30
XL-Trace ® System Installation and Operation Manual Pipe freeze protection and flow maintenance

XL-Trace System Installation and Operation Manual

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: XL-Trace System Installation and Operation Manual

XL-Trace® System Installation and Operation Manual

Pipe freeze protection and flow maintenance

Page 2: XL-Trace System Installation and Operation Manual

ii iii

WARNING: Fire and shock hazard. This heat-tracing system must be installed correctly to ensure proper operation and to prevent shock and fire. Read these important warnings and carefully follow all the instal-lation instructions.

To minimize the danger of fire from sustained •electrical arcing if the heating cable is damaged or improperly installed, and to comply with Tyco Thermal Controls requirements, agency certifica-tions, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit breakers.

Approvals and performance are based on the use of •Tyco Thermal Controls-specified parts only. Do not substitute parts or use vinyl electrical tape.

Bus wires will short if they contact each other. Keep •bus wires separated.

Connection kits and cable ends must be kept dry •before and during installation.

The black heating cable core is conductive and can •short. It must be properly insulated and kept dry.

Damaged bus wires can overheat or short. Do not •break bus wire strands when preparing the cable for connection.

Damaged heating cable can cause electrical arcing •or fire. Do not use metal attachments such as pipe straps or tie wire. Use only Tyco Thermal Controls approved tapes and cable ties to secure the cable to the pipe.

Do not attempt to repair or energize damaged heat-•ing cable. Remove damaged sections at once and replace them with a new length using the appropri-ate Raychem splice kit. Replace damaged connec-tion kits.

Use only fire-resistant insulation materials such as •fiberglass wrap or flame-retardant foams.

Note: Pipes are shown without insulation for illustra-tive purposes only. All pipe installations must be fully covered with thermal insulation.

Table of Contents

GeneralInformation 1–3

1.1 UseoftheManual 11.2 XL-TraceApplications 11.3 SafetyGuidelines 21.4 Approvals 3

InstallationGuidelines 4–23

2.1 HeatingCableStorage 42.2 Pre-InstallationChecks 42.3 HeatingCableInstallation 52.4 HeatingCableConnections 17

ThermalInsulation 24–25

3.1 InsulatingtheSystem 243.2 InsulationInstallation 24

PowerSupplyandElectricalProtection 26–27

4.1 VoltageRating 264.2 CircuitBreakerSizing 264.3 ElectricalLoading 264.4 Ground-FaultProtection 26

TemperatureControls 28–33

5.1 AmbientSensingSystems 285.2 LineSensingSystems 285.3 WiringSchematicforThermostat 31

CommissioningandPreventiveMaintenance 34

6.1 Tests 34TestProcedures 35–43

7.1 SystemTests 357.2 Fault-LocationTests 40

TroubleshootingGuide 44–45

Appendix 46–51

InstallationGuidelines 52-53

6

3

2

1

4

5

7

8910

Page 3: XL-Trace System Installation and Operation Manual

iv 1

1.1 Use of the ManualThismanualcoverstheinstallationofRaychem®XL-Trace®self-regulatingheatingcablesandconnectionsforcommer-cialconstructionpipesystemsinordinary(nonhazardous)areas.Themanualcoversgeneralheatingcableinstallationproceduresandspecificinstallationdetailsandshowsavailableconnectionkitsforthedifferentapplications.Themanualalsodiscussescontrols,testing,andperiodicmaintenance.

Thismanualassumesthattheproperheat-tracingdesignhasbeencompletedaccordingtothePipe Freeze Protection and Flow Maintenance Design Guide(H55838).OnlytheapplicationsdescribedinSection1.2areapprovedbyTycoThermalControlsforXL-TracesystemswhenusedwithapprovedRaychemconnectionkits.Theinstructionsinthismanualandtheinstallationinstructionsincludedwiththeconnectionkits,controlsystems,powerdistribu-tionsystems,andaccessoriesmustbefollowedfortheTycoThermalControlswarrantytoapply.ContactyourTycoThermalControlsrepresentativeforotherapplicationsandproducts.

Foradditionalinformation,contact:Tyco Thermal Controls307ConstitutionDriveMenloPark,CA94025-1164USATel (800)545-6258Tel(650)216-1526Fax(800)527-5703Fax(650)[email protected]

1.2 XL-Trace ApplicationsXL-Traceheat-tracingsystemsareapprovedandqualifiedfortheapplicationslistedbelow.

Freeze protectionGeneral water piping.• Freezeprotection(40°F(4°C)maintain)ofinsulatedmetallicorplasticwaterpiping.Sprinkler piping systems.• Freezeprotection(40°F(4°C)maintain)ofinsulatedmetallicstandpipesandsupplypipingupto20".

General Information1

Page 4: XL-Trace System Installation and Operation Manual

2 3

Flow maintenanceGreasy waste lines.• Flowmaintenance(110°F(43°C)maintain)ofinsulated-greasedisposallines.Fuel lines.• Flowmaintenance(40°F(4°C)maintain)forinsulatedmetallicpipingcontaining#2fueloil.

Forheatingcableapplicationsotherthanthoselistedabove,pleaseseeyourTycoThermalControlsrepresentativeorcallTycoThermalControlsat(800)545-6258.

1.3 Safety GuidelinesAswithanyelectricalequipment,thesafetyandreliabilityofanysystemdependsonthequalityoftheproductsselectedandthemannerinwhichtheyareinstalledandmaintained.Incorrectdesign,handling,installation,ormaintenanceofanyofthesystemconnectionkitscoulddamagethesystemandmayresultininadequateperfor-mance,overheating,electricshock,orfire.Tominimizetheserisksandtoensurethatthesystemperformsreliably,readandcarefullyfollowtheinformation,warnings,andinstructionsinthisguide.

Notesaremarked• Note

Importantinstructionsaremarked• Important

• Thissymbolidentifiesparticularlyimportantsafetywarningsthatmustbefollowed.

1.4 ApprovalsXL-Traceheat-tracingsystemscarryagencyapprovalsforthedifferentapplicationsshowninsection1.2.Fordetailedinformationonwhichapprovalsarecarriedforthespecificapplication,refertothePipeFreezeProtectionandFlowMaintenancedesignguide(H55838).

WarrantyTycoThermalControls’standardlimitedwarrantyappliestoallproducts.Anextensionofthelimitedwarrantyperiodtoten(10)yearsfromthedateofinstallationisavailableifaproperlycom-pletedonlinewarrantyformissubmittedwithinthirty(30)daysfromthedateofinstallation.Youcanaccessthecom-pletewarrantyonourwebsiteatwww.tycothermal.com.

General Information1 General Information1

Page 5: XL-Trace System Installation and Operation Manual

4 5

Walkthesystemandplantheroutingoftheheatingcable•onthepipe.Inspectthepipingandremoveanyburrs,roughsurfaces,•orsharpedges.

