Powerware series 20-160 kVA
Eaton 9390 UPS
2 EATON CORPORATION Product Catalog
Eaton 9390 20-160 KVA
3 www.eaton.com/powerquality 1.800.356.5794
Benefits• Leadingsustainability - Highestefficiencyratingslowerutilitycosts - Lowesttotalcostofownershipandlifecyclecarbonfootprint - Smallestfootprintandweight - Lowesttransportationandinstallationcosts
• Strongerpowerperformance - LowestinputTHDenhancescompatibilitywithupstream powersystems - LowestoutputTHD - Optimumgeneratorsizing - PFCpowersupplycompatibility - Widestvoltagerangeoffering
• Highestreliabilityandavailability - PowerwareHotSync®wirelessparalleling - Superiorbatterymanagement - Inherentredundancy - Scalablearchitectureadaptstoincreasingpowerrequirements
• Robustmanageability - Superiorcontrolandconnectivity
TheEaton®9390uninterruptiblepowersystem(UPS)isadouble-conversionUPSthatresolvesallutilitypowerproblemsandsuppliesclean,continuous,uninterruptiblepowertoconnectedequipment.Whetheryou’reselectingaUPSforabranchoffice,manufactur-ingfloor,medicalfacility,ordatacenter,there’sa9390modelthatdeliversjusttherightcombinationofperformanceandpriceforyourneeds.
Applications
The9390deliverscentralizedbackupsupportandprotectionforthefollowingtypesofapplications:
• Mid-sizedatacenters
• Medicalfacilities
• Schools
• Broadcasting,includingTV,radio,cellandremotestations
• Factory/industrialsuchasPCs,criticalmachineryandoperations
• Pharmaceuticals
• Mid-sizeofficebuildings(PCs,network,phone,storageand serverrooms)
• Mediumsizeretail(phonesystems,officePCs,POS)
• Hotelsandcasinos
• Banking
• Co-locationdatacenterfacilities
100-160 kVA
Innovative design delivers industry-leading power performance
20-80 kVA
4 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Energy efficiency means substantial cost savingsAllUPSsconsumeenergytooperate,andsomeunusedenergyisdissipatedasheatasitpassesthroughtheUPS—themoreheatanddissipatedenergy,thehighercostofoperation.TheefficiencyratingofaUPSmeasureshowlittleenergyiswasted.For exam-ple, a 90% efficient UPS delivers 90 kW of useful power for every 100 kW taken in.Withatransformerlessdesignandsophisticatedsensingandcontrolcircuitry,the9390deliversanefficiencyofupto94 percentwithdouble-conversionprotection.Inadditiontothecostsavings,thisenhancedefficiencyextendsbatteryruntimesandproducescoolerUPSoperatingtemperatures,extendingcompo-nentlifeandincreasingreliabilityandperformance.
Comparison of 90% versus 94% efficient 80 kVA UPS
Percent Wasted kW Cost per kWh Extra energy Extra air Annual savings vs. efficiency hours* and demand cost conditioning cost less-efficient model 90 63,072 $0.13 $8,199 $5,740 94 37,843 $0.13 $4,919 $3,444 $5,576
* Mostly dissipated as heat.
Power performance
Input THD Output PF Efficiency
Eaton9390 <4.5% 0.9 94%Competitor“A” <7.5%* 0.8 92.5-93%Competitor“B” <10%* 0.8 90-95%Competitor“C” <10%* 0.8 92-93%Competitor“D” <7%* 0.8 87-93%Competitor“E” <7%* 0.8 90-93.3%Competitor“F” <3% 0.8 88.5-94%Competitor“G” <3-7% 0.8 87%(estimated)
*w/filter (~30% w/out)
80
100160 kVA @ 480V
100908070605040302010
82
84
86
88
90
92
94
96
9894.65%
% Load
Eaton 9390 160 kVA Efficiency Curve
% E
ffic
ien
cy
Operational savings
Efficiency comparison
Efficiencydifference: 2% 3% 4% 1year 5years 1year 5years 1year 5yearsSavings–80kVAUPS $2,788 $13,940 $4,182 $20,910 $5,576 $27,880Savings–160kVAUPS $5,576 $27,880 $8,363 $41,815 $11,151 $55,755CO2Savings–80kVA 19.3tons 96.5tons 23.1tons 115.5tons 26.9tons 134.5tonsCO2Savings–160kVA 26.9tons 134.5tons 34.5tons 172.5tons 42.2tons 211tons
Alternative voltages for IT data center poweringInadditiontoconventional(208and480)voltagecapabilities,the9390nowhastheabilitytosupportdirect-connect400/230VacforpoweringdirectlytotheITrack.ThiscapabilityallowsforthedeploymentofaUL/CEratedUPSthatcanprotectanddistribute400/230VacdirectlytoITrackswithoutanadditionalstep-down transformer.Someoftheefficienciesandbenefitsofthisalternativevoltagepoweringare:
• Eliminationofthestep-down480-208volttransformerlowersheatlossesandsavesvaluablefloorspace inthedatacenter
• HighervoltagedirectlytoITequipmentallowsittooperateathigherefficiency(nochangesrequired,as virtuallyallserversareratedtooperateatupto240Vac)
• Nochangestopowerdistributionequipmentsinceconnectorsandcircuitbreakersalreadyexistwith theseratings
• TheuseofEaton’shighefficiency9390UPSinsuchanapplicationfurtherimprovessystemoverallefficiency.
• Multiplestudiesshowthatupto5%overallefficiencygainscanbemadeversusequivalent480or208Vacsystems,resultinginthousandsofdollarsinsavingsperyear.
5 www.eaton.com/powerquality 1.800.356.5794
Consistent efficiency throughout UPS load rangeManyUPSscitegreaterthan90%efficiencywithoutmentionoflowornoloadrange.Today’saveragesystemoperatesatonly55%ofitsratedloadorcapac-ityrange.However,efficiencyisusuallyreducedinthislower-loadoperatingstatus—notsowiththe9390,whichreachesoptimalefficiencyratesatlessthanhalfload—andmaintainsthisoptimalefficiencythrough-outtheloadrange!
