Updated Questions & Answers concerning:
INVITATION TO BID – ITB Goods & related services
Ref: UGA/1972-Kasubi Tombs Firefighting Equipment &
Installation
Date: 4 June 2019 UNESCO Regional Office for Eastern Africa received the following questions from potential bidders, which are being shared with all interested parties along with the response from UNESCO:
Q1) We would like to request you if you would organize for us site visit so that we know the exact nature of the where the fire fighting equipment shall be installed.
A1) A group visit can be arranged for potential bidders. Please contact: Mr. Samuel Sentongo to schedule a time: [email protected] Update 4 June 2019: A site visit was organized at 10am on 31 May 2019. Twelve potential bidders participated; however, they were unable to access the actual site due to the need for special permission; therefore, a question and answer session was organized in the parking lot of the site. The additional questions and answered have been included in this updated document dated 4 June 2019 starting with question 4 below.
Q2) We would be pleased to receive a clarification on the following:
Annex 1, A, 10 (a): Since the equipment / material requested comes "off the shelve" and is commonly available, it will be very difficult, if not impossible to get a manufacturer's authorization. May we therefor request a waiver on this specific point of the ITB.
A2) The following items should have Manufacturer’s Authorization:
1. Multistage Fire Pump Set 2. Hose Reels 3. Fire Hydrants 4. 320A 6way TPN MCCB Distribution Board 5. 200KVA Transformer
The rest are ordinary off the shelf items and do not need manufacturer’s authorization. The supplier will be responsible for the 1 year warranty.
Q3) Please we need to get drawing and plans for the implementation and we
have a request for clarification : - Lot 1 item 9 : firefighting pumps : "Multi stage horizontal centrifugal Fire pump set (2no) rated at 120m3/hr at 100m Head. One pump to be driven by diesel engine, and the second pump to be driven by an Electric Motor 3 phase 415V, 2900 RPM, plus a jockey pump 16m3/hr. at 60m head 4KW to maintain pressure at 6bars, complete with 600litre pressure tank, 400litre diesel tank, control panel and all accessories. (Pumps must have an NPSH of at least 6m)". Does driver diesel engine and driver electric motor and jokey pump are existing items or must be supplied ? Please we need more details for this item If it will be supplied please we need more details and specifications about diesel engine
A3) The Fire Pump Set is a package unit with a diesel engine driven pump rated at 120m3/hr at 100m Head, an electric motor driven pump rated at 120m3/hr at 100m Head and an electric jockey pump rated at 16m3/hr. at 60m. This is a new pump set to be supplied by the bidder ready to be installed and work. Nothing exists. The pump set must be supplied complete with all the items described. Note: Four Installation drawings are attached as an annex to this document
Q4) Following the organized site visit at Kasubi Tombs, may we request the following: As per technical description the (fire) water will be pumped-out of the newly build basin. There is however also a borehole. If we notice the size of the pumps 2 x 120m3./hr at 100m head and 1 x jockey pump 16m3./h at 60m head, we wonder where the pumps should be installed. The depth of the basin is only 4 m. So why these over-rated pumps for a depth of only 4 m.? Will these pumps be used to pump water out of the borehole ?
A4) There is an existing borehole which is already motorised and will deliver water into the proposed 120m3 underground tank. The firefighting pump set will pump from the 120m3 underground tank. The three pumps form a set with only one pump operating at a time.
Q5) May we request a possible extension of the closing-date?
A5) Bids will be extended two weeks until 21 June 2019
Q6) Can Tenderers submit their Bids On-line?
A6) No all bids must be sent in sealed envelopes as per the instructions and in line with our procurement rules.
Q7) What is the material of the walls of the pump house?
A7) The wall will be made of 200mm concrete Blocks
Q8) What is a Fire Point and how many Fire Points are there?
A8): A fire point is made up of a short freestanding wall on which will be mounted two Fire Extinguishers. One will be a Water Type Extinguisher 5kg the second one is a Dry Powder Fire Extinguisher 9kg.