2.3 Heating Cable InstallationMinimuminstallationtemperatureof:0°F(–18°C).Heatingcableinstallationinvolvesthreebasicsteps:

Payingouttheheatingcable1.Attachingtheheatingcabletothepipe2.Wrappingheatsinks3.

Paying out the heating cableMountthereelonaholderandplaceitneareitherendofthepiperuntobetraced.UseareelholderthatpaysoutsmoothlywithlittletensionasshowninFigure2.Avoidjerkingtheheatingcablewhilepulling.

Payouttheheatingcableandlooselystringitalongthepipe,makingsuretheheatingcableisalwaysnexttothepipewhencrossingobstacles.IftheheatingcableisonthewrongsideofacrossingpipeorI-beam,youwillhavetoreinstallitorcutandspliceit.

Figure 2: Paying out the heating cable

2.1 Heating Cable StorageStoretheheatingcableinaclean,drylocation.•Temperaturerange:0°F(–18°C)to140°F(60°C).Protecttheheatingcablefrommechanicaldamage.•

2.2 Pre-Installation Checks

Check materials received

Catalog number: 5, 8 or 12 XL — 1 or 2 -CR -CT

Power output (W/ft)

Product family

Voltage 1 = 120 Vac (only available for 5 or 8) 2 = 208–277 Vac (available for 5, 8, or 12)

Jacket type: Polyolefin or

Fluoropolymer(Required for grease and fuel lines)

Figure 1: XL-Trace catalog number

Reviewtheheatingcabledesignandcomparethelistof•materialstothecatalognumbersoftheheatingcablesandconnectionkitsreceivedtoconfirmthatthepropermaterialsareonsite.Theheatingcabletypeisprintedonitsjacket.Ensurethattheservicevoltageavailableiscorrectforthe•XL-Traceheatingcableselection.Inspecttheheatingcableandconnectionkitstoensure•thereisnoin-transitdamage.Verifythesystemdesigndoesnotexceedthemaximum•exposuretemperatureoftheheatingcable5XL/8XL:150°F(65°C)12XL:185°F(85°C)Verifythattheheatingcablejacketsarenotdamaged•byconductingtheinsulationresistancetest(refertoSection7)oneachreelofheatingcable.Donotpowertheheatingcablewhenit’sonthereel.

Check piping to be tracedMakesureallmechanicalpipetesting(i.e.hydrostatic•testing/purging)iscompleteandthesystemhasbeenclearedbytheclientfortracing.

Installation Guidelines2 Installation Guidelines2

Page 6: XL-Trace System Installation and Operation Manual

6 7

Figure 3: Attaching the heating cable

When paying out the heating cable, AVOID:Sharpedges•Excessivepullingforceorjerking•Kinkingorcrushing•Walkingonorrunningovertheheatingcablewith•equipment

WARNING: Fire and shock hazard. Do not install damaged heating cable. Connection kits and heating cable ends must be kept dry before and during instal-lation.

Attaching the heating cableOncetheheatingcablehasbeenrunfortheentiresec-tion,beginfasteningittothepipe.Startattheendandworktowardthereel.TheadditionalheatingcablerequiredforvalvesandotherheatsinksisshowninTables1and2.Refertopages18–19fortheadditionalheatingcablerequiredforconnectionkits.Theheatingcablemaybeinstalledinsingleorinmultiplerunsasrequiredbythedesign.

Installation Guidelines2 Installation Guidelines2

Page 7: XL-Trace System Installation and Operation Manual

8 9

Table 1: Additional Heating Cable for Valves

Pipe diameter (IPS) Heating cable in feet (meters)

1/2 0.8 (0.24)

3/4 1.3 (0.4)

1 2.0 (0.6)

1-1/4 3.3 (1.1)

1-1/2 4.3 (1.3)

2 4.3 (1.3)

3 4.3 (1.3)

4 4.3 (1.3)

6 5.0 (1.5)

8 5.0 (1.5)

10 5.6 (1.7)

12 5.9 (1.9)

14 7.3 (2.2)

18 9.4 (2.9)

20 10.5 (3.2)

Table 2: Additional Heating Cable for Pipe Supports and Flanges

Support Additional heating cable

Pipehangers(insulated) Noadditionalheatingcable

PipehangersnoninsulatedandU-boltsupports

Add2xpipediameter

Weldedsupportshoes Add3xthelengthoftheshoe

Flanges Add2xpipediameter

Note:Forapplicationswheremorethanoneheatingcableisrequiredperfootofpipe,thiscorrectionfactorappliesforeachheatingcablerun.

Runinsulationthroughthepipehangerensuringthatthe•pipeisnotrestingontheheater.

Heating cable

Heating cable beneath insulation

and pipe hanger

Heating cableover pipe hanger

Pipe hanger under insulation

Pipe hanger over insulation

Insulation overpipe hanger

Heating cable

Figure 4: Pipe hanger with heating cable

Figure 5: Single pipe floor penetration

Whenmakingfloororwallpenetrations,makesurethe•holeislargeenoughtoaccommodatethepipeandthethermalinsulation.Whensealingaroundpipesatfloorpenetrations,avoiddamagingorcuttingtheheatingcable,orpinchingitbetweenthepipeandtheconcrete.

Installation Guidelines2 Installation Guidelines2

Page 8: XL-Trace System Installation and Operation Manual

10 11

Theheatingcablemustnotbeembeddeddirectlyinthe•sealingmaterial;thepipeshouldhavethermalinsulationoverit(ifallowedbylocalcodes)ortheheatingcableshouldberunthroughthepenetrationinatubeorconduit.Iftheconduitmustbesealed,useapliablefire-resistantmaterial(DowCorningFireStop,3MFireBarrier,orT&BFlame-Safe)thatcanberemovedifnecessary.

Figure 6: Multiple pipe floor penetration

Onverticalpipinggroups,runtheheatingcablealong•theinsideofthepipeclosetootherpipessoitwillnotbedamagedifthepipehitsthesideofthefloorpen-etration.Runtheheatingcableovertheoutsideofthepipesupport.Donotclamptheheatingcabletothepipewiththepipesupport.

Inhigh-riseconstructionitmaybenecessarytoinstall•theXL-Tracesystem10or12floorsatatimetofitintotheconstructionschedule.Ifso,theendoftheheatingcableshouldbesealedwithaRayClic-Eendsealandplacedinanaccessiblelocation.Thisallowstestingofonepartoftheheatingcableatatime,andallowssplic-ingittoanothersectionwhenthesystemiscomplete.

WhenXL-Traceisinstalledbehindwalls,thepowercon-•nectionkitmustbeaccessible.

Wheneverpossible,positiontheheatingcableonthelowersectionofthepipeasshowninFigure7toprotectitfromdamage.

One heating cable

45°

Two heating cables

45° 45°

Figure 7: Positioning the heating cable

Securing the heating cable

WARNING: Damage to the heating cable can cause electrical arcing or fire. Do not use metal attachments such as pipe straps or tie wire. Use only Tyco Thermal Controls-approved tapes or plastic cable ties.