Low input current THD enhances generator compatibilityElectronicdevicesandUPSsarebuiltwithsomecomponentsthatarenon-linear.Whenvoltageisappliedtoacircuitconstructedofnon-linearcomponents,thecircuitmaynotrespondlinearly(currentmaynotfollowthevolt-ageinalinearmanner).Thesecomponentsmayevencreatefrequenciesotherthanthefun-damentalappliedfrequency(60Hz).
Thesefrequencies(harmonics)occurinoddmultipliesof 60Hz.Thedegreeofoccurrenceiscalledtotalharmonicdistor-tion(THD).Ifthepowersourcecan’trespondtoallfrequenciesdemandedbythecircuit,thenfurtherdistortionoftheappliedvoltagemayoccur—creatingmorecomplication.EveryUPSproducesalevelofharmon-ics.Unchecked,harmonicscanreduceoverallpowerfactor,causesensitivedevicestomal-function,prematurelyageequip-ment,andcausescreensanddisplaystoflicker.
Toavoidthesenegativeeffects,the9390usesaspecialinputcircuitthatkeepscurrentTHDatlessthan4.5%atfullload—withoutcompromisingefficien-cy.Asaresult,the9390trans-fersmaximumpowerbetweenthesourceandprotectedloadandisexceptionallycompatiblewithmultiplepowersources,especiallyauxiliarygenerators.InthePowerPerformancechartonthepreviouspage,notethatmostmanufacturersrequireaninputfiltertominimizeTHD.ThisaddedfilterresultsinlowerefficiencyfortheUPS—acon-sequencenotgenerallynotedinmarketingmaterials.
LOAD Power Factor RANGE Chart
Leading Lagging
-1 -0.75 -0.50 -0.25 0 0.25 0.50 0.75 1kVAr
kW
PF=0.9 100% kW PF=1 PF=0.9PF=0.8
Most competitors UPSs must derate 30-40% to support loads in this range
Without derating
1
0.75
0.50
0.25
Many competitive UPSs cannot operate in this range without significant derating
V1
V2
Full range of load power factor
Power factor perfor-mance maximizes com-patibility and meets high power factor load requirements Powerfactor(PF)describestheslightphaseshiftbetweenvoltageappliedtoacircuitandcurrentthatthecircuitdrawsinresponsetotheappliedvolt-age.Themaximumpowerfac-torpossibleisunity(1.0),ornophaseshiftbetweenthevoltageappliedandthecircuitcurrentresponse—maximumtransferofpowerbetweensourceandload.However,intherealworld,theUPSmustbeabletoacceptpowerfromanddeliverpowertocircuitsthathaveawiderangeofpowerfactors.
Olderorwornequipmentoftenresultsinlowerpowerfactorreadings.Somenewserversoperateatunitypowerfactor.Lightlyloadedfacilitiessuchasbrandnewdatacenters,canoftenshowleadingpowerfactorreadings.
Onoutput,theultrahigh-speedswitchingpulsewidthmodula-tion(PWM)inverterenablesthe9390toprovideitsfullratedpowercapabilitytotheload,downto0.9leadingpowerfac-torwithoutde-rating.
Double-conversion design offers highest available protection Unlikeothercommerciallyavail-ableUPStechnologies,thedouble-conversiondesigncom-pletelyisolatesoutputpowerfromallinputpoweranomaliesanddelivers100%conditioned,perfectsinewaveoutput— regulatingbothvoltageandfrequency,providingprotectionfromallninecommonpowerproblems.
Duetothe9390’sbuiltinhigh-efficiencycapability,itoperatesinaconsistent,efficientstatuswithoutcompromisingpowerprotection.Evenwhenpresent-edwiththemostseverepowerproblems,poweroutputremainsstablewiththe9390.OutputvoltageTHDisheldwithintwopercentofnominalspecificationforlinearloads,withinfiveper-centfornon-linearloads—mak-ingthe9390idealforsupportingequipmentthatissensitivetoadistortedvoltageinputasaresultofharmonicloads.Intheeventofautilitypowerfailure,thereisnodelaytransferringtobackuppower.
6 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Scalable architecture meets your current and future load requirementsThe9390supportsupto160kVAtodeliverpowerprotectionforsmallbranchofficestolargecorporatedatacentersandcommunicationnetworks.Uptosixequivalent9390modulescanbeparalleledforadditionalcapacityorredundancy,withouthavingtoutilizeacentralbypasscabinet.Inallparallelingcon-figurations,eachUPSmoduleoperatesindependentlyyetiscompletelysynchronizedwiththeothers.ParallelUPSmodulescanprovideN+1,N+2,orgreaterredundancy.
Powerware Hot Sync technology: The culmination of power reliabilityEaton’spatentedPowerwareHotSynctechnologyenablesmultipleUPSstosharetheloadequally,eliminatingthetransfertimewhenshiftingtheloadfromonemoduletotheother.Theloadsharecontrolalgo-rithmsmaintainadjustmentstovariationsintheoutputpowerrequirements.
WhentwoormoreUPSsoper-ateinparallelforcapacityandredundancy,HotSyncaddressesthetwoprimaryconcernsofloadsharingandselectivetrip-
Powerware Hot Sync wireless paralleling technology for capacity or redundancyThistwo-modulesystemshownbelowcanbeconfiguredas160kVAN+1redundant(320kVAcapacity with36-inchtiecabinet).Thewidthofthisconfigurationisacompact164.6inches.
