Technical Data Sheet Uninterruptible Power Supply
GE Consumer & Industrial SA
General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52
www.gecriticalpower.com
g
imagination at work
SGSE_010-040_S1_UPS_GE_01
Critical Power
Modifications reserved Page 2/6
GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1
Model: SG Series 10 – 15 - 20 – 30 - 40 PurePulse™ CE S1
Issued by: Product Document Department – Riazzino - CH
Approved by: R & D Department – Riazzino - CH
Date of issue: 03.12.2013
File name: GE_UPS_TDS_SGS_PCE_K10_K40_1GB_V010
Revision: 1.0
Identification No.:
Up-dating
Revision Concern Date
COPYRIGHT © 2013 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE’s Critical Power.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Critical Power
Modifications reserved Page 3/6
GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1
GENERAL DATA
Topology VFI, static double conversion UPS with integrated transformer
Nominal output apparent power at PF=0.6 lag. to 0.9 leading KVA 10 15 20 30 40
Nominal output active power at PF=1 kW 10 15 20 30 40*
Overall efficiency in VFI mode % Up to 92.3
Heat dissipation at 100% load in VFI mode, PF=0.8 lag. and charged battery
kW 0.65 1.11 1.27 2.18 2.69
Cooling air (25°C ÷ 30°C) m3/h 189 323 371 637 785
Audible noise level dB(A) 58 58 58 65 65
Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
Operating temperature range UPS: 0°C ÷ 40°C Battery: 20°C ÷ 25°C recommended
Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter
the storage time of the battery)
Storage time of the battery without recharge at 20°C Max. 6 months
Relative humidity Max. 95% (non-condensing)
Max. altitude without power de-rating Power de-rating (according to EN/IEC 62040-3)
1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%
Protection degree IP 20 (IEC 60529)
Standards EN/IEC 62040, CE marking
EMC (Electromagnetic Compatibility) EN/IEC 62040-2
Electrostatic discharge immunity 4kV contact / 8kV air discharge
Internal protection All internal live parts shrouded
Transport Cabinet suitable for handling by forklift
Colour RAL 9003 (white)
Installation Can be positioned against a wall and floor fixed
Service access Access required at front and top
External cable connections Bottom at front of the cabinet (standard)
Cooling Forced bottom to top by internal fans
Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (optional)
RECTIFIER
Rectifier bridge Three phase, IGBT rectifier, PurePulseTM technology, over-temperature protection
Standard input voltage Nominal: 3 x 380V / 400V / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V
Other input voltages On request
Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)
Power factor 0,99
Input current THD 2% at 100% load <5% at 50% load
Inrush current Limited by soft-start circuit
Power walk-in 15 seconds
Output voltage tolerance +/- 1%
DC voltage ripple <1%
Battery charging characteristic IU (DIN 41773), T° compensated floating voltage
Battery charging current limit Programmable
Input power data kVA 10 15 20 30 40
Input power at inverter nominal load and charged battery
at PF=0.8 lag. at PF=1
kW 8.7
10.9 13.2 16.5
17.4 21.7
26.4 33.0
34.9 43.7
Max. input power at inverter nominal load And max. battery recharge current (programmable)
kW 11.7 16.8 21.8 32.7 43.5
Max. battery charging current (programmable) at the beginning of battery recharge at nominal load
at PF=0.8 lag. at PF=1
A 11 5
13 5
17 6
25 8
33 11
*) at 30°C operating temperature
Critical Power
Modifications reserved Page 4/6
GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1
BATTERY
Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
Number of 12V blocks, 6 cells/block 30 to 32 (30 blocks can be mounted in the UPS cabinet)
Float voltage at 20°C 405V ÷ 436V (dependent on the number of blocks)
Min. discharge voltage (programmable) 306V
Recharge time <5 hours up to 90% of battery capacity
“Battery to earth” fault detection Standard
Automatic and manual battery test Standard
Manual battery contactor Standard, with automatic safety disconnection
Battery power data kVA 10 15 20 30 40
DC power at full load and PF=0.8 kW 8.4 12.6 16.8 25.3 33.7
DC power at full load and PF=0.9 kW 9.5 14.2 18.9 28.4 37.9
DC power at full load and PF=1.0 kW 10.5 15.8 21.1 31.6 42.1
Matching battery cabinets See table on page 5 and 6
INVERTER
Nominal Total output power 10 – 15 – 20 – 30 – 40 kVA/kW
Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N
Inverter bridge SVM (Space Vector Modulation) and IGBT technology
Output transformer (for galvanic separation) Standard
Output waveform Sine wave