Important: Before taping the heating cable to the pipe, make sure all heat-tracing allowances for flanges, valves, supports, and other connection kits have been verified.Useoneofthefollowingattachmentmethodstosecuretheheatingcableontothepipe:GT-66orGS-54glassclothtape,AT-180aluminumtape,orplasticcableties.

Glass cloth adhesive tapeGT-66(66-footroll)general-purposetapeforinstallation•at40°F(4°C)andabove.Applyat1-footintervals.GS-54(54-footroll)general-purposetapeforinstallation•below40°F(4°C).Applyat1-footintervals.

AT-180 aluminum tapeRequiredforplasticpipeapplicationstoensureproper•poweroutputofheatingcable.Tapelengthwiseovertheheatingcableasrequiredbythe•designdrawingorspecification(seeFigure8).Recommendedforheat-tracingpumpbodiesorodd-•shapedequipment,orascalledoutinthedesigndrawingasaheat-transferaid.Installattemperaturesabove32°F(0°C).•

Installation Guidelines2 Installation Guidelines2

Page 9: XL-Trace System Installation and Operation Manual

12 13

Heating cable

1 ft (0.3 m)

PipeThermal insulation

Weather proofingGlass cloth tape

AT-180 aluminum tape overheating cable (Required for proper

output for plastic pipe applications)

Heatingcable

PipeAT-180aluminum tape

Figure 8: Attaching the heating cable

Cable tiesRecommendedinapplicationswherethepipesurface•preventspropertapeadhesion.Useplasticcabletiesonly.•Cabletiesmustbehand-tightenedonlytopreventdam-•agetoheatingcable!

Bending/Crossing/Cutting the Heating Cable

Bending the heating cableWhenpositioningtheheatingcableonthepipe,donotbendtighterthan1/2"radius.Theheatingcabledoesnotbendeasilyintheflatplane.Donotforcesuchabend,astheheatingcablewillbedamaged.

1/2"

Figure 9: Bending technique

Installation Guidelines2 Installation Guidelines2Crossing the heating cableXL-Traceheatingcablesareself-regulatingandmaybeoverlappedwhenevernecessarywithoutoverheatingorburningout.

Cutting the heating cableCuttheheatingcabletothedesiredlengthafteritisattachedtothepipe.XL-Tracecanbecuttolengthwithoutaffectingtheheatoutputperfoot.

Wrapping the Heat SinksOncethestraightsectionsaresecuredtheheatingcablecanbesecuredtotheheatsinks.AttachtheheatingcabletotheheatsinksaccordingtoFigure10below.Thelengthofheatingcableinstalledisdeterminedinthedesign.

Valve body

Multiple crossovers allowedfor self-regulating cables

Single crossover only, allowedfor power-limiting cables

Glass tapePipe

Heating cable

Pipe

Heating cable

Note: Cable loop length varies depending on heat loss.

Figure 10: Valve

Page 10: XL-Trace System Installation and Operation Manual

14 15

Installation Guidelines2 Installation Guidelines2Glass tape(typical)

Heating cable Loop length is twice the diameter of the pipe

Figure 11: Flange

Heating cable

Glass tape

Pipe

Figure 12: Pressure gauge

Glass tape

Pump discharge

Pump body

Heating cable

Pumpsuction

Use AT-180tape

Motor

To power connection

Figure 13: Split case centrifugal pump

Heating cable secured to pipe

Glass tape

Heating cable loop

Support shoe Pipe

Figure 14: Pipe support shoe

Heating cable

Glass tape(typical)

For pipe diameters of 2"and larger, the heatingcable should be installedon the outside (long)radius of the elbow.

Figure 15: Elbow

Page 11: XL-Trace System Installation and Operation Manual

16 17

Installation Guidelines2 Installation Guidelines2

Heating cable

Heating cable beneath insulation

and pipe hanger

Heating cableover pipe hanger

Pipe hanger under insulation

Pipe hanger over insulation

Insulation overpipe hanger

Heating cable

Figure 16: Pipe hanger

2.4 Heating Cable Connections

General RequirementsAllXL-Tracesystemsrequireapowerconnectionandendsealkit.Spliceandteekitsareusedasrequired.UseTable3(forabovegroundapplications)andTable4(forbelow-groundapplications)toselecttheappropriateconnectionkits.

Whenpractical,mountconnectionkitsontopofthepipe.Electricalconduitleadingtopowerconnectionkitsmusthavelow-pointdrainsinstalledtoavoidcondensationentryintotheheatingsystem.Allheatingcableconnectionsmustbemountedabovegradelevel.

Ifyourdesignhasanexposuretemperature>150°F(65°C)but<185°F(85°C),installallconnectionskitsoffthepipe.

WARNING: Connection kit approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape. Follow installa-tion instructions provided with each kit.

RayClic-PCpower connection

Junctionbox

EC-TS-AMBelectronicthermostat

RayClic-Ssplice

RayClic-Ttee

Insulation

RayClic-LElighted end seal

(optional)

RayClic-Eend seal

Figure 17: Aboveground XL-Trace System

Page 12: XL-Trace System Installation and Operation Manual

18 19

UseTable3forgeneralabovegroundpiping,sprinklerpip-ing,andgreaseandfuellines.Allowextraheatingcableforeaseofconnectionkitinstallation.

Table 3: Connection Kits for General Aboveground Piping

Catalog number DescriptionHeating cable allowance1

RayClic-PC2,3

Powerconnectionandendsealkit;use1percircuitStandard pkg:1

2ft(0.6m)

FTC-P4,5

Powerconnectionandendsealkit;use1percircuitStandard pkg:1Junction box not included

2ft(0.6m)

RayClic-S2,3,6

SpliceusedtojointwosectionsofheatingcableStandard pkg:1

2ft(0.6m)

RayClic-T2,6

Teekitwithendseal;useasneededforpipebranchesStandard pkg:1

2ft(0.6m)

RayClic-LE

AlternatelightedendsealStandard pkg:1

2ft(0.6m)

Installation Guidelines2 Installation Guidelines2Table 3: Connection Kits for General Aboveground Piping

Catalog number DescriptionHeating cable allowance1

Continued

FTC-HST4

Low-profilesplice/tee;useasneededforpipebranchesStandard pkg:2

3ft(0.9m)

RayClic-E3

ReplacementendsealStandard pkg:1

0.3ft(0.1m)

1Foreaseofcomponentinstallation,allowextraheatingcable.2Poweredsplice,poweredtee,andcross(teewiththreelegs)connectionsarealsoavailable.

3Forgreaseandfuellines,installRayClic-LEorendsealoffthepipeinjunctionbox.

4Notpermittedwithgreaseorfuellines.5Useforcircuitssuppliedwith40Acircuitbreaker.6Forgreaseandfuellines,installteesandsplicesonpipemountingbracket(RayClic-SB-04).

