Surge Protective Devices (SPDs)Residential
Catalog6671CT9701R08/12
2012
CONTENTS
Whole House Surge Protective Devices (SPDs) . . . . . . . . . . . . . . . . . . . . 3SDSB1175C / SDSB1175CB Whole House SPDs . . . . . . . . . . . . . . . . . .4SDSB1175R / SDSB1175RB Whole House SPDs . . . . . . . . . . . . . . . . . .6Whole House Surge Protective Device Accessories . . . . . . . . . . . . . . . .8
SDSA1175 Type 1 Surge Protective Devices. . . . . . . . . . . . . . . . . . . . . . . 9Home Electronics Protective Devices (HEPD) . . . . . . . . . . . . . . . . . . . . . 10Plug-on Surge Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Surgelogic™
Surge Protective Devices (SPDs)Contents
© 2012 Schneider ElectricAll Rights Reserved
208/2012
ContentsWhole House Surge Protective Devices (SPDs) ...............................................................................3
SDSB1175C / SDSB1175CB Whole House Surge Protective Device ............................................4Features .....................................................................................................................................4System Performance .................................................................................................................4Specifications .............................................................................................................................5
SDSB1175R / SDSB1175RB Whole House Surge Protective Device ............................................6Features .....................................................................................................................................6System Performance .................................................................................................................6Specifications .............................................................................................................................7
Whole House Surge Protective Device Accessories .......................................................................8Coaxial Modules ........................................................................................................................8Telephone Modules ...................................................................................................................8AC Modules ...............................................................................................................................8
SDSA1175 Type 1 Surge Protective Devices.....................................................................................9
Features .....................................................................................................................................9Specifications .............................................................................................................................9Accessories ................................................................................................................................9
Home Electronics Protective Devices (HEPDs)...............................................................................10
Features ...................................................................................................................................10Specifications ...........................................................................................................................10Accessories ..............................................................................................................................10
Plug-On Surge Protective Devices ...................................................................................................11
Features ...................................................................................................................................11Applications ..............................................................................................................................11Specifications ...........................................................................................................................11
Dimensions .........................................................................................................................................12
SDSB1175C / SDSB1175CB Whole House Surge Protective Devices ...................................12SDSB1175R / SDSB1175RB Whole House Surge Protective Devices ...................................12SDSA1175 Surge Protective Device ........................................................................................13HEPD Surge Protective Device ...............................................................................................13QOSAMK Mounting Bracket ....................................................................................................13TVSXRFMK Flush Mount Bracket ...........................................................................................14HOM2175SB Homeline Surge Protective Device ....................................................................14QO2175SB QO Surge Protective Device ................................................................................14
Wiring ..................................................................................................................................................15
SDSB1175C / SDSB1175CB or SDSB1175R / SDSB1175RB Whole House SPDs ...............15Network Interface Device .........................................................................................................15SDSA1175 SPDs .....................................................................................................................15HEPD SPDs .............................................................................................................................16
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
308/2012© 2012 Schneider Electric
All Rights Reserved
Whole House Surge Protective Devices (SPDs)Whole House devices are designed to deliver surge suppression that addresses the entire home. AC modules are connected to the circuit breaker load center and provide suppression for all equipment connected to the power system. Whole House systems incorporate AC modules as well as modules for other metallic lines coming into the home including telephone/DSL and coaxial video/data.
United States and Canadian UL® Listed as a Type 2 SPD to UL 1449 3rd Edition. The AC surge suppression module is UL and Canadian UL Listed as a Type 1 SPD. Both Type 1 and Type 2 SPDs comply with requirements of CSA 233.1-87, and CSA C22.2 No. 8-M1986 as appropriate. Telephone and coaxial video modules are UL® Recognized to UL 497A 3rd Edition and UL 497B 4th Edition, respectively.
