HYUNDAI Vacuum Contactors are designed and manufactured
for frequent switchings, especially taking into account safety and quality assurance.
They are suitable for switching and controlling squirrel cage
and slipring motors, medium voltage loads and resistance furnaces,
and capacitors and transformers.
Vacuum Contactor
[ C O N T E N T S ]
Features / Operation and Application 04 ⅠRatings 05
Technical Data 06 ⅠAccessories 10 ⅠCircuit Diagrams 11
Dimensions 12 ⅠOrder Information 18
Vacuum ContactorVC
4 HYUNDAI HEAVY INDUSTRIES
| Superior Switching PerformanceSwitching a vacuum makes for rapid breaking.Rapid build-up of the dielectric strength ensures safety breaking.The fuse mounted type also provides for protection against short-circuit currents.
| Optimum DesignOptimized structure and mechanism complement frequent switching.
| Low SurgeSpecial WCAg contact limits the chopping current up to 1A to protect the load from high surge.
| High ReliabilityRigid insulation frame and operating mechanism offer high reliability, especially for safety and quality assurance.
| Customer ConvenienceLight weight and compact size enable easy installation with high efficiency in space.Optimum design makes maintenance convenient.
Features>>
| Continuously Energized TypeHaving longer mechanical life time than a latched type, more suitable for frequent switching.When the transformer for controlling power fails to supply power due to accidents, continuously energized type protects theloads by tripping automatically.
| Latched TypeLatched type keeps the closing condition without the supply of power, so it is suitable for the system which has unstablepower or the load which requires automatic closing with power. With the separate tripping circuit, DC control voltage is recommended for stable power supply. When AC control voltage isused, the CTD(condesor trip device) should be installed.
Operation and Application>>
6
7
[ 3.6/7.2kV M1 cradle ] [ 3.6/7.2kV E1/F1 cradle]
3
4
1
2
[ Continuously energized type] [ Latched type]
◀
5◀
◀
3
4
◀
9
◀
◀
▶
▶
1
2
▶
8
▶
▶
� ON/OFF indicator
� Counter
� Control jack
� Draw-out mechanism
� Fuse
� Fuse holder
� Fuse melting detector (Optional)
� Manual checking hole (Latched type only)
� Trip button (Latched type only)
HCA Type
5HYUNDAI HEAVY INDUSTRIES
45 60 75 45 60 75
16 20 28 16 20 28
2 2 2 2 2 2
AC3 AC4 AC3 AC4
4kA (O-3min-CO-3min-CO)
6.3 6.3 6.3 6.3 6.3 6.3
2.4 2.4 2.4 2.4 2.4 2.4
1,000 1,000 1,000 1,000 1,000 1,000
250 250 250 250 250 250
300
AC110/220, DC110/220
2a2b2)
3.6 7.2 12 3.6 7.2 12
3.3 6.6 11 3.3 6.6 11
Ratings
| Qualified Standard & Approval
▶Standard- IEC 60470-NEMA ICS 3
▶Approval- KR/Korea Korean Register of Shipping- GL/Germany Germanischer Lloyd- LR/U.K Lloyd’s Register of Shipping-NK/Japan Nippon Kaiji Kyokai
>>
Fixed type
F Without fuse holderA With single fuse holderJ With double fuse holder1)
Draw-out type
B Without fuse holder D With single fuse holder H With double fuse holder1)
Rated insulation voltage (kV)
Rated operation voltage (kV)
Rated frequency (Hz)
Rated current (A)
Control dielectric strength(min, kV)
Utilization category
Breaking capacity
※1)Double fuse holder is not applicable to 12kV.2) In case of 3.6/7.2kV fixed type without fuse, 3a3b is standard.3)The weight of 3.6/7.2kV draw-out type is based on F1 cradle.4)The weight of 12kV draw-out type is measured without cradle.