Q9): What is FH?
A9): FH stands for Fire Hydrant. It will have an underground Type Fire Hydrant in a chamber with a cover, and an associated Fire Box mounted nearby consisting of a freestanding metal box containing two Fire Hoses and a Nozzle.
Q10) What is FHR?
A10) FHR stands for Fire Hose Reel. This point consists of a semi-rigid rubber hose wound on a reel. The hose is 30m long and diameter is 20mm.
Q 11) There is need for a Pressure Reducing Valves between the Fire Hydrants and hose reels.?
A11) Yes. The BOQ is now amended to introduce 2no. Pressure Reducing Valves. (please see revised annex attached)
Q12): In item 1 of the BOQs the 65mm HDPE PN16 water pipes are measured in m. In item 2 of the BOQs the 160mm HDPE PN16 water pipes are measured in 6 lengths. Please clarify.
A12) In item 1 of the BOQs the 65mm HDPE PN16 water pipes are measured in m. 60m this is correct. In item 2 of the BOQs the 160mm HDPE PN16 water pipes are measured in 6m lengths. We have reviewed the measurement unit and changed it to m. The correct length to deliver is 420m. The contractor is free to deliver the 420m in units of 6m for butt welding or in units of 50m rolls.
Q13) What is the Shape and capacity of underground tank?
A13) The shape is rectangular: 6x6m in plan and a height of 4m
Q14) Item 9 in the BOQs indicates a multi-stage horizontal pump. This pump will have problems of priming.
A 14): This item has already been changed to read : “Multi stage Vertical centrifugal Fire pump set (2no) rated at 120m3/hr at 100m Head. One pump to be driven by diesel engine, and the second pump to be driven by an Electric Motor 3 phase 415V, 2900 RPM, plus a jockey pump 16m3/hr. at 60m head 4KW to maintain pressure at 6bars, complete with 600litre pressure tank, 400litre diesel tank, control panel and all accessories. (Pumps must have an NPSH of at least 6m).”
Q15): The BOQs do not indicate the Suction line and foot valve for the pump.
A15) The BOQ is amended to introduce the Suction line and foot valve for the pump.
Q 16): There is need for Air Release Valves in the network.
A 16): Yes. The BOQ is amended to introduce 2no. Air Release Valves in the network
Q17): Type of Fire extinguishers?
A17): Two types: Water Type and Dry Powder Type
Q18) Can Bidders present an Insurance Bond instead of a Bank Bond as Bid Bond?
A 18) This issue of insurance bond instead of bank guarantee will be dealt with at a later stage once selection is completed.
Q19) Will an Insurance Bond instead of a Bank Bond be accepted as a Performance Bond?
A 19) This issue of insurance bond instead of bank guarantee will be dealt with at a later stage once selection is completed.
Q20): Will UNESCO give a time extension to the bid submission of a Week?
A20) See Q5 and A5 Above, the bid will be extended by two weeks until 21 June 2019.
Q 21) Can Tenderers submit their Bids On-line?
A21): No all bids must be sent in sealed envelopes as per the instructions and in line with our procurement rules.
Q22) Item 44 indicates a Provisional Sum of US$3,500,000 for UMEME connections, is this correct?
A22) This Provisional Sum should read as US$3,500 (US Dollars Three Thousand Five Hundred only) and not US3,500,000.
Q23): Item 9 and Item 32 are repeated. Does that mean there are two Fire Pump Sets?
A23): The BOQs consist of two Lots namely Lot 1 and Lot 2. Lot 1 which is for supply of materials and equipment has Items 1 to 21. Lot 2 which is for the installation of the supplied materials and equipment has Items 22 to 49. Therefore Item 9 is for the supply of the Fire pump set and item 44 is for installation of the same set.
Q24): There is need for 160x160x160mm HDPE PN16 Ts in the network.
