Winter, ACC’s, and Lost MW’s heatrate.com James Koch Performance Consultant www.heatrate.com Christopher Haynes Author of FCYCLE, CCYCLE, NCYCLE Plant Design and Operations Power Software Associates, Inc. Dr. Melanie Derby Professor of Mechanical Engineering Specializing in Heat Transfer and Condensing Kansas State University heatrate.com

Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

  • Upload
    trandat

  • View
    218

  • Download
    3

Embed Size (px)

Citation preview

Page 1: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter, ACC’s, and Lost MW’s

heatrate.com

James Koch

Performance Consultant

www.heatrate.com

Christopher Haynes

Author of FCYCLE, CCYCLE, NCYCLE

Plant Design and Operations

Power Software Associates, Inc.

Dr. Melanie Derby

Professor of Mechanical Engineering

Specializing in Heat Transfer and Condensing

Kansas State University

heatrate.com

Page 2: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter, ACC’s, and Lost MW’s

heatrate.com

• Winter back pressures are too high

• The resulting MW loss can be significant (up

to 5% of STG MW’s)

• The loss depends on “End Loading”

• The high backpressures are due to high air

in-leakage, metal wastage concerns, freezing

concerns

• Heatrate.Com and Power Software are

developing instrument and control mods to

minimize these losses.

heatrate.comOut of the box thinking

Page 3: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter, ACC’s, and Lost MW’s

heatrate.com

• Jim Koch, Performance Consultant,

www.heatrate.com, 30+ years in Power

Plant Testing, Modeling, and Analysis

• Chris Haynes, Power Software Associates

40+ years in Plant Design and Operations

Author of FCYCLE CCYCLE NCYCLE

• Dr. Melanie Derby, Kansas State University

Professor of Mechanical Engineering,

Interest in Heat Transfer & Condensing

heatrate.comThe A Team

Page 4: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Summer Backpressure

heatrate.comCan of worms

Page 5: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter Losses due to High Backpressure

heatrate.com

Many steam turbines operate at higher than

optimum backpressures during the winter

heatrate.comSharpen your pencil !

Page 6: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter Losses due to Backpressure

heatrate.com

• Owners know that high backpressure is bad

• This is usually only a summertime concern

• Owners are often unaware of possibility of

lost MW’s during the winter

• The loss can often be 5% of STG MW’s

• For a 100 MW STG, this can be up to $1.5

million per winter with high power prices

• These losses are unit specific

Low hanging fruit

Page 7: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Rule of Thumb ?

heatrate.com

• Years ago, common adage was “1 inch

equals 1%”

• This is INCORRECT ! !

• The rule of thumb is that there is NO rule of

thumb

• The relation between back pressure and

MW’s is UNIT SPECIFIC

Red herring

Page 8: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Turbine A

heatrate.com

Up to 5% of output can be lost.

heatrate.comHocus pocus

Page 9: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Turbine B

heatrate.com

Losses are, at most, 2% of output.

heatrate.comHorse of another color

Page 10: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Turbine A vs Turbine B

heatrate.com

• Turbine A and Turbine B have very different

losses due to high backpressure

• The difference is due to the size of the last

stage blade, relative to steam flow

• This is called the “End Loading”

heatrate.comApples and Oranges

Page 11: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

End Loading

heatrate.com

What is “End Loading?

End Loading = ___Lb/hr of exhaust steam flow__

(Square feet of exhaust flow area)

Very Small Last Stage: 18,000 lb/hr-sqft

Very Large Last Stage: 6,000 lb/hr-sqft

heatrate.comBack of the envelope

Page 12: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Exhaust Flow Area

heatrate.comheatrate.comThe straight skinny

RO

OT

DIA

TIP

DIA

Page 13: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

End Loading

heatrate.com

Q. Why does End Loading matter?

A. It sets the Blading Efficiency, for any given

steam flow and backpressure

• End Loading determines Steam Velocity

• Steam Velocity determines Velocity Ratio

• Velocity Ratio determines Blading Efficiency

heatrate.comDoing more with less

Page 14: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Efficiency Depends on Velocity Ratio

heatrate.comheatrate.comSong and dance

Page 15: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

How does Backpressure affect MW’s?

heatrate.com

Backpressure has two effects:

1. Ideal (Carnot) cycle efficiency changes

2. Last stage blade efficiency changes

heatrate.comView from 30,000 feet

Page 16: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

How does Backpressure affect MW’s?

heatrate.comheatrate.comThe $64,000 question

Q. How do you get the effect of backpressure?

A. From a Heat Balance Model

Page 17: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

How does Backpressure affect MW’s?

heatrate.com

Megawatt losses vary from one unit to another.