• 120/240 Vac, 80 kA/phase AC surge suppression
• LED status indicators for AC surge suppression
• Telephone surge suppression module supports four lines with tool-less Insulation Displacement Connectors (IDC)
• Coaxial surge suppression module supports one line of video/data
TelephoneModule
ACModule
Coax Modules
TelephoneModule
ACModule
Coax Modules
SDSB1175C NEMA 1Shown without cover and with 2nd
optional coax module (SDSA2V)
SDSB1175R NEMA 3RShown without cover and with 2nd
optional coax module (SDSA2V)
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
© 2012 Schneider ElectricAll Rights Reserved
408/2012
SDSB1175C / SDSB1175CB Whole House Surge Protective DeviceSquare D™ Whole House Surge Protective Devices (SPDs) provide suppression of electrical surges to AC power as well as telephone and television cables (optional with SDSB1175CB). Installed next to the circuit breaker panel, the device is hard-wired to the electrical panel. The telephone module (SDSA4P) accommodates four telephone lines (eight with two telephone modules). The coaxial module (SDSA2V) accommodates one coaxial television line (two lines with two modules).
Features
• Design allows for field replacement of components.
• Multi-path surge suppression capability covers all electrical entrance points to the home.
• 80,000 A surge current capacity for a longer service life and suppression of high-energy surges.
• LED status indicator allows for visual indication of the SPD status.
• Hardwire connection method provides direct connection means to the electrical panel.
• Coordinated fuse technology allows disconnection methods for thermal and high-current events.
System Performance
Electrical
• Surge suppression capability up to 80,000 A per phase
• Discrete thermal disconnect surge suppression
• cULus Listed to UL 1449 3rd Edition, Type 2 SPD
• Modes of surge suppression: Line 1-to-Neutral, Line 2-to-Neutral, Line 1-to-Ground, Line 2-to-Ground, Line 1-to-Line 2, Neutral-to-Ground.
Telephone (where applicable)
• Surge suppression for up to four telephone lines (up to eight lines with optional second Telco unit Cat. No. SDSA4P)
• Suitable for digital telephone lines and high-speed internet services
• Self-resetting fusing elements
• Three-mode SiBod™ for fast common mode and differential mode suppression
• All mode surge suppression: Tip-to-ground, ring-to-ground, and tip-to-ring
• Insulation-Displacement Connector (IDC): no special tool required
Television (where applicable)
• Surge suppression for one coaxial (antenna, cable or satellite) line (two lines with optional second SDSA2V module)
• Suitable for use on all state-of-the-art television and hybrid fiber/coaxial systems
• 140–200 Vdc Gas Discharge Tube (GDT) surge suppression
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
508/2012© 2012 Schneider Electric
All Rights Reserved
Specifications
SDSB1175C Specifications
Performance—AC Protection
Surge Current Rating per Phase 80 kA
Short Circuit Current Rating 25 kA
Modes of Protection 6
Fusing Individually fused MOVs
Thermal Fusing Yes
Overcurrent Fusing Yes
Operating Frequency 50/60 Hz
Mechanical Description
Enclosure Carbon Steel
NEMA Rating NEMA 1
Connection Method #12 AWG, Stranded
Weight 10.5 lbs
Mounting Method Four screws, #10
Circuit Type Parallel
Operating Altitude Sea Level to 12,000 ft. (3,658 m)
Storage Temperature -40°F to +149°F (-40°C to +65°C)
Operating Temperature -40°F to +149°F (-40°C to +65°C)
Diagnostics
Green status LEDs
Listings and Performance
• cULus Listed to UL 1449 3rd Edition Type 2 SPD• CSA C22.2 No. 8-M1986, C233.1-87• UL Recognized to UL 497A 3rd Edition• UL 497B 4th Edition• CSA C22.2 No. 226-92
Catalog Numbers
Description Included Models Cat. No.
Whole House NEMA 1 Basic AC SDSB1175CB
Whole House NEMA 1 AC, Telephone, Coax (1) SDSB1175C
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
© 2012 Schneider ElectricAll Rights Reserved
608/2012
SDSB1175R / SDSB1175RB Whole House Surge Protective DeviceSquare D™ Whole House Surge Protective Devices (SPDs) provide suppression of electrical surges to AC power as well as telephone and television cables (optional with SDSB1175RB). Installed next to the circuit breaker power panel, the device is hard-wired to the electrical panel. The telephone module (SDSA4P) accommodates four telephone lines (eight with two telephone modules). The coaxial module (SDSA2V) accommodates one coaxial television line (two lines with two modules).