A24): Yes. The BOQ is amended to introduce 3no. 160x160x160mm HDPE PN16 Ts in the network
Q25): There is need for 160mm PN16 O S & Y Valves in the network.
A 25) Yes. The BOQ is amended to introduce 12no. 160mm PN16 O S & Y Valves in the network
Q26): There is need for 160mm PN16 O slow bends.
A26): Yes. The BOQ is amended to introduce 5no. 160mm PN16 90degrees slow bends and 5no. 160mm PN16 135degrees slow bends in the network.
ATTENTION / PLEASE NOTE: Attached please find the amended BOQs in Annex VII with two additions namely: Items 8d) and 8e), which concern “Air Release Valve” and “Pressure Reducing Valves”. Additional annexes of drawings referred to above in A3 are also attached.
320A
C1R-2
C1R-3
C1R-4
TO CONSUMER UNIT
320A,TPN 6-WAY TPN MCB SURFACE MAIN DISTRIBUTION BOARD
(MUZIBU AZAALA MPANGA)
WIRED BY 4Cx50mm²PVC/SWA/PVC
COPPER CABLES
WIRED BY 4C x16mm² PVC/SWA/PVC COPPER CABLES
100A
100A
63A
TO CONSUMER UNITWIRED BY 4C x16mm² PVC/SWA/PVC COPPER CABLES
TO CONSUMER UNITWIRED BY 4C x16mm² PVC/SWA/PVC COPPER CABLES
(NJAGALA KASAAYI,KAJJAGA,GAZIMBE,
ABALONGA ABASIMBIRI)
(KATALAMA,BUJJA BUKULA,.....)
C1R-5
160A
SPARE
C1R-6
63A
SPARE
320A
M
meter
cutout
200KVA
11KV/415V
Transformer
160A
C1R-1 WIRED BY 4C x16mm² PVC/SWA/PVC COPPER CABLES
TO FIRE FIGHTING SET 01
400 200200 1300 200200 400
300 3000 300
360030
0
3000
300
400 200200
1300200200
400
400
200
200
1300
200
200
400
2000
300
Sump To Hold TX Oil
Sump To Hold TX Oil
Sum
p To
Hol
d T
X O
il
Sum
p To
Hol
d T
X O
il
TRANSFORMER DETAILScale 1:100
YY200KVA, 50 Hz,11KV/433VTransformer
BASE for TX
Steel Fencing aroundTransformer
1500
30050
450
200200
1300
200200
40050
3007502100750
3600
Sump To Hold TX Oil
SECTION Y-YScale 1:100
PROPOSED RE-CONSTRUCTIONOF KASUBI TOMBS ON PLOT....., NABULAGALA.
SCHEMATICS: MAIN DISTRIBUTION BOARD
BUGANDA KINGDOMP.O BOX 1754,
MECHANICAL AND ELECTRICAL ENGINEERS
M E ASSOCIATESCONSULTING ENGINEERS
P. O. BOX 4052KAMPALA, UGANDATEL 501894, FAX 501893email: [email protected]
M & E
50/25
100/50
R100
SV
200
200 30m x 25mmRubber Hose Reel
HOSE REEL DETAIL
FIRE HYDRANT CONNECTION
80mmØ
200mmØ
GROUND LEVEL
A
D+400 min.
SECTION A-A
A
A
Finished ground level
820
200 min.
Concrete class C15
GATE VALVESCALE: 1:50
UNDER GROUND FIRE HYDRANT CHAMBER DETAILS
UNDER GROUND FIRE HYDRANT CHAMBER DETAILS
Water mains
800X800mm
Valve Chamber
Ductile Iron Cover
Duck foot Bend
Specifications:
HYDRANT
Model No. NHYD 058-2C
Body: Ductile Iron Body to BS EN 1563
Outlet: 2.5" ∅ BS High Tensile Brass, BS round threaded
Inlet: 3" ∅ Flanged, O.D 200mm, PCD 160mm, 8 Holes ∅ 19mm
Test Pressure: 25 Bar
DUCK FOOT BEND:
Model No. NHYD 070
Body: Grey Cast iron BS 1503
Outlet: 4"
Inlet: 4" Flanged
OF KASUBI TOMBS ON PLOT....., NABULAGALA.