A has larger last stage, lower end loading

B has smaller last stage, higher end loading

Megawatt Gain

2.5 to 0.5 in Hga

“A”: 0 MW

“B”: 5 MW

heatrate.comGive or take

Page 18: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter Time Backpressure

heatrate.com

Revisit typical curve of back pressure vs. ambient T

Focus on region between 32 F and 40 F

heatrate.comIn the ballpark

Page 19: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Backpressure, Dollars, and Freezing

heatrate.com

• The trade-off between backpressure and

enhanced freezing protection methods

depends on End Loading

• In HIGHLY End Loaded Units, there is LITTLE

advantage to reducing backpressure

• In LIGHTLY End Loaded Units, there is GREAT

advantage to reducing backpressure

heatrate.comParadigm Shift

Page 20: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Why are Winter Backpressures so high?

heatrate.com

1. High air In-Leakage

2. Erosion concerns

3. Freezing concerns

heatrate.comWhole ball of wax

Page 21: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

In-Leakage and Winter Backpressure

heatrate.com

• High air in-leakage can increase

backpressure. It also increases

danger of freezing.

• ACC’s are more susceptible to air in-

leakage than water cooled units

• Air removal pumps have less

capacity when backpressure is low

heatrate.comThe tail wagging the dog

Page 22: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Backpressure and Erosion concerns

heatrate.com

• “ Erosion” includes both conventional erosion

and flow accelerated corrosion (FAC).

• Both are worsened at LOW backpressure, as

velocity and amount of moisture increase

• FAC is being mitigated with chemistry control

• Progress in corrosion mitigation now makes

lower backpressures achievable.

heatrate.comDucks in a row

Page 23: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Need for Better ACC Freeze Protection

heatrate.com

• Conservative freeze protection procedures prevent

plants from taking advantage of achievable lower

winter back pressure

• When “not quite freezing” these guidelines are too

restrictive, margins are overly-conservative

heatrate.comHorse and buggy thinking

Page 24: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Need for Better ACC Freeze Protection

heatrate.com

• Visited a 125MW STG site with 18 cell ACC

• 1 condensate drain temperature reading per K-cell

• Provided limited information to operators

• As a result, Operators are discouraged from being too

aggressive in winter, leaving MW’s “on the table”

heatrate.comSame old same old

Page 25: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Development of Improved Freeze Protection

Instrumentation and Control

heatrate.com

• 15 temperature readings are too few

• 1,000,000 readings are better

heatrate.comSomething you can hang

your hat on

Page 26: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Development of Improved Freeze Protection

Instrumentation and Control

heatrate.com

• Development, simulation and field testing of Improved

Instrumentation and Controls (patent pending)

Technology

• Program to be undertaken by heatrate.com and a

selected “Alpha Site”

• Pursue “Beta Site” opportunities

• How to monitor temperature at 1,000,000 locations on

the ACC ?

heatrate.comCrossing the T’s and

dotting the I’s

Page 27: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Thermography Measurement, ACC Fan Control System

heatrate.com

• IR Thermograpghy will locate cold ACC tubes

• These will be displayed and alarmed in the control

room, and digitized to provide control system input

• The Plant DCS control computer will “burp” the air

pockets from the condenser

heatrate.comThe big picture

Page 28: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Development of Improved Freeze Protection

Instrumentation and Control

heatrate.comheatrate.comBells and whistles

Page 29: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Development of Improved Freeze Protection

Instrumentation and Control

heatrate.com

Tasks:

• Development and field testing of thermography

measurement, display and digitizing technology

• Simulation and field testing of burping methods to

expel air pockets to prevent freezing

• The “Burp-o-matic” (patent pending)

heatrate.comHit the ground running

Page 30: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter, ACC’s, and Lost MW’s

heatrate.com

• Winter back pressures are too high

• The resulting losses can be up to 5% of

steam turbine MW’s

• The loss depends on “End Loading”

• The high backpressures are due to high air

in-leakage, metal wastage concerns, freezing

concerns

• Heatrate.Com and Power Software are

developing instrument and control mods to

minimize these losses

heatrate.comWin-win

Page 31: Winter, ACC’s, and Lost MW’sacc-usersgroup.org/wp-content/uploads/2015/10/07.J.Koch-C.Haynes... · Winter, ACC’s, and Lost MW’s ... is due to the size of the last stage blade,

Winter, ACC’s, and Lost MW’s

heatrate.com

James Koch

Performance Consultant

www.heatrate.com

Christopher Haynes

Author of FCYCLE, CCYCLE, NCYCLE

Plant Design and Operations

Power Software Associates, Inc.

Dr. Melanie Derby

Professor of Mechanical Engineering

Specializing in Heat Transfer and Condensing

Kansas State University

heatrate.com