ASHP 06
ASHP 05
ASHP 04
ASHP 03
ASHP 02
ASHP 01
100 mmøHTG F&R
P2
P1 EV 01
EV 02
WH 01
BS 01
54 mmø
35 mmø
35 mmø
28 mmø
22 mmø
54 mmø 35 mmø54 mmø
50 mmø50 mmø
35 mmø
80 mmø 80 mmø
50 mmø
HTG F&R
Air/Dirt separator (Domestic hot water)
P04
6L Chemical dosing pot
60L Expansion vessel
Distribution board
Main LV panel
Mechanical control panel
Pressurisation unit (Domestic hot water)
Pressurisation unit(Heating)
300L Expansion vessel(Heating)
Cold water packagedbreak tank
Booster set c/wcontrol panel
Air/Dirt separator 12L Chemical dosing pot
P01 P02 P03
150ø Low loss header HTG & DWS pipeworkdrop to serve plantroom
HTG & DWS pipeworkruns at HL
HTG & DWS pipeworkrise from below
PV
P05
300.000
500.0
00
500.0
00
500.0
00
500.0
00
500.0
00
900.0
00
300.000
ASHP526kg (Heating)
ASHP526kg (Heating)
ASHP526kg (Heating)
ASHP526kg (Heating)
ASHP526kg (Heating)
ASHP526kg (Domestic hot water)
Hot water cylinder967kg
A/C External unit 43kg(Sensor Room)
THIS DRAWING IS TO BE READ IN CONJUNCTION WITHALL RELEVANT ARCHITECTURAL & STRUCTURALDRAWINGS.
THIS DRAWING IS TO BE READ IN CONJUNCTION WITHALL RELEVANT BUILDING SERVICES DRAWINGS & THERELEVANT SECTIONS OF THE SPECIFICATIONS &SCHEDULES.
THIS DRAWING IS NOT TO BE SCALED.
ALL DIMENSIONS ARE IN mm UNLESS OTHERWISESTATED.
1.
2.
3.
4.
NOTES
Website:
Rev:
DATEREV DESCRIPTION BY
Client:
Title:
Project:
Scale at A0: Date: Designed: Drawn: Design:
Drawing No:
Visit - www.buildingservicesdesign.co.uk
C
Do Not Scale. Work to Figured Dimensions Only
Copyright BUILDING SERVICES DESIGN
CAD:
REGISTEREDISO
A
FIRM9001
S:2000
1 Brisbane House, Corbygate Business ParkPriors Haw Road, Corby Northamptonshire. NN17 5JGTel:(01536) 403304, Fax:(01536) 403838E-mail: [email protected] in: London, Cambridge, Birmingham, Manchester and Leicester
Building Services DesignConsulting Engineers
REGISTEREDISO
A
FIRM9001
S:2000
www.buildingservicesdesign.co.uk
1 : 20
PRINCE WILLIAM SCHOOL
SCIENCE BLOCK
MECHANICAL SERVICES
PROPOSED ROOF PLANTROOMLAYOUT
SEPT 15 TV KG
141220/M/1700 P1
PRELIMINARY
11.09.15 KGPRELIMINARY ISSUEP1
Plantroom Schedule of EquipmentPlantroom Schedule of EquipmentPlantroom Schedule of EquipmentPlantroom Schedule of Equipment
ReferenceReferenceReferenceReference LocationLocationLocationLocation EquipmentEquipmentEquipmentEquipment Output/DutyOutput/DutyOutput/DutyOutput/Duty ManufacturerManufacturerManufacturerManufacturer ModelModelModelModel
ASHP 01ASHP 01ASHP 01ASHP 01 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
ASHP 02ASHP 02ASHP 02ASHP 02 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
ASHP 03ASHP 03ASHP 03ASHP 03 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
ASHP 04ASHP 04ASHP 04ASHP 04 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
ASHP 05ASHP 05ASHP 05ASHP 05 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
