SATEC’s Branch-Feeder-MonitorTM (BFM) is our new generation energy management meter designed for energy and demand monitoring, load profiling, and multi-tariff (TOU), multi-client billing applications. Each BFM monitors up to 12 three-phase circuits, 18 two-phase circuits, 36 single-phase circuits, or any combination thereof. This flexibility makes the BFM especially suitable for multi-tenant facilities such as residential and office buildings, shopping malls, hotels, hospitals, universities, supermarkets and data centers. Ideal for both new and retrofit projects, the BFM’s compact size is designed to easily fit into existing panel boards, thus eliminating expensive retrofitting costs or allocating extra space for the instrument. The BFM provides the ideal solution for sub-metering applications and is designed to answer the monitoring and billing needs of multi-tenant facilities. The BFM monitors up to 36 current inputs via external sensors. Each sensor measures and reports the current and power consumed by each of the branch circuits at the panel board. For billing purposes, one can define single or multiple circuits for each customer. This flexibility allows one to simply reassign circuit groups to changing customers without complicated wiring changes. Further, the building owner saves time and effort by monitoring up to 36 circuits directly at the main panel board or load center. The BFM’s programmable alarm system enables one to take preventive maintenance steps to avoid unnecessary outages. SATEC also provides
split-core current transformers and wireless communication options to simplify installation.
Class 1 Accuracy - including CTs 64 samples per cycle 3 Voltage Inputs (up to 480VAC panels) 36 Current Inputs Measuring range up to 400A Split Core CT (100A & 400A) Time-of-Use(TOU) metering Harmonics and Vectors Integrates with eXpertManager
system and eXpertPower service Multi-circuit energy reading 8 MB Flash data storage Event Log 120-day daily load profile Real-time Clock Built-in RS485 (COM 1) Optional COM 2 Ethernet, modem, RS485, external 900
MHz or 2.4 GHz RF wireless Compact Design
FEATURES & BENEFITS ANSI C12.16 and IEC 62053-21 compliance Provides the complete set of energy and
demand data for billing purposes Easy installation into existing electric panel
boards thanks to its compact design Multi-point energy and demand load profiling Communications Ports: standard RS485,
optional second RS232, RS485, Ethernet, wireless RF Modem (ZIGBEE) or 56K Modem
Communications Protocols: Modbus TCP/RTU/ASCII
Flash memory data storage requires no battery backup
Interval data and Time-of-Use (TOU) capability
Advanced and user friendly options for data access: ♦ Optional LCD display for local data access ♦ PAS: free configuration software support ♦ eXpertManager PQ SCADA system access, or
eXpertPowerTM: Internet access to data, from anywhere, anytime, featuring highly advanced features for total energy management and billing
Real-time waveform monitor feature allows for quick and easy installation verification
Model CT126 Single CT 100A, 600V
Inner Diameter 12 mm Cable length 2.5 meters
Model CT4A6 Single CT 400A, 600 V Inner Diameter 26 mm Cable length 2.5 meters
Model CT3CT 3CT Strip 100A, 600V
Up to 12 units per BFM Cable length 2.5 meters
Model CT236 Single CT 100A, 600V Large Hole
Inner Diameter 23 mm Cable length 2.5 meters
BFM136 Branch-Feeder-Monitor TM
The BFM provides a variety of electrical data such as per phase voltage and current, kW total, kVAR total, kVA total, PF total, Freq, kWH, kVARH, kVAH, demands and maximum demands. It also captures billing usage data in two formats, fixed rate or TOU based. The data can be viewed on the BFM’s LCD display (BFM136) or transferred via communication to software applications for more sophisticated analysis. The BFM allows easy integration with Energy Management or SCADA systems via the industry standard Modbus RTU/ASCII protocols. Through communications, one can access all measured parameters remotely and perform device configuration. Billing Tariffs vary according to the type of consumers - residential, commercial or industrial, and the amount of electricity consumed. The BFM’s TOU feature provides data in compliance with the rates set by the local electricity supplier and in accordance with the specified voltage level – high, medium, or low. The BFM provides information on peak demands and allows for the assessment of penalty if the power factor falls below a level defined by the local authority. PAS Software, eXpertPowerTM e-Service,and eXpertManagerTM system The BFM is bundled with PAS, our easy to use software designed for configuring, viewing and analyzing data from our instruments. For more advanced options, eXpertPowerTM, SATEC’s web-based energy management e-service, andeXpertManager provides real-time visibility and reporting capability for the entire power systemsover the Internet. PAS Features Included with every BFM Easy to use remote configuration software Supports off-line programming to allow easy
downloading of a standard configuration to multiple instruments
Supports scheduled polling, viewing of real-time data, and the automatic retrieval of load profile.
