MiCOM C264 PSL &INTERLOCKINGSCONFIGURATION
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
2/30
Schneider Electric 2- CS&P – C264 PSL 1 Interlock Configuration – E01
• Content
General Features
PSL Creation
Interlocking Equation Creation
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
3/30
Schneider Electric 3- CS&P – C264 PSL 1 Interlock Configuration – E01
• Content
General Features
PSL Creation
Interlocking Equation Creation
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
4/30
Schneider Electric 4- CS&P – C264 PSL & Interlock Configuration – E01
• Technical Data (1)1) Number max of PSL / INTERLOCK per MiCOM C264 => 768
2) PSL Inputs :- SPS, DPS, MPS (Boolean value per status defined in profile) - MV (Thresholds, Boolean values defined in profile)
- SPC, DPC (Boolean value per control defined in profile ) 3) PSL Outputs :- SPS (advised, advantage => follow execution)
- SET when PSL TRUE- RESET when PSL FALSE
- SELF-CHECK-FAULTY when PSL INVALID- SPC, DPC (FORBIDDEN)
- SET/CLOSED when PSL TRUE- RESET/OPEN when PSL FALSE- NOTHING when PSL INVALID
4) PSL Timers :- Settable timer through MiCOM S1 PACiS
5) PSL Booleans :- Settable input through MiCOM S1 PACiS
Limit = 50 / C264
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
5/30
Schneider Electric 5- CS&P – C264 PSL & Interlock Configuration – E01
• Technical Data (2)1) Since PACiS V4.6 version, it is possible to filter the transient 00 position
in PSL evaluation for DPS (jammed). This allow to see in FBD the lastposition during jammed position.Ex: if from Open state, it goes to jammed , so Open state is considered in
the FBD till Closed state appears.2) To configure this possibility, in the “Interlocking ” tab of DPS profile ,choose “Ignored ” for “Motion ” parameter, as follow:
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
6/30
Schneider Electric 6- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function AND
TRUE
FALSE
INV
TRUE
TRUE
FALSE
INV
FALSE
FALSE
FALSE
FALSE
INV
INV
FALSE
INV
AND
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
7/30
Schneider Electric 7- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function OR
TRUE
FALSE
INV
TRUE
TRUE
TRUE
TRUE
FALSE
TRUE
FALSE
INV
INV
TRUE
INV
INV
OR
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
8/30
Schneider Electric 8- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function NOT
TRUE
FALSE
INV
FALSE
TRUE
INV
NOT
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
9/30
Schneider Electric 9- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function XOR
TRUE
FALSE
INV
TRUE
FALSE
TRUE
INV
FALSE
TRUE
FALSE
INV
INV
INV
INV
INV
XOR
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
10/30
Schneider Electric 10- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function BISTABLE (RS)
Properties :
- Transition detection- Q is SET when SET input goes from 0 to 1
- Q is RESET when RESET input goes from 0 to 1- Reset has priority on Set
This function is working like this up to PACiS V4.5.0!
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
11/30
Schneider Electric 11- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function BISTABLE (RS)
Properties :- State detection
- Q is SET when SET input 1- Q is RESET when RESET input 1
- Reset has priority on Set
! This function is working like this since PACiS V4.5.1
- Q-1 is the previous value or the value before C264 Init(after DB change only = 0)
Set
Reset
Q
10
10
10
Q-1
INV
INV
INV
INV
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
12/30
Schneider Electric 12- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function TON
Output delayed
Pick-up Timer
Input
Output
INV INV INV
Timer stops
INV INV INV
1
0
1
0
! This timer cannot use value less than 50ms
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
13/30
Schneider Electric 13- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function TOFF
Drop-off output
Drop-off timer
INV INV
INV
INV
Timer stops
INV
INV INV INV
Input
Output
1
0
1
0
! This timer cannot use value less than 50ms
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
14/30
Schneider Electric 14- CS&P – C264 PSL & Interlock Configuration – E01
• Logic Function nMPSnMPS MASK is used for Fast Load Shedding. It reads an MPS status andaccording on boolean values of the gate will output 1 or 0 depending onMPS statusEx: if MPS state is 3, R goes to 0 , and if MPS state is 8, R goes to 1 …
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
15/30
Schneider Electric 15- CS&P – C264 PSL & Interlock Configuration – E01
• Timer & Boolean Settings1) Possibility to dynamically change TON/TOFF timer value using a settableinput.
2) Possibility to create a fixed Boolean value that can be dynamically
changed by setting.
3) These parameters are configured in SCE then appears in C264 setting file
which can be readable using MiCOM S1 PACiS.
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
16/30
Schneider Electric 16- CS&P – C264 PSL 1 Interlock Configuration – E01
• Content
General Features
PSL Creation Interlocking Equation Creation
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
17/30
Schneider Electric 17- CS&P – C264 PSL & Interlock Configuration – E01
• Add / Configure a PSL (1)1) PSL = FBD Automation can be added at Substation , Voltage Level , Bay ,Module level in Electric hierarchy.
