FLEXIBLE HOSE NOT ALLOWED TO LIE ON GROUND
INSTRUCTIONS SIGN RECOMMENDED BY THE MN DEPT OF HEALTH
Instructions Connect your hose to holding tank, place other end securely in drain opening while holding cover with foot. Open RV tonk drain valve. Wash away any spillage on concrete into drain.
MINIMUM 2' ELEVATION - ----i--t----
CONCRETE PAD PITCHED TO DRAIN-~
DANGER Not to be used for drinking or domestic purposes.
,---+-+- WATER CONTROL
II II
VALVE
SELF-CLOSING, TIGHT FITTING, FOOT OPERATED HATCH SET FLUSH WITH PAD
3/4-INCH POTABLE WATER SUPPLY
--...-1-t--- 4-INCH SANITARY SEWER PIPED TO APPROVED SEWAGE DISPOSAL SYSTEM
NOTE 1:
M.R. CHAPTER 4714, SECTION 724.0
ASSE 1001 ATMOSPHERIC VACUUM BREAKER. NO VALVE DOWNSTREAM IS PERMITTED.
INSTRUCTIONS SIGN RECOMMENDED BY
===:::::===@ Ii: 1
THE MN DEPT OF HEALTH
1GN: 2' x 2' MINIMUM
STOP AND WASTE VALVES ARE NOT PERMITTED TO BE INSTALLED UNDERGROUND (SEE SECTION 603.5.18)
NOTE 2:
---------MINIMUM 10' SEPARATION OF ---- BURIED SEWER AND WATER
RISER, UNLESS SEWER MATERIAL IS APPROVED FOR USE WITHIN BUILDINGS (SEE SECTION 609.2). 5' MINIMUM SEPARATION RECOMMENDED.
CURB OR BUMPER TO PROTECT RISERS
CONCRETE PAD: -MINIMUM 3' X 3' DIMENSIONS -MINIMUM 3-1 /2" THICKNESS -TROWELED SMOOTH FINIISH
A DIRECT CONNECTION BETWEEN THE POTABLE NO YARD HYDRANT OR OTHER WATER SUPPLY PIPING IS WATER SYSTEM AND THE RV HOLDING TANK IS ALLOWED WITHIN 1O' HORIZONTALLY OF A HOLDING TANK NOT ALLOWED (SEE SECTION 603.4.4) OR OTHER SOURCE OF CONTAMINATION (SEE SECTION 609.6.1)
RV Sanitary Disposal Station ConstructionDEPARTMENT OF LABOR AND INDUSTRY
Telephone: (651) 284-5063 dli.mn.gov/business/plumbing-contractors/2015-minnesota-plumbing-code
12/20