Bill Comparison via eXpertPowerTM The BFM provides eXpertPowerTM all the necessary data to perform bill comparisons. Facilities with several utility meters can utilize eXpertPowerTM to combine meters for billing, resulting in significant cost savings. Data Management with eXpertManager The BFM136 integrates with SATEC'seXpertManager system to provide a real timedata acquisition and control system that allowsfacility operators to manage data.
The BFM can be configured to monitor 12 3-phase circuits, 18 2-phase circuits, 36 single-phase circuits or any combination thereof. The sub-meter configuration is performed through an intuitive interface with the PAS software. Virtual totalization sub-meters A minimum of 4 totalization sub-meters Allows for automatic totalization of multiple
sub-meters that belong to the same tenant BFM Measurement Parameters Once the sub-meters have been properly configured, each sub-meter provides the following measurement parameters: Real-time ♦ Voltage and Current per sub-meter ♦ Watts per phase and total sub-meter ♦ VARs per phase and total sub-meter ♦ VA per phase and total per sub-meter ♦ PF per phase and total per sub-meter ♦ Frequency
Demands and Max. Demands ♦ V and I per phase ♦ Total Watts per sub-meter ♦ Total VARs per sub-meter ♦ Total VAs per sub-meter
Energy Measurements ♦ Wh Import per sub-meter ♦ VARh Import per sub-meter ♦ VAh per sub-meter
TOU Daily Load Profile ♦ 8MB of Flash memory ♦ Energy and Demand Tariff Profile ♦ 120-day capacity
Time-of-Use (TOU) User-friendly programmable TOU schedule 4 energy / demand registers x 4 tariffs 4 seasons x 4 types of days 8 tariff changes per day
Sub-meter Configuration
TOU Calendar
TOU Daily Profiles
BFM136 Branch-Feeder-MonitorTM
Load Profile and Event Log 8MB of non-volatile memory 1 Event Log 120-day daily load profile Daily energy profile for each tariff and total Daily maximum demand profile for each
tariff and total Daily summary profile of all tariffs Separate for each sub-meter
User Defined Setpoint Alarms 4 setpoints per sub-meter ♦ Over / Under Voltage ♦ Over / Under Current ♦ Over / Under Frequency ♦ Over kW Imp ♦ Over kVA
Setpoints System
Power Quality Real-time waveform monitor Installation and wiring verification Harmonics and Phasor analysis for V, I and
Power via PAS Separate for each sub-meter
Real-time Waveform Monitor
Front Panel Display (BFM136) 2 x 16 character backlit LCD display Auto-scroll feature 4 push buttons
Model CTSC400 400A Split core CT, 600V Up to 36 units per BFM Cable length 6 feet - JAN 09
Communications 2 independent and simultaneous connections Unique “Assignable Register Map” Firmware upgrade via communications,
eliminating chip replacement COM1
Optically isolated RS485 port Isolation: 2000VAC (IEC1010-1) Selectable baud rate to max. 115,200 Protocols supported: Modbus RTU/ASCII
COM2 Optional RS232 port
Isolation: 2000V RMS Selectable baud rate to max. 115,200 Protocol supported: Modbus RTU/ASCII
Optional RS485 port Isolation: 2000V RMS Selectable baud rate to max. 115,200 Protocol supported: Modbus RTU/ASCII
Optional Ethernet Transformer-isolated 10/100BaseT Connector: RJ45 Protocol supported: Modbus TCP
Optional Dial-up Modem Transformer-isolated 56KB modem Connector: RJ11 Protocol supported: Modbus RTU/ASCII
Optional RS485 port with eXternal Trio unit 900 MHz, 1 Watt RF Protocol supported: Modbus RTU
Real-time clock
Accuracy: 1 minute per month @ 25°C Time retained for a minimum of 24 hours,
