White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

Embed Size (px)

Citation preview

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    1/15

    Technical Paper

    Determine wire gauge (AWG) &

    insulation type for a system current(amperes) requirement

    Ray-Q Ltd.

    Gilboa St.

    Ben-Gurion Airport City

    70100, Israel

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    2/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 2 of 15

    List of Revisions

    Rev. Change Description DateNew First Issue 02/09

    A Update 08/11

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    3/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 3 of 15

    Can a conductor rated at 10 amps carry 10 amps? Maybe yes probably not. Thereason lies in the test conditions used to rate the conductor. If these conditions donot adequately reflect application conditions, actual allowable current levels may

    be lower than specified levels.For example, many manufacturers test a single conductor in air. This gives anaccurate measure of the basic current-carrying capacity of the conductor. Use theconductor alone in air and it can certainly carry 10 amps. Use it in a multi positionconductors surrounded by other current-carrying conductor or in high ambienttemperatures and the conductor should carry less current.

    This technical paper was composed in order to help the designer set theappropriate current level and specified the current carrying capacity (ampacity) ofa wire or harness.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    4/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 4 of 15

    The ampacity is the maximum amount of current an insulated conductor can carrywithout heating beyond a safe limit. Major influences are:

    1. Conductor Size: The larger the cross section area, the greater the currentcarrying capacity.

    2. Temperature Rating: Wires and cables are rated for continuous operationtemperature. The wire temperature ratings in this technical paper are inaccording to common applications:

    Marine Application: 90C and 105C

    Ground Application: 125C and 150C

    Airborne Application: 150C and 200C

    Space application: 200C

    3. Conductor material: Ampacity is affected by conductivity. Thus theampacity of an aluminum conductor is approximately 80% that of the samesize copper conductor.

    4. Insulation Material: The amount of heat generated should never exceedthe maximum temperature rating of the insulation. Therefore, the higherthe temperature rating of the insulation, the greater current carryingcapacity of the wire.

    5. Ambient Temperature: The higher the ambient temperature, the less heat

    required to exceed the maximum temperature rating of the insulation.6. Installation Method: In air, conduit, duct, tray or direct burial. Bundling,

    stacking and spacing all affect heat dissipation.

    7. Installation Environment: Heat dissipation by conduction, convection,forced air flow, altitude, air conditioning etc.

    8. Number of conductors: Single conductors have a higher ampacity ratingthan equivalent size conductors bundled in a cable.Heat dissipation is lessened as the number of individually insulatedconductors, bundled together, is increased.

    9. Amperage: Heat increase is not linear; it varies as the square of theapplied current.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    5/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 5 of 15

    These many factors make it impossible to construct a general chart for ampacity.

    The values shown in Table1 are MAXIMUM for a single conductor in free air,based on ambient temperature of 30C at sea level, enabling a temperature risefit for different wire types.

    For cable or harness with two (2) or three (3) conductors use Table2.

    For cable or harness with more than three (3) conductors, make circuit analysisfor the bundle to define the percentages of wires in the bundle that carrying powercurrent nearly at or up to capacity. Use correction factor in Table 4 to correct thevalues in Table1.

    For actual use temperatures above an ambient temperature of 30C, reduce themaximum ampacity by use of correction factor in Table 3 to correct the values inTable1 and Table2.

    For altitude above sea level, reduce the maximum ampacity by use of correctionfactor in Table 5 to correct the values in Table1 and Table2.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    6/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 6 of 15

    Table1: Lead Wire Current Carrying Capacity(Amperes per Conductor)

    AWG 90C 105C 125C 150C 200C

    30 3 3 3 3 4

    28 4 4 5 5 6

    26 5 5 6 6 7

    24 7 7 8 8 10

    22 10 11 12 14 16

    20 13 14 15 18 2118 18 20 22 24 28

    16 22 25 26 28 32

    14 30 33 37 42 50

    12 40 45 50 55 68

    10 55 60 65 75 88

    8 80 90 97 106 124

    6 105 121 131 155 165

    4 140 160 172 190 2202 190 215 232 255 293

    1 220 247 266 293 344

    1/0 260 286 309 339 399

    2/0 300 329 355 390 467

    3/0 350 380 410 451 546

    4/0 405 446 481 529 629

    Note:

