Product Specification
03248C
MFR 2
Multi Function Relay
Mains & GeneratorProtection & Control
DESCRIPTION (continued)
Protection (all versions) ANSI #Mains
Over-/undervoltage (59/27) Over-/underfrequency (81O/U)
Voltage asymmetry (47)
Phase/vector shift (78)
Generator
Over-/undervoltage (59/27)
Over-/underfrequency (81O/U)
Overload (32)
Reverse/reduced power (32R/F)
Unbalanced load (46)
Re-active power monitoring
Loss of excitation (40Q)
Time-overcurrent (50)
Controller(all versions) Synchronizer for 2 CB
Discrete raise/lower for n/f/V/P/Q
Speed/frequency/real power
Voltage/power factor
Isolated operation
Mains parallel operation
Load/var sharing (up to 8 units)
Dead bus operation
MFR 2/PSVA (unique features)MFR 2/PSVA additionally includes:
df/dt (ROCOF) (81RL) 2 conf. analog outputs (20 mA)
2 conf. pulse outp. for kWh/kvarh
Real power set-point input (20 mA)
MFR 2/PSVT (unique features)MFR 2 for generator protection andsynchronization of 1 CB incl. a step-uptransformer (in other respects asMFR 2/PSV)
Generator and mainsprotection
Synchronization fortwo breakers
Frequency andvoltage matching
Real power control
Power factor control
Load/var sharing
Counters for kWh,
operating hours,maintenance call
Programmable relayoutputs
PC and front panelconfigurable
CAN bus basedcommunication
Microprocessor
technology forflexible and reliableoperation
CE marked
UL/cUL Listed
APPLICATIONS
Based on micro-controller technology,Woodward's MFR 2 Multi Function Relay
incorporates functions and features for multipleapplications (e.g. gensets, hydropower, etc.) inisolated or parallel utility operation. The MFR 2is designed for generators and switchgearequipment that require independent protection.
The ability for the MFR 2 to quickly decouplefrom the mains when working in parallel withthe mains gives complete generator protectionfor frequency, voltage, and real and re-activepower control allowing load/var sharingbetween as many as eight units.
DESCRIPTION (MFR 2/PSV)The Series of MFR 2 Multi Function Relaysconsists of three models. The MFR 2/PSV isthe base model. The MFR 2/PSVA hasadditional features, and the MFR 2/PSVT is forspecial applications.
Features (all versions) Battery voltage monitoring
kWh/oper.hours/start/maintenance counter
4 configurable discrete alarm inputs
4 configurable relays
Two-line LC display Synchroscope
Multi level password protection
Configuration directly or via PC
CAN bus communication
7/28/2019 WW-MFR2(multifunction relay)
2/4
SPECIFICATIONS
Accuracy ....................................................................Class 1Power supply ..............................................24 Vdc (+/-30 %)Intrinsic consumption ............................................max. 15 W
Ambient temperature ..........................................-20 to 70 CAmbient humidity ............................... 95 %, non-condensing
Voltage Rated: [1] 57/100(120) Vac or [4] 230/400 VacVL: [1] max. 150 Vac or [4] max. 300 Vac
Setting range: [1] 50 to 125 Vac or [4] 50 to 440 VacMeasuring frequency .........................50/60 Hz (40 to 70 Hz)Linear measuring range up to .................................1.3Vrated
Input resistance ............................... [1] 0.21 M, [4] 0.7 MMax. power consumption per path............................. 0.15 W
Current ............................................[../1] ../1 A or [../5] ../5 ACurrent-carrying capacity................................ Igen = 3.0Irated
Imains = 1.5IratedLoad.......................................................................< 0.15 VARated short-time current (1 s) .....[../1] 50Irated, [../5] 10IratedDiscrete inputs ........................................................ isolatedInput range..............................................18 to 250 Vac or dc
Input resistance .............................................. approx. 68 k