Page 13: XL-Trace System Installation and Operation Manual

20 21

Table 4: Accessories for General Aboveground Piping

Catalognumber Description

Heating cable allowance

ETL

“ElectricTraced”label(use1labelper10feetofpipe)

10labels

GT-66

Glassclothadhesivetapeforattachingheatingcabletopipeat40°F(4°C)orabove.SeeTable7.

66ft

GS-54

Glassclothadhesivetapeforattach-ingheatingcabletopipeabove–40°F(–40°C).SeeTable7.

54ft

AT-180

Aluminumtape.Requiredforattachingheatingcabletoplasticpipe(use1footoftapeperfootofheatingcable).

180ft

RayClic-SB-04

Pipemountingbracket.Requiredformountingthekitsoffthepipeforexpo-suretemperaturesgreaterthan150°F(65°C)andforgreaseandfuellinesplicesandtees.

1ea

Installation Guidelines2 Installation Guidelines2110F

43C

90F32C

70F21C

50F10C

30F–1C

Temperature sensor

Insulation

EC-TS-10 or EC-TS-25electronic thermostat

Conduit

XL-Traceheating cable

Ground

Alternatepower connection

Alternateend seal

Ground

Wall

RayClic-LE*

RayClic-PC*

Junction boxRayClic-E

end seal

Conduit

Wall

with wallmountiungbracket

with wallmountiungbracket

FTC-XCpower connection

*To protect the heating cablerun it inside Convolex tubing betweenthe conduit and the RayClic connection kits.

Figure 18: Buried pipe XL-Trace System

Page 14: XL-Trace System Installation and Operation Manual

22 23

Table 5. Connection Kits for General Buried Piping

Catalog number DescriptionHeating cable allowance*

FTC-XC

Powerconnectionand•endsealJunctionboxsuppliedby•customerUse1percircuit•

Standard pkg:1

2ft(0.6m)

3 1/8"

RayClic-PC

PowerconnectionandendsealkitStandard pkg:1

RayClic-E

Replacementendseal.Standard pkg:1

0.3ft(0.1m)

RayClic-LE

AlternatelightedendsealStandard pkg:1

2ft(0.6m)

*Foreaseofconnectionkitinstallation,allowextraheatingcable.

Table 6: Accessories for General Buried Piping

Catalognumber Description

Standard pkg

ETL “ElectricTraced”label(use1labelper10feetofpipe)

10labels

GT-66 Glassclothadhesivetapeforattachingheatingcabletopipeat40°F(4°C)orabove.SeeTable7.

66ft

GS-54 Glassclothadhesivetapeforattach-ingheatingcabletopipeabove–40°F(–40°C).SeeTable7.

54ft

AT-180 Aluminumtape.Requiredforattachingheatingcabletoplasticpipe(use1footoftapeperfootofheatingcable).

180ft

RayClic-SB-02 Wallmountingbracket 1

Table 7: Quantity of Glass Cloth Adhesive Tape Required (attach at 1-foot intervals)

Pipe size (in) <2 3 4 6 8 10

FeetofpipeperGT-66roll 60 50 40 25 20 15

FeetofpipeperGS-54roll 49 41 33 20 16 12

Installation Guidelines2 Installation Guidelines2

Page 15: XL-Trace System Installation and Operation Manual

24 25

Thermal Insulation3 Thermal Insulation33.1 Insulating the System

Pipesmustbeinsulatedwiththecorrectthermalinsulationtomaintainthedesiredpipetemperatures.Confirmthattheinsulationthicknessagreeswiththesystemdesign.

3.2 Insulation InstallationBeforeinsulatingthepipe,visuallyinspecttheheating•cableandconnectionkitstoensuretheyareproperlyinstalledandtherearenosignsofdamage.Damagedheatingcableorconnectionkitsmustbereplaced.Checkthattheinsulationtypeandthicknessiscorrect.•Insulatethepipesimmediatelyaftertheheatingcableis•installedandhaspassedallteststominimizedamagetotheheatingcable.Insulatethepipeatfloorandwallpenetrations.Failureto•dosowillcausecoldspotsinthewatersystemandcouldleadtodamagetotheheatingcable.Iflocalcodesdonotallowthis,theheatingcableshouldberunthroughaconduitorchannelbeforethefirestopisinstalled.Useafire-resistantsealingcompoindsuchasDowCorningFireStop,3MFireBarrier,orT&BFlame-Safe.Donotusestaplestosealinsulation.Usetapeorthethe•adhesive-linededgeoftheinsulationtoensurethattheseamremainssealed.Staplescandamagetheheatingcable.

Figure 19: Sealing the insulation seam

Allsystemsforoutdoor,buried,orwetareasmustuse•waterprooffire-resistantthermalinsulation.Markthelocationofsplices,tees,andendsealsonthe•outsideoftheinsulationwithlabelsprovidedinthekits,whileinstallingtheinsulation.Uselargediameterinsula-tionorsheetstocoversplices,tees,orserviceloops.

Figure 20: Installing connection kits below insulation

Figure 21: Installing connection kits above insulation

Makesurethatallheat-tracedpiping,fittings,wallpen-•etrations,andbranchpipingareinsulated.Correctlydesignedsystemsrequireproperlyinstalledanddryther-malinsulation.Uninsulatedorwetsectionsofpipecanresultincoldspotsorfrozensections.Afterinstallinginsulation,electricalcodesrequirethatyou•install“ElectricTraced”labelsalongthepipingatsuitableintervals(10-footintervalsrecommended)onalternatesides.

WARNING: Use only fire-resistant insulation mate-rials such as fiberglass wrap or flame-retardant foams.

Page 16: XL-Trace System Installation and Operation Manual

26 27

4.1 Voltage RatingVerifythatthesupplyvoltageiseither120or208–277voltsasspecifiedbytheXL-Tracesystemdesignandprintedonthejacketoftheheatingcable.

4.2 Circuit Breaker SizingCircuitbreakersmustbesizedusingtheheatingcablelengthsshownintheAppendix.Donotexceedthemaxi-mumcircuitlengthshownforeachbreakersize.Usecircuitbreakersthatincorporate30-mAground-faultcircuitprotection,orprovideequivalentlevelsofground-faultprotection.

4.3 Electrical LoadingThemaximumcurrentdrawforXL-TraceheatingcablesisshownintheAppendix.Tosizethetransformer,multiplythetotalheatingcablelength(ft)bytheappropriatecurrentdraw.

4.4 Ground-Fault ProtectionIftheheatingcableisimproperlyinstalledorphysicallydamagedtothepointthatwatercontactsthebuswires,sustainedarcingorfirecouldresult.Ifarcingdoesoccur,thefaultcurrentmaybetoolowtotripconventionalcircuitbreakers.TycoThermalControlsandnationalelectricalcodesrequirebothground-faultprotectionofequipmentandagroundedmetalliccoveringonallheatingcables.Ground-faultprotectionmustbeprovidedbytheinstaller.