ASHP 06ASHP 06ASHP 06ASHP 06 PlantroomPlantroomPlantroomPlantroom Air Source Heat PumpAir Source Heat PumpAir Source Heat PumpAir Source Heat Pump 45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C45KW @ 50°C/45°C MitsubishiMitsubishiMitsubishiMitsubishi CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**CAHV-P500YA-HPB**
BS 01BS 01BS 01BS 01 PlantroomPlantroomPlantroomPlantroom Booster Pump Set C/W Break TankBooster Pump Set C/W Break TankBooster Pump Set C/W Break TankBooster Pump Set C/W Break Tank 2.55 L/sec2.55 L/sec2.55 L/sec2.55 L/sec Aquatech PressmainAquatech PressmainAquatech PressmainAquatech Pressmain AMV2-6-5** With APT2275 One Piece Break TankAMV2-6-5** With APT2275 One Piece Break TankAMV2-6-5** With APT2275 One Piece Break TankAMV2-6-5** With APT2275 One Piece Break Tank
EV 01EV 01EV 01EV 01 PlantroomPlantroomPlantroomPlantroom Expansion VesselExpansion VesselExpansion VesselExpansion Vessel 300 Litres300 Litres300 Litres300 Litres Aquatech PressmainAquatech PressmainAquatech PressmainAquatech Pressmain 300VR**300VR**300VR**300VR**
EV 02EV 02EV 02EV 02 PlantroomPlantroomPlantroomPlantroom Expansion VesselExpansion VesselExpansion VesselExpansion Vessel 60 Litres60 Litres60 Litres60 Litres Aquatech PressmainAquatech PressmainAquatech PressmainAquatech Pressmain 60VR**60VR**60VR**60VR**
P1P1P1P1 PlantroomPlantroomPlantroomPlantroom Pressurisation unitPressurisation unitPressurisation unitPressurisation unit -------- Aquatech PressmainAquatech PressmainAquatech PressmainAquatech Pressmain Micropack 'ETM' Unit**Micropack 'ETM' Unit**Micropack 'ETM' Unit**Micropack 'ETM' Unit**
P2P2P2P2 PlantroomPlantroomPlantroomPlantroom Pressurisation unitPressurisation unitPressurisation unitPressurisation unit -------- Aquatech PressmainAquatech PressmainAquatech PressmainAquatech Pressmain Micropack 'ETM' Unit**Micropack 'ETM' Unit**Micropack 'ETM' Unit**Micropack 'ETM' Unit**
P 01P 01P 01P 01 PlantroomPlantroomPlantroomPlantroom Primary Heating Circuit PumpPrimary Heating Circuit PumpPrimary Heating Circuit PumpPrimary Heating Circuit Pump 10.72 L/sec @ 32 Kpa10.72 L/sec @ 32 Kpa10.72 L/sec @ 32 Kpa10.72 L/sec @ 32 Kpa GrundfosGrundfosGrundfosGrundfos Magna 3 D 100-60F**Magna 3 D 100-60F**Magna 3 D 100-60F**Magna 3 D 100-60F**
P 02P 02P 02P 02 PlantroomPlantroomPlantroomPlantroom VT HTG Secondary Circulation PumpVT HTG Secondary Circulation PumpVT HTG Secondary Circulation PumpVT HTG Secondary Circulation Pump 2.156 L/sec @ 28.8 Kpa2.156 L/sec @ 28.8 Kpa2.156 L/sec @ 28.8 Kpa2.156 L/sec @ 28.8 Kpa GrundfosGrundfosGrundfosGrundfos Magna 3 D 40-60F**Magna 3 D 40-60F**Magna 3 D 40-60F**Magna 3 D 40-60F**
P 03P 03P 03P 03 PlantroomPlantroomPlantroomPlantroom CT HTG Circuit Pump For AHU Heater BatteriesCT HTG Circuit Pump For AHU Heater BatteriesCT HTG Circuit Pump For AHU Heater BatteriesCT HTG Circuit Pump For AHU Heater Batteries 6.66 L/sec @ 36 Kpa6.66 L/sec @ 36 Kpa6.66 L/sec @ 36 Kpa6.66 L/sec @ 36 Kpa GrundfosGrundfosGrundfosGrundfos Magna 3 D 65-120F*Magna 3 D 65-120F*Magna 3 D 65-120F*Magna 3 D 65-120F*
