    Product Specification

    03248C

    MFR 2

    Multi Function Relay

    Mains & GeneratorProtection & Control

    DESCRIPTION (continued)

    Protection (all versions) ANSI #Mains

    Over-/undervoltage (59/27) Over-/underfrequency (81O/U)

    Voltage asymmetry (47)

    Phase/vector shift (78)

    Generator

    Over-/undervoltage (59/27)

    Over-/underfrequency (81O/U)

    Overload (32)

    Reverse/reduced power (32R/F)

    Unbalanced load (46)

    Re-active power monitoring

    Loss of excitation (40Q)

    Time-overcurrent (50)

    Controller(all versions) Synchronizer for 2 CB

    Discrete raise/lower for n/f/V/P/Q

    Speed/frequency/real power

    Voltage/power factor

    Isolated operation

    Mains parallel operation

    Load/var sharing (up to 8 units)

    Dead bus operation

    MFR 2/PSVA (unique features)MFR 2/PSVA additionally includes:

    df/dt (ROCOF) (81RL) 2 conf. analog outputs (20 mA)

    2 conf. pulse outp. for kWh/kvarh

    Real power set-point input (20 mA)

    MFR 2/PSVT (unique features)MFR 2 for generator protection andsynchronization of 1 CB incl. a step-uptransformer (in other respects asMFR 2/PSV)

    Generator and mainsprotection

    Synchronization fortwo breakers

    Frequency andvoltage matching

    Real power control

    Power factor control

    Load/var sharing

    Counters for kWh,

    operating hours,maintenance call

    Programmable relayoutputs

    PC and front panelconfigurable

    CAN bus basedcommunication

    Microprocessor

    technology forflexible and reliableoperation

    CE marked

    UL/cUL Listed

    APPLICATIONS

    Based on micro-controller technology,Woodward's MFR 2 Multi Function Relay

    incorporates functions and features for multipleapplications (e.g. gensets, hydropower, etc.) inisolated or parallel utility operation. The MFR 2is designed for generators and switchgearequipment that require independent protection.

    The ability for the MFR 2 to quickly decouplefrom the mains when working in parallel withthe mains gives complete generator protectionfor frequency, voltage, and real and re-activepower control allowing load/var sharingbetween as many as eight units.

    DESCRIPTION (MFR 2/PSV)The Series of MFR 2 Multi Function Relaysconsists of three models. The MFR 2/PSV isthe base model. The MFR 2/PSVA hasadditional features, and the MFR 2/PSVT is forspecial applications.

    Features (all versions) Battery voltage monitoring

    kWh/oper.hours/start/maintenance counter

    4 configurable discrete alarm inputs

    4 configurable relays

    Two-line LC display Synchroscope

    Multi level password protection

    Configuration directly or via PC

    CAN bus communication

  • 7/28/2019 WW-MFR2(multifunction relay)

    2/4

    SPECIFICATIONS

    Accuracy ....................................................................Class 1Power supply ..............................................24 Vdc (+/-30 %)Intrinsic consumption ............................................max. 15 W

    Ambient temperature ..........................................-20 to 70 CAmbient humidity ............................... 95 %, non-condensing

    Voltage Rated: [1] 57/100(120) Vac or [4] 230/400 VacVL: [1] max. 150 Vac or [4] max. 300 Vac

    Setting range: [1] 50 to 125 Vac or [4] 50 to 440 VacMeasuring frequency .........................50/60 Hz (40 to 70 Hz)Linear measuring range up to .................................1.3Vrated

    Input resistance ............................... [1] 0.21 M, [4] 0.7 MMax. power consumption per path............................. 0.15 W

    Current ............................................[../1] ../1 A or [../5] ../5 ACurrent-carrying capacity................................ Igen = 3.0Irated

    Imains = 1.5IratedLoad.......................................................................< 0.15 VARated short-time current (1 s) .....[../1] 50Irated, [../5] 10IratedDiscrete inputs ........................................................ isolatedInput range..............................................18 to 250 Vac or dc

    Input resistance .............................................. approx. 68 k

    Relay outputs...........................................................isolatedContact material ........................................................ AgCdOLoad (GP)...........................24 Vdc@2 Adc, 250 Vac@2 AacPilot duty (PD) ............................................... 24 Vdc@1 Adc

    Analog output .......................................................... isolated