Tie Cabinet
160 kVA UPS Modules
BatteryBattery
ping.Toaddresstheseconcernsforreliability–thedegreeofautonomyandthecomplexityofimplementation–HotSynccombinesdigitalsignalprocess-ingandanadvancedcontrolalgorithmtoprovideautomaticloadsharingandselectivetrip-pinginaparallelsystem,aswellascompleteautonomyofthemodulesandaskillfullysimpleimplementation.The9390achievesoptimumreliabilityandflexibilitywiththefollowingdesignfeatures:
• Unlikeotherparallelingtech-niques,thereisnosystem-levelsinglepointoffailure
• HotSyncsystemsarecapableofparallelingforbothredun-dancyandcapacity
• Byusingapeerconfigura-tionasopposedtoamaster-slaveconfiguration,HotSyncensuresthateachmoduleisoperatingindependently
• Noaddedcircuitryorcom-ponentsarerequiredtobeswitchedintooperatein parallel
• Withthousandsofsuccessfulsystemsinstalledglobally,HotSyncisaproventechnology
• TheoutputofmultipleUPSsremainsinphasesothatstatictransferswitchescon-nectedbetweentheseparatedistributionpathsmaychangestateseamlesslywhennec-essary
Eachparallelunitoperateswithitsownbatterystring–ifanyunitgoesofflineoristakendownformaintenance,theremainingunitssupporttheloadfullywiththeirbatterycapabilities.Ifanybatterystringfails,theremainingstringscon-tinuetosupporttheload–thuseliminatingakeypotentialsinglepointofsystemfailure.
7 www.eaton.com/powerquality 1.800.356.5794
Static Auto TieTheStaticAutoTie(SAT)systemenhancesreliabilityevenfurthersofullloadtransferscanbemadeautonomously.SATaddsawrap-aroundstaticswitchtothetiebreakerintheHot-Tiesystem,thenaddsintelligentcontrolssoapowerprotectionsystemmadeupoftwoormoreseparateUPSsystemscanauto-maticallytransferentireloadsintheeventoftraumatic,cata-strophicfailureoronesystem–ararebutcostlycircumstance.
IntheSATconfigurationdis-playedinthediagrambelow,thereisaHot-TiecircuitbetweentheoutputsofthetwoUPSmodulesthatautomaticallytransferstheloadsfromonetotheotherasnecessary.Thislesscomplex,dualpatharchitecturestreamlinesthedistributionsys-temtoeliminateseriesswitch-ingandreducethepotentialdowntimeofsinglepowercordloadsbyupto50percent.Asaresult,theSATarchitectureoffersanumberofbenefits,including:
• Reducedcapitalexpenses
• Eliminatesneedfortraditionaldownstreamstatictransferswitches
• Reducedinstallationcosts
• Increasedsystemreliabilityandefficiency
• Decreasedmaintenancerequirements
• Reducedraisedfloorspacerequirements
Advanced battery management optimizes battery performance and service lifeEaton’sABM®technologyusesauniquethree-stagecharg-ingtechniquethatsignificantlyextendsbatteryservicelifeandoptimizesrechargetime,comparedtotraditionaltricklecharging.Anintegratedbatterymanagementsystemtestsandmonitorsbatteryhealthandremaininglifetime,andpro-videsadvancenotificationtoguidepreventivemaintenance.Optionaltemperature- compensatedchargingmoni-torstemperaturechangesandadjuststhechargerateaccord-inglytoproperlychargethe
batteryandgreatlyextendbat-terylife.Avariablebatterybusaccommodates384to480V(192-240cell)configurations,sothebatterycapacitycanbematchedtoyourexactruntimerequirements—eitheraspecificruntime,anextensiontoexistingbatteryruntime,orutilizationoflegacybatteryinstallations.
WithremotemonitoringoftheUPSandbatterysystem,Eatonistherewithyou—abletorespondtoalarmsandseereal-timebatterydatatoavertpoten-tialbatteryproblems.
Fully Deployed Static Auto Tie Configuration
Generator
PDU
PDU
PDU PDU
PDU
S TS A TS
Batteries
9390 UPS 9390 UPS
A TS
STATIC AUTO TIE
SIS SIS
Static S wit c h Auxiliary Generator
Bus
SBM SBM Auto
Static AutoTie Controls
A TS
TIE
Single P ower Cord L oads Single P ower Cord L oads
Utility S ource A
Utility S ource B Auxiliary Generator
Bus
Dual PowerCord Loads
8 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Flexible installation options expedite deployment and save valuable spaceThe9390offersthesmallestfootprintofanyUPSinitsclass—35to50percentsmallerthancompetitiveunits.CablingcanentertheUPSfromeitherthetoporbottomofthecabinettoprovideeasierandflexibleinstallation.The9390providesfrontpanelaccessforallservicesandoperation,increasingserviceabilityandreducingmeantimetorepair(MTTR).Andsincethecompact9390cabinetcanbeinstalledagainstbackandsidewalls,youhavemorelocationoptions,installationisfastandeasy,deploymentcostislower,andyousavevaluabledatacenterspace.
WeightAt$.30perpound,the9390averagesacross-countryfreightsavingsofover$630.Withatransformerlessdesign,EatonUPSsolutionsmeetorexceedvirtuallyallfloorloadingstandards.Andwiththislowerweight,unitscanbemovedwithoutheavycapitalequipmentandcanfitinallstandardfreightelevators.
Space savingsWithafootprintof597squareinches,the9390isafractionofthe1281squareinchesthat
thecompetitiontakesup.Withamanageablesize,includingacompact72-inchheight,the9390fitsthroughmostdoorswithease,andrequiresnodismantlingtogetittoitsfinalinstallationlocation.
Retrofit applicationsThe9390isperfectforretrofitoperations.WhenanexistingUPSisexceedingcapacitybuthasnoroomtoexpand,orwhentheservicecontractisexpir-ing,theexistingUPScanberemovedandreplacedwitha9390thatoffersmorepowerinlessspace.
Eaton 9390 Weight = 580 pounds 18.9 x 31.6 in.
Competition’s Weight = 2700 pounds 32.5 in. x 34.9 in.
Big power, small footprint
• Serviceprotectionplan7x24coverage,eight-hourresponse(upgradetofour–ortwo-hourwhereavailable),parts,laborandunlimitedon-siteemer-gencyresponsesupport
• eNotifyRemoteMonitoringservice:7x24criticalalarmnotificationandmonthlyreportsonUPSbatteryhealth
• 7x24technicalsupportaccess
Inadditiontothewarrantyandfirstyearofon-sitecoverage,Eatonoffersawidevarietyofsupportagreementsforcon-tinuedpreventiveandemer-gencyresponsemaintenance.PowerTrust™ServicePlansinclude:
• UPSandbatteryscheduledpreventivemaintenance
* Refer to the Eaton Corporation Limited Factory Warranty for Eaton three-phase UPS products for specifications, limitations and terms. Service and support specifications may vary by country.