Continuously energized
Latched
Impulse (kV)
Power frequency (1min, kV)
Continuously energized(1,000 times)
Latched (1,000 times)
Operating
method
Type
F 21
A 30
J 33
50/60
Short-timecurrent(kA)
Mechanical
life time
Applicable
load capacity
1 sec
30 sec
Electrical lifetime (1,000 times)
Control voltage (V)
Auxiliary contact
Weight without fuse(kg)
Motor (kW)
Transformer (kVA)
Condensor (kVAR)
Withstand
voltage
F 22
A 32
J 35
F 61
A 68
B 38
D 40
H 43
3)
3)
3)
B 41
D 43
H 46
3)
3)
3)
B 80
D 83
4)
4)
32C� 34C� 62C� 64C� 82C� 84C� 32C� 34C� 62C� 64C� 82C� 84C�
32L� 34L� 62L� 64L� 82L� 84L� 32L� 34L� 62L� 64L� 82L� 84L�
750 1,500 1,500 3,000 3,000 6,000 750 1,500 1,500 3,000 3,000 6,000
1,000 2,000 2,000 4,000 4,000 8,000 1,000 2,000 2,000 4,000 4,000 8,000
750 1,200 1,500 2,000 3,000 4,000 750 1,200 1,500 2,000 3,000 4,000
200 400 200 400 200 400 200 400 200 400 200 400
5a5b
6 HYUNDAI HEAVY INDUSTRIES
Closing current (A)
3.6/7.2kV 12kV
Holding current (A) Opening
current (A)
Closing
time (ms)
Opening
time (ms)
DC110V
DC220V
AC110V
AC220V
DC110V
DV220V
AC110V
AC220V
2.5
1.6
2.0
1.0
2.7
1.7
1.9
1.2
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
1.0
0.7
0.8
0.5
3.0
3.0
3.0
3.0
Max. 40
Max. 40
Max. 25
Max. 25
5.0
4.0
3.5
3.0
3.6/7.2kV 12kV
Continuously
energized
type
Latched
type
-
-
-
-
-
-
Max. 80
Max. 80
Max. 120
Max. 120
Closing
Opening
85 - 110% of rated voltage
70 - 110% of rated voltage
Technical Data
| Operating Time and Current
| Closing & Opening
HCA type vacuum contactor consists of a three-pole insulated monoblock containing three vacuum interrupters. The following are main components in relation to operations of the vacuum contactor.
| Control Voltage
AC110V
AC220V
5A
2A
| Rated Current of Auxiliary Contact
>>
[ CLOSED condition ]
Latch device
Vacuum ContactorVC
[ Continuously energized ] [ Latched ]
�
�
� �
�
�
� �
�
�
�
�
�▶
▶
◀
▶
▶
▶
▶
▶
▶
�
�
�
▶
▶
▶
◀
◀ �◀
◀
◀
7HYUNDAI HEAVY INDUSTRIES
� Closing coil
� Moving core
� Opening spring
� Pressing plate
� Main shaft
� Charging spring
� Vacuum interrupter
� Auxiliary switch
� Resistance
� Latch device
� Insulation frame
� Shaft for auxiliary switch
� Rear shaft
[ OPEN condition ]
Latch device
▶Closing
When the closing coil(� ) is energized, the moving core(� )moves to the closing coil and compresses the openingspring(� ). At the same time the pressing plate(� ), which isfixed on the main shaft(� ), pushes the charging spring(� ),so the movable stem of the vacuum interrupter(� ) is movedup to make the CLOSED condition.
�Continuously energized type: When the moving core(� )moves, the auxiliary switch(� ) leads the control power toresistance(� ) and reduces the current of the closing coil(� ).
�Latched type: When the contactor is closed, the latch device(� ) of the contactor fixs the moving core(� ) mechanicallyand keeps the closed condition. Then the control power isremoved.
▶Opening
�Continuously energized type: When the closing coil(� ) isde-energized by the OFF signal, the opening spring(� ) isreleased to the OPEN condition.
�Latched type: When the opening coil is energized by theOFF siginal or the opening button is pushed, the latchdevice(� ) is released and the opening spring(� ) lets themoving core(� ) move to the OPEN condition. During a power failure, the trip button or condensor tripdevice(CTD) of the latched type also enable the opening ofthe contactor.
HCA Type
�
�
�
[ Continuously energized ] [ Latched ]
▶
▶
� ▶
� ▶
� ▶
◀
◀
�◀
�◀
Vacuum ContactorVC
8 HYUNDAI HEAVY INDUSTRIES
Case Principle Release
it cannot be drawn-in from testposition to connection positionWhen the
contactoris closed, it cannot be drawn-out from
connection position to test position
When the contactor is located in betweeneach named position(DISCONNECTION-TEST, TEST-CONNECTION), it cannot beclosed.