Features
• Design allows for field replacement of components.
• Multi-path surge suppression capability covers all electrical entrance points to the home.
• 80,000 A surge current capacity for a longer service life and suppression of high-energy surges.
• LED status indicator allows for visual indication of the SPD status
• Hardwire connection method provides direct connection means to the electrical panel.
• Coordinated fuse technology allows disconnection methods for thermal and high-current events.
System Performance
Electrical
• Surge suppression capability up to 80,000 A per phase
• Discrete thermal disconnect surge suppression
• cULus Listed to UL 1449 3rd Edition, Type 2 SPD
• Modes of surge suppression: Line 1-to-Neutral, Line 2-to-Neutral, Line 1-to-Ground, Line 2-to-Ground, Line 1-to-Line 2, Neutral-to-Ground.
Telephone (where applicable)
• Surge suppression for up to four telephone lines (up to eight lines with optional second Telco unit Cat. No. SDSA4P)
• Suitable for digital telephone lines and high-speed internet services
• Self-resetting fusing elements
• Three-mode SiBod™ for fast common mode and differential mode suppression
• All mode surge suppression: Tip-to-ground, ring-to-ground, and tip-to-ring
• Insulation-Displacement Connector (IDC): no special tool required
Television (where applicable)
• Surge suppression for one coaxial (antenna, cable or satellite) line (two lines with optional second SDSA2V module)
• Suitable for use on all state-of-the-art television and hybrid fiber/coaxial systems
• 140–200 Vdc Gas Discharge Tube (GDT) surge suppression
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
708/2012© 2012 Schneider Electric
All Rights Reserved
Specifications
SDSB1175R Specifications
Performance—AC Protection
Surge Current Rating per Phase 80 kA
Short Circuit Current Rating 25 kA
Modes of Protection 6
Fusing Individually fused MOVs
Thermal Fusing Yes
Overcurrent Fusing Yes
Operating Frequency 50/60 Hz
Mechanical Description
Enclosure Carbon Steel
NEMA Rating NEMA 3R
Connection Method #12 AWG, Stranded
Weight 15.3 lbs
Mounting Method Four screws, #10
Circuit Type Parallel
Operating Altitude Sea Level to 12,000 ft. (3,658 m)
Storage Temperature -40°F to +149°F (-40°C to +65°C)
Operating Temperature -40°F to +149°F (-40°C to +65°C)
Diagnostics
Green status LEDs
Listings and Performance
• cULus Listed to UL 1449 3rd Edition Type 2 SPD • CSA C22.2 No. 8-M1986, C233.1-87• UL Recognized to UL 497A 3rd Edition • UL 497B 4th Edition • CSA C22.2 No. 226-92
Catalog Numbers
Description Included Models Cat. No.
Whole House NEMA 3R Basic AC SDSB1175RB
Whole House NEMA 3R AC, Telephone, Coax (1) SDSB1175R
Surge Protective Devices (SPDs)Whole House Surge Protective Devices (SPDs)
© 2012 Schneider ElectricAll Rights Reserved
808/2012
Whole House Surge Protective Device AccessoriesAccessories for expanding systems or for replacing existing modules. Up to three coaxial SPD modules, or two telephone suppressor modules can be installed in a Whole House SPD.
Coaxial Modules
• SDSA2V provides suppression of externally generated surges. Uses dual F-type coaxial connectors compatible with video, audio, and high-speed cable internet lines.
• Clamping Voltage: 140–200 Vdc
• Frequency Range: DC to 3 GHz
• US and Canadian UL Recognized to UL 497B 4th Edition.
Telephone Modules
• SDSA4P provides suppression of externally generated surges.
• Each accommodates up to four lines, using tool-less IDC terminations for quick connection.
