11
Table 10. Finite element analysis data from Reference r 261 on run moments (branch moments shown for comparison) c (a) c (b) l R/T r/R t/T tn/T r/rp rz/tn 2r Mor H. Mtr Mob Hi.b Mtb Lr UA 50.5 0.5 0.5 0.5 0.990 1.00 1. 10 4.62 4.35 16.6 7.00 1. 39 B 40.5 0.5 0.5 0.5 0.998 1.00 1.09 4.54 4.18 15. 1 6.54 1.32 c 20.5 0.5 0.5 0.5 0.976 1.00 1. 05 4.09 3.53 10.8 5.17 1. 2 5 D 10.5 0.5 0.5 0.5 0.955 1.00 1.04 3.60 3.41 5.77 3.28 1. 39 E 5.5 0.5 0.5 0.5 0.917 1.00 1.03 3. 17 2.79 3.50 2.64 1. 43 F' 5.5 0.08 0.08 0.08 0.917 6.25 1.04 3. 11 2.12 l. 27 1.36 1.02 SlA 50.5 0.5 0.5 4.34 0.861 0.500 1.04 2.19 2.98 11. 1 2.19 1. 16 B 40.5 0.5 0.5 4.01 0.843 0.500 1.04 2.23 2.87 9.84 2.09 1.16 c 20.5 o.s 0.5 3. 14 0.780 0.500 1.04 2.25 2.43 5.64 1. 51 1. 17 D 10.5 0.5 0.5 2.45 0.705 0.500 1.04 2.07 2. 11 2.81 1.42 1 • 16 E 5.5 0.5 0.5 1. 92 0.623 0.500 1. 03 2.07 1. 70 1. 56 1. 49 1. 1 3 F 20.5 0.32 0.32 2.56 0.732 0.500 1.04 2.36 2.01 2.56 1.22 1.06 G 10.5 0.32 0.32 1.98 0.649 0.500 1.04 2.23 1. 92 1. 43 l. 37 1.07 H 5.5 0.32 0.32 l. 52 0.563 0.500 1.03 2.08 1.68 1.39 1. 37 LOS I 20.5 0.16 0.16 1. 88 0.646 0.500 1. OS 2.49 1.81 1.22 1. 2 3 1.02 J 10.5 0.16 0.16 1.43 0.555 0.500 1.04 2.38 l. 78 1.26 1.25 1.02 K 5.5 0.16 0.16 1. 08 0.468 0.500 1.02 2,33 1. 64 1.33 1. 32 1.03 L 20.5 0.08 0.08 1.38 0.551 o.soo 1.06 2.52 1.76 1.18 1.22 1.01 H 10.5 0.08 0.08 1. 03 0.459 0.500 1. 04 2.61 l. 7 5 1. 18 1. 21 1. 01 N 5.5 0,08 0.08 0.72 0.391 0.500 1.03 2.63 1.68 1 • 21 1.20 1.02 E'30A 50.5 0.32 0.32 3. 19 0.808 0.500 1.03 2.24 2.30 3.73 1. 19 1.08 B 20.5 0.32 0.32 2.13 0.743 0.500 1.04 2.39 2.13 1.84 1,24 1.08 c 10.5 0.32 0.32 1. 60 0.695 0.500 1. 03 2.27 1.97 1.39 1.32 1.07 D 5.5 0.32 0.32 1.23 0.659 0.500 1.03 2.05 1. 7 3 1.33 1.35 1.05 E 5.5 0.08 0.08 0.533 0.556 0.938 1. 03 2.68 1. 72 1. 19 1. 20 1. 01 (a) c # 2r = a/ (H/Z ) r (b) Czb = o/(M/Zb) can be written as i 9 liu = 3.75[(t/T)/(r/R)] 112 (r/rP). Now, as an upper bound to i9/i11 the ratio (t/T)/(r/R) is not likely to exceed 5, r/R is not permitted to exceed 0.5 and r/rp cannot exceed 1.0. Accordingly, (ig/ill)max = 3.75 X 5 X 0.5 112 X 1.0 = 13. This means that use of Eq. (9) instead of Eq. (11) might result in an overestimate of i-factors for check- ing run ends by a factor of up to 13. To bound possible underestimates, (t/T)(r/R) is not likely to be less than 1.0 and r/rp is not likely to be less than 0.5. Then i 9 /i 11 will be less than 1.0 if r/R is less than (1/1.875) 2 = 0.284. However, even for R!T = 50 the maximum underestimate is by a factor of 1.544 and this factor decreases to 1.50 at r/R = 0.213 because both i 9 and i 11 are equal to their lower bounds. Accordingly, the effect of including Eq. (11) in ANSI B31.1 for "Branch connections" will almost al- ways be to reduce the conservatism in checking the run ends. 4.5 Combination of Moments Up to now, we have been discussing the accuracy of i-factors for individual moments. In piping systems, a branch connection will be subjected to the nine mo- ments indicated in Fig. 3. Let us suppose that we could determine accurate SIFs for each of the three individ- ual branch moments, balanced by one end of the run pipe. Then we might estimate the combined fatigue- effective stress by: SE =[i()M() + i,M, + itMtl/Zb (32) or by S - [(' M )2 ('M)2 (' M )2]1/2/Z E - La o + ti i + 1 t t b (33) Equation (32) is an upper bound because it assumes that the maximum fatigue stress due to each of the three moments occurs at the same point on the branch connection and lies in the same direction so as to add algebraically. However, we know that fatigue usually initiates near the longitudinal plane for M 1 b, but near the transverse plane for Mob· Equation (33) has a theo- retical foundation for straight pipe but for branch Stress Intensification Factors 25

Wrc 329-1987 Accuracy of Stress Intensification Factors for Branch Connections_part3

Embed Size (px)

DESCRIPTION

fafa

Citation preview

  • Table 10. Finite element analysis data from Reference r 261 on run moments (branch moments shown for comparison)

    c ~ (a) c (b) ~1ode l R/T r/R t/T tn/T r/rp rz/tn 2r

    Mor H. Mtr Mob Hi.b Mtb Lr UA 50.5 0.5 0.5 0.5 0.990 1.00 1. 10 4.62 4.35 16.6 7.00 1. 39

    B 40.5 0.5 0.5 0.5 0.998 1.00 1.09 4.54 4.18 15. 1 6.54 1.32 c 20.5 0.5 0.5 0.5 0.976 1.00 1. 05 4.09 3.53 10.8 5.17 1. 2 5 D 10.5 0.5 0.5 0.5 0.955 1.00 1.04 3.60 3.41 5.77 3.28 1. 39 E 5.5 0.5 0.5 0.5 0.917 1.00 1.03 3. 1 7 2.79 3.50 2.64 1. 43 F' 5.5 0.08 0.08 0.08 0.917 6.25 1.04 3. 11 2.12 l. 27 1.36 1.02

