qualified electrician required to install power supply

• Planning permission

• Scaffolding tower and/or ladder access for installation and

servicing at high level

• Protection from physical damage/vandalism

Living

Environmental

Systems Division

108

Electrical Considerations

• A qualified part P certified Electrician is required to install the power supply

• Power should be isolated locally within 1.5 metres

• 6mm core cable protected by a 32 amp MCB

• All other internal protection is supplied pre-wired in the package

Living

Environmental

Systems Division

109

Interconnecting pipe work and wiring

• Pipe work and insulation

• Visual Impact

• Essential protection requirements

• Wiring

Living

Environmental

Systems Division

110

Interconnecting pipe work and insulation

22mm 28mm

PUHZ-W50VHA

PUHZ-W85VHA

PUHZ-HW140VHA

Required pipe work diameters between outdoor and indoor.

Note – Larger diameter required for 14KW model

Living

Environmental

Systems Division

111

Interconnecting pipe work and insulation

• Gledhill package - interconnecting pipe run must not exceed 60 metres equivalent length (30 metres difference between units) inclusive of height difference.

• Standalone package – flow rates for each heat pump model must be achieved by sizing the circulating pumps to suit the pipe work.

• Provisions should be made to fit AAV‟s or bleed valves at the highest point in the pipe work

• Pipe work MUST be insulated with Armaflex™ or similar insulation (thermal conductivity 0.04W/m.K).

• To ensure minimal thermal heat loss

*(Failure to to insulate the pipe work WILL reduce the efficiency of the system dramatically)

• For weather protection

• To help prevent freezing

Living

Environmental

Systems Division

112

Air locks, evacuation and lack of flow rate

Precautions should be taken to ensure the evacuation of all air from

the entire primary system.

To accomplish this automatic air-vents should be installed at the

highest point of the primary pipe work.

Failure to do so will result in the heat pump boiler displaying one of

the following errors on the Ecodan PCB LED display

7 Segment LED 7 Segment LED

OR

U1 P6

To reset turn the power to the Ecodan OFF & ON. Continuous reset with

failure to rectify the fault will result in damage to the boiler

Living

Environmental

Systems Division

113

Heating System Bypass

Automatic bypass valves will be required in the heating systems if it is proposed to fit

thermostatic radiator valves (TRV‟s) to all radiators or fit zone valves to control all the

separate heating circuits. To meet the requirements of Building Regulations for a boiler

interlock, it is recommended that the radiator in the area where the room thermostat is

installed should be fitted with lock shield valves on both connections

Living

Environmental

Systems Division

114

The Hot & Cold Supplies

Secondary Hot Water CirculationIf the dead leg volume of the

hot water draw-off pipe work

is excessive a secondary hot

water circulation system

could be considered.

*As a rule of thumb if the hot

water delivery time is greater

than 60 seconds

Hot flow & return pipe work must be insulated

SH WHB

WHB

SCV

SINK

BATH

1

2

34

1. Bronze circulator2. Expansion Vessel3. Hot water return pipework4. Single check valve/non return valve - should be fitted

as close as possible to the Accolade 2000 appliance

Living

Environmental

Systems Division

115

Visual Impact Considerations

• Location of Ecodan

• External pipe work

• Minimise external pipe runs

• Trunking

– E.g inaba-denko

Living

Environmental

Systems Division

116

Interconnecting cables

PUHZ-(H)W50/85/140VHA with Flow Temperature Controller

• A 4 core interconnecting cable is required, this is not supplied with the package

• Minimum conductor size 1.5mm²

• Must not exceed 30 Metres in length

• Must be one cable without any joints

Living

Environmental

Systems Division

117

Essential protection requirements

Filters

– The heat exchanger must be protected from particulate

contaminates in the water circuit.

– When retrofitting provision shall be taken to avoid

contaminates blocking the water circuit within the Heat

Pump.

– A Fernox boiler buddy is supplied with the package and

MUST be fitted to the system between the Ecodan and

Boilermate as close to the Ecodan as possible in the flow

line.

* It is not weather proof so should be positioned indoors

Living

Environmental

Systems Division

118

Freezing!