    1. Values (amperes) shown in this table are maximum for a single conductorin free air with an assumed ambient temperature of 30C, and altitude atsea level.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    7/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 7 of 15

    Table2: Current Carrying Capacity of 2 or 3 conductors(Amperes per Conductor)

    AWG 90C 105C 125C 150C 200C

    30 1 2 2 2 3

    28 2 3 3 3 4

    26 3 3 4 4 4

    24 4 4 5 5 6

    22 6 7 8 9 10

    208

    9

    10

    13

    15

    18 14 15 16 17 20

    16 18 19 20 22 25

    14 25 29 31 34 36

    12 30 36 39 43 45

    10 40 46 50 55 60

    8 55 64 69 76 83

    6 75 81 87 96 110

    4 95 109 118 120 125

    2 130 143 154 160 171

    1 150 168 181 186 197

    1/0 170 193 208 215 229

    2/0 195 229 247 251 260

    3/0 225 263 284 288 297

    4/0 260 301 325 332 346

    Notes:

    1. Current carrying capacity of not more than three (3) conductors within acable, tubing, conduit or bundled together.

    2. The values (amperes) shown in this table are maximum at an assumedambient room temperature of 30C at sea level altitude.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    8/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 8 of 15

    Table 3: Ambient temperatures Correction factors forTable1 & Table2

    AmbientTemperature

    (C)

    Insulation Temperature Rating

    90C 105C 125C 150C 200C

    31 35 0.96 1.00 1.00 1.00 1.00

    36 40 0.91 1.00 1.00 1.00 1.00

    41 45 0.87 0.93 0.94 0.95 0.97

    46 50 0.82 0.93 0.94 0.95 0.97

    51 55 0.76 0.85 0.87 0.90 0.94

    56 60 0.71 0.85 0.87 0.90 0.94

    61 70 0.58 0.76 0.80 0.85 0.90

    71 80 0.41 0.65 0.73 0.80 0.87

    81 90 0.53 0.64 0.74 0.83

    91 100 0.38 0.54 0.67 0.79

    101 120 0.24 0.52 0.71

    121 140 0.30 0.61

    141 160 0.50

    161 - 180 0.35

    Note:

    1. For ambient temperatures over 30C, multiply the ampacities shown inTable1 or Table2 by the appropriate correction factor to determine themaximum allowable load current.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    9/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 9 of 15

    Table 4: More than three conductor correction factor forTable1

    Number ofConductors

    Bundle Loading Percentage

    20% 40% 60% 80% 100%

    4 thru 6 0.85 0.75 0.70 0.65 0.60

    7 thru 9 0.80 0.65 0.60 0.55 0.50

    10 thru 20 0.65 0.55 0.55 0.40 0.35

    21 thru 30 0.60 0.45 0.40 0.35 0.30

    31 thru 40 0.55 0.40 0.35 0.30 0.25

    41 and above 0.50 0.35 0.30 0.30 0.25

    Note:

    1. If more than three (3) conductors are in a cable, tubing, and conduit orbundled together; the values given in Table1 must be reduced using theabove correction factor.

    2. Make circuit analysis for the bundle to define the percentages of wires inthe bundle that carrying power current nearly at or up to capacity.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    10/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 10 of 15

    Table 5: Above sea level correction factor forTable1 & Table2

    Altitude (ft) Correction factor

    1,000 thru 5,000 0.975

    5,001 thru 10,000 0.950

    10,001 thru 15,000 0.925

    15,001 thru 20,000 0.900

    20,001 thru 30,000 0.875

    30,001 thru 40,000 0.850

    40,001 thru 50,000 0.825

    50,001 thru 60,000 0.800

    60,001 thru 70,000 0.775

    70,001 thru 80,000 0.750

    80,001 thru 90,000 0.725

    90,001 thru 100,000 0.700

    100,001 and above 0.600

    Vacuum 0.500

    Note:

    1. If above sea level the values given in Table1 & Table2 must be reducedusing the above correction factor

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    11/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 11 of 15

    Example:

    Application: airborne

    System Maximum Current: 8 amps.

    Cable: 12 wires bundle, 6 wires carrying power currents nearly at or up tocapacity.

    Ambient temperature: 70C.