    SlA 50.5 0.5 0.5 4.34 0.861 0.500 1.04 2.19 2.98 11. 1 2.19 1. 16 B 40.5 0.5 0.5 4.01 0.843 0.500 1.04 2.23 2.87 9.84 2.09 1.16 c 20.5 o.s 0.5 3. 14 0.780 0.500 1.04 2.25 2.43 5.64 1. 51 1. 17 D 10.5 0.5 0.5 2.45 0.705 0.500 1.04 2.07 2. 11 2.81 1.42 1 1 6 E 5.5 0.5 0.5 1. 92 0.623 0.500 1. 03 2.07 1. 70 1. 56 1. 49 1. 1 3 F 20.5 0.32 0.32 2.56 0.732 0.500 1.04 2.36 2.01 2.56 1.22 1.06 G 10.5 0.32 0.32 1.98 0.649 0.500 1.04 2.23 1. 92 1. 43 l. 37 1.07 H 5.5 0.32 0.32 l. 52 0.563 0.500 1.03 2.08 1.68 1.39 1. 37 LOS I 20.5 0.16 0.16 1. 88 0.646 0.500 1. OS 2.49 1.81 1.22 1. 2 3 1.02 J 10.5 0.16 0.16 1.43 0.555 0.500 1.04 2.38 l. 78 1.26 1.25 1.02 K 5.5 0.16 0.16 1. 08 0.468 0.500 1.02 2,33 1. 64 1.33 1. 32 1.03 L 20.5 0.08 0.08 1.38 0.551 o.soo 1.06 2.52 1.76 1.18 1.22 1.01 H 10.5 0.08 0.08 1. 03 0.459 0.500 1. 04 2.61 l. 7 5 1. 18 1. 21 1. 01 N 5.5 0,08 0.08 0.72 0.391 0.500 1.03 2.63 1.68 1 21 1.20 1.02

    E'30A 50.5 0.32 0.32 3. 19 0.808 0.500 1.03 2.24 2.30 3.73 1. 19 1.08 B 20.5 0.32 0.32 2.13 0.743 0.500 1.04 2.39 2.13 1.84 1,24 1.08 c 10.5 0.32 0.32 1. 60 0.695 0.500 1. 03 2.27 1.97 1.39 1.32 1.07 D 5.5 0.32 0.32 1.23 0.659 0.500 1.03 2.05 1. 7 3 1.33 1.35 1.05 E 5.5 0.08 0.08 0.533 0.556 0.938 1. 03 2.68 1. 72 1. 19 1. 20 1. 01

    (a) c # 2r = a/ (H/Z ) r (b) Czb = o/(M/Zb)

    can be written as i9liu = 3.75[(t/T)/(r/R)] 112(r/rP).

    Now, as an upper bound to i9/i11 the ratio (t/T)/(r/R) is not likely to exceed 5, r/R is not permitted to exceed 0.5 and r/rp cannot exceed 1.0. Accordingly,

    (ig/ill)max = 3.75 X 5 X 0.5 112 X 1.0 = 13. This means that use of Eq. (9) instead of Eq. (11) might result in an overestimate of i-factors for check-ing run ends by a factor of up to 13.

    To bound possible underestimates, (t/T)(r/R) is not likely to be less than 1.0 and r/rp is not likely to be less than 0.5. Then i 9/i 11 will be less than 1.0 if r/R is less than (1/1.875) 2 = 0.284. However, even for R!T = 50 the maximum underestimate is by a factor of 1.544 and this factor decreases to 1.50 at r/R = 0.213 because both i9 and i 11 are equal to their lower bounds.

    Accordingly, the effect of including Eq. (11) in ANSI B31.1 for "Branch connections" will almost al-ways be to reduce the conservatism in checking the run ends.

    4.5 Combination of Moments Up to now, we have been discussing the accuracy of

    i-factors for individual moments. In piping systems, a branch connection will be subjected to the nine mo-ments indicated in Fig. 3. Let us suppose that we could determine accurate SIFs for each of the three individ-ual branch moments, balanced by one end of the run pipe. Then we might estimate the combined fatigue-effective stress by:

    SE =[i()M() + i,M, + itMtl/Zb (32) or by

    S - [(' M )2 ('M)2 (' M )2]1/2/Z E - La o + ti i + 1t t b (33) Equation (32) is an upper bound because it assumes that the maximum fatigue stress due to each of the three moments occurs at the same point on the branch connection and lies in the same direction so as to add algebraically. However, we know that fatigue usually initiates near the longitudinal plane for M 1b, but near the transverse plane for Mob Equation (33) has a theo-retical foundation for straight pipe but for branch

    Stress Intensification Factors 25

  • Table 11. Finite element and strain gage data on run moments (branch moments shown for comparison)

    Ref. no.

    25

    23

    Hodel Hethod R/T

    ORNL-1 F. E. S.G.

    ORNL-2 F.E. S.G.

    ORNL-3 F.E. S.G.

    ORNL-4 F.E. S.G.

    1 S.G. 2 s.G. 3 S.G. 4 S.G.

    49.5

    49.5

    24.5

    24.5

    20.7 12.4

    7.6 5.7

    r/R

    0.49

    1. 00

    0.111

    0.125

    1.00 1.00 1. 00 1.00

    t/T

    0.50

    1. 00

    0.84

    0.32

    1.00 1.00 1. 00 1. 00

    2.7 2.3 5.9 4.5 1 1 1.2 1. 0 1.3

    3.68 2.58 1.68 1. 72

    C ' (a)

    5.7 3.8

    10.1 14.9

    2.5 3.2 3.1 4.0

    8.03 5.35 3.48 2.87

    13.0 10.0 37.5 24.2

    5.6 2.5 5.1 5.0

    6.8oc 5 .18c 3.55 3.20

    37.2 35.3 17.8 15.8

    7.3 5.0 7.6 8.5

    9.33 6.65 4.14 3.53

    c ~ (b)

    10.9 10.0 15.2 11.0

    5.6 3.7 7.2 6.1

    12.14 8.14 4.48 3.92

    5. 1 12.5 37.5 31.3 0.6 1.7 1.0 1.5

    1 o. 4 9 7.38 4.36 4.53

    (a) a/(M/Z ) for M and Mir a/(M/22 ) for H r tr r or

    (b)

    (c) Maximum and minimum principal stresses have same signs, except for these two cases: a = 6.68, a i = -6.80 ; a -5.18, a i = 0.23

    max m n max m n

    connections it only represents a judgmental evalua-tion of the effect of the three combined moments.