• Compatible with telephone and high-speed DSL or dial-up internet lines.
• Clamping voltage: 330 Vdc
• US and Canadian UL Recognized to UL 497A 3rd Edition.
AC Modules
• US and Canadian UL Listed as Type 1 SPD to UL 1449 3rd Edition.
• Complies with requirements of CSA 233.1-87, and CSA C22.2 No. 8-M1986 as appropriate.
Description Cat. No.
Coaxial video surge suppressor SDSA2V
Description Cat. No.
4-Line telephone surge suppressor with tool-less IDC terminations SDSA4P
Description Cat. No.
Whole House AC Module (HEPD80) replacement kit HEPD80RK
SDSA2V Coaxial SPD Module
SDSA4P Telephone SPD Module
HEPD80RK SPD Module
Surge Protective Devices (SPDs)SDSA1175 Type 1 Surge Protective Devices
908/2012© 2012 Schneider Electric
All Rights Reserved
SDSA1175 Type 1 Surge Protective DevicesSDSA1175 SPDs are designed and listed for indoor or outdoor installation and surge suppression for single-phase three-wire 120/240 Vac or two-wire 120 Vac 60 Hz electrical services. This product is ideal for residential applications for single phase power systems. SDSAs work together with surge protection plug strips to provide surge suppression for sensitive electronics. Two SDSA1175 surge protection devices can be installed to provide suppression for 208Y/120 Vac three-phase four-wire services.
Features
• High-energy suppression circuitry that can be located at any point in the electrical system. As a Type 1 rated device, they have the flexibility to be used with or without an Overcurrent Protection Device (OCPD).
• Surge suppression for equipment from severe transient activity.
• Each Metal Oxide Varistor (MOV) is individually fused
• NEMA Type 4X rating suitable for installing indoors, outdoors, or in other harsh environments.
• US and Canadian UL Listed as Type 1 SPD to UL 1449 3rd Edition.
• Complies with requirements of CSA 233.1-87, and CSA C22.2 No. 8-M1986 as appropriate.
• LED indicates operational status
• Short circuit current rating: 25 kA
• Convenient back-nipple mounting
Specifications
Accessories
QOSAMK Mounting Bracket
SDSA1175 Specifications
Performance
Surge Current Rating per Phase 36 kA
Short Circuit Current Rating 25 kA
Modes of Protection 3
Fusing Individually fused MOVs
Thermal Fusing Yes
Overcurrent Fusing Yes
Operating Frequency 50/60 Hz
Mechanical Description
Enclosure Non-metallic
NEMA Rating Type 4X
Connection Method #14 AWG, Solid
Weight 0.64 lbs (0.29 kg)
Mounting Method Close-nippled, back-mounted
Operating Altitude Sea Level to 12,000 ft. (3,658 m)
Storage Temperature -40°F to +149°F (-40°C to +65°C)
Operating Temperature -40°F to +149°F (-40°C to +65°C)
Diagnostics
Green status LED
Listings and Performance
• cULus Listed to UL 1449 3rd Edition Type 1 SPD• CSA C22.2 No. 8-M1986, C233.1-87
SDSA1175
QOSAMKMounting Bracket
Surge Protective Devices (SPDs)Home Electronics Protective Devices (HEPDs)
© 2012 Schneider ElectricAll Rights Reserved
1008/2012
Home Electronics Protective Devices (HEPDs)Square D™ brand Home Electronics Protective Devices (HEPDs) are compact and affordable surge suppressors designed for residential load centers. HEPDs work together with surge protection plug strips to provide surge suppression for sensitive electronics. HEPDs reduce surges that might otherwise overwhelm plug strips and damage connected household equipment.
HEPDs also provide surge suppression for important items such as washers, dryers, refrigerators, stoves, and lighting that plug strips don’t protect.
Features
• High-energy suppression circuitry helps protect household equipment
• Each Metal Oxide Varistor (MOV) is individually fused
• NEMA Type 4X enclosure rating suitable for installing indoors, outdoors, or in other harsh environments.