When you draw in the contactor, it stops atthe TEST position.
The interlock pin of the contactor, which isinserted in the TEST/CONNECTION hole ofcradle, mechanically prevents the contactorfrom moving.
The interlock pin of the contactor mechanicallyprevents the contactor from closing.
The interlock pin of the contactor is insertedin the TEST hole of the cradle andmechanically prevents the contactor frommoving to the CONNECTION position.
Electrical interlock (option): The auxiliaryswitch cuts off the control power when thecontactor is in the incorrect position.
Open the contactor and draw in/out torequired position.
After drawing in/out the contactor to therequired position, close it.
E1/F1 Cradle: Hold up the interlock lever ofthe contactor, and push the contactor to theCONNECTION position.
M1/T1 Cradle: Insert the draw-in/out handleto the stopper, and draw-into the contactor toCONNECTION position by turning the handlein a clockwise direction.
| Interlock Function
▶Interlock Mechanism
Incorrect position Test & Connection position
▶Interlock Release
M1 cradleE1/F1 cradle
Technical Data>>
Draw-in/out handle
Stopper
Interlock lever
1
Closing coil
Moving core
Interlock pin
Cradle TEST or CONNECTION hole
Closing coil
Interlock pin
Moving core
Cradle
TEST or CONNECTION hole
1
HCA Type
9HYUNDAI HEAVY INDUSTRIES
| Fuse
▶without Fuse Holder Type
The breaking current of without fuse type is limited, so a circuit breaker should be installed in the upper circuit of the line side.In the case of draw-out types, the fuse holder connection part is replaced by a bus-bar. When it is required, the fuse holdercan be installed under our instruction.
▶with Fuse Holder Type
The user can select and install fuses according to the specifications of the system. Fuses shall cut the short-circuit currentwithin the capacity of the contactor. A protection relay is recommend for over-current protection. A fuse Melting Detector can be offered as an option. The user can compose protection circuits for earth leakage andshort-circuit of single-phase by using a fuse melting detector.
▶Fuse Selection
3φMotor (kW) 3φTransformer (kVA) 3φCondenser (kVAR)
3.3kV 6.6kV 3.3kV 6.6kV 3.3kV 6.6kV
Load Applicablefuse current
---
90100125160200275315400500600500650750
---
160200250330400550650830
1,0001,2001,0001,3001,500
5080100125160200250315400500630750900800
1,0001,250
100 160 200250315400500630800
1,0001,2501,5001,8001,6002,0002,500
305075100125150200250300375500600700600750
1,000
60100150200250300400500650750
1,0001,2001,4001,2001,5002,000
20A
30A
40A
50A
63A
80A
100A
125A
160A
200A
250A
315A
355A
2×160A
2×200A
2×250A
※- This table is based on SIBA catalogue, and is for the 3-phase motor with starting time max. 15 seconds and starting frequency 2 times per hour. - SIBA recommends choosing the next highest voltage range in the condensor load.- Please contact us for the further details of application data.
| Operating Condition
▶Altitude : less than 1,000m A.S.L(above sea level)
Multiply the impuIse and the withstand voltage in accordance with the following correction factor (k) for high locations.
▶Relative humidity : below 85%
Please consider a heater in switchgears for extremely humid conditions.
▶Ambient temperature : -5℃ - +40℃
Multiply the rated current in accordance with the following correction factor (α) in high temperature conditions. Proper ventilation should be considered when installing more than three vacuum contactors into one switchgear.
▶Special conditions
Please contact us for information on special cases like seashore use, corrosive chemical environments, and so on.
1,000m 1,500m 2,000m 2,500m 3,000m
1.0 1.05 1.1 1.15 1.2Applied altitude
Correction factor (k)
40℃ 45℃ 50℃ 55℃ 60℃
1.0 1.05 1.1 1.15 1.2Ambient temperature
Correction factor (α)
Vacuum ContactorVC
10 HYUNDAI HEAVY INDUSTRIES
| Vacuum Checker
Accessories>>
| Standard Accessories
| Additional Option
Control lead cable (1.2m) Manual closing handle for latched type
Fuse melting detector Position switch
▶Electrical Interlock
▶Potential Transformer
▶Condensor Trip Device
When the latched type vacuum contactor isused in AC control voltage, the condensortrip device should be installed inside the3.6/7.2kV contactor as an internal option.For 12kV contactor, it should be installedin switchgear.
