Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Fire Detection - W
ireless
WLS/MCP - Wireless Manual Call Point
• Bi-directional wireless communication
• 3rd party approval to EN54-11 & EN54-25
• Resettable element
• Self optimising wireless frequency andamplitude algorithms
• Utilises standard low cost lithiumbattery technology
• 5 year expected battery life
• High reliability
A D D R E S S I N G S A F E T Y S Y S T E M S W I T H I N T E L L I G E N C E
Fire Detection - W
ireless
The WLS/MCP Manual Call Point (MCP) is a fully intelligent device which is compatible with all Protec Translator and Expander Modules. The unit has a resettable plastic element, which displays a drop down warning flag when operated. A key is supplied with the MCP for reset and case opening. The unit can be fitted with an optional transparent cover for protection against accidental operation or with a weatherproof enclosure for use oudoors or in hostile environments.
Company Policy is one of continuous improvement, we reserve the right to change specification without prior notice
Tel: 01282 717171 Web: www.protec.co.uk Email: [email protected]
Fire Detection - W
ireless
Technical Specification
Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT
MED2155 Issue 2
Technical Specification
Operating frequency range 868 – 870 MHz
Max radiated power 5dBm (3mW)
Radio signal modulation type FSK
Operating frequency channels 7
Communication range with the ≤ 150 m (in open space)Translator or Expander Module
IP rating IP42
Dimensions (mm) 86(W) x 86(H) 59(D)
Weight (without batteries) 186g
Primary battery CR123A (3 V & 1.2 Ah)
Secondary battery CR2032A (3 V & 0.24 Ah)
Primary battery lifespan (typical) 5 years
Secondary battery lifespan (typical) 2 months
Operating Temperature (no icing) -10°C to +55°C
Max humidity 95% RH (non condensing)
Relevant Standard EN54 Part 11 & 25
© 2017 - 2021 Protec Fire and Security Group Ltd.
Dimensions (mm)
Operating Element Cover
86 24 35 86
86
Base
2831