PROTECTION OF
INDUCTION MOTOR
SUBMITTED TO:
Mr. Prateek SinghalElectrical & Electronics Dept.
HCST Mathura
SUBMITED BY:
Devendra Singh(0806421021)Dhirendra Singh(0806421022)
Divyanshu Singh (0806421023)
Diwakar Dubey (0806421024)
8/3/2019 Protection of Induction Motor
2/30
CONTENTS: Introduction.
Abnormal Operating Condition.
Protection Requirements. Protection of Low Voltage IM.
Protection of Large Motor.
Overload Protection of IM.
Protection Against Unbalance.
Protection Against Single-phasing.
Phase Reversal Relay.
8/3/2019 Protection of Induction Motor
3/30
CONTENTS: Phase to Phase Fault Protection.
Stator to Earth-fault Protection.
Fault in Rotor Winding. Reference .
8/3/2019 Protection of Induction Motor
4/30
INTRODUCTIONThe type of protection used for a particular motor
depends upon the switchgear used for its control.
Basically two type of protection are providedfor every motor, and these are-
Thermal Overload Protection. AND
Short Circuit Protection.
The switchgear used for motor control
classified as following two category-
8/3/2019 Protection of Induction Motor
5/30
CONT.... Contactor starter with HRC fuse and thermal over
current relay.
Circuit breaker and associated protective relays.Contactor and fuse are used for motor up to
approximately 150kw.Whereas for large motor circuitbreakers are used.
8/3/2019 Protection of Induction Motor
6/30
ABNORMAL OPERATING
CONDITIONSThe abnormal conditions can be classified as
follow-
Mechanical Overload.(CAUSES)a) Sustained overloads
b) Stalling
c) Prolonged starting or locked rotor
Abnormal Supply Conditions.(CAUSES)a) Loss of Supply Voltageb) Unbalanced supply Voltage
c) Phase Sequence reversal of Supply Voltage
8/3/2019 Protection of Induction Motor
7/30
CONT....d) Over Voltagee) Under Voltagef) Under frequency
Fault in Starting Supply/Circuit.(CAUSES)a) Interruption in Phasesb) Blowing of fuse/Single Phasingc) Short Circuit in Supply Cable
Internal Fault in Motor itself. (CAUSES)
a) Phase to Phase Faultb) Phase to Earth Faultc) Failure to Phase (open circuit)d) Mechanical Failure
8/3/2019 Protection of Induction Motor
8/30
PROTECTION REQUIREMENTSThe cost of protective system of motor should be
within about 5% of motor cost.
The choice of motor protection scheme depend
upon the followings:
Size of motor , rated voltage , kW.
Type: squirrel-cage OR wound rotor.
Type of starter , switchgear and control gear.
Cost of motor and driven equipment.
Type of load , starting current , possible abnormalconditions , etc.
8/3/2019 Protection of Induction Motor
9/30
PROTECTION OF LOW VOLTAGE
IM(BELOW 1000V AC)
The important point regarding this, are- SCHEME OF STARTING CIRCUIT:
This can be understand by the help of following
fig.
8/3/2019 Protection of Induction Motor
10/30
CONT.... BIMETAL OVERLOAD DEVICE:
These are very popular. In case of 3-phase motor
triple pole bimetal relays are generally employed. Thebimetal strips are either heated by current flowingthrough them or by special heater coil through whichmotor current f low.
Incase of bigger motors they are connected insecondary circuit of CTs.
Bimetal strip can be self setting type or handresetting type.
8/3/2019 Protection of Induction Motor
11/30
CONT....While selecting the bimetal-overload devices formotor protection, the following aspect should be
considered------
a) Characteristic of Relay, Characteristic of motor.
b) Nature of loading.
c) Type of Starting, Starting Current.
d) Protection against overload.e) Protection against single phasing.
8/3/2019 Protection of Induction Motor
12/30
CONT.... SHORT CIRCUIT PROTECTION BYHRC FUSES:
Fault current exceeding 10 times the rated current
can be considered as short circuit current and theseshould be covered by Short Circuit Protecting Devices(SCPD). The SCPD may be in one of the followingform-------
a) HRC Fuseb) Short circuit release opening the circuit-breaker
c) Instantaneous high set overcurrent relay trips the CB
8/3/2019 Protection of Induction Motor
13/30
PROTECTION OF LARGE MOTORLarge motors are provided with protection
against following:
1. Fault in winding and associated circuit .2. Reduction of loss of supply voltage.
3. Excessive overload.
4. Phase unbalance and Single phasing.
5. Phase reversal.6. Switching overvoltage.
7. Surge.
8/3/2019 Protection of Induction Motor
14/30
CONT.... Type of relay available for motor protection:
1. Thermal protection only.
2. Thermal protection, Instantaneous overcurrentprotection .
3. Thermal, Instantaneous Three phase Overcurrent,Instantaneous unbalance, single phasing.
4. Thermal, Instantaneous Three phase Overcurrent,Instantaneous unbalance, single phasing andinstantaneous Earth fault.
8/3/2019 Protection of Induction Motor
15/30
CONT....In the protection of large IM all the relays are such
that the time reduces with increase in current.