The portable vacuum checker can beused to check the condition ofvacuums.
Rated input voltage
Ordinary charging voltage
Ordinary current
Frequency
Applied standard
HCAS0012 HCAS0013Order code
AC110V
DC145V
DC2A
50/60Hz
IEC 60694/KSC 4611
AC220V
DC290V
▶Terminal Connection 1,2: Input power(AC) / 5,6: Closing power(DC) / 5,7: Trip power
Rated input voltage
Rated out-put voltage
Dimension
Weight
HAFS-VC9Order code
AC200/220V
AC11/22kV
W200 x L350 x H176mm
22kg
HCA Type
11HYUNDAI HEAVY INDUSTRIES
Circuit Diagrams>>
※�Vza, Vzb: Control Switch �R: Resistor �CC: Closing Coil �Aux. Switch: Auxiliary Switch �X: Relay�TC: Trip Coil �CTD: Condensor Trip Device �SCU: Control Unit �S8, S9: Internal Position Switch
[ Continuously energized ]
[ Continuously energized ]
[ Continuously energized ]
[ 3.6/7.2kV ] [ 12kV ]
[ Latched ]
[ Latched ]
[ Latched ]
3.6/7.2kV DC Control
AC Control3.6/7.2kV
12kV
Option
without fuse holder3.6/7.2kV Fixed type
(Unit: mm)
(Unit: mm)
(Unit: mm)
12 HYUNDAI HEAVY INDUSTRIES
Dimension A
200A
25
400A
32
※Dimensions may be revised without notice.
Dimensions>>
with single fuse holder3.6/7.2kV Fixed type
with double fuse holder3.6/7.2kV Fixed type
Vacuum ContactorVC
Dimension Y
200A
25
400A
32
Dimension A
200A
25
400A
32
13HYUNDAI HEAVY INDUSTRIES
(Unit: mm)
with single fuse holder3.6/7.2kV Draw-out type, E1 cradle
※Dimensions may be revised without notice.
(Unit: mm)
without fuse holder3.6/7.2kV Draw-out type, E1 cradle
HCA Type
Vacuum ContactorVC
14 HYUNDAI HEAVY INDUSTRIES
Dimensions>>(Unit: mm)
(Unit: mm)
(Unit: mm)
※Dimensions may be revised without notice.
without fuse holder3.6/7.2kV Draw-out type, F1 cradle
with single fuse holder3.6/7.2kV Draw-out type, F1 cradle
with double fuse holder3.6/7.2kV Draw-out type, F1 cradle
HCA Type
15HYUNDAI HEAVY INDUSTRIES
(Unit: mm)
(Unit: mm)
(Unit: mm)
※Dimensions may be revised without notice.
without fuse holder3.6/7.2kV Draw-out type, M1 cradle
with single fuse holder3.6/7.2kV Draw-out type, M1 cradle
with double fuse holder3.6/7.2kV Draw-out type, M1 cradle
16 HYUNDAI HEAVY INDUSTRIES
Dimensions>>
(Unit: mm)
(Unit: mm)
(Unit: mm)
※Dimensions may be revised without notice.
without fuse holder12kV Fixed type
with single fuse holder12kV Fixed type
with double fuse holder3.6/7.2kV Draw-out type, T1 cradle
[ front ] [ side ] [ top ]
[ front ] [ side ] [ top ]
Vacuum ContactorVC
17HYUNDAI HEAVY INDUSTRIES
※Dimensions may be revised without notice.