Industry-leading war-ranty and service plans deliver peace of mindEatonrecognizesthatsuperiorreliabilityrequiresflawlessexe-cutionfromitsservicesteam.Every9390includesanonsitestart-upfromafactory-trainedfieldtechniciantoensureproperinstallation,operationandcus-tomertraining.Inaddition,weincludeafullyearofonsite7x24partsandlaborwarrantyandserviceprotectionplancover-ageatnoextracost.Includedatnoextrachargewitheverynew9390:
• 7x24x365startupserviceandcustomertraining
• One-yearlimitedfactory warranty*
Serviceability and accessibility Beingapre-wired,integratedmodule,the9390savestimeandcostofinstallationandcablingexpensesbecauseofstandardtoporbottomentrydesign.Andwithfrontaccess,the9390canbeplacedinacorneroragainstawall—easilyavailableforserviceandsavingvaluablespace.
Internal scalabilityUpgradinga9390isassimpleasaphonecalltoanEatonservicetechniciantorequestaninternalupgrade.Forexample,a40kVAunitcanbefieldupgrad-edtoan80kVA,anda100kVAunitcanbeupgradedtoa160kVA—allperformedonsiteandwithoutcostlyadditionalcabine-tryandconnections.Thisfeatureallowsyoutoplanelectricallyforgrowthandeliminatefuturecablingcosts.
• Partsandlaborcoverageforelectronicsand/orbatteries
• Factory-trainedtechnicianswithgenuinePowerwarepartsanddiagnostictools
• eNotifyRemoteMonitoringservice
• Availablecoverage:7x24,eight/four/two-hourresponse,or8x5nextbusinessdayresponse
• 7x24technicalsupportaccess
9 www.eaton.com/powerquality 1.800.356.5794
eNotify Remote Monitoring serviceAllPowerTrustServicePlansincludeEaton’seNotifyRemoteMonitoringservice,enablingEatonservicetechnicianstoremotelymonitoryourUPSandbatteries.Withtechnicalexpertsavailabletorespondimmedi-atelyandresolvemanyissuesremotely,eNotifyfeatures7x24real-timemonitoringof100+UPSandbatteryalarms.
TheeNotifyserviceprovidesyouwithmonthlye-mailreportsdetailingtheongoinghealthofyour9390UPS.Thecustomermonitoringreportdeliversinfor-mationonyourunit’svoltages,loadsandexternalfactorssuchastemperatureandhumidity.Additionally,thereportprovidesinformationabouttheattachedbatteriesandsystemavailability.AllofthesefactorscontributetotheRelativeHealthIndex(RHI)scorethatallowsyoutocom-pareyourunit’shealthtoEaton’soptimumUPSoperatinglevels.
Proactivemonitoringisalsoincluded.Uponreceiptofbothstatusandevente-mails,anom-aliesarecheckedforincomingparametricoreventdatalogs.Ifananomalyisdetected,Eatonanalystsfurtherstudythedataforpossibleimpendingfailuresandtakeappropriateaction.Thefollowingcriticalalarmsarepro-videdbyeNotify:
• UPSoutputpowerwillturnoffaftertheconfigured delayperiod
• Lowbatteryalarmpresent
• UPShardwarefaultdetected
• UPSbatterycompletely discharged
• UPSinverterfaultdetected
• UPSinternallybypassed
• UPSoutputhasbeen turnedoff
• UPSshutdownimminentalarmconditionexists
• Thefailureofoneormorefuseshasbeendetected
• Arelay,contactororbreakerhasfailed
TheeNotifyRemoteMonitoringServiceprovidesconfidencethatEatoniscontinuallywatch-ingyour9390andwillcombineitstechnicalresourcesandfieldtechniciansasneededtoquicklyrespondtocriticalalarms.
Eaton’s total PowerChain Management solutionEatonviewsyourpowersys-temasastrategicasset–anapproachwecallPowerChainManagement®.Eaton’sPowerChainManagementsolu-tionscanhelptransformcom-plicatedpowersystemsintoasingle,integratedsystemeasilyvisibleandmanageableasastrategicbusinessasset,pro-vidingasignificantcompetitiveadvantage.
Ifyourcompanyislikemost,itspowersystemwasbuiltovertime.Astheorganization’sneedschanged,additionalequip-mentwaslikelyretrofittedintothesystem,withacircuitbreak-eraddedhereandatransformerreplacedthere.Theresultcanbeapowersystemthatisacom-plicatedmixtureofoldandnewequipmentfromseveraldifferentmanufacturers.Becausethereisnocommonmeansofcommuni-catingacrossvariedequipment,gatheringdataacrosstheenter-prisecanbequitechallenging.
Power Xpert ArchitectureThecomplexityofgatheringdataamongvariousdevicesmakesitdifficulttogetaclearpictureofwhat’shappeninginsideyourpowersystem,whichdecreasesyourabilitytomanageyourpowersystemeffectively.Consequently,businessresultssuffer,becauseyourenterprisedependsonitspowersystem.
Eaton’sPowerXpert® Architecture,thebackboneofourPowerChainManagementsolutions,enablesyoutomoni-tormuchmorethanyour9390UPS;ittransformsyourpowersystemintoanintegrated,agilesystemthatdeliversrealcompetitiveadvantages.WiththesoftwareandhardwarecomponentsofPowerXpertArchitecture,youcanmoni-tor,control,andmanageyour
completepowersystemeffec-tivelyandefficiently,includingPDUs,batteriesandothercriti-calequipment.Usingasimple,Web-basedinterface,thevariedelementsofyourpowersystemareintegratedintoasingleview,withtheabilitytoeasilymonitortheavailabilityandreliabilityofelectricalpower,lowerenergycosts,extendequipmentlife,andmore.