• One of the biggest risk to the system is freezing the water

contained in the plate heat exchanger.

• Heat exchanger has 1mm capillaries

– Therefore vulnerable to ice damage

• A burst heat exchanger will cost £300

• Plus a days labour from a fridge engineer

• Possible compressor damage

• Potential bill of £900+

Living

Environmental

Systems Division

119

• Provision shall be taken to avoid this pipe work

freezing during winter months i.e. antifreeze/inhibitor,

such as:

• Fernox PROTECTOR ALPHI-11™

• Protects against

– corrosion and limescale

– commonly used in heating systems

– Non-toxic, environmentally friendly

– Combined antifreeze and inhibitor

Essential protection requirements

• Should make up 25% of the total volume.

Living

Environmental

Systems Division

120

Commissioning

Living

Environmental

Systems Division

121

Commissioning Checklist

• Add Fernox Alphi 11 (anti freeze)

• Check air charge is in expansion vessels

• Pressurise primary circuit to approximately 1.50 Bar

• Open all isolating valves

• Release ALL air from the system using automatic air vents

at the highest points of the system

Living

Environmental

Systems Division

122

Before bleeding the air from the system the zone valves should be manually

opened to prevent air lock and possible damage of the circulating pumps.

Commissioning

Living

Environmental

Systems Division

123

FTC System Commissioning

• Operate the system by selecting constant run for BOTH

channels on the installed two channel time clock

• DHW heating will then take priority and raise the hot water

store until the cylinder thermostat is opened.

• Once this temperature is achieved check that the DHW zone

valve closes and CH valve opens. With the boost switch link

between terminals 1 and 2 the system should then target the

preset temperature selected in heating mode during the “Initial

Setting mode”.

Living

Environmental

Systems Division

124

Commissioning

• Indications should be placed on the system and in the

house instructions to ensure that if for any reason the

heating system is emptied the anti-freeze in the pipe-work is

replaced.

Living

Environmental

Systems Division

125

Service and Maintenance

Living

Environmental

Systems Division

126

Annual Servicing (Boilermate)

Service/maintenance recommendations relating to the

Un-vented store.

• Check that the correct rating and type of fuse is fitted to the electrical supply.

• Check for the presence of supplementary earth bonding.

• Clean out the strainer in the combination valve.

• Check the expansion charge pressure and top up if necessary (1.5 bar).

• Clean flow regulators (restrictors/aerators) as applicable and check for correct flow rate.

Living

Environmental

Systems Division

127

• Low maintenance sealed system

– Like a fridge!

• Refrigeration engineer not required

• Essentially a visual inspection

• Unit needs to be kept clear of debris

• Check for signs of damage to unit

• Heat exchanger to be kept clean

- Calclean environmentally friendly coil cleaner

- Brush to remove debris e.g. leaves

Annual Servicing (Ecodan)

Living

Environmental

Systems Division

128

7 Segment LED

ON

1 2 3 4 5 6

Display Mode

O Off

C Cool

H Heat

d Defrost

Display Comp4-way

valve

Solenoid

valve

Warm

up

0 - -

1 - - ON

2 - ON

3 - ON ON

4 ON -

5 ON - ON

6 ON ON

7 ON ON ON

8 ON

System Monitoring & Diagnosis

LED Display inside Ecodan Unit

Living

Environmental

Systems Division

129

7 Segment LED

ON

1 2 3 4 5 6

Set dip switches to

monitor system

parameters – either

current or pre fault

condition

Please Refer to the Technical

Manual for Settings – Note

settings are not the same as

other Mr. Slim

System Monitoring

Living

Environmental

Systems Division

130

System monitoring – examples

• Water inlet temperature (TH32)

• Ambient temperature (TH7)

• LEV-A & B opening pulses

• Discharge temperature (TH4)

• Discharge superheat

• Compressor running current

Note – All of the above examples can be checked for current or pre fault code values