P 04P 04P 04P 04 PlantroomPlantroomPlantroomPlantroom Primary Heating Circuit PumpPrimary Heating Circuit PumpPrimary Heating Circuit PumpPrimary Heating Circuit Pump 2.12 L/sec @ 32 Kpa2.12 L/sec @ 32 Kpa2.12 L/sec @ 32 Kpa2.12 L/sec @ 32 Kpa GrundfosGrundfosGrundfosGrundfos Magna 3 D 32-100**Magna 3 D 32-100**Magna 3 D 32-100**Magna 3 D 32-100**
P 05P 05P 05P 05 PlantroomPlantroomPlantroomPlantroom HWS Return Secondary PumpHWS Return Secondary PumpHWS Return Secondary PumpHWS Return Secondary Pump 0.25 L/sec @ 25 Kpa0.25 L/sec @ 25 Kpa0.25 L/sec @ 25 Kpa0.25 L/sec @ 25 Kpa GrundfosGrundfosGrundfosGrundfos UPS 15-50B-130**UPS 15-50B-130**UPS 15-50B-130**UPS 15-50B-130**
WH 01WH 01WH 01WH 01 PlantroomPlantroomPlantroomPlantroom Hot Water CalorfierHot Water CalorfierHot Water CalorfierHot Water Calorfier 750 Litre750 Litre750 Litre750 Litre HamworthyHamworthyHamworthyHamworthy ST750**ST750**ST750**ST750**
5
6
7
8
9
10
\
\
\
\
\
FS
FS
FS
FS
FS
RWP
FS
FS
FS
FS
FS
FS
FS
FS
RWP
RWP
RWP
RWP
RWP
RWP
FS
FS
RWP
RWP
FW PPIC
CL 31.20
IL 29.29
FS
FS
FS
FFL 29.675
FFL 29.675
FFL 29.675
FW PPIC
CL 29.10
IL 28.42
FW PPIC
CL 29.50
IL 28.20
FW PPIC
CL 29.50
IL 27.98
FW PPIC
CL 29.50
IL 27.60
FW PPIC
CL 29.50
IL 27.40
RWP
FW PPIC
CL 29.50
IL 27.17
FW PPIC
CL 29.25
IL 27.10
SW PPIC
CL 28.80
IL 27.60
FW PPIC
CL
IL 26.78
FW PPIC
CL 29.20
IL 28.50
R
is
in
g
m
a
in
FW Pumping station
(2.41m rise, 26.77m length)
CL 29.83
IL 26.46
SW PPIC
CL 28.75
IL 28.15
SW PPIC
CL 29.20
IL 28.30
SW PPIC
CL 29.66
IL 28.47
SW PPIC
CL 29.50
IL 28.44
SW PPIC
CL 29.50
IL 28.20
SW PPIC
CL 29.50
IL 28.14
1
5
0
Ø
l
a
i
d
@
1
:
8
0
1
5
0
Ø
l
a
i
d
@
1
:
3
0
1
5
0
Ø
l
a
i
d
@
1
:
3
5
150Ø laid @ 1:35
100Ø laid @ 1:80
1
0
0
Ø
1
0
0
Ø
1
0
0
Ø
l
a
i
d
@
1
:
8
0
1
0
0
Ø
l
a
i
d
@
1
:
8
0
1
0
0
Ø
l
a
i
d
@
1
:
8
0
1
0
0
Ø
l
a
i
d
@
1
:
8
0
1
0
0
Ø
l
a
i
d
@
1
:
8
0
SW PPIC
CL 28.90
IL TBC
1
5
0
Ø
p
e
r
f
o
r
a
t
e
d
p
i
p
e
l
a
i
d
t
o
f
a
l
l
FW PPIC
CL 30.85
IL 29.20
1
5
0
Ø
@
1
:
1
1
5
1
5
0
Ø
l
a
i
d
@
1
:
8
0
FW PPIC
CL 29.50
IL 100Ø 27.31
IL 150Ø 27.26
1
5
0
Ø
l
a
i
d
@
1
:
8
0
1
5
0
Ø
l
a
i
d
@
1
:
8
0
S
W
C
e
l
l
u
l
a
r
S
t
o
r
a
g
e
8
m
x
8
m
x
0
.
8
m
d
e
e
p
S
L
2
7
.
8
0
I
L
2
7
.
0
0
RWP
SW PPIC
(Double sealed
recessed cover)
CL 30.540
IL 29.95
FFL 30.540
1
5
0
Ø
1
5
0
Ø
SW PPIC
CL 30.75
IL 29.95
Title
Project
Client
Status
Scale at A1
Drawn by Checked by
Date
Project ref Drawing no.
Revision
NCC
Proposed Extensions
Prince William School
Herne Road, Oundle
Science, Drama & Music
Block Drainage Plan
1:200 DGB MRL September 2015
For TenderS7426FA E100 T1
Rev DateBy
GENERAL
Do not scale from this drawing
This drawing is to be used in conjunction with all relevant drawings, specifications and details.
All dimensions are in millimetres and levels in metres unless noted otherwise.
Overall setting-out information to be taken from Architect's drawings.