1 week typical upon loss of power Accuracy Voltage: 0.3% reading + 0.05% F.S. Range: 0 to 600V Current: 0.5% reading + 0.05% F.S. (1% to 100% F.S.) Range: 0 to CT Primary Starting Current: 0.1% F.S. Frequency: 0.02% reading (50 or 60 Hz) PF: 1.0% F.S. (|PF| ≥ 0.5) Watts: 1.0% reading + 0.02% F.S. (|PF| ≥ 0.5) -120.00 to +120.00 kW VARs: 1.0% reading + 0.02% F.S. (|PF| ≤ 0.9) -120.00 to +120.00 kVAR VAs: 1.0% reading + 0.02% F.S. (|PF| ≥ 0.5) 0 to 120.00 kVA Wh: Class 1S as per IEC 62053-21: 2003 0 to +99,999,999.9 kWh VARh: Class 1S as per IEC 62053-21:2003 0 to +99,999,999.9 kVARh VAh: Class 1S as per IEC 62053-21: 2003 0 to 99,999,999.9 kVAh
INPUT SPECIFICATIONS Voltage: Direct Input: 120 / 240 /480 VAC Max. Voltage: 320 VLN / 544 VLL PT Ratio: 1.0 Range: 0-600 VAC Burden: < 1.5W per phase Overload: 1000 VAC continuous 2000 VAC for 1 second Isolation: 2.5kV RMS, 60Hz, 1 min. Leakage current: < 0.005A per circuit Impulse: 1.2/50uS 6kV Wire size: 10 AWG max. Current: Input ratings: 50A nominal/100A max. Test current: 15A Overload: 3000A for ½ cycle @ 60Hz Burden: < 1VA per phase Isolation: 2.5kV RMS, 60 Hz, 1 min. CT Ratio: 1-100 Range: 0-10000A Standards of Compliance: UL Approved CE EMC: 89/336/EEC as amended by
92/31/EEC and 93/68/EEC LVD: 73/23/EEC as amended by
93/68/EEC and 93/465/EEC EN Harmonized standards to which
conformity is declared: EN55011: 1991; EN 50082-1: 1992; EN61010-1: 1993; A2/1995 EN50081-2: 1994 Generic Emission
Standard – Industrial Environment EN50082-2: 1995 Generic Immunity
Standard – Industrial Environment EN55022:1994 Class A EN61000-4-2: 1995 Electrostatic
Discharge EN61000-4-4: 1995 Electrical Fast
Transient EN61000-4-8: 1993 Radio Frequency
Electromagnetic Field, Amplitude Modulated.
ENV50140: 1995 (200Hz) Radio Frequency Electromagnetic Field, Pulse Modulated
ENV50204: 1995 (900MHz) ENV50141: 1993 Radio Frequency
Common Mode, Amplitude Modulated ANSI C12.2 1998 IEC 62053-21 Class 1S
MISCELLANEOUS Warranty: 3-Year limited warranty Environmental Conditions Operating Temp.: -20 to +60°C (-4 to 140°F) Storage Temp.: -25 to +80°C (-13 to 176°F) Humidity: 0 to 95% non-condensing Model TRIO JR900-00-001-E00 900 MHz ISM Band 1 Watt, Half Duplex
Model CTSC100 100A Split core CT, 600V
Up to 36 units per BFM Cable length 6 feet
BFM136 Options CALIBR
50 60
COM2 –0 R2 R4 MODETH RFM
MOUNT0 D
ACCESSCT12CT23CT4ACTSCCT3C
CTSC400 Single Split Core CT 400A, 1 x 1.85 inches; Qty: 1-36 *The CTconnect
EXAMPLBFM136-6 SATEC Integrated Solutions 10 MilltoUS Toll FTel: +1 (Fax: +1 Email: sahttp://w
Revisio
B
6
:
RATION 50Hz 60Hz
– second COM porNone RS232 RS485
D 56K modem Ethernet
RF Modem (future) TING
Wall mount DIN
SORIES* 26 Single CT 100A36T Single CT 100AA6 Single CT 400AC100 Single Split CoCT 3 CT Strip 1” (
T assembly includestor on one end for e
ES: 60Hz-ETH-D
own Court, UnioFree: 1-888-657-2832(908) 686-9510 (908) [email protected]
on Date: Octobe
FM Branch-Fee
rt
A, 12 mm; QTY: 1-3A, 23 mm; QTY: 1-3A, 26 mm; QTY: 1-3 re CT 100A, 0.6 25mm) between CT
s a 6-foot (2 meterseasy connection.
on, NJ, 07083 0
20
Future 900MHz
Model M56K Mod
er 2008
RS485
RF
RS485
DIAL-UPMODEMTELEPHON
eder-Monitor TM
36 36 36
in.; Qty: 1-36 T centers. QTY 1-12
s) long color-coded
MOD dem
BFM
Tx
M
2
wire cables with sn
Optional
M136 B
RS485
RS2
RS485
ETHE
Rx
nap
Model R2 RS232
Model ETH Ethernet
COM 2 Com
Branch-
32
ERNET
mmunicati
-Feeder-
+
No COMoption
Model RRS485
ion add on
-Monito
RS485
NONE
RS485
RS485/422
M 2 n
R4 5
port
or TM