    ANSI B31.1 and the ASME Code both combine stresses by:

    SE = i[~ + MJ + A(;?jl12/Z (34) To the extent that i = max(i0 , ii, i1), which is generally the intent, and for branch connections where io ii and i 1 are different, then Eq. (34) would be more conserva-tive than Eq. (33). Both ANSI B31.1 and the ASME Code also use Eq. (34) for run moments. Calculated values of S E for both the branch end and the run ends must be less than the Code allowable stress.

    Fig. 14 illustrates a problem in evaluating combined moments. Figs. 14(a) and 14(c) show the combination of moments for which we have i/s for branch moments. However, there is an infinity of possible run moments between (a) and (c) which will balance the branch moment and which might occur in piping systems, one of which is shown as (b). Fig. 14(b) is of particular interest because 29720 and Fujimoto21 analyses are based on these run end conditions.

    If a fatigue test were run with the end conditions shown in Fig. 14(b), would the resulting ir be different from (a) or (c)? We do not have any such tests, but would speculate that if r/R is less than about%, the difference would be small. However, for r/R = 1.0 there might be a difference in that ir for Fig. 14(b) would be less than for (a) or (c). It is the latter that we have i/s for; hence, in this sense our i/s may represent upper bounds.

    Figs. 14(d) and (e) illustrate other possible moment combinations. Fig. 14(e) is the pure run moment case for which we do have some data as discussed in Section 4.4.

    Fig. 14(d) illustrates the more complex case; the ASME Code Class 1 method of separating these into branch moments and run moments is shown. The total calculated stress is then obtained by adding the stress-es due to the branch moments to those due to the run moments. ASME Code for class 2/3 piping and ANSI Codes follow a conceptually different procedure in that each of the three ends is checked separately. Comparisons between these two conceptual methods is discussed in detail in Ref. 27 so we will not discuss it further except to note that:

    1. The conceptual difference is significant only for the type of moment combinations illustrated by Fig. 14(d).

    2. For a narrow range of branch connection parame-ters and moments, the ASME Code Class 1 meth-od is more conservative by a factor of up to two.

    3. Neither conceptual method can be demonstrated to be accurate or even relatively more accurate.

    4.6 Branch Connection Description Inconsistencies In the quest for more accurate i-factors, a desirable

    Code characteristic is that for a given configuration of branch connection the Code should give the same i-factors. However, note the following:

    The ASME Code, Class 2/3 piping, for a UFT gives:

    26 WRC Bulletin 329

  • Table 12. Run moments, maximum stresses

    Table 10 max. Table 11 max.

    c2;' ASME c2;' 2i, ASME Hodel 2 X Eq. (ll) 2i, Class 1' Model 2 X Eq. (11) Class 1' max. (4) max. Eq. (4) (a) Eq. Eq. (30) (b) Eq (30) UA 4.62 5.46 24.6 5.36 25-1 6.5 t 5.28 24.3 5.31

    B 4.54 4.72 21.2 5.08 5.0 t 5.28 24.3 5.31 c 4.09 3.00 13.5 4.28 25-2 18.8 t (10.8) 24.3 (5.34) D 3.60 3.00* 8.6 3.62 14.9 (10.8) 24.3 (5.34) E 3.17 3.00* 5.6 3.08 25-3 2.8 t 3.00* 15.2 2. 70 F 3. 11 3.00* 5.6 3.08 3.2 3.00* 15.2 2. 70

    25-4 3.1 3 .00* 15.2 3.54 S1A 2.98 t 5.46 24.6 3.13 4.0 3.00* 15.2 3.54

    B 2.87 t 4.72 21.2 3.02 c 2.43 t 3.00 13.5 2.71 23-1 8.03 (6.03) 13.6 (4.29) D 2. 11 t 3.00* 8.6 2.65* 23-2 5.35 (4.29) 9.7 (3.78) E 2.07 3.00* 5.6 2.65* 23-3 3.48 (3. 09) 7.0 (3. 34) F 2.36 3.00* 13.5 2.65* 23-4 2.87 (2.55) 5.7 (3.11) G 2.23 3.00* 8.6 2.65* H 2.08 3.00* 5.6 2.65* I 2.49 3.00* 13.5 2.65* J 2.38 3.00* 8.6 2.65* K 2.33 3.00* 5.6 2.65* L 2.52 3.00* 13.5 2.65* a 2.61 3,00* 8.6 2.65* N 2.63 3.00* 5.6 2.65*

    P30A 2.30 t 3.50 24.6 3.02 B 2.39 3.00* 13.5 2.67 c 2.27 3.00* 8.6 2.65* D 2.05 3.00* 5.6 2.65* E 2.68 3.00* 5.6 2.65*

    (a) From Table 10, maximum of c 2' for Mar Mir' Mtr' Maximum is either from Mir or Mtr; where from Mtr' value is followed by a 10t".

    (b) From table 11, maximum of c 2; for Mar' Mir or 1/2 of c2; for Mtr" Maximum is either from Mir or Htr; where from Htr' value Is followed by a "t",

    i(t/T) = [0.9(RITf1~ (tiT), for checking branch (35) i = 0.9(RIT) 213 , for checking run ends (36)

    The ASME Code, Class 213 piping, for a "Branch con-nection," gives:

    ib = 3.0(RIT)213(riR) 112(tiT) (r/r p) ;;::: 2.1 mimimum (37)

    ir = 0.8(RIT) 213(riR) ;;::: 2.1 minimum (38)

    We have written Eqs. (35)-(38) so that they are direct-ly comparable with respect to calculation of S e; i.e., Eqs. (35) and (37) would be used with Zb Eqs. (36) and (38) would be used with Zr. We have written Eqs. (37) and (38) for r 2-not-provided [see Table 1, footnote 6(h)] so that Fig. 2(d) is geometrically identical to a UFT. The i-factors for i(tiT) for Eq. (35)] for RIT = 50, riR =tiT, and rlrp = 0.99, are:

    r/R =tiT Equation 0.1 0.2 0.3 0.4 0.5

    (35) 1.22 2.44 3.66 4.89 6.11 (37) 2.1 3.61 6.62 10.2 14.3 (36) 12.2 12.2 12.2 12.2 12.2 (38) 2.1 2.17 3.26 4.34 5.43

    We have discussed the relative accuracy of these SIF equations elsewhere; our point here is that for geomet-rically identical branch connections the Code gives different i-factors. A code user, not recognizing that a UFT with r IR up to 0.5 is also covered by "Branch connection," might do something unnecessary such as adding a pad or changing the piping system. The Code would be improved in this respect by adding a foot-note, tied to UFT's, saying that for riR ~ 0.5, UFT's can alternatively be evalauted as "Branch connec-tions."