WARNING: To minimize the danger of fire from sustained electrical arcing if the heating cable is dam-aged or improperly installed, and to comply with Tyco Thermal Controls requirements, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit breakers.

WARNING: Disconnect all power before making connections to the heating cable.

Power Supply and Electrical Protection4 Power Supply and Electrical

Protection44.5 Important Power Supply Safeguards

Makesurethattheheatingcableloadyouareconnecting•iswithintheratingofthecontrolsystemselected.Checkthedesigndrawingsfortheheatingcableload.Theelectricalconduitthatfeedswiringtothecontrol•devicemusthavealow-pointdrainsocondensationwillnotenterthethermostatenclosure.Makesurethatthelinevoltageyouareconnectingtothe•controlsystemiscorrect.Forproperwiring,followtheinstallationinstructionsenclosedwiththecontroldevice.

Page 17: XL-Trace System Installation and Operation Manual

28 29

5.1 Ambient-Sensing ControlAmbient-sensingsystemsenergizethecircuitwhentheambienttemperaturedropsbelowthesetpoint.Mountthedeviceabovegradelevelandoutofsunlight.•Mountthedevicewhereitwillbeexposedtothecoldest•temperatureandthehighestwind.

R

AMC-1Aambient-sensingthermostat

EC-TS-AMBambient-sensingthermostat

Figure 22: Ambient-sensing thermostats

5.2 Line-Sensing ControlLine-sensingsystemssensethepipetemperaturebymeansofasensorattachedtothepipeandconnectedtothedevice.Installthesensoronthepipeat90degreesfromthe•heatingcablesothattheheatingcabledoesnotthermallyinterferewiththesensor.Besurethesensorisfirmlyattachedwithaluminumtapetothepipeinordertogetgoodthermalcontactbetweenthebulbandthepipe.Locatethesensoratleast3feet(1meter)fromanyheat•sinks,suchasvalves,pipesupports,andpumps.Ideally,thesensorshouldbelocatedattheendoftheheatingcablecircuit.Besurethatyousetthecontroltotheproper•temperature.Mountthedeviceonanearbywallorsupport,orinstall•amountingstanchion.Thermostatsmustbemountedabovegradelevel.Inallcases,protectthesensorfromphysicaldamage.Topreventdamage,mountthedevicewhereitwillbeawayfromfootandequipmenttraffic.Topreventwaterentry,sealtheinsulationwherethecap-•illarytubeexitstheinsulation.

R

R

AMC-1Bline-sensingthermostat

AMC-F5ambient/line-sensingthermostat with afixed setpoint at 40°F

Figure 23: Mechanical thermostats

EC-TS-10/25line-sensingelectronic thermostat

Figure 24: Electronic thermostat

Temperature Controls5 Temperature Controls5

Page 18: XL-Trace System Installation and Operation Manual

30 31

DigiTrace 910electronic controller

DigiTrace 920electronic controller

Figure 25: Electronic controllers

Temperature Controls5 Temperature Controls55.3 Wiring Schematic for Thermostat

Thefollowingisatypicalwiringschematicforathermostat.

Single circuit control

Temperaturecontroller

1-poleGFEP breaker

1N

G

Heatingcable

øø supply

Heating cable sheath, braid or ground

Figure 26: Single circuit control

Group control

C

Temperaturecontroller

Contactor

1-poleGFEP breaker

N

G (Typ 3)

ø2

ø1

ø3

3-phase 4-wiresupply (WYE)

3-pole mainbreaker

ø

ø 1 supply

N

Heating cable sheath, braid or ground

Figure 27: Group circuit control

Page 19: XL-Trace System Installation and Operation Manual

32 33

Temperature Controls5 Temperature Controls5

A

COMMON ALARMPUSH TO ACKNOWLEDGE

HAND/OFF/AUTO

1

2

3

4

5

6

7

8

9

10

11

12

Main circuitbreaker

Maincontactor

Distributionpanelboard

Fuse holder

C

POWER ON

TB 1

TB 2

ARR

Groundbus bar

Selector switch

Alarm relay(optional)

Terminals(optional)

Push button for light testing

Alarm horn (optional)

Alarm option shown above

Doordisconnect(optional)

Figure 28: HTPG power distribution panel

Three-pole maincircuit breaker

Three-pole maincontactor

One-polewith 30-mA

ground-fault trip(120/277 Vac)

Two-polewith 30-mA

ground-fault trip(208/240 Vac)

Power connection

Heating cable

Alarmremoteannunciation(with alarm option)

End seal

Heating cable circuit

Heating cable circuit

Heating cable shealth, braid or ground

NØ1

Panelenergized

Contactorcoil

C NC

External controller/thermostat*

Hand AutoOffØ3Ø2 G

Figure 29: HTPG schematic

Page 20: XL-Trace System Installation and Operation Manual

34 35

TycoThermalControlsrequiresaseriesofcommissioningtestsbeperformedontheXL-Tracesystem.Thesetestsarealsorecommendedatregularintervalsforpreventivemaintenance.Resultsmustberecordedandmaintainedforthelifeofthesystem,utilizingthe“InstallationandInspectionRecord”(refertoSection9).Submitthismanu-alwithinitialcommissioningtestresultstotheowner.

6.1 TestsAbriefdescriptionofeachtestisfoundbelow.DetailedtestproceduresarefoundinSection7.

Visual InspectionVisuallyinspectthepipe,insulation,andconnectionstotheheatingcableforphysicaldamage.Checkthatnomoistureispresent,electricalconnectionsaretightandgrounded,insulationisdryandsealed,andcontrolandmonitoringsystemsareoperationalandproperlyset.Damagedheatingcablemustbereplaced.

Insulation ResistanceInsulationResistance(IR)testingisusedtoverifytheintegrityoftheheatingcableinnerandouterjackets.IRtestingisanalogoustopressuretestingapipeanddetectsifaholeexistsinthejacket.

Circuit Length Verification (Capacitance Test)TheinstalledcircuitlengthisverifiedthroughacapacitancemeasurementoftheXL-Traceheatingcable.Comparethecalculatedinstalledlengthagainstthesystemdesign.Ifthecalculatedlengthisshorterthanthesystemdesign,confirmallconnectionsaresecureandthegroundingbraidiscontinuous.

Power CheckThepowercheckisusedtoverifythatthesystemisgen-eratingthecorrectpoweroutput.Thistestcanbeusedincommissioningtoconfirmthatthecircuitisfunctioningcorrectly.Forongoingmaintenance,comparethepoweroutputtopreviousreadings.

Theheatingcablepoweroutputperfootiscalculatedbydividingthetotalwattagebythetotallengthofacircuit.Thecurrent,voltage,operationtemperature,andlengthmustbeknown.Circuitlengthcanbedeterminedfrom“asbuilt”drawings,metermarksontheheatingcable,orwiththecapacitancetest.ThewattsperfootcanbecomparedtotheheatingcableoutputinFigure32onpage40foranindicationofheatingcableperformance.

