Transcript
Page 1: Ex Cable Glands installation: PAPD - Helyum Elektrikhelyumelektrik.com/shared/dosyalar/urunler/tr_urun_5803afdfd49b5.pdf · Ex Cable Glands CABLE GLANDS FOR ... ON REqUEST ACCESSORiES:

YOUR PARTNER FOR SAFETY

Since 1961

Explosion Proof Electrical Equipment

PAPD

PAPD

Feam Catalogue 03 - 1

Ex Cable Glands

CABLE GLANDS FOR ARMOURED, LEAD SHEATHED CABLES

ON REqUEST ACCESSORiES: •Locknuts,Gaskets,PVCShrouds,EarthingTags,Sealing(SeeACCESSORIbulletin)

Mechanical characteristicsBody/cap OT-58marinebrass(ON)-AISI-316Lstainlesssteel(IX)

Finishes fullnickelplatingthreatment(brassmaterialonly)

Rubberrings EDPMrubber-50-60shorehardness

O-ring siliconrubber-60shorehardness

Skidwasher nylon6

Chamberforsealing OT-58marinebrass("R"versiononly)

installation: hazardousareas-Zone1/2(Gases)-Zone21/22(Dusts) Classification: GroupII-Category2G2D

APPLiCATiON •FORSTEELWIREARMOUREDCABLES(SWA)FORSTEELTAPEARMOUREDCABLESANDFORLEADINNERSHEATHCABLES

•DOUBLECOMPRESSIONTYPEFORINDOORANDOUTDOORUSE

•PROVIDEDARMOURCLAMPINGUSINGCLAMPINGARRANGEMENTSSUITABLEFORALLARMOURWIRE/BRAIDTYPES

•INTERNALLEADDEVICEFORELECTRICALBONDOFCABLELEADINNERSHEATH

•DOUBLECOMPRESSION-UNDERARMOURANDOVERALLOFARMOURCABLE(INNERANDOUTERSEALING)

•SEALINGWITHPROPERRESININTO"CHAMBEROFSEALING"(ONBARRIERTYPEVERSION"R"ONLY)

(1) EDPM-60INTERNALRUBBERRINGS - (2) SILICON-60INTERNALRUBBERRINGS

CABLE GLANDS

ATEX 94/9/EC iEC Ex iNMETRO GOST-R (RTR/RTN) GOST-K

EXECUTiONII2GExeIICII2GExdIICII2DExtDA21

ExeIICGbExdIICGbExtbIIICDb

ExeIICGbExdIICGbExtbIIICDb

ExeIICGbExdIICGbExtbIIICDb

ExeIICGbExdIICGbExtbIIICDb

AMBiENT TEMPERATURE

-40°C÷+90°C (1)-60°C÷+180°C (2)

-40°C÷+90°C (1)-60°C÷+180°C (2)

-40°C÷+90°C (1)-60°C÷+180°C (2)

-40°C÷+90°C (1)-60°C÷+180°C (2)

-40°C÷+90°C (1)-60°C÷+180°C (2)

PROTEC. DEGREE IP66/68 IP66/68 IP66/68 IP66/68 IP66/68

CERTiFiCATE REF. INERIS07ATEX0001X IECExINE13.0018X CEPEL12.2177X POCCIT.ME92.B02924 No.07/43-269

RULES OF COMPLiANCE

EN60079-0:2004;EN60079-1:2004;EN60079-11:2006;EN61241-0:2004;EN61241-1:2004

IEC60079-0:2011;IEC60079-1:2007;IEC60079-7:2006;IEC60079-31:2008

ABNTNBRIEC60079-0:2008;ABNTNBRIEC60079-1:2007;ABNTNBRIEC60079-7:2008;ABNTNBRIEC60529-0:2009;

ГОСТРМЭК60079-0:2011;ГОСТРМЭК61241-0:2007;ГОСТРМЭК61241-1:2004;

ГОСТР51330.0/1/8/14-99ГОСТРМЭК61241-1-1-2002

ATEX / iECEx / GOSTNEC 505 NEC 500Class i Class i Class ii Class iii

Zone 0 1 2 20 21 22 Zone 0 1 2 Division 1 2 1 2 1 2X X X X X X X X X X X

Page 2: Ex Cable Glands installation: PAPD - Helyum Elektrikhelyumelektrik.com/shared/dosyalar/urunler/tr_urun_5803afdfd49b5.pdf · Ex Cable Glands CABLE GLANDS FOR ... ON REqUEST ACCESSORiES:

YOUR PARTNER FOR SAFETY

Since 1961

PAPD

13121

32

45

14

67

8

9

1011

PAPD# 01 M ONPAPD# 03 N iX

2 - Feam Catalogue 03

ExCableGlands

PAPD Cable gland selection table

CABLE GLAND ORDERiNG EXAMPLES

LEGEND

= PAPD#01MON (NON-BARRIERCABLEGLANDNICKELPLATEDBRASSISO-M20THR.)