    As indicated in Table 1, ANSI B31.3 incorporates a commendable effort to distinguish between different

    Stress Intensification Factors 27

  • (a) Fatigue Test Moments

    -10

    (b) Some A.n~tl.ysee Moments

    -10

    0 _ __,_ __ 10 (c) Fatigue Teat Moments

    -10

    -1Q __ L 20- (d) Branch and Run Combination -10

    + -10_1_ 10

    0

    (e) Pure Run Moments 10 -10

    Fig. 14-lllustration of combinations of branch and run moments

    types of branch connections. This, in the long run, will provide improved Code guidance for adequate but not over-costly piping systems. However, there is an in-consistency between UFT's and the "Branch welded-on fitting (integrally reinforced)" which merits some discussion.

    First, footnote 7 tied to "Welded-on" reads: "The designer must be satisfied that this fabrication has a pressure rating equivalent to straight pipe." Now, there isn't anything simple about reducing-outlet branch connections so we ask the question: Which straight pipe, the run or the branch? We think the intent is the run pipe so that question could be an-swered by inserting the word "run" before pipe in the footnote. The question then arises as to how the de-signer meets the requirement of footnote 7. Presum-ably, the intent is that the designer orders fittings from a manufacturer with a designated wall thickness (e.g., Sched. 40) with, perhaps, a requirement in his purchase order that the fitting must have a pressure rating equivalent to the desired schedule run pipe.

    There appears to be a couple of ways the manufac-turer could assure himself and his customers that his fittings, when properly welded into designated run pipe, would have a pressure rating equivalent to the run pipe:

    1. Run burst tests. 2. Show compliance with paragraph 304.3 of B31.3,

    using designated wall thickness rather than cal-culated by Eq. (2) of B31.3.

    Now the potential inconsistency arises because UFT's

    (unreinforced fabricated tees), if they are to meet B:31.3, must be reinforced as required by paragraph

    304.~3 of B3 U~ for the design pressure. We think that most UFT's will meet both burst tests and paragraph :304.3 for the designated wall thicknesses. We note that Table l(f) indicates an angle like On in Fig. 2(c), but with no control of that angle; i.e., it could be zero. We presume this omission of a control on 0, is intentional; i.e., it covers fittings such as indicated by Figs. 2(a) and (b) as well as (c). Our point is that, without a control on 0,, it may also include UFT's Fig. 2(d). Noting in Table 1 the differences in h, B31.3 indicates that for geometrically identical branch connections, we might have SIFs that differ by a factor of (3.3) 2/:l = 2.2.

    4.7 ANSI B16.9 Tees, Sweepolets (Bonney Forge Trade name)

    In order to keep this report from becoming even more complex than it is, we have not given data on ANSI B16.9 tees or Sweepolets. There is a fairly sub-stantial amount of data on B16.9 tees. Data are avail-able for r!R = 1.0 and for r/R = "'-'0.5; but nothing in between. Accordingly, we do not know if there is a peak in the SIF for Mob as suggested by Figs. 6, 7 and 8. At present, plans are being made to fatigue test some 4 x 3, std. wt. ANSI B16.9 tees with Mob loadings. These tees have an r/R ratio of 0.77 and should give some indication as to whether a peak does exist.

    Sweepolets in sizes 12 x 6 and 14 x 10, both standard weight, have been fatigue tested with both Mob and M,b loadings. The r/R ratio of these two sizes is 0.51 and 0.76, respectively. The Mob tests indicate that there is a peak somewhere around 0.75. The Mib tests agree with the general relationship (see Figs. 6-10) that the it for M;b is much lower than for Mob and there is no significant peak as a function of r/R. 4.8 Stress Limit, Sx

    As indicated by Eq. (12), having calculated SE the Code then provides a limit; SE.::::: Sx. The stress limit is an important part of assessing the significance of the accuracy of i-factors. The Codes prescribe the stress limit, Sx, as:

    where f = cycle dependent factor ranging from 1.0 for

    7000 cycles to 0.5 for > 100,000 cycles Sc = allowable stress at cold temperature in cycle sh = allowable stress at hot temperature in cycle Ss = sum of longitudinal stresses due to pressure,

    weight and other sustained loads. The significance of the stress limit is discussed in de-tail in Ref. 27. For the purpose of this report, we make the following observations;

    (1) For materials like ASTM A106 Grade B carbon steel at temperatures up to about 600 F, with S, and S11 from the ASME Code or from B31.1, there is a margin between failure and Code a!-

    28 WRC Bulletin 329

  • lowable moments that ranges from about 8 for 100 cycles of moments to about 2 for 7000 or more of moments. Many piping do not undergo more than 100 cycles of full moment range; hence, for those an un-derestimate of S E by up to a factor of 8 would not necessarily imply failure.

    (2) Observations in (I) are also applicable to aus-tenitic stainless steel materials like ASTM 312 Type 304 or Type 316.

    (3) Observations (1) and (2) are predicated on the assumption that environmental effects are no worse than the room temperature/water inside environment of the fatigue tests.

    (4) Branch connections made of materials with val-ues of and sh that are higher than those for ASTM A106 Grade Bare not necessarily better in low cycle fatigue strength than A106 Grade B; hence, the margins indicated in (1) may be re-duced.

    (5) ANSI B31.3 uses a margin of 3 on ultimate ten-sile strength (UTS) in establishing allowable stresses, Sc and Sh. The ASME Code and B31.1 use a margin of 4. For some materials/tempera-tures; this means that the margins in (1) would be decreased by a factor of 3/4.

    (6) For temperatures in the creep range, allowable stresses decrease because Sh in Eq. (39) de-creases. However, it is not apparent that this decrease reflects the actual decrease in low cycle fatigue strength at temperatures involving creep-fatigue.

    (7) The above observations are based on the hy-pothesis that only cyclic moments included in theSE evaluation cause fatigue failures. Equa-tion (39) provides some allowance for cyclic pressures through the term S,, but none for cy-clic thermal gradients. Fatigue failures due to vibration of small piping sometimes occur but vibration is seldom included in routine Code evaluations of s.

    4.9 Flexibility Factors In discussing the calculation of S E and the accuracy

    of i-factors, we have been making an implicit assump-tion that the moments shown in Fig. 3, which come from a piping system analysis, are accurate. However, present Code guidance for flexibility of branch con-nections can be very inaccurate. If the Code guidance is followed, there can be inaccuracies in the calculated moments and, thus, in S E, that may be greater than that due to any of the inaccuracies in i-factors we have discussed.

    Table 1 shows flexibility factors, k, of "1" for all branch connections. We do not know what this means and no one that we have talked to does know. Many people interpret k = 1 to mean that the juncture of the line representing the run pipe with the line represent-ing the branch pipe is to be considered as rigid. In the preceding paragraph, where we indicated that the Code guidance can be very inaccurate, we are referring

    to the rigid-juncture interpretation of the Code guid-ance.