Optimize your power systemPowerChainManagementcanalsohelpyoumanageyourpowersystemforpeakper-formancebyintegratingandoptimizingyourpowerassetsandensuringthattheyalignwithyourbusinessgoals.
OnceyourpowersystemislinkedtoanEthernetnetworkviathePowerXpertArchitecture,youcanconnecttoandshareinformationwithavarietyofapplications,suchasthebuildingmanagementsystemmonitoringyourHVACequipment,oryourenterpriseaccountingsystem.PowerXpertArchitecture’sopenstandardsandscalableapproachmakeiteasyforyourpowersystemtogrowandadapttoarapidlychangingenvironment.
Power Xpert Software is designed to take the complexity out of manag-ing your power system and provides a clear picture of what is happen-ing at a component, device and system level.
10 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Specialized applicationsThe9390isn’tjustanindustry-leadingUPS–italsoservesinspe-cializedcapacitiesacrosstheglobe.Withitslightweightdesignandminimalfootprint,itisusedinavarietyofapplicationswheremobil-ityisarequirement.
Power conditionerThe9390isadouble-conversionpowerconditionerthatresolvesutilitypowerproblemsandsuppliesclean,continuous,regulatedpowertoconnectedequipment.Whetheryou’reselectingapowerconditionerforabranchoffice,manufacturingfloor,medicalfacilityoralargedatacenter,there’sa9390modelthatdeliversjusttherightcombinationofperformanceandpriceforyourneeds.
Medical imaging and equipment protectionHavingbeentestedandcertifiedforuseinmedicalimagingsystemapplicationsbyallmajorsuppliersofX-ray,MRI,andCTmachines,the9390medicalimagingversionisspecificallydesignedtoprotectthesecriticalmachines.
Frequency converterThe9390canbeconfiguredtooperateasafrequencyconverter forspecializedapplicationswhereprotectedpowerisrequiredandconversionfrom50to60Hzor60to50Hzisneededforsystemoperation.Forexample,the9390canactasafrequencyconverter inNorthAmericanapplicationswhereEuropeanelectricalequipmentisbeingusedorwhereNorthAmericanequipmentisdeployed internationally.
The 9390 can be used without batteries as a power conditioner.
The 9390 is designed to handle loads that can go from a minimal 5 kVA to 130 kVA instantly when a medical image is taken, for example.
11 www.eaton.com/powerquality 1.800.356.5794
Integrated Battery Cabinet (IBC)Eatonofferstwoversionsofbat-terycabinetswhichline-upandmatchthe9390;theIBC-SandtheIBC-L,eachofferingawidearrayofruntimes.See powerware.com/9390foroptionsandruntimecalculations.
Flexibility• Avariablebatterybus accommodates384to480Vconfigurations,sothebatterycapacitycanbematchedtoyourexactruntimerequire-ments–eitheraspecificruntime,anextendedruntime,anextensiontoanexistingbattery,orlegacybatteryinstallations
• Daisychainuptofour cabinetstogetherfor extendedruntimes
• Integral,line-up-and-matchconfigurationsarestandard
• Remoteconfigurations areavailable
• Powerwarebrandbatteries areavailablewithathree-yearwarranty;otherbattery configurationsareavailablewithaone-yearwarranty
Serviceability• Frontaccessonlydesign andtop/bottomcableentryprovidesinstallationflexibilityandenhancesservicing
• Modular,removablebatterytraydesignandquick disconnectsbetweentrayassembliesoptimizesperiodicmaintenance
• Variablebatterybusallowsthesystemtobereconfiguredtemporarilytomaintainopera-tionwhilereplacementbatter-iesareobtained
Reliability• BatterycabinetsareUL1778listed
• FlameretardantbatteriesmeetUL94V2forcomputerroominstallation
• DC-ratedcircuitbreakerineachcabinetallowsmultiplebatterystringstobeservicedindependentlyofeachother,assuringbackuppowerisalwaysavailabletotheUPS
• CircuitbreakerfeaturesUVRtripauxiliariesforsystemEPOandUPSsensingofbatterybreaker
IBC-S with door opened IBC-L with doors opened
73.7”
31.6”
22.4”
73.7”
31.6”42.7”
IBC-LIBC-S
12 EATON CORPORATION Eaton 9390 Uninterruptible Power System
• MaintenancebypassenablespowertocompletelybypasstheUPSpowermodule.Youcanthenserviceorreplacethemoduleincompletesafe-ty,withoutinterruptingpowertocriticalsystems.
MaintenancebypassisinternallywiredatthefactoryinsidetheIDCsothatonlyinputcablesandUPSconnectionsneedtobemadeinthefield.
Simplified installation and clean appearanceTheIDChasthesamelookandfinishasthe9390itcompli-ments.Thecabinetisshippedwithinterconnectingcablesforfastandeasyinstallation.Theresultisacleanlookthatenhancestheappearanceofyourdatacenter.
Integrated manage-ment and support for enhanced confidenceThe9390andtheIDCcanallbemonitoredandmanagedbyLanSafe®,PowerVision®,andFORESEER®software.This closeintegrationprovidesgreat-ervisibilitytoyourcompletepowerprotectionanddistribu-tionstructure.
EatonbacksuptheIDCwiththesameone-yearlimitedfactorywarranty*weofferonthe9390UPSmodels.Youcanhaveboththeconfidencethatbothyourpowerprotectionanddistribu-tionaresupportedbyEaton’sbest-in-classserviceorganizationandstrongcustomerservicecommitments.
* See the Limited Factory Warranty for 9390 products for details.
40-80 kVA IDC Bypass/transformer/ distribution cabinet
Integrated Distribution Cabinet (IDC)TheEatonIDCisspecificallydesignedtocomplimentthe9390.Withthisoptionalcabinet,Eatonoffersacomplete,one-stopshopforpowerprotectionanddistributionsolutionsthatiseasytodesign,install,custom-izeandmanage–whiledeliver-ingpay-as-you-growscalabilityforfutureexpansion.