    Altitude: 60,000 ft

    Step 1:

    Refer to Table1 determine the AWG and the current of the wire required for theapplication. Since the application is airborne and the required wire temperature

    rate is 150C the free air rating for size #22 is 14 amps, and the free air rating forsize #20 is 18 amps.

    Step 2:

    Refer to Table 4 ("More than three conductor correction factors"). For a 12conductor bundle use "10 thru 20" (on the first column). Since there are 12 wiresin the bundle and only 6 wires carrying power currents nearly at or up to capacity,the bundle loading percentage would be:

    12 wires / 6 wires = 50%

    To be on the safe side the correction factor will calculate for Bundle LoadingPercentage of 60%. Therefore the correction factor to use would be 0.55.

    Alternate #1

    Table1 state 14 amps for 22 AWG @ 150C, but when derated for bundle sizethe actual rating is:

    22 AWG 14 [Amps] X 0.55 [correction factor] = 7.7 Amps.

    The result gives out a rating of 7.7 Amps which is insufficient for the application.

    Alternate #2

    Table1 state 18 amps for 20 AWG @ 150C, but when derated for bundle sizethe actual rating is:

    20 AWG 18 [Amps] X 0.55 [correction factor] = 9.9 Amps.

    The result gives out a rating of 9.9 Amps which is sufficient for the application.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    12/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 12 of 15

    Alternate #3

    Table1 state 24 amps for 18 AWG @ 150C, but when derated for bundle sizethe actual rating is:

    18 AWG 24 [Amps] X 0.55 [correction factor] = 13.2 [Amps].

    The result gives out a rating of 13.2 Amps which is sufficient for the application.

    Step 3:

    Refer to Table 3 Ambient temperatures Correction factors, look for70C. Sincethat is the temperature at which the application will be operating and the wiretemperature rating is 150C. Determine that the wire correction factor to be 0.85.

    Alternate #1

    Calculate the derated ampacity of the 20 AWG wire by multiplying with thecorrection factor from Table 3:

    20 AWG 9.9 [Amps] X 0.85 [correction factor] = 8.415 Amps.

    The result gives out a rating of 8.415 Amps which is sufficient for the application.

    Alternate #2

    Calculate the derated ampacity of the 18 AWG wire by multiplying with thecorrection factor from Table 3:

    18 AWG 13.2 [Amps] X 0.85 [correction factor] = 11.22 Amps.

    The result gives out a rating of 11.22 Amps which is sufficient for the application.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    13/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 13 of 15

    Step 4:

    Refer to Table 5 Above sea level correction factor look for 60,000 feet (on thefirst column). Since that is the temperature at which the application will beoperating. Determine that the wire correction factor to 80%.

    Alternate #1

    Calculate the derated ampacity of the 20 AWG wire by multiplying with thecorrection factor from Table 5:

    20 AWG 8.415 [Amps] X 0.8 [correction factor] = 6.732 [Amps].

    The result gives out a rating of 6.732 Amps which is insufficient for theapplication.

    Alternate #2

    Calculate the derated ampacity of the 18 AWG wire by multiplying with thecorrection factor from Table 5:

    18 AWG 11.22 [Amps] X 0.8 [correction factor] = 8.976 [Amps].

    The result gives out a rating of 8.976 Amps which is sufficient for the application.

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    14/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Page 14 of 15

    Appendix A: Charts

    METRIC/AWG WIRE SIZE EQUIVALENTS

    In Europe wire and cable sizes are expressed in mm2 (cross sectional area),while in US the AWG (American Wire Gauge) is the standard system used forboth solid and strand conductors. See below for the cross reference scheme.

    Sq. MM AWG

    0.05 30

    0.08 280.14 26

    0.25 24

    0.34 22

    0.50 20

    0.75 18

    1.00 17

    1.50 16

    2.50 14

    4.00 126.00 10

    10.00 8

    16.00 6

    25.00 4

    35.00 2

    50.00 1

    70.00 2/0

    95.00 3/0

    120.00 4/0

    Note:

    1. Cross references are approximated

  • 8/3/2019 White Paper - Determine Wire Gauge Insulation Type for a System Current Requirement Rev A

    15/15

    White Paper

    Copyright Ray-Q Ltd.