    For 1 piping, the ASME Code some guid ance for flexibility of branch connection with r/R ~ 0.5, R/T ~ 50. This is shown herein as Fig. 15. This provides a definition of k's that can be readily used in piping system analysis computer programs. It should be noted that these k's have a lower bound of zero; hence, footnote 1 in Table 1 is not applicable.

    The significance of k depends upon the specifics of the piping system. Qualitatively, if k is small com-pared to the length (in d-units) of the piping system, including the effect of elbows and their k-factors, then the inclusion of k for branch connections will have only minor effects on the calculated moments. Conversely, of course, if k is large compared to the piping system length, then inclusion of k for branch connections will have major effects. The largest effect will be to greatly reduce the magnitude of the calculated moments act-ing on the branch connection.

    To illustrate the potential significance of k's for branch connections, we use the equation in Fig. 15 to calculate k for Mx3 ( = Mob) for a branch connection with Do= 30 in., d0 = 12.75 in., T = t = tn = 0.375 in.:

    kob = 0.1(80)1.5(0.425) 112 X 1.00 = 46.6 Reference 28 includes examples of the effect of branch connection k's on calculated moments in the piping system shown to scale in Fig. 15. In this particular example, using the rigid -joint interpretation that k = 1 rather than k = 46.6 leads to overestimating Mob by a factor of about 9!

    Of course, this example was selected to illustrate a rather extreme k-effect. In most piping systems, the effect would be much less than a factor of 9. Neverthe-less, it illustrates our main point; we do not necessarily achieve greater accuracy in Code evaluations by using more accurate i-factors unless more accurate k-factors are also used.

    The example used above can be continued to illus-trate what is wrong with using inaccurate k's. Refer-ence 28 happened to calculate moments for the piping system shown in Fig. 15 for a temperature increase from 76 F to 500 F, carbon steel material. Fork = 0 (essentially equivalent to the rigid-juncture interpre-tation of Code guidance), the calculated Mob is 368,000 in.-lb. The value of SE is then:

    SE = i(M/Zb) = [0.9/(T/R)21:l]M/Zb = 10.4(368,000/45.1) = 84.9 ksi

    This is well above the Code allowable stress Sx for carbon steel (e.g., A106 Grade B, for which Sx = 37.5 ksi at most). However, if the piping system analysis had been done using the more accurate k = 47, then

    S E = 84.9/9 = 9.4 ksi,

    and the branch connection is Code-acceptable because SE < Sx.

    Let us follow the designer who believes that the

    Stress Intensification Factors 29

  • ND-3686.5 Branch Connections [n Straight Pipe. (Foi branch connections in straight pipe meeting the dimensional limitations of NB-3338.) The load dis-placement relationships may be obtained by modeling the branch connections in the piping system analysis

    (NB-3672) as shown in (a) through ~d) below. (See Fig. ND-3686.5-1.)

    (a) The values of k are given below. ForMx3:

    k ,.. 0.1 (D IT, )U[(T, It" )(dID))"" (T'6 /T,) For Mz3:'

    k ... 0.2(D!T,)l(T,It.)(d!D)J"" (T'6 /T,) where

    M=Mx3or Mzl as defined in NB-3683.l(d) D= run pipe outside diameter, in. d=branch pipe outside diameter, in. lb=moment of inertia of branch pipe, in! (to be

    calc:;ulated using d and T' b) E=modulus of elasticity, psi T,=run pipe wall thickness, in. 4> =rotation in direction of moment, rad

    (b) For branch connections per Fig. NB-3643.3(a)-1 sketches (a) and (b):

    r. r. if Lt > 0.5[(2r1 + T6 )T.J"" T' if L1 < 0.5[(2r1 + T6 r ~

    {c) For branch connections per Fig. NB-3643.3(a)-l sketch (c):

    t,. ""T' + (-l)y if 0 s 30 deg. T' + 0.385L1 if 0 > 30 deg.

    {d) For branch connections per Fig. NB-3643.3(a)-1 sketch (d):

    .f,T',.=T,

    Element of negligible length with local flexibility for Mx3 and Mz3 such that cf> ecron the element Is equal to kMdl1.

    Rigid juncture

    FIG. NB-3686.5-1 BRANCH CONNECTIONS IN STRAIGHT PIPE

    ;---.r' 24011 1

    }-

    ri'" - /,on x 0.375" !'

    12.7511 X 0. 37511 I I

    J) 12011 -__ -:,

    Example: See text _:t

    \ '"

    Fig. 15-Fiexibility factors, definitions and equations from ASME Code for Class 1 piping, and example

    Code guidance is good and that k = 1 for branch means: assume a rigid juncture. He is faced with the dilemma of changing the piping system in Fig. 15 so it does meet the Code. He might consider changing the piping such as sketched in dashed lines in Fig. 15. This would be very expensive, so the designer might look at the possibility of using a pad reinforcement. By using a pad thickness of 1.5T, he can reduce the SIF to 4.14; his calculated S E is then 33.8 ksi and this might meet Code Sx limits. Let us suppose that it does and ask what the designer has accomplished by using a pad. First, since this piping system is assumed to go up to a temperature of 500 F, the pad may cause high ther-mal gradient stresses in the 30 in. pipe and thereby reduce its reliability. Has he improved the fatigue

    strength for the cyclic moment, Mob? We do not know much about the flexibility of a pad

    reinforced branch but, since a pad is usually welded to the run pipe at its inner and outer peripheries, the flexibility might be estimated by using the equation in Fig. 15 for Mob, but using 2.5T instead ofT. This would give a flexibility factor of:

    kp (for M0 b) e=: 46.6/(2.5)2 = 7 .5. Now, from Ref. 28 data, fork of 8, it appears that the

    moments would be overestimated by a factor of around 3 rather than a factor of 9 for k = 47. This means that the pad would cause the moments to in-crease by a factor of about 9/3 = 3. Assuming that the i-factors for UFT and pad reinforced branch indicate

    30 WRC Bulletin 329

  • at least their relative fatigue strength then the UFT to pad ratio is 10.4/4.14 = 2.5. However, since the mo-ment increased by a factor of 3, the addition of the pad has decreased the fatigue resistance of the branch connection.

    4.10 The Mob Inconsistency In the preceding, we have attempted to describe the

    complexity of trying to evaluate the fatigue strength of reducing outlet branch connections subjected to nine moment loadings. Hopefully, that attempt serves to bring the Mob inconsistency into perspective.

    Looking at Figs. (6), (7) and (8), it would appear that there is no Mob inconsistency. But instead the Code i-factor equations do not reflect the complex relation-ship between r/R and stresses. The remaining ques-tion is: Do fatigue tests reflect the trends shown in Figs. (6), (7) and (8)?