Living

Environmental

Systems Division

131

Air to Water Ecodan Refrigerant Circuit

1

8

3

2

10

11

4 5

7

6

9Water out

Water in

Plate

H/ex.TH4

TH7TH3

TH6

TH32

HP switch

P-sensor

Living

Environmental

Systems Division

132

Ecodan – Monitoring Parameters

Water out

Water in

Plate

H/ex.TH4

TH7

TH3

TH6

TH32

HP switch

P-sensor

Living

Environmental

Systems Division

133

on

off

4 hours 30 min

30 min

At power on, warm up mode operates 4 hours & stops 30mins

Outdoor temp 21°c or less warm up mode operates 30mins &

stops 30mins

Compressor „buzzes‟

Unit Applies Low frequency, Low current power to the

compressor

Warm up mode

Living

Environmental

Systems Division

134

Regulations and Legislation

Living

Environmental

Systems Division

135

Regulations

• Working at Heights

• Approved Document P: Electrical Safety

• Approved Document E: Resistance to the Passage of Sound

• Approved Document B: Fire Safety

• Approved Document L1A: Conservation of Fuel and Power (New Dwellings)

Living

Environmental

Systems Division

136

Electrical Regulations

• Approved Document P: to cover power supply to

Gledhill Unit

• Approved Document P: to cover power supply to

Mitsubishi Unit

• Wiring Regulations: 17th Edition apply in both

cases

Living

Environmental

Systems Division

137

Approved Document P: Electrical Safety

• Third party certification is not permitted

• The installation and commissioning of external

mains voltage equipment is a controlled service

• The interconnecting wiring is not subject to

approved document P, as it only carries 12v and is

classed as extra low voltage

Living

Environmental

Systems Division

138

Installers must have attained a City & Guilds Certificate

(6084) in Energy Efficiency to commission the unit

What the C&G 6084 course covers:

Why energy consumption affects the environment

How energy efficiency affects the heating installer

Legislation that forces change

The requirements of Approved Doc. L and supporting

documents such as CHeSS

Additional Qualifications

Living

Environmental

Systems Division

139

Approved Document L1A: Conservation

of Fuel and Power (New Dwellings)

• Installations must conform with this document

• The „Domestic Heating Compliance Guide‟ gives further guidance

• The installation of heat producing equipment is a controlled service

• Standard Assessment Procedure (SAP)

Living

Environmental

Systems Division

140

Microgeneration Requirements

• The government has produced a Microgeneration Installation Standard

• This outlines best practice for heat pump installations

• Any Grants and/or tax concessions will be dependant upon adhering to this standard

• Installations need to meet the requirements of the HVCA Guide to Good Practice – Heat Pumps (TR/30)

Living

Environmental

Systems Division

141

Microgeneration Requirements

• Installers must have current accreditation such as:-

– Appropriate NVQ level 3

– Other relevant training e.g. Manufacturer‟s product

training

– Membership of a competent person scheme

– Possession of a relevant Skillcard

– Experience gained through a mentoring process

– Demonstrable track record of successful installation

• The relevance of the above will require independent

verification

Living

Environmental

Systems Division

142

Microgeneration Requirements

• The contractor must understand the design and its application

and explain this to the customer

• This explanation must include the proportion of design heat

loss and design hot water load to be supplied by the heat

pump and an estimate of the annual energy performance

• The following disclaimer must be included:

Living

Environmental

Systems Division

143

Microgeneration Requirements -

Disclaimer

„The performance of Microgeneration heat pump

systems is impossible to predict with certainty due

to the variability of the climate and its subsequent

effect on both heat supply and demand. This

estimate is based upon the best available

information but is given as guidance only and

should not be considered as a guarantee.‟

Living

Environmental

Systems Division

144

The Future of the Heat Pump

• Cleaner electricity generation

– Lower CO2 emissions

– Heat pump advantage grows

– Carbon free generation = carbon free heating

– Low carbon electricity generation is enhanced by

a factor equal to the COP of the heat pump

• Carbon savings from installed heat pumps will improve

as each year passes

Living

Environmental

Systems Division

145

The Future of the Heat Pump

• If CO2 emission reduction is important, the heat

pump has a big future

• The air heating products have been available for

some time

• The water heating products have now arrived

• Advances in technology have now made water

heating a more than viable option

Living

Environmental

Systems Division

146

Thank you

Discussion