DEATAILS: GATE VALVE AND FIRE HYDRANT
BUGANDA KINGDOMP.O BOX 1754,
MECHANICAL AND ELECTRICAL ENGINEERS
M E ASSOCIATESCONSULTING ENGINEERS
P. O. BOX 4052KAMPALA, UGANDATEL 501894, FAX 501893email: [email protected]
M & E
1212
2800
8000
400
Fire Fighting
Set 01
Fire Fighting
Set 02
200mm Discharge
Manifold
150mm Suction
Manifold
200mm Suction Pipe
200mm Non Return
Foot Valve.
120 cum.
Reinforced
Concrete
Tank
PUMP ROOM
SECTION Z-ZScale 1:100
F
U
T
U
R
E
6000
4000
500 500
200
1200
100
400
1894
GL
FIRE HOSE REEL DETAILScale 1:50
FIRE BOX
800
Tempered Glass
Door
Z
FIRE FIGHTING PUMP HOUSE FLOOR PLANF
U
T
U
R
E
FIRE FIGHTING SET 02
REINFORCED
CONCRETE TANK
120cum.
Z
2007800
20
0m
m F
ire
F
ig
htin
g L
in
e to
Mu
zib
u A
za
ala
M
pa
ng
a
Wa
te
r C
an
no
n
10
0m
m F
re
sh
W
ate
r
Lin
e to
O
ve
r H
ea
d T
an
ks
20
0m
m F
ire
F
ig
htin
g
Lin
e to
F
ire
H
yd
ra
nts &
Ge
ne
ra
l F
ire
F
ig
htin
g
2000
F
U
T
U
R
E
6000
6000
800
600
HAND FIRE EXTINGUISHERS HUNG ON WALL[FIRE POINT (FP)]Scale 1:50
powder9kg
co²5kg
200
ElevtionScale, 1:100
6400
PROPOSED RE-CONSTRUCTIONOF KASUBI TOMBS ON PLOT....., NABULAGALA.
TANK,PUMP HOUSE & FIRE HYDRANT DETAILS
BUGANDA KINGDOMP.O BOX 1754,
MECHANICAL AND ELECTRICAL ENGINEERS
M E ASSOCIATESCONSULTING ENGINEERS
P. O. BOX 4052KAMPALA, UGANDATEL 501894, FAX 501893email: [email protected]
M & E
Grave
Yard
MASIRO ROAD
01
02
52
53
UNDER
GROUND RC
TANK
FHFHR 04
FHR 01
FHR 01
FH 02
FH 03
FH 04
FHFHR 05
FHFHR 06
FH
FHR 07
FH
FHR 08
160
160
160
160
160
160
160
160
160
160
160
160
100
160
160
160
160
160
160
160
160
160
160
160
Ø6m
PUMP HOUSE
GROUND MOUNTED
TRANSFORMER
315KVA 11KV/433V
100
160160
160
100
FHR
02
FHR 02
FHR 03
FHR 03FH 01
1
1
0
m
m
H
D
P
E
P
N
1
6
P
I
P
E
F
R
O
M
B
O
R
E
H
O
L
E
PROPOSED RE-CONSTRUCTIONOF KASUBI TOMBS ON PLOT....., NABULAGALA.
SITE PLAN: FIRE FIGHTING DESIGN
BUGANDA KINGDOMP.O BOX 1754,
MECHANICAL AND ELECTRICAL ENGINEERS
M E ASSOCIATESCONSULTING ENGINEERS
P. O. BOX 4052KAMPALA, UGANDATEL 501894, FAX 501893email: [email protected]
M & E
FOR DETAILS OF FIRE POINT (FP)SEE DRAWING MEA634-02
FIRE POINT
FIRE HYDRANT
FH
6
ANNEX VII – Technical Specifications
Item No UNESCO minimum
requirements/specifications
Bidder’s Compliance Statement YES/NO
Bidder’s Specifications (Mandatory - please fill in all details including proposed brand/model)
Lot 1: Firefighting equipment
1.