    To answer that question direclty, we would need a series of fatigue tests on, for example, UFT's with r/R the only variable. We do not have any such series of fatigue tests. In their absence, we must assume a para-metric relationship between ir and what we guess to be the significant parameters; e.g., R/T r/T and r/rp.

    Table 13 summarizes relevant fatigue test data; rel-evant meaning a series of tests including r/R == 1.00 and one or more tests with r/R less than 1.00. The data is plotted in Fig. 16.

    Looking first at UFT's in Fig. 16, we note that prior

    to the WFI tests, we had one point on the r/R-curve; i.e., Markl's test included in Table 2. Combining this with the WFI tests, using the parameter (R/T)21:l (t/ T), gives the 3 points shown in Fig. 16. These show directly that the Code i = 0.9(R/T) 2/:l for OFT's is unconservative for r/R = 0.8 and suggests that there is a peak somewhere in the range of r/R between 0.5 and 1.0.

    The Extruded outlets from Table 6 indicate a possi-ble peak at around r/R = 0.5. To remind us of the limits of our knowledge, we have also shown Extruded outlets from Table 3.

    The remaining points in Fig. 16 are for branch con-nections which we think are intended to be covered by Table 1, sketch (f). It can be seen that the B31.3 Code equation, i = [0.9/(3.3)21:J](R/T)21:l is unconservative for every point except the 4 x 4 sizes tests.

    One of the main initiators of the Mob inconsistency was the comparison between the 12 x 6 and 4 x 4 sizes in Table 13, Group D. The 6 x 4 point in Group D is inconsistent with theory which, as indicated in Figs. (6), (7) and (8), indicate a peak at r/R ""0.7.

    First, comparing Groups D and E, it shoud be noted that Group E specimens were fabricated by different welders and test as-welded with a deliberate intent to represent typical field conditions. Differences in weld details could fully explain the differences shown in Fig. 16. However, the 8 x 8 size in Group E appears anomalous in comparison to what would be expected

    Table 13. Datu Lcscd for Fig .16; all for M0 b

    Fig. 16 Nominal if Type iden. and r/R R/T t/T r/rp . a size l.f group iden. (R/T) 2/3(t/T)

    UFT 8 X 6 0.764 12.9 0.870 0.958 5.84 1.22 A 12 X 10 0.839 16.5 0.973 0.966 8.34 2 1. 32

    4 X 4 1.00 8.99 l. 00 0.947 2. 71 2 0.63

    Extruded X 16 X 4 0.285 7.26 0.230 0.947 1. 235 l. 42 Table 6 B 8 X 4 0.537 5.50 0.330 0.947 1.484 1.44

    6 X 4 0.703 5.39 0.422 0.947 1. 6 53 l. 27 4 X 4 0.943 4.71 0.494 0.947 1.49 4 1.07

    Extruded X' 20 X 6 0.326 9.5 0.432 0.935 1.2 0.62 Table 3 c 20 X 12 0.635 9.5 0.687 0.946 2.5 0.81

    Weld on {:, 12 X 6 0.513 16.5 0.747 O.G75 3.786 0.78 Table 3 D 6 X 4 0.672 11.3 0.846 0.627 2.203 0.52

    4 X 4 1. 00 8.99 1. 00 o. 71 1. 69 7 0.39

    Weld on 0 8 X 3 0.396 12.9 o. 671 o. 773 3.20 2 0.87 Table 5 E 8 X 4 0.513 12.9 0.736 0.812 3.49 2 0.86

    8 X 5 0.639 12.9 0.801 0.801 4.2o2 0.95 8 X 6 0.764 12.9 0.870 0.832 4. 73 3 0.99 8 X 8 1. 00 12.9 1. 00 0.852 5.19 3 0.94

    asuperscript is number of fatigue tests if more than one.

    Stress Intensification Factors 31

  • 1,

    o. A e UFT B I( Extruded, Table 6 C 1(1 Extruded, Table 3

    - D A lleld on, Table 3 E 0 \leld on, Table 5

    B

    Fig. 16-Relevant data on the Mob inconsistency

    from theory or from other fatigue tests. We would have expected the 8 x 8 size ir/[(R/T)213(t/T)] to be around 0.5.

    In any event, the available data indicates that the B31.3 equation in Table l(f) is significantly unconser-vative for reducing outlet Weld Ons and may be un-conservative even for full outlet Weld Ons. However, the unconservatism appears to be by a factor of not more than about two. In relation to other inaccuracies we have mentioned (e.g., use of rigid-joint flexibility assumption and the B31.3 use of i = 1.00 for torsional moments), the unconservatism of a factor of two is not particularly significant.

    5.0 Recommendations and Summary Considering the complexity of the branch connec-

    tion problem and the sparsity of information for most parts of the problem, the Codes have done a good job of providing simple design guidance. However, as ad-ditional information becomes available, such as that abstracted in this report, the Code committees may wish to review and perhaps revise their design guid-ance to more accurately reflect present information. To assist Code committees in such a review and possi-ble revisions, we have prepared a series of recommen-dations. These are listed in what we consider to be an appropriate order of priority. These recommenda-tions, in effect, summarize the contents of this report.

    5.1 General Recommendations (1) The ASME Code (Class 2/3), B:n.J and B31.3

    should delete the meaningless "1" in the column headed "Flexibility Factor, k" for branch connec-tions or tees. A note should be added, tied to branch connections/tees, such as;

    "In piping system analyses, it may be assumed that the flexibility is represented by a rigid joint at the branch-to-run center lines juncture. However, the Code user should be aware that this assumption can be inaccurate and should consider the use of a more appropriate flexibil-ity representation."

    (See discussion in Section 4.9) (2) The ASME Code (Class 2/3) and B31.1 should

    add a note to indicate that "Branch connection" is an acceptable alternative for unreinforced fab-ricated tees with r/R ~ 0.5; or delete the descrip-tion of unreinforced fabricated tees. [See discus-sion in Section 4.6 and Recommendation (10d).]

    (3) B31.1 should correct the i-factors for "Branch connection" to be the same as in the ASME Code (Class 2/3), including the footnote in (2) above. [See also Recommendation (10).]

    (4) B31.3 should include i-factors for "Branch con-nection" to be the same as in the ASME Code (Class 2/3), including the footnote of (2) above. (The main purpose of this is to provide realistic guidance for evaluating the runs of branch con-nections, see discussion in Section 4.4.)

    (5) B31.3 should, in some manner, eliminate the-in-dication that i = 1.0 for torsional moments ap-plied to branch connections. One way to do this would be to adopt the resultant moment, single i-factor approach of ASME and B31.1. However, this would introduce significant over-conserva-tism for small r/R. An alternative which might be used is:

    (6)

    (a) Revise B31.3 Eq. (17) to SE = [S~ + (itS/)] 112

    (b) Revise definition of S 1 to: 81 = MJZx

    (c) Define i1 as:

    Footnote 1, i ~ 1.0, is applicable

    (40)

    (41)

    (42)

    (d) Define Zx as Zb for checking branch end, Zr for checking run ends.