Pre-configured for ease of use, mix-and-match for flexibilityTheIDCispre-configuredwiththemostpopularpowerdistribu-tionoptionsforeaseofdesignandinstallation.Inaddition,theIDCalsoofferstheflexibilitytomixandmatchpowerdistribu-tion,voltagetransformationandmaintenancebypassoptionstoselecttherightcombinationofthefollowingcapabilitiesforyourdatacenterrequirements:
• Powerdistributionoptionsenableyoutodistributepowertoserversorracksviadistributionpanelboardsordistributepowertolargerloadsviadistributioncircuitbreakersorterminalblocks.
• Voltagetransformationallowsyoutochangeoutputvoltagelevels.Forinstance,youcouldconvert480VacoutputfromtheUPSinto208/120VacoutputfromtheUPStoservedatacenterloads.K-ratedtransformersareavailable tosupportloadswithhighharmoniccontent.
Features• Two,threeorfour-breakermaintenancebypass
• TransformeroptionsuptoK20
• (2)42-polepanelboards
Or
• (1)42-polepanelboardandupto(3)250Adistributionbreakers
Or
• Upto(6)250Adistributionbreakers
• Lineandmatchorremote
• Castersandlevelingfeet
• Panelboardscomewithindividual225Amainbreaker
• Neutralratedforharmonicloads(200%)
• DistributionbreakersareEatonJGelectronictrip -Twoelectronicsensorsavailable100Aand250A -100Asettings40-100Atrip(eightsettings) -250Asetting100-250Atrip(eightsettings)
13 www.eaton.com/powerquality 1.800.356.5794
Typical application of 9390 Integrated Distribution Cabinet distributing power to IT racks.
480V input and 208/120V output with BIB.
14 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Integrated Accessory Cabinets for customizable configurationsEatonoffersseveralconfigura-tionsofIntegratedAccessoryCabinets(IAC)forusewiththe9390UPS.MajorfunctionsoftheIACinclude:maintenancebypass,paralleltiecapabilityandpowerdistributionwithcombi-nationsupto(2)42-polepanel-boardsand(6)sub-feedbreakersperIAC.
TheIACisprimarilyavailableintwoforms–eithera200mm(8”)sidecarboltedtotheUPS(maintenancebypassortie)ora570mm(22.5”)free-standingcabinet(maintenancebypass,tieordistribution).ThesizeoftheIACisprimarilydependantonfunctionandrating.
IAC-SB and IAC-B Maintenance bypassMaintenancebypassconfigura-tion(MBP)andmaintenanceisolation(MIS)breakersenablepowertocompletelybypasstheUPSpowermodule.Themodulecanthenbeservicedsafelyorreplacedwithoutinterruptingpowertocriticalsystems.Anoptionalbypassbreaker(BIB)andrectifierinputbreaker(RIB)provideasinglewiringpointinputtotheUPSaswellasaconvenientmethodforremovingpowerfromtheUPSwhenusingmaintenancebypasstosupplytheload.
Features
• Lineandmatchdesign
• Two,threeorfour-breakermaintenancebypass
• Nointernaltransformers
• SmallestcabinetshipsboltedtoUPS(IAC-SB)
• Largecabinetcanberemote-lylocated(IAC-B)
IAC-ST and IAC-T Tie Cabinet• ParallelUPStiecabinet (redundant).Seeone-line diagramonnextpage.
• Two-breakertiewithmainte-nancebypass(IAC-Tonly)
• Two-breakertie-with mainoutput
• Two-breakertie
• Wall-mountedmaintenancebypass,tieanddistributionpanelsarealsoavailable
IAC-B Maintenance bypass (160 kVA)
Rectifier input (not shown)
Bypass input
Bypass breaker
UPS output (isolation)
System load breaker (SLB)
UPS #2 output (MOB 2)
UPS #1 output (MOB 1)
IAC-T Parallel Tie Cabinet
8” 22.5”
160 kVA 208V IAC-B
80 kVA 208 & 480V
160 kVA 480V IAC-SC
IAC-D Distribution Cabinet• Usedtoadd(2)additional42-polepanelboards
Or
• (1)42-polepanelboardsand upto(3)250Adistributionbreakers
Or
• Upto(6)250Adistributionbreakers
• Lineandmatchorremote
• Castersandlevelingfeet
• Panelboardscomewithindi-vidual225Amainbreaker
• Neutralratedforharmonicloads(200%)
• DistributionbreakersareEatonJGelectronictrip - Twoelectronicsensors available100Aand250A - 100Asettings40-100Atrip (eightsettings) - 250Asetting100-250Atrip (eightsettings)
15 www.eaton.com/powerquality 1.800.356.5794
42-pole panelboard
Main Breaker (225A)
for 42-pole panelboard
IAC-D (with dead front removed)
Distribution breakers electronic adjustable with 250A sensors 100-250A with 100A sensors 40-100A
IAC-D Distribution Cabinet
Two UPS parallel configuration with 8-inch sidecar tie cabinet
Neutral connections
Distribution breakers
16 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Power Distribution Unit (PDU)TheEatonPDUprovidesreliabledatacenterpowerdistributionforbothraisedandnon-raisedfloorapplications.Toensurethehighperformancerequiredfortoday’sdatacenters,thisEaton-designedandmanufacturedPDUprovidesthefollowinginanintegrated,factory-testedpackage:
• State-of-the-artmetering
• Isolation
• Voltagetransformation
• Electricaldistribution
• Equipmentprotection
• Computer-gradegrounding
Additionally,whencomparedtohard-wiringmethods,thePDUgreatlyshortensinstallationtimeandallowsforeasyrelocationofequipmentduringconsolida-tion,upgrade,orrelocationofthedatacenter.ThePDUoffersabroadrangeofoptionsthatpresentcustomizedpowerdis-tributionsolutionsforeachcus-tomer’sdatacenter.
Itsstate-of-the-artmeteringsys-temprovidesmonitoring,alarm-ing,andremotecommunicationsprovisionstoenableproactivepowerdistributionmanage-mentinthedatacenter.Eaton’sworld-classserviceorganizationsupportsthePDUthroughouttheentirelifecycleofyourdatacenter,increasingreliabilityandprovidingyouwithpeaceofmind.