• US and Canadian UL Listed as Type 1 SPD to UL 1449 3rd Edition.
• Complies with requirements of CSA C233.1-87, and CSA C22.2No. 8-M1986 as appropriate.
• LED indicates operational status
• Short circuit current rating: 25 kA
• Convenient side-nipple mounting
Specifications
Accessories
TVSXRFMK Flush Mount Bracket
HEPD80
HEPD Specifications
Performance
Surge Current Rating per Phase 80 kA
Short Circuit Current Rating 25 kA
Modes of Protection 6
Fusing Individually fused MOVs
Thermal Fusing Yes
Overcurrent Fusing Yes
Operating Frequency 50/60 Hz
Mechanical Description
Enclosure Non-metallic
NEMA Rating Type 4X
Connection Method #12 AWG, Solid
Weight 1.8 lbs
Mounting Method Close-nippled, side-mounted
Operating Altitude Sea Level to 12,000 ft. (3,658 m)
Storage Temperature -40°F to +149°F (-40°C to +65°C)
Operating Temperature -40°F to +149°F (-40°C to +65°C)
Diagnostics
Green status LEDs
Listings and Performance
• cULus Listed to UL 1449 3rd Edition Type 1 SPD• CSA C22.2 No. 8-M1986, C233.1-87
TVSXRFMKMounting Bracket
Surge Protective Devices (SPDs)Plug-On Surge Protective Devices
1108/2012© 2012 Schneider Electric
All Rights Reserved
Plug-On Surge Protective DevicesSquare D™ brand QO™ and Homeline™ load center surge protective devices are easy to install plug-on units that install as quickly as a standard circuit breaker. The Surge Protective Devices (SPDs) use two pole spaces in a QO or Homeline load center or NQ panelboard.
These SPDs offer an effective method to bring surges down to manageable levels and can offer additional value in a cascaded SPD system.
Features
• Plug-on design requires two pole spaces
• LED indicates operational status
• 22.5 kA per phase
• cULus Listed per UL 1449 3rd Edition Type 2 SPD
Applications
• QO2175SB: For QO load centers, combination devices, and NQ panelboards
• HOM2175SB: For Homeline loadcenters and combination devices
Specifications
QO and HOM SPD Specifications
Performance
Surge Current Rating per Phase 22.5 kA
Short Circuit Current Rating 22 kA
Modes of Protection 3
Fusing Individually fused MOVs (Metal Oxide Varistor)
Thermal Fusing Yes
Overcurrent Fusing Yes
Operating Frequency 50/60 Hz
Mechanical Description
Enclosure Non-metallic
NEMA Rating Type 1
Connection Method Quick plug-on
Weight 0.54 lbs
Operating Altitude Sea level to 12,000 ft. (3,658 m)
Storage Temperature -4°F to +149°F (-20°C to +65°C)
Operating Temperature -4°F to +149°F (-20°C to +65°C)
Diagnostics
Green Status LED
Listings and Performance
• cULus Listed per UL 1449 3rd Edition Type 2 SPD• CSA C22.2 No. 8-M1986, C233.1-87
Catalog Numbers
Description Cat. No.
QO Load Center SPD, 120/240, 22.5 kA, 1-phase, 3-wire QO2175SB
Homeline Load Center SPD, 120/240, 22.5 kA, 1-phase, 3-wire HOM2175SB
QO2175SB
HOM2175SB
© 2012 Schneider ElectricAll Rights Reserved
Surge Protective Devices (SPDs) Dimensions
1208/2012
DimensionsSDSB1175C / SDSB1175CB Whole House Surge Protective Devices
SDSB1175R / SDSB1175RB Whole House Surge Protective Devices
6.88[174.7]
3.55[90.1]
3.38[98.5]
5.93[150.6]
14.13[358.9]
13.18[334.7]
9.25[234.9]
9.73[247.1]
9.13[231.9]
5.10[129.5]
4.25[107.9]
1.63
[41.