    This could introduce some underestimates, but these would be much less than using the present i = 1.00 and generally would be more accurate. (See discussion in Section 4.3.) B31.3 should consider deleting the use of ii = (0.75i0 + 0.25) for branch connections/tees; i.e., change to show the same factor as is presently done in (f) of Table 1. The main reason for this

    32 WRC Bulletin 329

  • suggestion is for evaluating run ends, where B31.3 gives the wrong relative magnitude for Mur versus Mir Also it underestimates the difference between Mob and Mb for r/R between about 0.3 and 0.95 and perhaps over-estimates the differ-ence for r/R below 0.2 and for r/R = 1.0 [See discussion in Section 4.4 and Recommendation (12).]

    (7) B31.1 and B31.3: Add a restriction to the Code i-factor tables that indicates they are valid for R!T

    ~ 50. (See discussion in 4.2.1 on validity of R/T extrapolations.)

    (8) All Three Codes: Add a note for branch connec-tions saying that i-factors are based on tests and/ or theories in which the branch connection is in straight pipe with about two or more diameters of run pipe on each side of the branch. The effect of closely spaced branch connections may require special consideration. This represents the cau-tion now in footnote 6(c); see Table 1 herein. Also see Recommendation (10), in which the footnote is shortened.

    (9) All Three Codes: Add a note for branch connec-tions/tees saying that i-factors are only applica-ble where the axis of the branch pipe is normal to within 5 of the surface of the run pipe. This represents footnote 6(b); see Table 1 herein. The i-factors do not cover laterals or hillside branch connections.

    (10) Changes in the present ASME Code, Subsection NC, for "Branch connection." This recommenda-tion consists of four interrelated portions. They are presented here and then discussed in Section 5.2.

    (lOa) Change the stress intensification factor equa-tions to: ib = 1.5(R/T)213(r/R) 112(r/rp);

    ib(t/T) ~ 1.5 for (r/R) ~ 0.9, ( 43) ib = 0.9(R/T) 213(r/r p);

    ib(t/T) ~ 1.0 for (r/R) = 1.0, (44) ir = 0.8 (R/T) 213(r/R); 2.1 minimum (45)

    where lb = is to be used for checking the branch end and

    linear interpolation is to be used for (r/R) be-tween 0.9 and 1.0;

    ir = is to be used for checking the run ends. (lOb) Change footnote (6), in its entirety, to:

    "If a radius r 2 is provided that is not less than the larger of Tb/2, (t~ + Y)/2 [Fig. NC-3673-2(b)-2 sketch (c)] or Tr/2, then the calculated values of ib and ir may be divided by 2.0 but with ib ~ 1.5 and ir ~ 1.5. (Terminology is that of the ASME Code.)

    (lOc) Change those portions of the Codes dealing with reduced outlets to say "For checking branch ends, use Z = 1rr2t and i(t/

    T) in place of i with i(t/T) ~ 1.0." (lOd) Delete the "Unreinforced fabricated tee" from

    Code Fig. NC-3673.2(b)-L (11) Recommendations in (10) are deemed to be

    equally applicable to ASME Code Subsection ND (Class 3 piping) and to ANSI B31.1

    (12) Changes to B31.~3 Analogous to Recommendation (10)

    Recommendation (5) would bring the B31 treatment of torsional moments into better ac-cord with available data and also preserve the B31.3 approach of keeping separate i's for M0 , Mi and M1 Recommendation (6) suggested deletion of ii = (0.75 ip + 0.25) because it is incorrect for evaluating run moments.

    In keeping with the B31.3 approach, consider-ation might be given to a set of six SIFs: iob, iib, itb, ior iir and tr The fatigue test data indicate that iib can be significantly less than iob and B31.3 may wish to incorporate that difference into their SIFs.

    Figs. 9 and 10, in conjunction with available Mib tests, suggests'the equation

    iib = 0.6(R/T)213 [1 + 0.5(r/R)3](r/rp), but not greater than iob (46)

    For branch connections with r2 provided, use iib/2.

    Table 14 summarizes available Mib fatigue test data, previously given in Tables 2, 3, and 5. Cal-culated values of iib(t!T) by Eq. (46) are shown. Calculated values of ib(t/T) are also shown so that the advantage in using separate iob and iib can be seen for the test models. In general, for r/R between about 0.5 and 0.9, iib ~ 0.6 iob At r/R = 1.0 and for r/R < 0.16, iib = iob These iobliib ratios agree reasonably well with data directly from fa-tigue tests where both ir for Mob and M;b are available. But the ratios are less than might be inferred by comparing Fig. 6 and Fig. 9.

    If B31.3 were to follow Recommendation (10), then Table l(c) and (f) should be removed; i.e., Eqs. (43)-(46) are intended to apply to both UFT's and Weld Ons.

    (13) In Fig. NC/ND-3683 2(b)-2 of the ASME Code, delete the note:

    "If L1 equals or exceeds 0.5 vrr:rb then r ~ can be taken as the radius to the center of Tb." (See discussion at end of Section 4.1.)

    Detailed implementation of the above recommen-dations would require considerable additional work. Nomenclature and consistency with existing Code text would vary with each specific Code. Appendix A is a detailed implementation of the recommendations spe-cifically for NC-3600 of ASME Code Section III. Anal-ogous changes for ND-3600 would be appropriate. 5.2 Discussion of Recommendation (10)

    No change is intended for ir. We have simply rewrit-

    Stress I ntensi[ication Factors 33

  • Table 14. Mib comparisons, fatigue test and Eq. (46)

    Source 1i b t/T table Hodel R/T r/R t/T r/rp if i ib t /T ib t/T number (a) f (b)

    UFT 2 4 X 4 8.99 1. 00 l.OO 0.947 2.34 3.68 1. 57 3.68 2 4 X 4 10.6 1.00 1.00 0.955 2.95 4. 15 1.41 4.15 2 4 X 4 22.0 1. 00 1. 00 0.978 6.12 6.91 1.13 6. 91 2 4 X 4 41.8 1. 00 l.OO 0.988 11.0 10.7 0.97 10.7 3 6 X 6 12.0 1.00 1. 00 0.960 3.62 4.53 l. 25 4.53 3 20 X 4 41.4 0. 19 7 1.00 0.942 2.67 6.79 2.54 7. 51 3 20 X 8 24.6 0.375 0.50 0.974 2. 7 5 2.54 o. 92 3.78 3 20 X 14 24.6 0.702 0.60 0.983 3.47 3.51 1. 01 6.27 3 20 X 20 41.4 1.00 l.Oa 0.988 6.90 10.6 1.54 10.6 5 8 X 6 12.9 a.764 a.87a a.958 l. 85 3.36 I. 82 6.01