Water Supply Line
65mm HDPE PN16 water supply line pipes.
Unit m: Quantity: 60
2.
Fire Fighting Pumping Main
160mm HDPE PN16 Fire fighting water distribution line pipes in 6m lengths.
Unit m: Quantity: 35420 .
3.
110mm HDPE PN16 Fire fighting water distribution line pipes
Unit m: Quantity: 110
4.
160mm PN16 butterfly valve
Unit: No. Quantity: 2
5.
160x160x100mm HDPE PN16 T 5a) 160x160x160mm HDPE PN16 T
Unit: No. Quantity: 128 Unit: No. Quantity: 3
6.
110x50mm PN16 Reducer Unit: No. Quantity: 84
7.
50x40mm PN16 Reducer Unit: No. Quantity: 4
8.
110mm PN16 O S & Y gate valve 8a) 160mm PN16 O S & Y gate valve. 8b) 160mm PN16 90degrees Slow Bends. 8c) 160mm PN16 135degrees Slow Bends. 8d) 110mm PN16 Air Release Valve 8e) 160mm PN16/PN8 Pressure Reducing Valve
Unit: No. Quantity: 4 Unit: No. Quantity: 12 Unit: No. Quantity: 5 Unit: No. Quantity: 5 Unit: No. Quantity: 2 Unit: No. Quantity 2
9.
Fire Fighting Pumps
Multi stage horizontal Verticalcentrifugal Fire pump set (2no) rated at 120m3/hr at 100m Head. One pump to be driven by diesel engine, and the second pump to be driven by an Electric Motor 3 phase 415V, 2900 RPM, plus a jockey pump 16m3/hr. at 60m head 4KW to maintain pressure at 6bars, complete with 600litre pressure tank, 400litre diesel tank, control panel and all accessories. (Pumps must have an NPSH of at least 6m). 9a) Flanged Ductile Iron suction pipe 3.6m long complete with fanged 160mm foot valve.
Unit: Set Quantity: 1 Unit: No. Quantity: 1
10. 1Swinging arm automatic semi-rigid hose Unit: No. Quantity: 48
Formatted Table
Formatted Table
Formatted: French (France)
7
1
reel 20mm diameter and 30m long to BSEN 671-1-2001 and BSEN 694-2001 complete with all accessories including wall mounting box, Jet and Spray nozzle and all accessories.
11. Underground type Fire hydrant to BS 750:1984 and BS 336: 1989, inlet DN80, complete with all fittings, adaptors, distance pieces, valves, etc. and all other fittings to make the installation complete, as specified, all fittings to PN16, including chamber.
Unit: No. Quantity: 4
12. Water delivery hose reel to BS 6391: 1983 for couplings to BS:336:1989 with female and male couplers, Type 2 with elastomeric lining and synthetic fibre reinforcement with electrometric coating diameter 65mm and length 30m to PN 16 pressure,
Unit: No. Quantity: 8 as NAFFCO NF-DH2 65R or equal approved.
13. Handheld delivery nozzle to PN16 and to BS 336:1989
Unit: No. Quantity: 4 as NAFFCO NF -FB-320 or equal approved.
14. Metal box to hold 2 hose reels and nozzle 1600x900x300mm fixed in the ground on legs, with reinforced glass door complete with all accessories.
Unit: No. Quantity: 4
15. Water Type portable fire extinguisher 5kg Unit: No. Quantity: 24 as NAFFCO CO2 gas extinguisher Model NC5 or equal approved.