A 24-month history log provides a powerful aid in capacity planning and diagnosis.
300 kVA PDU with optional sidecar and Energy Management System (EMS)
Monitoring and connectivity EatonPDUsareequippedwiththeEnergyManagementSystem(EMS).TheEMSpro-videsstate-of-the-artmonitoringandalarmingprovisionsthatallowyoutomonitorpowercon-sumptionandquality,manageandplanpowerneeds,andreactquicklytoanypotentialproblemsdowntothebranchcircuitlevel.Comprehensiveconnectivityoptionsenablesecure,remotepowermanagement,real-timesystemstatusinformationandnetworkconnectivitywiththeoptionalPowerXpertGatewayinterfacecard.Thelatesttech-nologyisemployedbythemoni-toringsystem,whichincludesan 8”x40”LCDforclarity,asoft-keydrivenmenuforeaseofuse,andaudio/visualindicatorsthatprovidealarmingandstatusupdates.
Powerconsumptiontrendsforupto24monthscanbeviewedthroughahistorylog—apower-fulaidincapacityplanninganddiagnosisaseventsaretime-anddatestampedastheyoccur.Customalarmsettingsmaybeprogrammedatthefactory,bytheuserorbyourservice organization.
Inaddition,Eaton’soptionalbranchcircuitmonitorwithintheEMScontinuouslymeasuresthecurrentonbranchcircuitsandwarnsofimpendingtrouble,soyoucantakeproactiveaction.Thebranchcircuitmonitoringsystemassessescircuitactivity7x24andprovidestime-stampedmetering,alarmandstatisti-calinformationforeachbranchcircuit.Youreceivesignificantinformationthatisneededtoeffectivelymanageyourentirepowerdistributionsystem.Armedwiththeseinsights,datacenterandfacilitiesmanagerscanmoreeffectivelymanageenergyconsumptiontopreventoverloadconditions,optimizepowerdistribution,andwhenapplicable,accuratelybillinternalcustomersforpowerusage.
17 www.eaton.com/powerquality 1.800.356.5794
Powerware 9390 160 kVA
A closer look inside the 9390
X-Slot communication bays
Top cable entry area
Replaceable converter/inverter modules
Redundant power supplies
Slide out fan trays
Input/Output connections
DC connections
Bottom cable entry area
Modular static switch assembly
Redundant power supplies
160 kVA
X-Slot® communication bays
System control and interface boards
Modular static switch assembly
Top cable entry area
Replaceable convert-er/inverter modules
Redundant power supplies
Input/Output connections
DC connections
Bottom cable entry area
Slide out fan tray
80 kVA
18 EATON CORPORATION Eaton 9390 Uninterruptible Power System
Flywheel integrationAsanalternativetoconventionalbatteries,the9390isflywheelcompatible.(Aflywheelstoreskineticenergywellsuitedforhigh-power,short-dischargeapplications.)Thissystemfea-turesexcellentreliabilityandanadvancedcontrolsystemthatenabletheflywheeltochargeanddischargeathighratesforcountlesscycles—for100%availabilityofpowerandanalter-nativetoconventionalbatteries.
Flywheel features and benefits• Greentechnology–eliminatesleaduseinfacility(batteries),reducesenergyconsumption
• Longerusefullife(20yearsversusaverageoffiveyearsforbatteries)
• Spacesavings
• Easeofinstallation–smallfootprint,nofloorloadcon-cerns,noburdenontem-peraturecontrolsystems,nohazardousmaterials
• Reliability–flywheelsystemscanbeusedinconjunctionwithbatteriesasneededtoprovideacriticalbackupforbatterysystems
Eaton delivers a new level of confidenceTheculminationof40yearsofR&Dexcellence,the9390meansconfidence—confidencethatyourorganization’scriticalsystemsareprotectedbythemostreliable,efficient,andfull-featuredprotectionavailable,andconfidencethatEatonwillbetherewithyouforthelongtermwithpremiumwarrantycoverageandexperttechnicalsupport.
Tofindoutmore,visitourWebsiteatwww.powerware.com/9390,orcontactusat1.800.356.5794.
VDC-XE Flywheel VDC-XE Flywheel with doors open
Flywheel module
DC disconnect circuit breaker
Field-serviceable vacuum pump
19 www.eaton.com/powerquality 1.800.356.5794
IDC technical specifications1
9390 Integrated Distribution Cabinet
General characteristicsInstallation LineupandmatchtoUPS Frontaccessonly Color SameasUPS Construction NEMA1ventilated Inputvoltage 208,480V
Output voltage Isolation 208,208/120V Distribution 208/120V
Dimensions and weight 20-80kVA HxWxD:73.7x35.6x31.6in./1872x904x803mm20-80kVA 1200lb.(maximum) weight100-160kVA HxWxD:73.7x42.7x31.6in./1872x1085x803mm100-160kVA 2185lb.(maximum) weight
CertificationSafety UL1778 Markings UL,CUL
User interfaceCableentry Toporbottom Remote Optional monitoring
Transformer optionElectrostatic Standard shield Insulation 150ºCRise,ClassH Impedance 5%(maximum) K-factor K-1(standard);K13,K20(optional) Compensation 2-FCAN,4-FCBNstandard taps Overload Standard protection
Power distribution option - Panelboard distributionQuantity 2(maximum) Voltage 208/120V Mainbreaker 225A,65kAIC Circuits 84(maximum) Distribution (inlieuofpanelboards) breakers Quantity 6(maximum) Voltage 208/120V Size 250A,65kAIC,adjustabletrip