    Weld On 3 4 X 4 8.99 1. oa 1. oa o. 6 3 1.75 2.45 1.40 2. 45 3 4 X 4 8.99 1. 00 1. 00 0.79 1.!36 3.07 1.65 3.07 3 12 X 6 16.5 0.513 o. 7 4 7 0.675 1.28 2.09 1.64 3.51 3 8 X 4 12.9 0.513 a. 7 36 0.79 0.81 2.05 2.53 3.44

    Insert 3 14 X 6 18.2 0.466 0.747 0.83 0.98 1. 35 1. 38 2.20 3 12 X 8 16.5 a. 6 71 a.859 a.82 1.52 l. 58 1.04 2.80 3 8 X 4 12.9 a.513 a.736 o. 775 1. oa 1.00 1.aa 1.69 5 12 X 6 16.5 a.513 a.747 0.86a 1.32 1. 33 1. at 2.24 5 12 X 8 16.5 o. 6 71 0.859 a.82a 1.31 1. 58 1. 21 2.80 5 12 X 8 16.5 0.671 a.859 a.874 1.53 1.68 1.10 2.99

    (a) Calculated by Eq. ( 46); Inserts have rz provided. (b) Calculated by Eqs. ( 43) or (44); Inserts have rz provided.

    ten the equation to cover the probably more common case of r2-not-provided. Equations (43) for ib does not have the (t/T) factor but that is not really a change because of (lOc). Note in this respect that the present rather complex instructions for reducing outlets leads to exactly the same SEas our recommended note: "For checking branch ends, use i(t/T) in place as i and Z = Zb." By taking the (t/T) out of Eq. (43), this instruc-tion applied to all branch connections/tees.

    The change in the equation for ib is intended to: (a) Provide a single ib, conceptually the maximum of

    i0 b, i;b, i1b, for use with the resultant branch mo-ment. This is a continuation of present practice, but the ASME might wish to consider adopting the B31.3 concept of different i-factors; see Rec-ommendation (12).

    (b) Provide an ib that covers the relatively high i-factors for Mob in the r/R range between about 0.5 and 1.0.

    (c) Reduce the over-conservatism in ib to the extent

    deemed prudent from available fatigue test data. Table 15 summarizes available Mob fatigue test

    data, previously given in Tables 2, 3 and 5. Calculated values of ib(t/T) by Eqs. (43) or (44) are shown. The right-most column shows the ratio of i6(t/T)/ir. Con-sidering the scatter encountered in fatigue tests, we consider the correlation to be adequate. In particular, the proposed ib adequately solves the Mob inconsisten-cy. Note that the 8 x 6 and 12 x 10 UFT's are encom-passed by ib, and the 12 x 6 Weld On is brought into reasonable consistency with the 4 x 4 Weld Ons. Also note that an appropriate credit is given for an outer fillet radius, rz; i.e., for the 20 x 6 and 20 x 12 Extruded outlets and all Inserts.

    While ib provides a good fit to the fatigue test data, it seems to pose an anomaly with respect to calculated stresses. Assuming that (R/T) 213 is an accurate param-eter, then the ib equation (for r/rp = 1) appears as shown in Fig. 8. If Kzb =La, then we would expect it to be below the theoretical curve by a factor of 2.0. But

    34 WRC Bulletin 329

  • Table 15. Mob comparisons, fatigue test and Eqs. (43) or (44)

    Source ib t/T ib t/T table Hodel R/T r/R t/T r/rp if number (a) f

    UFT 2 4 X 4 8.99 1.00 1.00 0.947 2.71 3.68 1. 36 3 20 X 12 9.5 0.635 0.687 0.946 3.9 3.48 0.89 5 8 X 6 12.89 0.764 0.870 0.958 5.84 6.01 1. 03 5 12 X 10 16.5 0.839 0.973 0.966 8.34 8.37 1.00

    Weld On 3 4 X 4 8.99 1.00 1.00 0.63 1. 65 2.45 1. 49 3 4 X 4 8.99 1.00 1.00 0.79 1. 72 3.07 1. 79 3 6 X 4 11.33 0.672 0.846 0.63 2.20 3.31 1.50 3 6 X 4 11.33 0.672 0.846 0.63 1. 87 3.31 1.77 3 12 X 6 16.5 0.513 0.747 0.675 3.78 3.51 0.93 5 8 X 3 12.89 0.396 0.671 0.773 3.20 2.69 0.84 5 8 X 4 12.89 0.513 0.736 0.812 3.49 3.53 1.02 5 8 X 4 12.89 0.513 0.736 0.853 3.45 3.71 1. 07 5 8 X 5 12.89 0.639 0.801 0.801 4.20 4.23 1.01 5 8 X 6 12.89 0.764 0.870 0.832 4.73 5.22 1.10 5 8 X 6 12.89 0.764 0.870 0.868 3.95 5.44 1.38 5 8 X 8 12.89 1.00 1.00 0.852 5.19 4.22 0.81

    Extruded 6 4 X 4 4.71 0.943 0.494 0.947 1.49 1. 60 1.07 6 6 X 4 5.39 0.703 0.422 0.947 1.65 1. 55 0.94 6 8 X 4 5.50 0.539 0.330 0.947 1.48 1.sob 1.01 6 16 X 4 7.26 0.285 0.230 0.947 1.23 1. sob 1. 22 3 20 X 6 9.5 0.326 0.432 0.935 1.2 1.50b,c 1. 25 3 20 X 12 9.5 0.635 0.687 0.946 2.5 1. 74c 0.70

    Insertc

    3 14 X 6 18.2 0.466 0.747 0.83 2.64 2.20 0.83 3 12 X 8 16.5 o. 671 0.859 0.82 2.18 2.80 1.29 3 8 X 4 12.9 0.513 0.736 0.775 1.89 1.69 0.89 5 12 X 6 16.5 0.513 0.747 0.819 2.25 2.13 0.95 5 12 X 6 16.5 0.513 0.747 0.860 2.44 2.24 0.92 5 12 X 8 16.5 0.671 0.859 0.820 2.75 2.80 1.02 5 12 X 8 16.5 0.671 0.859 0.800 2.25 2.74 1.22 5 12 X 8 16.5 0.671 0.859 0.874 2.41 2.99 1. 24

    (a) Calculated by Eqs. (43) or (44) as modified by recommendations (lOb) and (lOc); linear interpolation on 4 x 4 Extruded.

    (b) == lower bound of 1. 5. (c) = r2 provided.

    Stress Intensification Factors 35