Ground-Fault TestTestallground-faultbreakerspermanufacturer’sinstructions.

Commissioning and Preventive Maintenance6 Test Procedures7

7.1 System TestsThefollowingtestsmustbedoneafterinstallingthecon-nectionkits,butbeforethethermalinsulationisappliedtothepipe:

Visualinspection1.Insulationresistancetest2.

Afterthethermalinsulationhasbeeninstalledonthepipe,thefollowingtestsmustbeperformed:

Visualinspection1.Insulationresistancetest2.Circuitlengthverification(Capacitancetest)3.Powertest4.Temperaturetest5.

Alltestproceduresaredescribedinthismanual.Itistheinstaller’sresponsibilitytoperformthesetestsorhaveanelectricianperformthem.RecordtheresultsintheInstallationandInspectionRecordinSection10.

Visual Inspection TestCheckinsideallpower,splice,andteekitsforproper•installation,overheating,corrosion,moisture,orlooseconnections.Checktheelectricalconnectionstoensurethatground•andbuswiresareinsulatedovertheirfulllength.Checkfordamaged,missing,orwetthermalinsulation.•Checkthatendseals,splices,andteesareproperly•labeledoninsulationcladding.Checkthecontrollerforpropersetpointandoperation.•Refertoitsinstallationandoperationmanualfordetails.

Insulation Resistance TestFrequencyInsulationresistancetestingisrequiredduringtheinstal-lationprocessandaspartofregularlyscheduledmainte-nance,asfollows:Beforeinstallingtheheatingcable•Beforeinstallingconnectionkits•Beforeinstallingthethermalinsulation•Afterinstallingthethermalinsulation•Priortoinitialstart-up(commissioning)•Aspartoftheregularsysteminspection•Afteranymaintenanceorrepairwork•

Page 21: XL-Trace System Installation and Operation Manual

36 37

Test Procedures7 Test Procedures7ProcedureInsulationresistancetesting(usingamegohmmeter)shouldbeconductedatthreevoltages:500,1000,and2500 Vdc.Potentialproblemsmaynotbedetectediftest-ingisdoneonlyat500and1000volts.Firstmeasuretheresistancebetweentheheatingcablebuswiresandthebraid(TestA),thenmeasuretheinsulationresistancebetweenthebraidandthemetalpipe(TestB).Donotallowtestleadstotouchjunctionbox,whichcancauseinaccu-ratereadings.

Note: System tests and regular maintenance procedures require that insulation resistance testing be performed. Test directly from the controller or the junc-tion box closest to the power connection.

Insulation resistance criteriaAclean,dry,properlyinstalledcircuitshouldmeasurethousandsofmegohms,regardlessoftheheatingcablelengthormeasuringvoltage(500–2500Vdc).

Allinsulationresistancevaluesshouldbegreaterthan1000megohms.Ifthereadingislower,consultSection8,TroubleshootingGuide.

Note: Insulation resistance values for Test A and B for any particular circuit should not vary more than 25 percent as a function of measuring voltage. Greater variances may indicate a problem with your heat-tracing system; confirm proper installation and/or contact Tyco Thermal Controls for assistance.

Test A

Test B

Attach to pipe

L2

L1

Figure 30: Insulation resistance test

Page 22: XL-Trace System Installation and Operation Manual

38 39

Test Procedures7 Test Procedures7Insulation Resistance test procedure

De-energizethecircuit.1.Disconnectthecontrollerifinstalled.2.Disconnectbuswiresfromterminalblock.3.Settestvoltageat0Vdc.4.Connectthenegative(–)leadtotheheatingcable5.metallicbraidorRayClicgreenwire.Connectthepositive(+)leadtobothheatingcablebus6.wiresorRayClicblackwires.Turnonthemegohmmeterandsetthevoltageto5007.Vdc;applythevoltageforoneminute.Meterneedleshouldstopmoving.Rapiddeflectionindicatesashort.RecordtheinsulationresistancevalueintheInspectionRecord.RepeatSteps4–7at1000and2500Vdc.8.Turnoffthemegohmmeter.9.Ifthemegohmmeterdoesnotself-discharge,discharge10.phaseconnectiontogroundwithasuitablegroundingrod.Disconnectthemegohmmeter.Repeatthistestbetweenbraidandpipe.11.Reconnectbuswirestoterminalblock.12.Reconnectthetemperaturecontroller.13.

Circuit length verification (capacitance test)Connectthecapacitancemeternegativeleadtobothbuswiresandthepositiveleadtothebraidwire.Setthemetertothe200nFrange.Multiplythisreadingbythecapaci-tancefactorforthecorrectheatingcableshownbelowtodeterminethetotalcircuitlength.Length(ftorm)=Capacitance(nF)xCapacitancefactor (ft/nForm/nF)

Table 9: Capacitance Factors

Capacitance factor

Heating cable ft/nF (m/nF)

5XLand8XL 5.0 (1.6)

12XL 5.8 (1.8)

Comparethecalculatedcircuitlengthtothedesigndraw-ingsandcircuitbreakersizingtables.

Figure 31: Capacitance test

Power CheckThepoweroutputofself-regulatingheatingcableistemperature-sensitiveandrequiresthefollowingspecialproceduretodetermineitsvalue:

Powertheheatingcableandallowittostabilizefor21.hours,thenmeasurecurrentandvoltageatthejunctionbox.Ifacontrollerisused,refertodetailsbelow.Checkthepipetemperatureunderthethermalinsulation2.atseverallocations.Calculatethepoweroftheheatingcablebymultiply-3.ingthecurrentbytheinputvoltageanddividingbytheactualcircuitlength.

Power(w/ftorm)=Volts(Vac)xCurrent(Amps)

________________________ Length(ftorm)

Thepowercalculatedshouldbesimilartothevaluegener-atedby:RatedPower(w/ftorm)=Volts(Vac)xRatedCurrent

Pipe temperature

Pow

er W

/ft

50(10)

30(–1)

40(5)

60(15)

70(21)

80(27)

90(32)

100(38)

110(43)

120(49)

130(54)

°F(°C)

10

8

14

12

6

4

2 0

5XL1-CR and 5XL1-CT (120 V)5XL2-CR and 5XL2-CT (208 V)

8XL1-CR and 8XL1-CT (120 V)8XL2-CR and 8XL2-CT (208 V)

12XL2-CR and 12XL2-CT (208 V)

Figure 31: Power output

Page 23: XL-Trace System Installation and Operation Manual

40 41

Test Procedures7 Test Procedures77.2 Fault Location Tests

Therearethreemethodsusedforfindingafaultwithinasectionofheatingcable.

Ratiomethod1.Conductancemethod2.Capacitancemethod3.