4]
13.4
4[3
41.3
]
12.7
1[3
22.8
]
5.29[134.3]
Surge Protective Devices (SPDs)Dimensions
1308/2012© 2012 Schneider Electric
All Rights Reserved
SDSA1175 Surge Protective Device
HEPD Surge Protective Device
QOSAMK Mounting Bracket
2.250 [57]
2.250 [57]
2.685 [68]
1.935
0.5 [17.7]NPT straight
[49]
in.[mm]
3.75[95]
3.60[91]
3.00[76]
0.87[22]
2.67[68]
in.[mm]
0.5 [12.7]NPT straight
3.64[92.5]
3.10[78.7]
.88[22.4]
1.52[39]
2.12[54]
1.82[46.2]
.47[11.9]
.27[6.9]
1.31[33.3]
© 2012 Schneider ElectricAll Rights Reserved
Surge Protective Devices (SPDs) Dimensions
1408/2012
TVSXRFMK Flush Mount Bracket
HOM2175SB Homeline Surge Protective Device
QO2175SB QO Surge Protective Device
2.91
7.00 6.00 3.51
1.75
0.506.00
7.00 0.88
3.50
1.85
3.31
1.52
0.06
0.50
2.38[60.5]
2.05
4X Ø 0.25[6.4] [74]
[89]
[44.5]
[152]
[152][178]
[12.7]
[1.52]
[52.1]
[22.4]
[38.6]
[84]
[47]
[89]
[178]
[12.7] Ø
1.97[50]
2.58[65]0.19
[5]
3.69[94]
0.19[5]
1.48[37]
2.55[65]0.25
[6] 0.30[8]
3.66[93]
0.19[5]
Surge Protective Devices (SPDs)Wiring
1508/2012© 2012 Schneider Electric
All Rights Reserved
WiringSDSB1175C / SDSB1175CB or SDSB1175R / SDSB1175RB Whole House SPDs
Network Interface Device
SDSA1175 SPDs
OCPD L2 N
Green
L1
White
Black
Black
Sub-Panel or Service Entrancewith Grounding Bar
120/240 Vac Single-phase 3-Wire + Ground Service
Service Entrancewithout Grounding Bar
120/240 Vac Single-phase 3-Wire Service
L2 N
Green
L1
White
Black
Black
Equipment Grounding Bar
OCPD
SPD Enclosure
SPD Enclosure
I
Telephone SPD Module
Modular Jack
RJ Type Modular
Plug
Terminal Strip Inside
Cable
Customer Side
Telephone Company SideGround
Telephone Company
Cable
White White
Black
SDSA1175120/240 Vac Single-phase
3-Wire Service Two SDSA1175 3-wire units on 208Y/120 Vac
Three-phase 4-Wire Service
Black
Black
Black
Black
Black
White
Black
White
SDSA1175T120 Vac Single-phase
2-Wire Service
6671CT9701R08/12 © 2012 Schneider Electric All Rights Reserved Replaces 6671CT9701R9/06, 09/2006
08/2012
Schneider Electric USA, Inc.1751 South 4800 WestSalt Lake City, UT 841041-888-778-2733www.schneider-electric.us
Square D™ and Schneider Electric™ are trademarks or registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners.
HEPD SPDs
HOM2175SB Homeline Surge Protective Device
QO2175SB QO Surge Protective Device
Black
Black
Green
White
L1
N
L2Green
Black
White
L
N
120/240 Vac Single-phase 3-Wire + Ground Service
120 Vac Single-phase 2-Wire + Ground Service
Neutral Assembly
0.50 in.[13 mm]
Bus ConnectorsWhite Wire
NOTE: The SPD requires two adjacent mounting spaces and must be installed as close to neutral assembly and main circuit breaker or main lugs as possible. Keep wire lengths as short as possible with no sharp bends.
Neutral Assembly
0.50 in.[13 mm]
White Wire Bus Connectors
NOTE: The SPD requires two adjacent mounting spaces and must be installed as close to neutral assembly and main circuit breaker or main lugs as possible. Keep wire lengths as short as possible with no sharp bends.