    Gilboa St.Ben-Gurion Airport City

    70100, Israel

    Tel: (972) 3 9753333Fax: (972) 3 9753300

    DETERMINE WIRE GAUGE (AWG) &

    INSULATION TYPE FOR A SYSTEMCURRENT (AMPERES) REQUIREMENT

    08081//

    Rev. A

    Fahrenheit (F) to Celsius (C) conversion

    F C F C F C F C F C F C F C F C

    1.0 -17.2 51.0 10.6 101.0 38.3 151.0 66.1 201.0 93.9 251.0 121.7 301.0 149.4 351.0 177.2

    2.0 -16.7 52.0 11.1 102.0 38.9 152.0 66.7 202.0 94.4 252.0 122.2 302.0 150.0 352.0 177.8

    3.0 -16.1 53.0 11.7 103.0 39.4 153.0 67.2 203.0 95.0 253.0 122.8 303.0 150.6 353.0 178.3

    4.0 -15.6 54.0 12.2 104.0 40.0 154.0 67.8 204.0 95.6 254.0 123.3 304.0 151.1 354.0 178.9

    5.0 -15.0 55.0 12.8 105.0 40.6 155.0 68.3 205.0 96.1 255.0 123.9 305.0 151.7 355.0 179.4

    6.0 -14.4 56.0 13.3 106.0 41.1 156.0 68.9 206.0 96.7 256.0 124.4 306.0 152.2 356.0 180.0

    7.0 -13.9 57.0 13.9 107.0 41.7 157.0 69.4 207.0 97.2 257.0 125.0 307.0 152.8 357.0 180.6

    8.0 -13.3 58.0 14.4 108.0 42.2 158.0 70.0 208.0 97.8 258.0 125.6 308.0 153.3 358.0 181.1

    9.0 -12.8 59.0 15.0 109.0 42.8 159.0 70.6 209.0 98.3 259.0 126.1 309.0 153.9 359.0 181.7

    10.0 -12.2 60.0 15.6 110.0 43.3 160.0 71.1 210.0 98.9 260.0 126.7 310.0 154.4 360.0 182.2

    11.0 -11.7 61.0 16.1 111.0 43.9 161.0 71.7 211.0 99.4 261.0 127.2 311.0 155.0 361.0 182.8

    12.0 -11.1 62.0 16.7 112.0 44.4 162.0 72.2 212.0 100.0 262.0 127.8 312.0 155.6 362.0 183.3

    13.0 -10.6 63.0 17.2 113.0 45.0 163.0 72.8 213.0 100.6 263.0 128.3 313.0 156.1 363.0 183.9

    14.0 -10.0 64.0 17.8 114.0 45.6 164.0 73.3 214.0 101.1 264.0 128.9 314.0 156.7 364.0 184.4

    15.0 -9.4 65.0 18.3 115.0 46.1 165.0 73.9 215.0 101.7 265.0 129.4 315.0 157.2 365.0 185.0

    16.0 -8.9 66.0 18.9 116.0 46.7 166.0 74.4 216.0 102.2 266.0 130.0 316.0 157.8 366.0 185.6

    17.0 -8.3 67.0 19.4 117.0 47.2 167.0 75.0 217.0 102.8 267.0 130.6 317.0 158.3 367.0 186.1

    18.0 -7.8 68.0 20.0 118.0 47.8 168.0 75.6 218.0 103.3 268.0 131.1 318.0 158.9 368.0 186.7

    19.0 -7.2 69.0 20.6 119.0 48.3 169.0 76.1 219.0 103.9 269.0 131.7 319.0 159.4 369.0 187.2

    20.0 -6.7 70.0 21.1 120.0 48.9 170.0 76.7 220.0 104.4 270.0 132.2 320.0 160.0 370.0 187.8

    21.0 -6.1 71.0 21.7 121.0 49.4 171.0 77.2 221.0 105.0 271.0 132.8 321.0 160.6 371.0 188.3

    22.0 -5.6 72.0 22.2 122.0 50.0 172.0 77.8 222.0 105.6 272.0 133.3 322.0 161.1 372.0 188.9

    23.0 -5.0 73.0 22.8 123.0 50.6 173.0 78.3 223.0 106.1 273.0 133.9 323.0 161.7 373.0 189.4

    24.0 -4.4 74.0 23.3 124.0 51.1 174.0 78.9 224.0 106.7 274.0 134.4 324.0 162.2 374.0 190.0