Ratio MethodTheratiomethodusesresistancemeasurementstakenateachendoftheheatingcabletoapproximatethelocationofabuswireshort.Ashortedheatingcablecouldresultinatrippedcircuitbreaker.Iftheresistancecanbereadonastandardohmmeterthismethodcanalsobeusedtofindafaultfromabuswiretothegroundbraid.ThistypeofshortwouldtripaGFPDandshowafailedinsulationresistancereading.Measurethebus-to-busheatingcableresistanceateachend(measurementAandmeasurementB)ofthesuspectedsection.

A B

A B

A B

Braid

Figure 32: Heating cable resistance measurement test

Theapproximatelocationofthefault,expressedasaper-centageoftheheatingcablelengthfromthefrontend,is:

Faultlocation: D= A x100 ________

(A+B)

Example: A= 1.2ohms B= 1.8ohms

Faultlocation: D= 1.2/(1.2+1.8)x100 = 40%

Tolocatealowresistancegroundfault,measurebetweenbusandbraid.

A B

A B

A B

Braid

Figure 33: Low resistance ground-fault test

Theapproximatelocationofthefault,expressedasaper-centageoftheheatingcablelengthfromthefrontend,is:

Faultlocation: D= A x100 ________

(A+B)

Example: A= 1.2ohms B= 1.8ohms

Faultlocation: D= 1.2/(1.2+1.8)x100 = 40%

Thefaultislocated40%intothecircuitasmeasuredfromthefrontend.

Conductance MethodTheconductancemethodusesthecoreresistanceoftheheatingcabletoapproximatethelocationofafaultwhentheheatingcablehasbeenseveredandthebuswireshavenotbeenshortedtogether.Aseveredheatingcablemayresultinacoldsectionofpipeandmaynottripthecircuitbreaker.Measurethebus-to-busheatingcableresistanceateachend(measurementAandmeasurementB)ofthesuspectsection.Sinceself-regulatingheatingcablesareaparallelresistance,theratiocalculationsmustbemadeusingtheconductanceoftheheatingcable.

A B

A B

A B

Braid

Figure 34: Heating cable resistance measurement

Page 24: XL-Trace System Installation and Operation Manual

42 43

Test Procedures7 Test Procedures7Theapproximatelocationofthefault,expressedasaper-centageoftheheatingcablelengthfromthefrontend,is:

Faultlocation: D= 1/A x100 ________

(1/A+1/B)

Example: A= 100ohms B= 25ohms

Faultlocation: D= (1/100)/(1/100+1/25)x100 = 20%

Thefaultislocated20%fromthefrontendofthecircuit.

Capacitance MethodThismethodusescapacitancemeasurement(nF)asdescribedonpage37,toapproximatethelocationofafaultwheretheheatingcablehasbeenseveredoracon-nectionkithasnotbeenconnected.Recordthecapacitancereadingfromoneendoftheheat-ingcable.Thecapacitancereadingshouldbemeasuredbetweenbothbuswirestwistedtogether(positivelead)andthebraid(negativelead).Multiplythemeasuredcapac-itancewiththeheatingcable’scapacitancefactoraslistedinthefollowingexample:

Example: 5XL2-CR=16.2nF

Capacitancefactor = 5.0ft/nF

Faultlocation = 42.2nFx5.0ft/nF=211ft(64m)

Theratioofonecapacitancevaluetakenfromoneend(A)dividedbythesumofbothAandB(A+B)andthenmultipliedby100yieldsthedistancefromthefirstend,expressedasapercentageofthetotalheatingcablecircuitlength.SeeTable10,page39,forcapacitancefactors.

Faultlocation: C= A x100 ________

(A+B)

Page 25: XL-Trace System Installation and Operation Manual

44 45

Troubleshooting Guide8Symptom Probable Causes Corrective Action

Circuitbreakertrips Circuitbreakerisundersized Recheckthedesignforstartuptemperatureandcurrentloads.Donotexceedthemaximumcircuitlengthforheatingcableused.Replacethecircuitbreakerifdefectiveorimproperlysized.

Connectionsand/orsplicesareshortingout.

Visuallyinspecttheconnectionkits.Replaceifnecessary.

Physicaldamagetoheatingcableiscausingadirectshort.

Checkfordamagearoundthevalvesandanyareawheretheremayhavebeenmaintenancework.Replacedamagedsectionsofheatingcable.

Buswiresareshortedattheend. Checktheendsealtoensurethatbuswiresarenotshorted.Ifadeadshortisfound,theheatingcablemayhavebeenpermanentlydamagedbyexcessivecurrentandmayneedtobereplaced.

Circuitlengthstoolong. Separatethecircuitintomultiplecircuitsthatdonotexceedmaxi-mumcircultlengths.

Nickorcutexistsinheatingcableorpowerfeedwirewithmoisturepresentormoistureinconnections.

Replacetheheatingcable,asnecessary.Dryoutandresealtheconnectionandsplices.Usingamegohmmeter,retestinsulationresistance.

GFPDisundersized(5mAusedinsteadof30mA)ormiswired.

ReplaceundersizedGFPDwith30-mAGFPD.ChecktheGFPDwiringinstructions

Loworinconsistentinsulationresistance

Nicksorcutsintheheatingcable.

Shortbetweenthebraidandheatingcablecoreorthebraidandpipe.

Ifheatingcableisnotyetinsulated,visuallyinspecttheentirelengthfordamage,expeciallyatelbowsinflangesandaroundvalves.Ifthesystemisinsulated,removetheconnectionkitsone-by-onetoisolatethedamagedsection.

Arcingduetodamagedheating-cableinsulation.

Replacedamagedheating-cablesections.

Moisturepresentintheconnectionkits. Ifmoistureispresent,dryouttheconnectionsandretest.Besureallconduitentriesaresealed,andthatcondensateinconduitcannotenterpowerconnectionboxes.Ifheating-cablecoreorbuswiresareexposedtolargequantitiesofwater,replacetheheatingcable.(Dryingtheheatingcableisnotsufficient,asthepoweroutputoftheheatingcablecanbesignificantlyreduced.)

Testleadstouchingthejunctionbox. Clearthetestleadsfromjunctionboxandrestart.