NOTES
ALL FOUL STACK AND RAINWATER PIPE LOCATIONS ARE TO BE CONFIRMED BY OTHERS PRIOR TO COMMENCEMENT OF ANY WORKS.
ALL FOUL DRAINAGE TO SCIENCE BLOCK IS TO BE CLAY PIPEWORK.
CONTRACTOR SHOULD ALLOW FOR INSPECTION OF ALL EXISTING UNDERGROUND SERVICES ON SITE PRIOR TO COMMENCEMENT OFANY WORKS.
EXISTING DRAINAGE AND SERVICES TAKEN FROM UTILITY SURVEY BY AMETHYST SURVEYS LIMITED.
This drawing is to be printed in colour.
DRAINAGE
Allow for jetting of all existing sewers being retained.
All foul water connecting the stacks to the main drainage shall be 100mm Ø laid with a maximum gradient of 1 in 10 and minimum gradient
of 1 in 80 for connections with at least 1 WC. For connections with no WC then a minimum gradient of 1 in 40 must be used.
All storm water connections shall be 100mm Ø laid no flatter than 1 in 100 unless stated otherwise.
Drain and sewer systems shall be constructed in accordance with the design and with particular consideration of the following:
a. Health, safety and welfare of construction personnel and other people.b. methods of dealing with existing flows in part completed systems or when carry out works in existing drains and sewers.c. protection of the environment.
The construction and testing of drains and sewers shall be carried out in accordance with BS EN 1610.
All new manhole and PPIC covers in vehicular trafficked areas are to be grade D400.
KEY
Existing Foul Drainage to Remain
Existing Storm Drainage to Remain
Existing Combined Drainage to Remain
Existing Foul Drainage to be Removed
Existing Storm Drainage to be Removed
Proposed Foulwater Drainage
Proposed Foulwater Stack
Proposed Foulwater PPIC
Proposed Foulwater PCC Manhole
Proposed Foulwater Rising Main
Proposed Stormwater Drainage
Proposed Stormwater Rainwater Pipe
Proposed Stormwater PPIC
Proposed Stormwater Linear Drainage Channel
Proposed Stormwater Cellular Storage
Proposed LevelsFFL 30.540
FS
RWP
2
3
4
14
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
RWP
RWP
RWP
RWP
RWP
FS
FS
FS
New PCMH
CL 31.10
IL 300Ø 28.38
IL 150Ø 28.53
L
i
n
e
a
r
d
r
a
i
n
a
g
e
c
h
a
n
n
e
l
New PPIC
CL 31.05
IL 100Ø 28.70
IL 150Ø 28.65
SW PPIC
CL 30.65
IL 29.00
R
is
in
g
m
a
in
FW Pumping station
(2.41m rise, 26.77m length)
CL 29.83
IL 26.46
FW PPIC
CL 30.70
IL 28.65
FFL 30.730
1
5
0
Ø
l
a
i
d
@
1
:
1
0
0
Rev DateBy
GENERAL
Do not scale from this drawing
This drawing is to be used in conjunction with all relevant drawings, specifications and details.
All dimensions are in millimetres and levels in metres unless noted otherwise.
Overall setting-out information to be taken from Architect's drawings.
NOTES
ALL FOUL STACK AND RAINWATER PIPE LOCATIONS ARE TO BE CONFIRMED BY OTHERS PRIOR TO COMMENCEMENT OF ANY WORKS.
ALL FOUL DRAINAGE TO SCIENCE BLOCK IS TO BE CLAY PIPEWORK.
CONTRACTOR SHOULD ALLOW FOR INSPECTION OF ALL EXISTING UNDERGROUND SERVICES ON SITE PRIOR TO COMMENCEMENT OFANY WORKS.
EXISTING DRAINAGE AND SERVICES TAKEN FROM UTILITY SURVEY BY AMETHYST SURVEYS LIMITED.
This drawing is to be printed in colour.
DRAINAGE
Allow for jetting of all existing sewers being retained.
All foul water connecting the stacks to the main drainage shall be 100mm Ø laid with a maximum gradient of 1 in 10 and minimum gradient
of 1 in 80 for connections with at least 1 WC. For connections with no WC then a minimum gradient of 1 in 40 must be used.
All storm water connections shall be 100mm Ø laid no flatter than 1 in 100 unless stated otherwise.
Drain and sewer systems shall be constructed in accordance with the design and with particular consideration of the following:
a. Health, safety and welfare of construction personnel and other people.b. methods of dealing with existing flows in part completed systems or when carry out works in existing drains and sewers.c. protection of the environment.