(Unit: mm)
(Unit: mm)
without fuse holder / with single fuse holder12kV Draw-out type, M1 cradle
without fuse holder / with single fuse holder12kV Draw-out type, E1/F1 cradle
HCA Type
Vacuum ContactorVC
18 HYUNDAI HEAVY INDUSTRIES
Order Information>>
Code Specification
Continuously energized LatchedCategory
HCA32CF 4000000
HCA62CF 4000000
HCA82CF 4000000
HCA32CD 4F16000
HCA62CD 4F16000
HCA82CD 4F1600A
HCA32CD 4M16000
HCA62CD 4M16000
HCA82CD 4M1600A
HCA34CF 4000000
HCA64CF 4000000
HCA84CF 4000000
HCA34CD 4F16000
HCA64CD 4F16000
HCA84CD 4F1600A
HCA34CD 4M16000
HCA64CD 4M16000
HCA84CD 4M1600A
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
200A
200A
200A
400A
400A
400A
VC V2
Fixed type without fuse holder,
AC220V, No cradle,
No fuse holder
Draw-out type with single fuse holder,
AC220V, F1 cradle, No fuse
Draw-out type with single fuse holder,
AC220V, M1 cradle,
No fuse
Fixed type without fuse holder,
AC220V, No cradle,
No fuse holder
Draw-out type with single fuse holder,
AC220V, F1 cradle, No fuse
Draw-out type with single fuse holder,
AC220V, M1 cradle,
No fuse
| Standard Order Code
※1) CTD of 12kV contactor will be delivered as separate part.
Code
HCA
HCA
ModelName
HCA
Code
3
6
RatedVoltage
3.6kV
6 7.2kV
8 12kV
Code
F
D
Structure
Contactor Fuse Holder
Fixed type up to 12kV
Fixed type up to 12kV
Fixed type up to 7.2kV
Draw-out type up to 12kV
Draw-out type up to 12kV
Draw-out type up to 7.2kV
-
A Single
J Double
B -
D Single
H Double
Code
1
4
ControlVoltage
DC110V
2 DC220V
3 AC110V
4 AC220V
Code
C
C
OperatingMethod
ContinuouslyEnergized
L Latched
Code
2
4
RatedCurrent
200A
4 400A
Code Specification
HCA32LF 4000000 AF
HCA62LF 4000000 AF
HCA82LF 4000000 BF1)
HCA32LD 4F16000 AF
HCA62LD 4F16000 AF
HCA82LD 4F16000 BF1)
HCA32LD 4M16000 AF
HCA62LD 4M16000 AF
HCA82LD 4M16000 BF1)
HCA34LF 4000000 AF
HCA64LF 4000000 AF
HCA84LF 4000000 BF1)
HCA34LD 4F16000 AF
HCA64LD 4F16000 AF
HCA84LD 4F16000 BF1)
HCA34LD 4M16000 AF
HCA64LD 4M16000 AF
HCA84LD 4M16000 BF1)
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
3.6kV
7.2kV
12kV
200A
200A
200A
400A
400A
400A
Fixed type without fuse holder,
AC220V, No cradle, No fuse holder,
AC220V CTD
Draw-out type with single fuse holder,
AC220V, F1 cradle, No fuse,
AC220V CTD
Draw-out type with single fuse holder,
AC220V, M1 cradle, No fuse,
AC220V CTD
Fixed type without fuse holder,
AC220V, No cradle, No fuse holder,
AC220V CTD
Draw-out type with single fuse holder,
AC220V, F1 cradle, No fuse,
AC220V CTD
Draw-out type with single fuse holder,
AC220V, M1 cradle, No fuse,
AC220V CTD
Counter (5 digit)
Manual closing handle (for latched type)
Latch device (DC110V)
Latch device (DC220V)
Fuse melting detector (3.6/7.2kV)
Position indicator (3.6/7.2kV)
Closing coil (DC110/220V, 3.6/7.2kV, 1EA)1)
Closing coil (DC110/220V, 12kV, 1EA)1)
Potential transformer (7.2kV/200VA)
Potential transformer (3.6kV/200VA)
Condenser trip device (AC110V)
Condenser trip device (AC220V)
Control lead cable (length 1.5m, 3.6/7.2kV)
Control lead cable (length 2.0m, 3.6/7.2kV)
Fuse holders for single type (3.6/7.2kV, 1EA)1)
Fuse holders for double type (3.6/7.2kV,1EA)1)
Fuse holders for single type (12kV, 1EA)1)
Isolating contact (3.6/7.2kV, 200A)
Isolating contact (3.6/7.2kV, 400A)
Isolating contact (12kV, 400A)
Vacuum interrupter (7.2kV, 400A)
Vacuum interrupter (12kV, 400A)
Fuse - 7.2kV/6.3A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/10A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/20A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/25A/63kA, 192mm, 1EA (SIBA)
HCA Type
19HYUNDAI HEAVY INDUSTRIES
Code Specification Category
HCAS0001
HCAS0002
HCAS0003
HCAS0004
HCAS0005
HCAS0006
HCAS0007
HCAS0008
HCAS0009
HCAS0011
HCAS0012
HCAS0013
HCAS0015
HCAS0016
HCAS0019
HCAS0020
HCAS0018
HCAS0021
HCAS0022
HCAS0023
HVC00704
HVC01204
HCAS6006
HCAS6010
HCAS6020
HCAS6025
| Spare Parts
VC V8
Fuse - 7.2kV/31.5A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/40A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/50A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/63A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/80A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/100A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/125A/63 kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/160A/63kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/200A/50kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/250A/50kA, 192mm, 1EA (SIBA)
Fuse - 7.2kV/315A/50kA, 292mm, 1EA (SIBA)
Fuse - 7.2kV/355A/50kA, 292mm, 1EA (SIBA)
Fuse - 12kV/6.3A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/10A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/16A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/20A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/25A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/32A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/40A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/50A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/63A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/80A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/100A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/125A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/160A/63kA, 292mm, 1EA (SIBA)
Fuse - 12kV/200A/50kA, 292mm, 1EA (SIBA)
Code Specification Category
HCAS6032
HCAS6040
HCAS6050
HCAS6063
HCAS6080
HCAS6100
HCAS6125
HCAS6160
HCAS6200
HCAS6250
HCAS6315
HCAS6355
HCAS7006
HCAS7010
HCAS7016
HCAS7020
HCAS7025
HCAS7032
HCAS7040
HCAS7050
HCAS7063
HCAS7080
HCAS7100
HCAS7125
HCAS7160
HCAS7200
VC V8
※- 442mm fuse is applicable to 12kV vacuum contactor, but not supplied by HHI.
1) 2EA is required for 1set of vacuum contactor.2) 6EA is required for 1set of vacuum contactor.
Code
00
M1
Cradle
N/A (for Fixed type)
without Shutter
with Insulation Shutter
with Metal Shutter and Bushing
with Metal Shutter, Bushingand Earthing Switch
E1F1M1
T1
Code
0000
6000
Fuse Application
Fuse Holder Fuse Specification
- -
6000 Single up to 250A, 192mm
600A Single 3.6/7.2kV 315/355A, 12kV, 292mm
600B600C
Double
Single
3.6/7.2kV, 192mm
442mm
Code
AMAP
Additional Option
CTD, AC110V
CTD, AC220V
Electrical Interlock
Fuse Melting Detector
Position Switch
Latched type,AC control
Application
Draw-out type
Insideof
contactor
Cradle
Insideof
contactor
for Fuse
Draw-out type
Potential Transformer, 3.6kV x 1EAPotential Transformer, 7.2kV x 1EA Potential Transformer, 3.6kV x 2EA Potential Transformer, 7.2kV x 2EA
All
Mounting
※Fuse is not included.
AEBEAFBFALBLAMBMAPBPT1T3T4T6
3.6/7.2kV12kV
3.6/7.2kV12kV
3.6/7.2kV12kV
3.6/7.2kV12kV
3.6/7.2kV12kV
3.6/7.2kV
HH
IS-W
C-LE
-B27-03, 2009. 04, D
esigned by JC C
omm
unication
www.hyundai-elec.com
Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea Tel: 82-52-202-8101~8 Fax: 82-52-202-8100
Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea (Sales & Marketing) Tel: 82-2-746-7510, 7589 Fax: 82-2-746-7647
Orlando 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A. Tel: 1-407-249-7350 Fax: 1-407-275-4940
New Jersey 300 Sylvan Avenue, Englewood Cliffs, NJ, 07632, U.S.A.Tel: 1-201-816-0286 Fax: 1-201-816-4083
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UKTel: 44-20-8741-0501 Fax: 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, JapanTel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093
Osaka I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, JapanTel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818
Dubai Unit 205, Level 2, Burj Dubai Square Building No.4, Sheikh Zayed Road, P.O.Box 252458Tel: 971-4-425-7995 Fax: 971-4-425-7996
Sofia 1271, Sofia 41, Rojen Blvd., BulgariaTel: 359-2-803-3200, 3220 Fax: 359-2-803-3203
Yangzhong No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, ChinaTel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231