FBD Automation :browse “User Function” in “Objects Entry”
2) Define PSL Inputs and Outputs under FBD Automation and link to
datapoint
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
18/30
Schneider Electric 18- CS&P – C264 PSL & Interlock Configuration – E01
• Add / Configure a PSL (2)3) FBD with Inputs and outputs linked to datapoints :
FBD Inputs :using SPS, DPS, …
FBD Output :producing SPS
Runs on PLC :
for substation, voltage level PSL, define onwhich C264 PSL is executed
4) FBD Edition
Right Click, FBD Edit
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
19/30
Schneider Electric 19- CS&P – C264 PSL & Interlock Configuration – E01
• PSL Edition (1)1) FBD Editor :
FBD Inputs
FBD Output
Logic Functions
AND OR XOR NOT RS TON TOFF nMPS
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
20/30
Schneider Electric 20- CS&P – C264 PSL & Interlock Configuration – E01
• PSL Edition (2)2) FBD Construction (1):
1) Select by clicking onleft mouse button,
2) click again to put it
on the desired place
1) Select point to link byclicking to the leftmouse button,
2) Keep the left mouse
pressed to link twopoints
3) when “white” stroke,release mouse
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
21/30
Schneider Electric 21- CS&P – C264 PSL & Interlock Configuration – E01
• PSL Edition (3)2) FBD Construction (2):
to invert input click onthe right button andchoice
“toggle negation”
to create connectionclick on the right
button and choice“insert H/VC”
to create new inputclick on the rightbutton and choice“duplicate”
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
22/30
Schneider Electric 22- CS&P – C264 PSL & Interlock Configuration – E01
• Save PSL1) PSL Saving :Coherence check done at FBD saving
FBD Status :computed by SCE - correct = no conception error inside editor
- failure / modified = conception error insideeditor
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
23/30
Schneider Electric 23- CS&P – C264 PSL & Interlock Configuration – E01
• Add Timer setting1) To create a settable timer value, add an FBD timer object in your
automation.2) Set the default, min, max and step values.3) Set if this parameter is visible & editable or visible & not editable in
MiCOM S1
4) Edit your FBD and link your FBD Timer to the PT input of TON/TOFFgate
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
24/30
Schneider Electric 24- CS&P – C264 PSL & Interlock Configuration – E01
• Add Boolean setting1) To create a settable boolean value, add an FBD Boolean object in
your automation.2) Set the default value, true and false labels.3) Set if this parameter is visible & editable or visible & not editable in
MiCOM S1.
4) Edit your FBD and use your FBD Boolean as any FBD input.
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
25/30
Schneider Electric 25- CS&P – C264 PSL & Interlock Configuration – E01
• Modify Timer & Boolean Values1) Start MiCOM S1 PACiS and open C264 setting file from zip
package generated by SCE.2) Start WFTPD software (ftp server)3) FBD Timers and FBD Boolean will appears as following :
4) You can so modify values according to SCE configuration.
5) Send new values
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
26/30
Schneider Electric 26- CS&P – C264 PSL & Interlock Configuration – E01
• Multi-C264 automation1) as PSL Inputs :- SPS, DPS, MPS coming from another C264
2) C264 exchanges :- GOOSE transmission
C264 executing PSL “has for IEC Server” the C264 sendinginformation to it, with property “Goose only”
(or “Data Model and Goose”)
“Auto Link Client / Server” is existing since PACiS 4.7.x
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
27/30
Schneider Electric 27- CS&P – C264 PSL 1 Interlock Configuration – E01
• Content
General Features
PSL Creation Interlocking Equation Creation
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
28/30
Schneider Electric 28- CS&P – C264 PSL & Interlock Configuration – E01
• Add an Interlocking equation1) Interlocks are added at SPC DPC level
Close Intlk SPS :typed information, result of a FBD when SET => control is allowed
2) SPC Interlocking
Close / Open Intlk SPS :typed information, result of a FBD when SET => control is allowed
3) DPC Interlocking
Intlk viol. SPS :typed information which is SET if a control is
refused due to interlock equation.This is used for some SCADA which have nopossibility to know the reason of a NACK(ex: Modbus protocol).
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
29/30
Schneider Electric 29- CS&P – C264 PSL & Interlock Configuration – E01
• Configure an Interlocking equation (1)1) Interlocks are Mini PSL, define inputs (no output, output is the interlockSPS) and link to datapoints
Close Intlk SPS :typed information, result of a FBD
FBD Interlock :runs on PLC
FBD Inputs :linked to datapoints
8/20/2019 L2 V4 06 C264 PSL & Interlock Configuration E 01
30/30
Schneider Electric 30- CS&P – C264 PSL & Interlock Configuration – E01
• Configure an Interlocking equation (2)2) Interlocks Edition : No RS, No TON, No TOFF