The construction and testing of drains and sewers shall be carried out in accordance with BS EN 1610.
All new manhole and PPIC covers in vehicular trafficked areas are to be grade D400.
KEY
Existing Foul Drainage to Remain
Existing Storm Drainage to Remain
Existing Combined Drainage to Remain
Existing Foul Drainage to be Removed
Existing Storm Drainage to be Removed
Proposed Foulwater Drainage
Proposed Foulwater Stack
Proposed Foulwater PPIC
Proposed Foulwater PCC Manhole
Proposed Foulwater Rising Main
Proposed Stormwater Drainage
Proposed Stormwater Rainwater Pipe
Proposed Stormwater PPIC
Proposed Stormwater Linear Drainage Channel
Proposed Stormwater Cellular Storage
Proposed LevelsFFL 30.540
FS
RWP
Title
Project
Client
Status
Scale at A1
Drawn by Checked by
Date
Project ref Drawing no.
Revision
NCC
Proposed Extensions
Prince William School
Herne Road, Oundle
Sports Hall Block
Drainage Plan
1:200 DGB MRL September 2015
For TenderS7426FA E101 T1
0
0
1
1
0.2
1.0 0.75 0.5
0.3
0.2
1.0
0.75
0.5
0.3
0.2
1.0
0.750.50.3
0.2
1.0
0.75
0.5
0.3
0.2
1.0
0.75
0.5
0.3
0.2
1.0
0.75
0.5
0.3
0.2
0.3
1.0 - 0.5
0.2
0.2
0.3
0.3
0.2
0.3
1.0 - 0.5
Email: [email protected]
Tel:(01536) 403304, Fax:(01536) 403838
Website: www.buildingservicesdesign.co.uk
PRINCE WILLIAM SCHOOL
ELECTRICAL SERVICES
EXTERNAL LIGHTING ARRANGEMENT
FOR NEW BUILD ELEMENTS ONLY
141220/E/2255 I1 I1
BUS TURN
Y0
B0
E0
R0
T0
A1
29
22
6
New Build Works
Internal Alterations / Refurbishment
Cadets
S0Z0
J0Q0
W0
K0
Prince William School - E0147A
M0
G0
Nursery
U0
Mobile M540(to be removed)
Mobile M925(to be removed)
Mobile M549(to be removed)
Remove trees tocreate New Parking& improve coachturning area
B11
Modify Kerbline
Re-markBus Bays
Remove 11 No. car spaces & create 2 No. coach bays
B1
B2
B3
B4
B5
B6
B7
B8
B12
B16
B15
B10
B14
B17
B13
B18
B9
Modify Kerb toease turning
Create NewStaff Parking
Re-locateGreenhouse
P1
P9
P10
P13
P14
P17
P18
P23
P24
P38
P39P40
Changes to Parking11 No. Existing Spaces changed to 2 No. Bus Spaces40 No. New Staff Parking Spaces indicated(29 No. Spaces gained overall)
Site for Temporary Modular Buildings
A0Main Hall
English & ModernForeign Languages
Music & Drama
Design Tecnology
Dining
Library
F0Sports Hall& Changing
Sports Hall
X0ALC
New Gate &Security Fencing
New Gate &Security Fencing
New Gates & Security Fencing
Extend Roadwayfor EmegencyAccess Vehicle
ModularBuildings
Fitness, Sports& Changing
DanceStudio
Science
Maths
Humanities
New Gates &Security Fencing
Music
All Weather Pitch
New Gate &Security Fencing
New ScienceBlock
C0Drama
P.E. &Drama
AdminD0
AEN
Drama
GenPurpose
NewReceptionand Admin
support
1
2
3
4
5
6
7
9
10
11
12
13
14
Issue Purpose:
Rev Date/Checked
pHppHp a r c h i t e c t s
Drawn by: Checked by:
Scale @ A1: Date:
CAD ref: Dwg no.: Rev:
Expansion & Re-organisation of Prince William SchoolNorthampton County CouncilHerne Road, Oundle, Northants
Site Strategy Plan - Ground Floor
PRELIMINARYmtp ocb
1:500 November 2014
PWS01 4157/01 P4
P1: Preliminary Issue for Comment 20-11-14 mtpP2: Fencing revised in accordance with school comments 27-11-14 mtpP3: Updated buildings to reflect current scheme, footpath altered to entrance 05-01-15 jbP4: New Science Block footprint updated 14-01-15 mtp
N
SCALE 1:50020m0 10m