Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region
www.EmersonNetworkPower.eu/400VDC
September 2015
Mirna Smrekar; Product Line Manager EMEA
2
Case Study Overview
Data center with Solar integration
• Small scale data center in 2N concept powered by 400VDC
• 400VDC used with integration of Solar power
• Feeding IT equipment, cooling and lighting
Traditional Data center with AC&DC
• 2N data center concept
• AC&400VDC architectures built in parallel
• Future proof data center design
Traditional Telecom site
• 400VDC used as „transport voltage”
• 400/48VDC conversion close to -48VDC load
• Maximize copper savings and floor space
High Performance Computing
• Minimum heat load
• Efficient DC power distribution within a cabinet
• Scalability with 15kW modules
Different Market Drivers Behind Every Implementation
3
Drivers for Implementation
Data Centers Telecom
Simplicity of Power Chain
Redundancy & Scalability
Integration of Renewables
Copper Savings
Installation Cost Saving
Centralized Battery
Future
Proof
High Performance Computing
Maximize Efficiency
Minimize Copper Content
4
Case Study 1 - Bachmann Demostration site for DCC+G Project Data center with 2N concept and integrated solar panels in
same system All components in the system are fed from 400VDC (IT
equipment, lighting, cooling)
5
Case Study 1 - Bachmann 400VDC rectifiers, Solar MPPT converters and batteries are
integrated in same cabinet
NetSure 4015
6
Case Study 1 - Bachmann
Emerson Central Rectifier, DC Solar MPPT
controller and batteries
IT cross connection
cabinet
380VDC server cabinet (HP servers)
AC server cabinets
380VDC inverters
Philips DC Lighting
3rd place prize for energy efficiency at the Future-Thinking Data Center Conference in Darmstadt in April 2015
7
Case Study 2 - Coromatic Coromatic as integrator provided energy efficient data center
inspired by Green.ch project to Scandinavian company Separate AC and 400VDC power paths are designed with 2N
redundancy with 250kVA per side in AC UPS and 120kW per side in 400VDC of installed power
8
Case Study 2 - Coromatic IT racks were installed with AC power strip on one side and
400VDC power strip on the other side to ensure flexibility Initial load include 80kW of AC power load (cooling, lighting, IT
equipment, auxiliary loads) and 30kW of 400VDC powered loads (HP and Cisco servers)
Future expansion plans 240kW in 400VDC and 300kW of AC power to be installed
9
Case Study 3 – African Telecom Provider 2 x 120kW 400VDC Power systems are installed in A+B
configuration and 30 minutes of centralized battery backup to ensure support of up to 2000A of -48VDC end loads
Distribution lengths between batteries and 400VDC power system to 400/48V DC/DC distribution can vary up to 77 meters
10
Installation is done on multiple floors with batteries and 400VDC power system being positioned on ground floor
Compared to traditional -48VDC topology for this site customer achieved 25% savings in Capex using 400VDC as „transportation voltage”
Majority of Capex savings is based on copper and installation simplicity using 400VDC distributed over long power lines
Case Study 3 – African Telecom Provider
400VDC w/ 400/48V Conversion
Comparable -48V Installation
Product
Installation 25% savings
11
Case Study 4 - RSC
Emerson with partnership with RSC installed 2 sites:
Saint Petersburg Polytechnic University (SPbPU)
o Polytechnic RSC PetaStream - 1st in Russia by energy efficiency level with 2,401.4 Mflops/Watt
o #8 in local Top50 supercomputers list for Russia/CIS
o Feed from NetSure 9500 120kW Power system and using Vicor 400/12V DC/DC converters
Joint Supercomputing Center of Russian Academy of Sciences (JSCC RAS)
RSC PetaStream - The first project on Intel® Xeon Phi™ 7120D in Russia and CIS
Feed from NetSure 4015 30kW Power system and using Vicor 400/12V DC/DC converters
12
Case Study Summary End User Application Typical
Power Type Primary 400VDC
Driver Power Distribution
Bachmann Data center AC Power
Elimination of conversion stages; integration of solar
power
400V DC distribution to 400V DC loads; AC loads
powered via inverters
Scandinavian Company Data Center AC Power Elimination of
conversion stages
Parallel power paths distributing both 400V DC
and AC power
African Telecom Telecom -48V DC
Cable reduction: cost and cable management
400V DC distribution to -48VDC conversion and
loads
SPbPU supercomputer center & JSCC RAS upgrade
HPC AC Power Reduce losses in
copper and connectors
400V DC distribution to 12V DC conversion and
loads
13
Conclusion NetSure™ 4015
NetSure™ 9500
NetSure™ 701 w/ 400V DC Input
NetSure™ 5100 w/ 400V DC Input
IP 55 Rectifier/Converter
400V DC Power Systems
400/48V DC/DC Converter Systems
Commercial deployments in Europe and Africa demonstrate increasing maturity and acceptance of 400V DC power as availability of 400VDC
equipment increases daily
14
Questions?