    25.0 -3.9 75.0 23.9 125.0 51.7 175.0 79.4 225.0 107.2 275.0 135.0 325.0 162.8 375.0 190.6

    26.0 -3.3 76.0 24.4 126.0 52.2 176.0 80.0 226.0 107.8 276.0 135.6 326.0 163.3 376.0 191.1

    27.0 -2.8 77.0 25.0 127.0 52.8 177.0 80.6 227.0 108.3 277.0 136.1 327.0 163.9 377.0 191.7

    28.0 -2.2 78.0 25.6 128.0 53.3 178.0 81.1 228.0 108.9 278.0 136.7 328.0 164.4 378.0 192.2

    29.0 -1.7 79.0 26.1 129.0 53.9 179.0 81.7 229.0 109.4 279.0 137.2 329.0 165.0 379.0 192.8

    30.0 -1.1 80.0 26.7 130.0 54.4 180.0 82.2 230.0 110.0 280.0 137.8 330.0 165.6 380.0 193.3

    31.0 -0.6 81.0 27.2 131.0 55.0 181.0 82.8 231.0 110.6 281.0 138.3 331.0 166.1 381.0 193.9

    32.0 0.0 82.0 27.8 132.0 55.6 182.0 83.3 232.0 111.1 282.0 138.9 332.0 166.7 382.0 194.4

    33.0 0.6 83.0 28.3 133.0 56.1 183.0 83.9 233.0 111.7 283.0 139.4 333.0 167.2 383.0 195.0

    34.0 1.1 84.0 28.9 134.0 56.7 184.0 84.4 234.0 112.2 284.0 140.0 334.0 167.8 384.0 195.6

    35.0 1.7 85.0 29.4 135.0 57.2 185.0 85.0 235.0 112.8 285.0 140.6 335.0 168.3 385.0 196.1

    36.0 2.2 86.0 30.0 136.0 57.8 186.0 85.6 236.0 113.3 286.0 141.1 336.0 168.9 386.0 196.7

    37.0 2.8 87.0 30.6 137.0 58.3 187.0 86.1 237.0 113.9 287.0 141.7 337.0 169.4 387.0 197.2

    38.0 3.3 88.0 31.1 138.0 58.9 188.0 86.7 238.0 114.4 288.0 142.2 338.0 170.0 388.0 197.8

    39.0 3.9 89.0 31.7 139.0 59.4 189.0 87.2 239.0 115.0 289.0 142.8 339.0 170.6 389.0 198.3

    40.0 4.4 90.0 32.2 140.0 60.0 190.0 87.8 240.0 115.6 290.0 143.3 340.0 171.1 390.0 198.9

    41.0 5.0 91.0 32.8 141.0 60.6 191.0 88.3 241.0 116.1 291.0 143.9 341.0 171.7 391.0 199.4

    42.0 5.6 92.0 33.3 142.0 61.1 192.0 88.9 242.0 116.7 292.0 144.4 342.0 172.2 392.0 200.0

    43.0 6.1 93.0 33.9 143.0 61.7 193.0 89.4 243.0 117.2 293.0 145.0 343.0 172.8 393.0 200.6

    44.0 6.7 94.0 34.4 144.0 62.2 194.0 90.0 244.0 117.8 294.0 145.6 344.0 173.3 394.0 201.1

    45.0 7.2 95.0 35.0 145.0 62.8 195.0 90.6 245.0 118.3 295.0 146.1 345.0 173.9 395.0 201.7

    46.0 7.8 96.0 35.6 146.0 63.3 196.0 91.1 246.0 118.9 296.0 146.7 346.0 174.4 396.0 202.2

    47.0 8.3 97.0 36.1 147.0 63.9 197.0 91.7 247.0 119.4 297.0 147.2 347.0 175.0 397.0 202.8

    48.0 8.9 98.0 36.7 148.0 64.4 198.0 92.2 248.0 120.0 298.0 147.8 348.0 175.6 398.0 203.3

    49.0 9.4 99.0 37.2 149.0 65.0 199.0 92.8 249.0 120.6 299.0 148.3 349.0 176.1 399.0 203.9

    50.0 10.0 100.0 37.8 150.0 65.6 200.0 93.3 250.0 121.1 300.0 148.9 350.0 176.7 400.0 204.4