Relay outputs...........................................................isolatedContact material ........................................................ AgCdOLoad (GP)...........................24 Vdc@2 Adc, 250 Vac@2 AacPilot duty (PD) ............................................... 24 Vdc@1 Adc
Analog output .......................................................... isolated
Type ....................................... 0/4 to 20 mA, freely scaleableResolution ............................. 8/12 Bit (depending on model)
Max. load 0/4 to 20 mA................................................ 500 Insulating voltage ..................................................3,000 VdcHousing ................................Type APRANORM DIN 43 700Dimensions................................................. 14472122 mmFront cutout ........................................................ 13867 mmConnection .......................... screw/plug terminals depending
on connector 1.5 mm or 2.5 mmFront.......................................................... insulating surfaceProtection system..........................................................IP 21Weight ...................... depending on version, approx. 1,000 g
Disturbance test (CE)............................ tested according toapplicable EN guidelines
Listings ................... UL/cUL listed (voltages up to 300 Vac)ordinary locations, file E212970
DIMENSIONS
Bottom view
72
DIN rail mountoption (please order
brackets P/N 8923-1023)
8
116 50
139
179
65
27
35
Back view withconnecting terminals
Front view
X1 X5
6570 6075 5450
0 24
48 25
2004-11-11 | MFR 2 Dimensions r2ww-4604-ab.skf
144
80 87
Configuration portConfiguration port
7/28/2019 WW-MFR2(multifunction relay)
3/4
7/28/2019 WW-MFR2(multifunction relay)
4/4
WoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811
Fax: +1 (970) 498-3058
Distributors & ServiceWoodward has aninternational network ofdistributors and servicefacilities. For your nearestrepresentative, call theFort Collins plant or seethe Worldwide Directoryon our website.
Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441
www.woodward.com
Subject to technicalmodifications.
This document is distributed forinformational purposes only. It is notto be construed as creating orbecoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.
We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]
Woodward Governor
Company, 2003All Righ ts Reserved
03248C - 05/1/S
TYPICAL APPLICATIONS
MFR 2
ANSI PSV
PSVA
PSVT
ControlBreaker 2 2 1
Synchronization 25 9 9 9
Isolated single-unit operation 9 9 9
Mains parallel operation 9 9 9
Accessories
kWh counter 9 9 9
kvarh counter 9 9 9
Operat. hours/start/mainten. counter 9 9 9
Configuration via PC#1 9 9 9
Protection
Gen.: Over-/undervoltage 59/27 9 9 9
Mains: over-/undervoltage 59/27 9 9 9
Gen.: Over-/underfrequency 81O/U 9 9 9
Mains: over-/underfrequency 81O/U 9 9 9
Mains: Voltage asymmetry 47 9 9 9
Mains: phase/vector shift 78 9 9 9
Mains: df/dt (ROCOF) 81RL 9
Gen.: Overload 32 9 9 9
Gen.: Reverse power 32R 9 9 9
Gen.: Reduced power 32F/37 9 9 9
Gen.: Unbalanced load 46 9 9 9
Gen.: Re-active power 9 9 9
Gen.: Loss of excitation 40Q 9 9 9
Gen.: Time-overcurrent 50/51* 9 9 9
Controller
Discrete raise/lower: n/f & P 9 9 9
Discrete raise/lower: V & Q 9 9 9
Active power setp.: 0/4 to 20 mA 9
Load/var sharing 9 9 9
I/O's
Discrete alarm inputs (config.) 4 4 4
Relay outputs (config.) 74 4 4 4
Analog outp. 0/4 to 20 mA (conf.) 2
Impulse output for kWh/kvarh 9
CAN bus communication #2 9 9 9
Listings/Approvals
UL/cUL listed 9 9 9
Product Number P/N
Measuring inputs 100 Vac, ../5 A8440-1286
8440-1287
8440-1593
Measuring inputs 400 Vac, ../5 A 8440-1734
8440-1735
8440-1594
52
52
MFR 2
CAN
RS232
0/4..20mA
I / O
G
81RL
78
90
79
47
81U
81O
59
27
25
25
27
59
81O50
79
32 81U
32R
32F
40Q
4639
38
12
4 9 55
90
74
* not according to ANSI guidelines (two-step protection instead of inverse time characteristic)#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)#2 Remote monitoring, control, configuration (GW 4 could be used for several interfaces)
For more information contact: