FireGuardWON-DOOR
The ORIGINAL horizontal slidingaccordion fire door.
TM
08 11 73/WONBuyLine 3726
3726_01 7/20/07 8:33 AM Page 1
2 WON-DOOR FIREGUARD
Fire Safety by Design
Setting the standard. . . . . 2
Typical applications . . . . . 3
Egress applications . . . . . 4
Non egress applications . . 5
Listings and approvals . . . 6
Standard features. . . . . . . 7
How to specify . . . . . . . . . 8
W O N - D O O RCORPORAT IONSalt Lake City, UT 84104
Phone : 800 -453 -8494w w w . w o n d o o r c o m
Founded in 1962, the Won-Door Corporation introduced the world’s most durableacoustically rated folding partition. In 1977 the company pioneered the development ofthe first-ever accordion type, fire rated horizontal sliding door. Today, more than 40years later, Won-Door remains the industry leader in the manufacture of fire doors andmoveable firewalls. Technology developed by Won-Door engineers continues toinfluence the building products and fire protection industries.
Setting the standardThe first to gain universal acceptanceThe development of the accordion type, horizontally sliding fire door – as manufacturedby the Won-Door Corporation – has had a profound influence on the model coderequirements that regulate their use, leading to its universal acceptance for use invirtually any means of egress application.
The first to be UL listedThe Won-Door FireGuard was the first accordion type fire door to successfully passnationally recognized tests to withstand the passage of fire. Won-Door FireGuardproducts are listed by Underwriters Laboratories Inc. (UL) for up to 3 hours as a rateddoor assembly and 2 hours as a moveable fire wall.
Still on the cutting-edgeOnly the Won-Door FireGuard uses astate-of-the-art microprocessor activatedcontrol system to guarantee reliabilityand enhance door function. Thistechnology provides almost limitlessopportunities for electroniccommunication, supervision, alarmactivation and more.
Engineered to fit YOUR needsBuilding codes encourage larger openings so why be limited by traditional forms ofopening protectives like roll-down shutters or swing-type doors? The custom-made
Won-Door FireGuard fire door canaccommodate virtually any opening.Capable of spanning wide openings andheights up to 28 feet* – even radialconfigurations are possible. Best of all,the single- or bi-parting doors areinstalled in the open position and fold tojust inches per foot behind pocket doorsthat you can design to blend with thesurrounding architecture.
* Increased custom heights available
Area separation between the old and new BWI Airport terminal.
Opening protective for a non-rated glass entranceto a tenant suite.
3726_02 7/20/07 8:34 AM Page 2
WON-DOOR FIREGUARD 3
08 11 73/WONBuyLine 3726
Superior performance, superior serviceMore than twenty branch sales offices and two Regional Sales Offices, plus a highlyskilled team of designers, engineers and field technicians, provide product service andsupport across the United States. Thoroughly knowledgeable about building code aswell as construction, our sales force can be relied upon to guide you every step of theway so you can get your ideas off the drawing board and into existence.
Typical applications include:
APPLICATIONElevator LobbySeparation in Type R Occupancy
PROJECTGold Country Hotel & Casino
LOCATIONOroville, California
PROJECTARCHITECTVarond Design GroupWon-Door FireGuardfire doors are used tocreate unobtrusive, yetcode-compliant,elevator lobbies thatare compatible withthe decor of this high-rise hotel andcasino in NorthernCalifornia.
The same Won-Door FireGuard fire doors are used in this elevator lobby/stairwell tosatisfy two code enclosure requirements – protection of a vertical opening as well aselevator lobby separation.
Area SeparationAtrium SeparationCorridor SeparationElevator Lobby SeparationHorizontal ExitsOccupancy SeparationSafe Areas of Refuge
Smoke BarrierSmoke and Draft ControlVertical Exit Enclosure SeparationSmoke CompartmentationStage Proscenium ProtectiveVertical Opening Protective
3726_03 7/20/07 8:34 AM Page 3
4 WON-DOOR FIREGUARD
Use Won-Door FireGuard in lieu of swing doors
Egress Applications
APPLICATIONVertical OpeningProtective
PROJECTArizona StateUniversity AthleticsFacility
LOCATIONTempe, Arizona
PROJECTARCHITECTDWL ArchitectsThe architect wantedthe natural light fromthe skylight of thisthree-story athleticbuilding to filterthrough colorfulbanners andilluminate a display ofathletic trophies andawards on the firstfloor. Using Won-DoorFireGuard fire doorsmade this possible.
Use Won-Door FireGuard in lieu of reducing the size of rated openings
"Fire doors" are not limited to just hollow metal swings. Won-Door FireGuard firedoors are code recognized and accepted anywhere an opening protective is required.
Rated openings in fire walls and fire barriers are permitted to be as large as 156 squarefeet, even in unsprinkled environments. The Won-Door FireGuard provides maximumdesign flexibility – beyond that of any other fire door or shutter.
3726_04 7/20/07 8:35 AM Page 4
WON-DOOR FIREGUARD 5
08 11 73/WONBuyLine 3726
Use Won-Door FireGuard in lieu of shutters
Non Egress Applications
APPLICATIONArea Separation
PROJECTProvo City Library
LOCATIONProvo, Utah
PROJECTARCHITECTMJSA ArchitectsA non-rated clerestoryjoins the renovatedhistoric 1892 buildingwith a large modernlibrary addition.Combining the old andthe new presented acode compliancechallenge. Since theaggregate squarefootage exceeded theallowable area definedin the current code, a2-hour fire barrier –the Won-DoorFireGuard – was usedto separate a largeportion of the historicrenovation. By takingadvantage of theapproved wide spanopening protectivecapabilities, historicambiance and codecompliance wereeasily accommodated.
Use Won-Door FireGuard in lieu of fire-rated glass
By redefining what is typically described as an “atrium” Won-Door FireGuard firedoors meet the required fire separation between adjacent spaces while eliminatingcostly atrium requirements such as sprinklers and smoke evacuation systems.
Won-Door FireGuard, the only microprocessor controlled fire door on the market, is thepreferred solution for lower cost and clear openings. Some models are approved for useas an ASTM E-119 compliant moveable fire wall in non-egress openings in fire barriers.
3726_05 7/20/07 8:35 AM Page 5
6 WON-DOOR FIREGUARD
Listings & Approvals
APPLICATIONElevator LobbySeparation/AccessControl
PROJECTSan DiegoInternational Airport
LOCATIONSan Diego, California
PROJECTARCHITECTSPGAThe Won-DoorFireGuard fire doorcan be used to isolateand control a securitybreach as well as stopthe spread of fire andtoxic fumes.
Building Code Reference 1008.1.2 exc #5 1008.1.2 exc #6 7.2.1.14
Performance Criteria 1008.1.3.3 1008.1.3.3 7.2.1.14
APPLICATIONS 2006 NFPA 1012006 IBC1
1Any application without occupant load limitation except H occupancies.
2003 IBC1
MODELNUMBER
MAX. OVERSIZELABEL SIZE
TESTCRITERIA
HOURLYRATING
U.L. FILENUMBER
SINGLE ORBI-PARTING
28'0" (h)Unrestricted (w)
20 minutesBoth
Available
28'0" (h)Unrestricted (w)1 hour
BothAvailable
28'0" (h)Unrestricted (w)1 1/2 hours
BothAvailable
28'0" (h)Unrestricted (w)3 hours
BothAvailable
N.A.2 hourSingle Parting
Only
N.A.1 hourSingle Parting
Only
Door AssemblyFireGuard FG20
Door AssemblyFireGuard FG603
Door AssemblyFireGuard FG903
Door AssemblyFireGuard FG1803
Wall AssemblyFireGuard MFW24
Wall AssemblyFireGuard MFW14
Automatic ClosingSystem5 N.A.
Can be used on allWon-Door FireGuard models
listed up to 3 hours
Can be usedfor both
3 Each door assembly, when required, complies with UL1784; and with the exception of FG20, can be labeled as Temperature Rise (TR). See ESR1394.4 MFW - Movable Fire Wall5 This listing applies for use on all Won-Door FireGuard models.6 Excluding cotton pad test.
ICC Research Rep. ESR-1394
State of California Door Assemblies MFW 3261-357:001; 1080-357:100
San Francisco Dept. of Public Works 387W18.2
City & County of Denver M-8275
State of Wisconsin 811003
City of New York Listed Assemblies MEA-127-79-M; MEA-124-79M; MEA-383-85-MOversized Assemblies MEA-377-86-M; MEA-70-87-M; MEA-69-87-M
Means of Egress Applications
Product Information
Other Won-Door FireGuard Listings and Reports
U.L. 10B(ASTM E-2074)6
U.L. 10B(ASTM E-2074)6
U.L. 10B(ASTM E-2074)6
U.L. 10B(ASTM E-2074)6
U.L. 263(ASTM E-119)
U.L. 263(ASTM E-119)
U.L. 864
R6799
R6799
R6799
R6799
R12272
R12272
E92690
3726_06 7/20/07 8:36 AM Page 6
WON-DOOR FIREGUARD 7
08 11 73/WONBuyLine 3726Standard Features
1. Exiting hardwareExiting hardware can be configured andplaced where appropriate, including toaccommodate persons with disabilities.
2. Leading edge obstruction detectorThe door will stop upon contact with anobstacle, pause, then re-seek the closedposition.
3. LeadpostDoors can be prevented from closing andcaused to re-open a preset distance byapplying light pressure to the leadpost.
4. Single- or bi-parting doorsA single door slides across the openinginto a recessed jamb located on theopposite wall. The spanning of largeropenings is possible by using the bi-parting configuration. The storagespace is then divided on each side of the opening.
5. Pocket cover doorPocket cover doors can be designed byyou to blend with any decor.
6. Track and trolley systemThis system allows the door toaccommodate wide span openings.Curved configurations are also possible.
7. Thermal lockout feature Ambient temperature at the door ismonitored and the operating device isautomatically disabled if the environmentbecomes untenable.
8. MicroprocessorA control unit located in the door’sstorage pocket provides continuousmonitoring of door status.
9. ElectronicsThe Won-Door FireGuard is a completelyelectronically supervised system utilizingsolid state circuitry as well as a backupDC power supply.
10. Floor gasket and fire linerA tight-fitting floor gasket and fiberglassliner provide an impenetrable barrieragainst the spread of smoke and flames.
11. Modular designModular design provides for in-placereparability using basic tools.
12. MaterialsDoor panels are constructed of 24-gaugesteel with a standard finish of platinumenamel. Optional colors are available fora nominal fee.
Standard features of the Won-Door FireGuard:
1
2
6
7
8
9
10
11
3726_07 7/20/07 8:36 AM Page 7
8 WON-DOOR FIREGUARD
Specifying the Won-Door FireGuardWhyWithout the use of floor tracks or exposed hardware of any kind, these fire doors are the most trouble free product in the fire protection industry.
• Design flexibility
• Custom made to fit your design without compromising code requirements
• Lower maintenance costs
• Modular construction means in-place reparability
• No parts exposed to wear and tear
• Fewer service calls
• Can be reset by building management by simply pushing a button
• Backup power supply so door operates even during a power outage
• Increase useable space
• Code compliant
• Access control options available
• Often cost less than other solutions
How• Our Design Manual containing a complete summary of architectural details and
specifications is available for free from your local Won-Door representative. Or call800-453-8494 to order.
• The Won-Door FireGuard Product Catalog prepared to standard CSI format for usewith most CAD systems is also available for download from our website atwww.wondoor.com
• Additionally, videos, in a variety of formats, can be downloaded from our online video archive. These informative short movies cover a range of topics from typicalapplications and product demos to technical topics and code compliance.
Learn and earnAIA members can learn more about Won-Door products and earn credits byparticipating in a Won-Door seminar either online or in person. Contact your localrepresentative for more information or visit www.wondoor.com and click on Continuing Education.
For more information contact your local representative.
Fire Safety by Choice
W O N - D O O RCORPORAT IONSalt Lake City, UT 84104
Phone : 800 -453 -8494w w w . w o n d o o r c o m
see us at
.com
3726_08 7/20/07 8:36 AM Page 8