= PAPD#03NiX (NON-BARRIERCABLEGLANDSTAINLESSSTEEL1”NPTTHR.)

(1) CABLE GLAND TYPE/MODEL PAPD# = NON-BARRIERCABLEGLAND - PAPD-R# = BARRIERCABLEGLAND (2) THREADiNG M = ISOMETRICpitch1,5mm - N = NPT(ANSI/ASMEB1.20.1) - G = UNi iSO-228(3) CABLE GLAND MATERiAL ON = NICKELPLATEDMARINEBRASS- iX = AISI-316LSTAINLESSSTEEL

REMARK: Due to the development of the national and international specifications and of the technology, the above technicalcharacteristicsshowedonthisbulletincanbeconsideredasbindingonourconfirmationonly.

PAPD DiMENSiONAL

SiZE

*Chamberwillbefilledwithsealingwhencableglandiscompletelyassembled.

1 BODY

2-3-4 INNERSEALINGRINGFORARMOUREDCABLE

5 ARMOURCLAMPINGCONE

6 ARMOURCLAMPINGRINGFORARMOUREDCABLE

7 GLANDBARREL

8-9 OUTERSEALINGRING

10 ANTIRUBBINGWASHER

11 GLANDNUT

12 O-RING(ONLYFORMETRICAL)

13 *CHAMBERFORSEALING("R"VERSIONONLY)

14 LEADWASHER

CODE ENTRY THREAD SiZE DiA. UNDER ARMOUR

OUTER SHEATH DiA.

HEXAGON MATERiAL

(1)METRiC

(2)NPT

(2)UNi iSO 228

(2)min [mm]

max [mm]

min [mm]

max [mm] [mm] (3)

PAPD#PAPD-R# 01 iSO-M20 1/2"NPT 1/2"

3,5 6,0 10,0 15,032,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON6,0 8,5

14,0 19,08,5 11,0 iX

PAPD#PAPD-R# 02 iSO-M25 3/4”NPT 3/4”

8,5 11,0 15,0 20,036,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON11,0 13,5

19,0 24,013,5 16 iX

PAPD#PAPD-R# 03 iSO-M32 1”NPT 1”

13,0 16,0 20,0 26,045,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON16,0 19,0

25,0 31,019,0 22,0 iX

PAPD#PAPD-R# 04 iSO-M40 1 1/4”NPT 1 1/4”

19,0 22,0

53,0NiCKEL PL.BRASSSTAiNLESS STEEL

ON22,0 25,0

25,0 28,0 iX

PAPD#PAPD-R# 05 iSO-M50 1 1/2”NPT 1 1/2”

22,0 25,0

61,0NiCKEL PL.BRASSSTAiNLESS STEEL

ON25,0 28,0

28,0 31,0 iX31,0 34,0

PAPD#PAPD-R# 06 iSO-M63 2”NPT 2”

34,0 37,0

71,0NiCKEL PL.BRASSSTAiNLESS STEEL

ON37,0 40,0

40,0 43,0 iX

PAPD#PAPD-R# 07 iSO-M75 2 1/2”NPT 2 1/2” 84,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON

iX

PAPD#PAPD-R# 08 iSO-M90 3”NPT 3” 101,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON

iX

PAPD# PAPD-R# 09 iSO-M100 4”NPT 4” 126,0

NiCKEL PL.BRASSSTAiNLESS STEEL

ON

iX

M N G

M N G

M N G

M N G

M N G

M N G

M N G

M N G

M N G

58,0 66,066,0 72,072,0 78,078,0 84,084,0 90,0

26,0 32,0

31,0 37,0

34,0 40,0

30,0 37,0

36,0 43,0

40,0 47,0

42,0 48,0

47,0 53,0

50,0 56,052,0 58,0

58,0 64,0

61,0 67,065,0 72,0

71,0 78,0

74,0 81,0

81,0 88,0

88,0 96,0

96,0 104,0

52,0 55,056,0 59,057,0 60,060,0 63,063,0 66,0

40,0 43,043,0 46,046,0 49,049,0 52,0