16. Dry powder portable fire extinguisher 9 kg
Unit: No. Quantity: 24 as NAFFCO ABC powder Model NP9 or equal approved.
17. Power Supply Cables to Fire Pump
4corex50mm2 PVC/SWA/ PVC Copper cables
Unit m: Quantity: 20
18. LV SWITCHGEAR
320A 6 way TPN MCCB free-standing Main Distribution Board, with 320A TPN MCCB incomer/main switch, complete with 1Nox125A, 2Nox100A, 3Nox63A, TPN MCCBs, Digital Universal meter, with Over-voltage/under-voltage and phase failure protection and surge protection, and all accessories
Unit: No. Quantity: 1 as made by Nile Power or equal approved.
19. Transformer
200KVA, 11KV/415V, 50Hz Ground mounted, outdoor type, natural oil power transformer complete with all accessories and acceptance tests by UMEME.
Unit: No. Quantity: 1
20. Cable from transformer to MDB 4corex70mm2 PVC/SWA/ PVC Copper cables
Unit m: Quantity: 20
21. Sub-Total for Lot 1
8
Lot 2: Installation of Fire Fighting Equipment
22. Underground tank
120m3 Reinforced Concrete Underground tank 6x6m in plan, 4m deep in 200mm RC Floor slab, 200mm RC Walls, and 200mm RC cover Slab, manhole, gs ladder, complete with 200mm ball valve for 65mm inlet, 160mm outlet at bottom and 110mm outlet at high level, and all accessories to the Structural Engineer's detail.
Unit: No. Quantity: 1
23. Water Utility Supply Line
Install 65mm HDPE PN16 water supply line buried at least 600mm on bed of sand 100mm and cover of sand 100mm complete with all accessories laid from the borehole to the underground tank.
Unit m: Quantity: 60
24. Fire Fighting Pumping Main
Install 160mm HDPE PN16 Fire fighting water distribution line buried at least 800mm on bed of sand 100mm and cover of sand 100mm complete with all accessories.
Unit m: Quantity: 200420
25. Install 110mm HDPE PN16 Fire fighting water distribution line buried at least 800mm on bed of sand 100mm and cover of sand 100mm complete with all accessories.
Unit m: Quantity: 110
26. Install 160mm PN16 butterfly valve Unit: No. Quantity: 2
27. Install 160x160x110mm HDPE PN16 T 27a) 160x160x160mm HDPE PN16 T
Unit: No. Quantity: 812 Unit: No. Quantity: 3
28. Install 110x50mm PN16 Reducer Unit: No. Quantity: 84
29. Install 50x40mm PN16 Reducer Unit: No. Quantity: 4
30. Install 110mm PN16 O S & Y gate valve 30a) 160mm PN16 O S & Y gate valve
Unit: No. Quantity: 4 Unit: No. Quantity: 12
31. Construct Valve chamber 600x750x800mm in sected burnt bricks complete with RC cover and all accessories.
Unit: No. Quantity: 8
32. Fire Fighting Pumps
Install Multi stage horizontal Vertical centrifugal Fire pump set (2no) rated at 120m3/hr at 100m Head. One pump to be driven by diesel engine, and the second pump to be driven by an Electric Motor 3 phase 415V, 2900
Unit: Set Quantity: 1
Formatted Table
9
RPM, plus a jockey pump 16m3/hr. at 60m head 4KW to maintain pressure at 6bars, complete with 600litre pressure tank, 400litre diesel tank, control panel and all accessories. (Pumps must have an NPSH of at least 6m). 32a) Flanged Ductile Iron suction pipe 3.6m long complete with fanged 160mm foot valve.
Unit: No. Quantity: 1
33. Install Swinging arm automatic semi-rigid hose reel 20mm diameter and 30m long to BSEN 671-1-2001 and BSEN 694-2001 complete with all accessories including wall mounting box, Jet and Spray nozzle and all accessories
Unit: No. Quantity: 48
34. Install Underground type Fire hydrant to BS 750:1984 and BS 336: 1989, inlet DN80, complete with all fittings, adaptors, distance pieces, valves, etc. and all other fittings to make the installation complete, as specified, all fittings to PN 16, including inspection chamber an cover.