Such type of protection can be understand byfollowing fig---
8/3/2019 Protection of Induction Motor
16/30
OVERLOAD PROTECTION OF IM The over load protective devices can be grouped as:
Those which respond to motor current.
Those which respond to winding temperature.The current sensing overload protecting devices
can sense the following abnormal conditions---
1. Overloads and undervoltage .
2. Single phasing.
3. Locked rotor , stalling.
8/3/2019 Protection of Induction Motor
17/30
CONT....4. Heavy starting.
5. Continuous overload.
6. Heavy breaking.
And the following condition can be sensed only
by embedded thermal device-----
Temperature rise due to various cause like,
Higher ambient temperature. Failure of cooling etc.
8/3/2019 Protection of Induction Motor
18/30
CONT....The characteristic of IM heating and Replica Relay
can be understand by following fig..
8/3/2019 Protection of Induction Motor
19/30
PROTECTION AGAINST UNBALANCEThe voltage supplied to three phase IM can be
unbalanced due to any of the following reasons:1. Single phase load on distribution service line.
2. Blow out fuse in power factor correcting plant.
3. Short circuit within or out side the motor.
4. Phase failure by blown fuse.(single phasing).
Unbalanced voltage cause the flow of Negative
Sequence current, this result as the heating the
motor winding, which may reach above the safe
limit.
8/3/2019 Protection of Induction Motor
20/30
CONT....The unbalanced voltage protection based upon
the following method:
1. Bimetallic relay arranged to trip faster for unbalancedcurrent.
2. Single phase relay sensing overcurrent in heavily loadedphase.
3. Phase unbalanced relay.
8/3/2019 Protection of Induction Motor
21/30
PROTECTION AGAINST SINGLE
PHASING(PHASE FAILURE)A 3-phase IM continuous to run even if one of the
supply line is disconnected. This cause the
unbalanced stator currents.The negative sequencecomponent of the unbalanced current cause the
heating of rotor and temperature rise.
Single phasing is the extreme unbalanced for
3-phase motor. In this condition the current in the
healthy phase increase by\/3 times. This increase
the heating in motor winding.
8/3/2019 Protection of Induction Motor
22/30
CONT....The connection of single-phasing preventer can be
understand by following fig..
8/3/2019 Protection of Induction Motor
23/30
PHASE REVERSAL RELAYPhase reversal occurs when supply connection arechanged, this cause the running of the motor in
wrong direction .
In some application phase reversal is dangerous
like Crane, Trams etc. Thats why we need phase
reversal relay.
The phase Reversal Relay based onelectromagnetic principal comprises a disk motor
driven by magnetic system actuated by
secondaries of two line CTs or VTs.
8/3/2019 Protection of Induction Motor
24/30
PHASE TO PHASE FAULT
PROTECTIONThe phase to phase fault short circuit in stator
winding cause burn-out of coil. Hence the motor
should be disconnected from supply very quickly.Fast Overcurrent Relay are provided for
phase to phase short circuit protection. Although
it has some limitation.
The working of Overcurrent Relay can be
understand by: Starting characteristics of squirrel-
cage IM co-ordinated with Overcurrent Relay for
8/3/2019 Protection of Induction Motor
25/30
CONT....phase fault. Which is as following
8/3/2019 Protection of Induction Motor
26/30
STATOR EARTH-FAULT PROTECTIONEarth-fault protection is set to disconnect the
motor from supply as early as possible so that the
damage to winding and lamination is minimum.Zero sequence current transformer (ZSCT) or
core balance type protection is very convenient
method of protection of motor from Earth Fault.
The connection of Core Balance CT(ZSCT) for
earth-fault protection can be understand
8/3/2019 Protection of Induction Motor
27/30
CONT....by help of following fig..
8/3/2019 Protection of Induction Motor
28/30
FAULT IN ROTOR WINDINGIn slip-ring IM , Rotor Fault is possible. This could
be of following types:
Inter-turn Fault. AND Ground or Earthing.
PROTECTION-----
To avoid this the Neutral Point of Supply,
should be Earthed at every Voltage level. Cascade
failure of motor can occur if supply neutral is not
Earthed.
8/3/2019 Protection of Induction Motor
29/30
REFERENCESwitchgear Protection & Power System.
By: Sunil S. Rao
Wikipedia.Power System Protection & Switchgear.
By: Badri Ram
D N Vishwakarma