Maintenance bypass optionMaintenance Optional;2,3or4breakerconfiguration bypass
1. Due to continuing product improvements, specifications are subject to change without notice.
Accessory cabinet dimensions and weight
Accessory cabinet IBC-S IBC-L IAC-B IAC-T
20-80 kVA(H”xW”xD”) 22.5x31.6x73.7 42.7x31.6x73.7 22.5x31.6x73.720-80 kVA(weight) Upto2445lbs Upto4835lbs Upto540lbs100-160 kVA(H”xW”xD”) 22.5x31.6x73.7 42.7x31.6x73.7 22.5x31.6x73.7 22.5x31.6x73.7100-160 kVA(weight) Upto2445lbs Upto4835lbs Upto700lbs Upto700lbs Accessory cabinet IAC-D M90 MBS MTC
20-80 kVA(H”xW”xD”) 22.5x31.6x73.7 Upto24x73x11.5 Upto36x90x11.520-80 kVA(weight) Upto420lbs Upto500lbs Upto500lbs100-160 kVA(H”xW”xD”) 22.5x31.6x73.7 Upto36x90x11.5 Upto36x90x11.5100-160 kVA(weight) Upto420lbs Upto775lbs Upto775lbs
Technical specifications1
Eaton 9390 UPS
UPS rating (0.9 power factor)kVA 20 30 40 50 60 80 100 120 160kW 18 27 36 45 54 72 90 108 144
General characteristicsEfficiency Upto94%Parallelcapability 6xmodulesw/otiecabinet;8xwithtiecabinetAudiblenoise <65dBA@1meterAltitude(max) 2000mat40ºC,104ºF
Input characteristicsVoltage 208,380,400,415,480,6002
Voltagerange +10%/-15%3
Frequencyrange 55-65HzPowerfactor 0.99(min)Inputcurrent <4.5%(noinputfilterrequired) distortionSoftstart Yes capabilityInternalbackfeed Yes protectionBroadcastglobal Yes support
Output characteristicsVoltage 2084,3804,4004,4154,4804,6005
Regulation ±1%Inverter PWMwithIGBTswitchingVoltageTHD <2%(100%linearload);<5%(non-linearload)Loadpower Downto0.9pfleadingwithoutde-rating factorrange
Heatdissipation 80kVA,208V:23.6 (BTU/Hrx1000/Hr)160kVA,208V:47.3 80kVA,380-480V:21.9 160kVA,380-480V:43.8
BatteryBatterytypes VRLA,AGM,Gel,Wet,EatonbatteriesalsoavailableBatteryvoltage 384-480VTemperature Optional compensationChargingmethod AdvancedbatterymanagementHeatdissipation <48BTU@fullload
Dimensions and weights40-80kVAmodules HxWxD:73.7x18.9x31.6in./ 1872x480x803mm120-160kVAmodules HxWxD:73.7x35.6x31.6in./ 1872x904x803mm40-80kVAmodules 640lb./290kg(208V);568lb./ 258kg(480V)100-160kVAmodules 1,060lb./481kg(208V,480V)
ServiceabilityBack/sideagainst Standard wallinstallation
Optional accessoriesModuletiecabinetExternalmaintenancebypassIntegrateddistributioncabinetIsolationtransformer
CertificationSafety UL1778,cULEMC IEC62040-2EN50091ClassA(restrictedaccess)Surge ANSIC62,41Cat,A&B
eNotify Remote Monitoring service7x24remotemonitoringofUPSandbatteryalarms,dailyheartbeat checkandmonthlyreportrequired.ConnectUPS-XWeb/SNMPCardand EnvironmentalMonitoringProbeareincludedwithenrollment.Pleasevisitwww.powerware.com/enotifyformoreinformation.
CommunicationsSoftwarecompatibility-PowerVision,LanSafe, FORESEER,PowerXpert Communicationscards-StandardsystemincludesoneConnectUPSWeb/SNMP/-XCardwithanEnvironmentMonitoringProbe.Twocommu-nicationsbaysstandard.Maximumoffourcommunicationbayswiththecommunicationexpansionoption. Thefollowingconnectivityoptionscanbeinstalledatanytime: -ModusCard -RelayInterfaceCard(UseforAS400s) -IndustrialRelayCard(5A@120V) -HotSyncCANBridgeCardprovidesCANcommunications, isolatedRS-485port -EnvironmentalMonitoringProbe(EMP)Remoteinputs/outputs-twobuildingalarmsinputsandonsummaryalarmcontact(5A@120V)standard FourmorebuildingalarminputsavailablewiththeCommunicationsExpansionOptionRemotepanel-eightbacklitstatusindicatorlampsplusanaudiblehorn
*See the Limited Factory Warranty for 9390 products for details. Batteries are warranted by the battery manufacturer and not by Eaton. **Requires the Parallel Card option (RS-485 port) and requires an external 120V power supply to drive the remote monitor panel.
1. Due to continuing improvements, specifications are subject to change without notice. 2. 600V applications require an input transformer. 3. At full load without battery discharge. 4. Output transformers are required if the desired output voltage is not the same as the input voltage. 5. 600V applications require an output transformer.
Eaton, Powerware, Powerware Hot Sync, ABM, PowerTrust, PowerChain Management, Power Xpert, LanSafe, PowerVision, Foreseer and X-Slot are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective owners.
©2009 Eaton CorporationAll Rights ReservedPrinted in USA9390FXAJanuary 2009
UNITED STATES 8609 Six Forks Road Raleigh, NC 27615 U.S.A. Toll Free: 1.800.356.5794 www.eaton.com/powerquality
CANADAOntario: 416.798.0112 Toll free: 1.800.461.9166
LATIN AMERICAArgentina: 54.11.4124.4000 Brazil: 55.11.3616.8500Caribbean: 1.949.452.9610Mexico & Central America: 52.55.9000.5252South Cone: 54.11.4343.6323
EUROPE/MIDDLE EAST/AFRICADenmark: 45.3686.7910 Finland: 358.94.52.661 France: 33.1.6012.7400 Germany: 49.0.7841.604.0 Italy: 39.02.66.04.05.40 Norway: 47.23.03.65.50Portugal: 55.11.3616.8500 Sweden: 46.8.598.940.00 United Kingdom: 44.1753.608.700
ASIA PACIFICAustralia: 61.2.9693.9366New Zealand: 64.0.3.343.3314 China: 86.21.6361.5599 HK/Korea/Taiwan: 852.2745.6682 India: 91.11.4223.2300 Singapore/SEA: 65.6825.1668