Unit: No. Quantity: 4
35. Install Water delivery hose reel to BS 6391: 1983 for couplings to BS:336:1989 with female and male couplers, Type 2 with elastomeric lining and synthetic fibre reinforcement with electrometric coating diameter 65mm and length 30m to PN 16 pressure,
Unit: No. Quantity: 8
36. Install Handheld delivery nozzle to PN16 and to BS 336:1989
Unit: No. Quantity: 4
37. Install Metal box to hold 2 hose reels and nozzle 1600x900x300mm fixed in the ground on legs, with reinforced glass door complete with all accessories.
Unit: No. Quantity: 4
38. Install Water Type portable fire extinguisher 5kg
Unit: No. Quantity: 24
39. Install Dry powder portable fire extinguisher 9 kg 39a) Fire Point: Freestanding wall 500x1500x200mm to hang the fire extinguishers.
Unit: No. Quantity: 24 Unit: No. Quantity: 12
40. Power Supply Cables to Pumps
Install Cabling from MDB position in Switch room to Fire Fighting Pump by 4corex50mm2 PVC/SWA/ PVC
Unit m: Quantity: 20
10
Copper cables in PVC duct/Cable trays/surface complete with terminations, glanding, clipping and all accessories.
41. LV SWITCHGEAR
Install 320A 6 way TPN MCCB free-standing Main Distribution Board, with 320A TPN MCCB incomer/main switch, complete with 1Nox125A, 2Nox100A, 3Nox63A, TPN MCCBs, Digital Universal meter, with Over-voltage/under-voltage and phase failure protection and surge protection, and all accessories
Unit: No. Quantity: 1
42. Earthing of the LV Switchgear Unit: No. Quantity: 1
43. Pump house
Pump house dimensions 8000mm diameter in plan 2800mm high, roofed in IT4 gauge 26 sheets on steel trusses and purlins, with steel window and steel door and frame, with plaster paint and cement screed, 200mm concrete slab with hardcore under, complete with grass thatch roof cover and all accessories.
Unit: No. Quantity: 1
44. Power Supply UMEME Connections (Electricity Utility)
Provisional Sum of US$3,500 ,000 for Power supply and UMEME connection charges.
Unit: LS. Quantity: 1
45. Attendance and profit on above
46. Transformer
200KVA, 11KV/415V, 50Hz Ground mounted, outdoor type, natural oil power transformer complete with all accessories and acceptance tests by UMEME.
Unit: No. Quantity: 1
47. Concrete Plinth for mounting the transformer 1500x1500x400mm complete
Unit: No. Quantity: 1
48. Earthing of the HV Switchgear Unit: No. Quantity: 1
49. Cable from transformer to MDB 4corex70mm2 PVC/SWA/ PVC Copper cables
Unit: m Quantity: 20
50. Sub-Total for Lot 2
51. GRAND TOTAL FOR LOT 1 AND LOT 2
11
Power Supply Requirement: Primary wall outlet type: Type G (BS-1363) Voltage: 220-240 volts AC @ 50 Hz For use in Uganda
Documentation, including installation and operating manuals shall be in English
Products to comply with EC or International quality and Safety standards: BS 476 Fire Tests BS EN 3: Portable Fire Extinguishers BS 336:2010 Fire Hose couplings BS 750: 2012 Underground Fire Hydrants BS 5041-1 1987 Fire Hydrant Equipment BS EN 671-1:2012 Hose Reels NFPA 20: Standard for the Installation of Stationery Pumps for Fire Protection Or any other Equivalent National Standards
Name of nearest local after-sales agent (if applicable): [Bidder to specify name & address]
Name/Signature of Bidder: To be returned to UNESCO as part of the Bid Submission.