    Type ....................................... 0/4 to 20 mA, freely scaleableResolution ............................. 8/12 Bit (depending on model)

    Max. load 0/4 to 20 mA................................................ 500 Insulating voltage ..................................................3,000 VdcHousing ................................Type APRANORM DIN 43 700Dimensions................................................. 14472122 mmFront cutout ........................................................ 13867 mmConnection .......................... screw/plug terminals depending

    on connector 1.5 mm or 2.5 mmFront.......................................................... insulating surfaceProtection system..........................................................IP 21Weight ...................... depending on version, approx. 1,000 g

    Disturbance test (CE)............................ tested according toapplicable EN guidelines

    Listings ................... UL/cUL listed (voltages up to 300 Vac)ordinary locations, file E212970

    DIMENSIONS

    Bottom view

    72

    DIN rail mountoption (please order

    brackets P/N 8923-1023)

    8

    116 50

    139

    179

    65

    27

    35

    Back view withconnecting terminals

    Front view

    X1 X5

    6570 6075 5450

    0 24

    48 25

    2004-11-11 | MFR 2 Dimensions r2ww-4604-ab.skf

    144

    80 87

    Configuration portConfiguration port

  • 7/28/2019 WW-MFR2(multifunction relay)

    3/4

  • 7/28/2019 WW-MFR2(multifunction relay)

    4/4

    WoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811

    Fax: +1 (970) 498-3058

    Distributors & ServiceWoodward has aninternational network ofdistributors and servicefacilities. For your nearestrepresentative, call theFort Collins plant or seethe Worldwide Directoryon our website.

    Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441

    www.woodward.com

    Subject to technicalmodifications.

    This document is distributed forinformational purposes only. It is notto be construed as creating orbecoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.

    We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]

    Woodward Governor

    Company, 2003All Righ ts Reserved

    03248C - 05/1/S

    TYPICAL APPLICATIONS

    MFR 2

    ANSI PSV

    PSVA

    PSVT

    ControlBreaker 2 2 1

    Synchronization 25 9 9 9

    Isolated single-unit operation 9 9 9

    Mains parallel operation 9 9 9

    Accessories

    kWh counter 9 9 9

    kvarh counter 9 9 9

    Operat. hours/start/mainten. counter 9 9 9

    Configuration via PC#1 9 9 9

    Protection

    Gen.: Over-/undervoltage 59/27 9 9 9

    Mains: over-/undervoltage 59/27 9 9 9

    Gen.: Over-/underfrequency 81O/U 9 9 9

    Mains: over-/underfrequency 81O/U 9 9 9

    Mains: Voltage asymmetry 47 9 9 9

    Mains: phase/vector shift 78 9 9 9

    Mains: df/dt (ROCOF) 81RL 9

    Gen.: Overload 32 9 9 9

    Gen.: Reverse power 32R 9 9 9

    Gen.: Reduced power 32F/37 9 9 9

    Gen.: Unbalanced load 46 9 9 9

    Gen.: Re-active power 9 9 9

    Gen.: Loss of excitation 40Q 9 9 9

    Gen.: Time-overcurrent 50/51* 9 9 9

    Controller

    Discrete raise/lower: n/f & P 9 9 9

    Discrete raise/lower: V & Q 9 9 9

    Active power setp.: 0/4 to 20 mA 9

    Load/var sharing 9 9 9

    I/O's

    Discrete alarm inputs (config.) 4 4 4

    Relay outputs (config.) 74 4 4 4

    Analog outp. 0/4 to 20 mA (conf.) 2

    Impulse output for kWh/kvarh 9

    CAN bus communication #2 9 9 9

    Listings/Approvals

    UL/cUL listed 9 9 9

    Product Number P/N

    Measuring inputs 100 Vac, ../5 A8440-1286

    8440-1287

    8440-1593

    Measuring inputs 400 Vac, ../5 A 8440-1734

    8440-1735

    8440-1594

    52

    52

    MFR 2

    CAN

    RS232

    0/4..20mA

    I / O

    G

    81RL

    78

    90

    79

    47

    81U

    81O

    59

    27

    25

    25

    27

    59

    81O50

    79

    32 81U

    32R

    32F

    40Q

    4639

    38

    12

    4 9 55

    90

    74

    * not according to ANSI guidelines (two-step protection instead of inverse time characteristic)#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)#2 Remote monitoring, control, configuration (GW 4 could be used for several interfaces)

    For more information contact: