EPIC FOR POWER SUPPLY PROJECT THROUGH SUBMARINE CABLES FROM RAS LAFFAN TO HALUL
SITE ACCEPTANCE TEST FOR 132kV GIS
ClientQatar PetroleumDocument No.3433-HW08-2-05-0003-F08
ContractorLSC / L&TDate / Rev.05/03/2015 / Rev. - 1
LocationPage No 1 of 1
Equipment TagTest Date
Make
Name / Type of equipment
Serial Number
RatingPowerVoltage
Current
Measurement of the resistance of the main circuit1. Measurement of the resistance of the main circuitsApplying DC Current of 100 Amps to main circuit normally, the entire resistance of GIS shall be measured by voltage drop method.Amb. Temp:.oCHumidity:%Test pointMeasured value () @ Amb. Temp.Calculated value () @ 20oCFAT test value () @ 20oCResult
Measuring point followed as per FAT report. Resistance at 20 C = Rt (1+0.00393(20-t))Where: Rt = Resistance at ambient temperature, t = Ambient temperature2. Test Equipments usedSr. No.Equipment / InstrumentMakeEquip. Sr. No.Calibration due date
Remarks:
L&TVendorLSCQP
Signature
Name
Designation
Date