Page 26: XL-Trace System Installation and Operation Manual

46 47

Appendix9Table A1 Circuit Breaker Sizing (Feet)

Start-up temperature (°F)

CB size (A)

Application 40°F/110°F Maintain*

Circuit breaker sizing (ft)

5XL1 8XL1 5XL2 8XL1 12XL2

120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V

–20°F

15 101 76 174 178 183 131 138 146 111 114 117

20 134 101 232 237 245 175 184 194 148 151 156

30 201 151 349 356 367 262 276 291 223 227 234

40 270 201 465 474 478 349 368 388 297 303 312

0°F

15 115 86 199 203 209 149 157 166 120 122 126

20 153 115 265 271 279 199 209 221 160 163 138

30 230 172 398 406 419 298 314 331 239 244 252

40 270 210 470 490 530 370/399 390/420 420/443 319 326 336

20°F

15 134 100 232 237 244 173 182 192 126 129 133

20 178 133 309 315 325 231 243 257 169 172 177

30 270 200 464 473 488 346 365 385 253 258 266

40 270 210 470 490 530 370/462 390/486 420/513 340/349 344 355

40°F

15 160 119 278 283 292 206 217 229 142 145 150

20 214 159 370 378 390 275 290 306 190 194 200

30 270 210 470 490 530 370/416 390/438 420/462 285 291 300

40 270 210 470 490 530 370/554 390/584 420/616 349/398 360/406 380/419

50°F(buried)

15 – – – – – 228 240 254 152 155 160

20 – – – – – 304 320 338 203 207 213

30 – – – – – 457 481 507 304 310 320

40 – – – – – 609 641 676 405 414 427

65°F(indoorsgrease)

15 – – – – – 272 286 302 169 172 178

20 – – – – – 362 381 402 225 230 237

30 – – – – – 543 572 603 338 345 356

40 – – – – – 610 660 720 430 460 490

*Whencircuitbreakersizingislistedin:• blacktype,thevalueisforapplicationswitha40°Fmaintain• red italictype,thevalueisforapplicationswitha110°Fmaintain

Page 27: XL-Trace System Installation and Operation Manual

48 49

Appendix9Table A2 Circuit Breaker Sizing (Meters)

Minimum start-up temperature (°C)

CB size (A)

Application 4°C/43°C Maintain*

Circuit breaker sizing (m)

5XL1 8XL1 5XL2 8XL1 12XL2

120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V

–29°C

15 31 23 53 54 56 40 42 44 34 35 36

20 41 101 71 72 75 53 56 59 45 46 48

30 61 151 106 108 112 80 84 89 68 69 71

40 82 201 142 145 149 106 112 118 90 92 95

–18°C

15 35 86 61 62 64 45 48 51 36 37 38

20 47 115 81 83 85 61 64 67 49 50 51

30 70 172 121 124 128 91 96 101 73 74 77

40 82 210 143 149 162 113/122 119/128 128/135 97 99 102

–7°C

15 41 100 71 72 74 53 56 59 39 39 41

20 54 133 94 96 99 70 74 78 51 52 54

30 82 200 141 144 149 106 111 117 77 79 81

40 82 210 143 149 162 113/141 119/148 128/156 104/106 105 108

40°C

15 49 119 85 86 89 63 66 70 43 44 46

20 65 159 113 115 119 84 88 93 58 59 61

30 82 210 143 149 162 113/127 119/134 128/141 87 89 91

40 82 210 143 149 162 113/169 119/178 128/188 104/121 110/124 116/128

10°C(buriedgrease)

15 – – – – – 70 73 77 46 47 49

20 – – – – – 93 98 103 62 63 65

30 – – – – – 139 147 155 93 95 98

40 – – – – – 186 195 206 124 126 130

18°C(indoorsgrease)

15 – – – – – 83 87 92 52 53 54

20 – – – – – 110 116 123 69 70 72

30 – – – – – 166 174 184 103 105 108

40 – – – – – 186 201 220 131 140 149

*Whencircuitbreakersizingislistedin:• blacktype,thevalueisforapplicationswitha4°Cmaintain• red italictype,thevalueisforapplicationswitha43°Cmaintain

Page 28: XL-Trace System Installation and Operation Manual

50 51

Table A3 Transformer Sizing (Amperes/foot)

Minimum start-up temperature (°F)

5XL1 8XL1 5XL2 8XL1 12XL2

120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V

–20 0.119 0.159 0.069 0.067 0.065 0.092 0.087 0.082 0.108 0.106 0.102

0 0.105 0.139 0.060 0.059 0.057 0.080 0.076 0.072 0.100 0.098 0.095

20 0.090 0.120 0.052 0.051 0.049 0.069 0.066 0.062 0.095 0.093 0.090

40 0.075 0.101 0.043 0.042 0.041 0.058 0.055 0.052 0.084 0.083 0.080

50 – – – – – 0.053 0.050 0.047 0.079 0.077 0.075

65 – – – – – 0.044 0.042 0.040 0.072 0.070 0.067

Table A4 Transformer Sizing (Amperes/meter)

Minimum start-up temperature (°C)

5XL1 8XL1 5XL2 8XL1 12XL2

120 V 120 V 208 V 240 V 277 V 208 V 240 V 277 V 208 V 240 V 277 V

–20 0.391 0.521 0.226 0.221 0.215 0.301 0.286 0.270 0.354 0.347 0.336

–18 0.343 0.457 0.198 0.194 0.188 0.264 0.251 0.238 0.329 0.322 0.312

–7 0.294 0.394 0.170 0.166 0.161 0.227 0.216 0.205 0.311 0.305 0.296

4 0.246 0.331 0.142 0.139 0.135 0.191 0.181 0.172 0.276 0.271 0.263

10 – – – – – 0.172 0.164 0.155 0.259 0.254 0.246

18 – – – – – 0.145 0.138 0.130 0.233 0.228 0.221

Appendix9

Page 29: XL-Trace System Installation and Operation Manual

52 53

Installation and Inspection RecordFacility

TestDate:

Circuitnumber:

Heatingcabletype:

Controllers:

Temperaturesetting:

Circuitlength:

Commission

Inspection date:

Visual inspection

Confirm30-mAground-faultdevice(properrating/function)

Visualinspectioninsideconnectionboxesforoverheating,corrosion,moisture,andotherproblems.

Properelectricalconnection,ground,andbuswiresinsulatedoverfulllength

Damagedormissingthermalinsulation;damaged,missing,crackedlaggingorweatherproofing.

Coveredendseals,splices,andteesproperlylabeledoninsulation.

Checkcontrollersformoisture,corrosion,setpoint,switchoperation.

Insulation resistance test M-Ohms

Bustobraid(TestA) 500Vdc

1000Vdc

2500Vdc

Braidtopipe(TestB) 500Vdc

1000Vdc

2500Vdc

Circult length verificationCapacitancetest:Circuitlength(ft)=Capacitance(nF)xCapacitancefactor(x3.28=m)

Power check

Circuitvoltage

Panel (Vac)

Circuitampsafter2hours (Amps)

Pipetemperature (°F)(°C)

Power=(voltsxampsafter2hrs)/circuitlength(watts/ft)(watts/m)

Installation and Inspection Record10

Page 30: XL-Trace System Installation and Operation Manual

©2008TycoTherm

alContro

lsLLC

H

580331

1/08Tyco,RayClic,DigiTrace,andXL-TracearetrademarksofTycoThermalControls

LLCoritsaffiliates.

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.

Tyco Thermal Controls307ConstitutionDriveMenloPark,CA94025-1164USATel (800)545-6258Tel (650)216-1526Fax (800)527-5703Fax (650)[email protected]

CanadaTyco Thermal Controls250WestSt.Trenton,OntarioCanadaK8V5S2Tel (800)545-6258Fax (800)527-5703