Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Honeywell Knowledge Series
NetAXS-123
Single Door PoE Installation
Part 2 – Hardware Overview
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
NetAXS-123 Modular Access Control System
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Enclosure Options
• 1, 2 and 3 door installations
• Universal Input 4 Amp Power Supply provides power for:
Standard (Metal)Compact (Plastic)
• High-Impact Plastic Enclosure
• Mount at the Door
• 1 Door POE • Controller
• REX (RTE)
• Readers
• Door Locks and Strikes
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Mounting Options
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Net-AXS-123 Building Blocks
Controller Board with1 Door of I/O
1 Door I/O Board
NXD1
2 DoorI/O Board
NXD2
Field upgradable from a 1-door
to a 2 or 3-door controller
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Net-AXS-123 Building Blocks
• Simple Installation– Power down panel
– Plug in add-on board – no wiring required
– Power up panel
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
NetAXS-123 Door Centric
Controller Only Controller plus1-Door Expansion
Controller plus2-Door Expansion
Three Doors One or Two Readers per Door
Two Doors One or Two Readers per Door
One Door One or Two Readers
Compact Enclosure Standard (Metal) Enclosure Standard (Metal) Enclosure
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Ordering - Made Simple
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
1 Door @ Compact Enclosure + PoE
Compact Enclosure
PoE powers panel and lock
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
1 Door In/Out @ Compact Enclosure + PoE
Compact Enclosure
PoE powers panel and lock
When using In and Out readers, BOTH readers must have HOLD lines
InReader
OutReaderIn
ReaderOut
Reader
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
2 Doors @ Compact Enclosure + 12VDC
Compact Enclosure
PoEonly
powers panel
1- DoorAdd-On Board
(NXD1)
4A, 12VDCPower Supply(Lock Power)
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
1 Door @ Standard Enclosure (internal 12VDC)
Built-in4A, 12VDC
Power Supply(Panel and Lock Power)
1 Door
Standard (metal) Enclosure
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
2 Doors @ Standard Enclosure (internal 12VDC)
Built-in4A, 12VDC
Power Supply(Panel and Lock Power)
2 Doors
Standard (metal) Enclosureincludes
1-Door Add-On BoardNXD1
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
3 Doors @ Standard Enclosure (internal 12VDC)
Built-in4A, 12VDC
Power Supply(Panel and Lock Power)
3 Doors
Standard (metal) Enclosureincludes
2-Door Add-On BoardNXD2
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Installation Scenario
Classroom / Site
Installation Scenario
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Classroom Installation Overview
A small business office with a handful of employees and a manager. The manager is looking for basic card access to prevent costs associated with giving out brass keys.
One door w/door strike (output relay #1) Unlocked during day (9am-5pm M-F)
No egress or door position switch
1 manager , 5 employees Access levels
Master – Always access 24/7 Employee – 6am-6pm M-F
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211 17
NetAXS-123Control Panel
Reader
Electric Strike
Classroom Installation Overview
PoESwitch/Hub
PC with Web Browser
CAT-5
Parts ListOne – NC-NX1P10 kit (includes one
compact enclosure and control panel, one Omni10 reader)
One – Door strike (12 VDC/450 ma)
One – PoE switch or injector
18 awg – 6c t/s18 awg
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Installation
Panel Connections
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Connections – Aerial View
Dip Switch
Jumpers
1
3
2
4
5
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Control Board
15CAT5
Ethernet Cable
Dipswitches
Jumpers2
3 Output Relay (Lock) 4Reader(s)
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Installation
Dip Switches & Jumpers
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
1 – Dip Switch Settings – Address 1/Gateway
NOTE: The gateway is always the first panel that makes the communications connection to PC
(Default Settings)
1
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
2 - Jumper Settings – PoE Power
2
These jumpers are specifically for lock power and DO NOT affect power used to power the
panel. Setting these jumpers tells output relay 1 & 2 if the relay should be NO or NC and to use either PoE or an external power source for lock power.
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Installation
Door Locks, Readers and Power
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
3 - Lock Connections – PoE
(from panel)
3Note: 18/2 Twisted Shielded cable for
up to 500’
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
3 - Lock Connections - External Power Supply
External Power
2
3
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
4 - Reader Connections
4
Note: 18/6Twisted Shielded cable for up to 500’
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
5 - Power & Communications
5
PoE Injector
• PoE injector (800mA to 900mA)• The board consumes 400mA
which leaves 450mA for other devices.
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Control Board Startup LED’s
1 PoEPower LED
2Run LED
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Installation
Panel Communications
Beyond a Single Panel
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
More then 3 NetAXS-123 Panels in Web ModeFIRST panel is always the
GATEWAY panel
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
`
Gateway Panel Plus Up to 30
More Downstream
Control Panels
Up to 64 Additional
Outputs per Control Panel
Up to 64 Additional Inputs per
Control Panel
`
Remote Web Browser
NX4L1 or
NX4S1
(Downstream mode)
World Wide WebLAN/WAN
VPN
Remote Web Browser
NetAXS-123
(Downstream mode)
NetAXS-123
(Gateway mode)
NetAXS-123 and NetAXS-4 in Web Mode
32
GATEWAY panelMUST be a NetAXS-123
Honeywell Proprietary
HoneywellAccess.comà
NetAXS-123_121211
Host Mode with WINPAKRS-485 CommunicationsSerial Communications
Ethernet CommunicationsRS-485 Communications
33
NetAXS-123Gateway
NetAXS-123Gateway