Output voltage tolerance: - static ......................................................................................................... +/- 1% - Dynamic (at load step 0 – 100 – 0%) .......................................... +/- 3% - Dynamic (at load step 0 – 50 – 0%) ............................................ +/- 2% - recovery time to +/-1% .................................................................... 20 ms - output voltage THD for 100% linear load ................................ <2% - output voltage THD for 100% non-linear load (EN 50091) <3%
Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%
Output frequency 50/60 Hz (selectable)
Output frequency tolerance: - free-running .......................................................................................... +/- 0.1% - with mains synchronisation adjustable to .............................. +/- 4%
Phase displacement: - at 100% balanced load .................................................................... 120°: +/- 1% - at 100% unbalanced load ............................................................... 120°: +/- 2%
Overload capability (@25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute
Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE
Protection clearance capability (selectivity) 20% In within 5-10 ms (with MCCB class C)
Crest factor >3:1
BYPASS
Input connection Separate (dual input-recommended) or common to the rectifier input
Primary components - Static switch (SCR) on bypass - Electro-mechanic contactor (back-feed protection) - Manual switch for maintenance bypass
Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)
Overload on bypass 200% for 1 minute and 35 times In for 10 ms, non repetitive
INTERFACING
6 programmable signalling voltage-free contacts (available on terminal blocks)
- Standard information for easy integration and signalling - 27 user settable signals
Serial channel RS232 (on Delta 9 pin connector) Standard
Input signals - EPO - Emergency Power Off (n/c contact, customer supplied) - GEN ON(emergency power supply ON, n/o contact, customer supplied) - 1 auxiliary signals with settable functionality
Auxiliary power supply - 24Vdc auxiliary power supply (optional)
Note: all indicated values are typical. Variations may be found from one unit to another.
Critical Power
Modifications reserved Page 5/6
GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1
CONTROL PANEL
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements:
Back lit Graphic Display (LCD) with the following characteristics:
Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;
Graphic diagram indicating UPS status.
Command keys and parameters setting.
UPS status control LED.
OPTIONS
COMMUNICATION:
1. Additional Customer Interface Card
2. 3-ph SNMP/WEB plug-in Adapter
3. Modbus RTU or Modbus/TCP Interface (only license)
4. GE iUPSGuard
5. GE Data Protection
BUILT-IN UPS OPTIONS: 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
1. RPA kit
2. Auxiliary Power Supply (APS) 24Vdc
3. Rectifier or bypass or UPS input transformer * * * * *
4. Input / Output cable connection kit
*) Mounted in UPS cabinet battery cavity, instead of battery
OPTIONS IN ADDITIONAL CABINETS:
Dimensions (WxDxH): 750 x 800 x 1450 mm 1100 x 800 x 1450 mm
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
1. Rectifier or bypass or UPS input transformer On request
2. Special voltages: input and/or output On request
3. Centralized maintenance bypass for RPA configuration On request
4. Empty battery cabinets
Critical Power
Modifications reserved Page 6/6
GE_UPS_TDS_SGS_PCE_10K_40K_1GB_V010.docx Technical Data Sheet SG Series 10 - 40 PurePulse™ CE S1
TECHNICAL DATA
SG Series 10 – 40 PurePulse™
Dimensions
(Width x Depth x Height):
680 x 800 x 1450 mm
Battery table Dimensions Weights
UPS Autonomy
time Battery
capacity Battery cabinet
Total width
UPS Battery Battery + cabinet
Total Floor
loading (kVA) (Min.) (Ah) (mm) (mm) (Kg) (Kg) (Kg) (Kg) (Kg/m2)
10
10 9Ah HR in UPS 680
285
110 - 395 726
24 2 x 9Ah HR in UPS 680 220 - 505 928
30 22Ah HR in UPS 680 230 - 515 947
51 33Ah HR in UPS 680 335 - 620 1140
80 (estimated) 50Ah HR 750 1430 - 600 885 1000
135 (estimated) 75Ah HR 750 1430 - 900 1185 1500
15
5.5 9Ah HR in UPS 680
335
110 - 445 818
15 2 x 9Ah HR in UPS 680 220 - 555 1020
19 22Ah HR in UPS 680 230 - 565 1038
30 33Ah HR in UPS 680 335 - 670 1232 52 50Ah HR 750 1430 - 600 935 1000
85 (estimated) 75Ah HR 750 1430 - 900 1235 1500
20
10 2 x 9Ah HR in UPS 680
335
220 - 555 1020
13 22Ah HR in UPS 680 230 - 565 1038
22 33Ah HR in UPS 680 335 - 670 1232
35 50Ah HR 750 1430 - 600 935 1000
60 75Ah HR 750 1430 - 900 1235 1500
30
5.5 2 x 9Ah HR in UPS 680
400
220 - 620 1140
7.5 22Ah HR in UPS 680 230 - 630 1158
13 33Ah HR in UPS 680 335 - 735 1351
22 50Ah HR 750 1430 - 600 1000 1000
36.5 75Ah HR 750 1430 - 900 1300 1500
40
5 22Ah HR in UPS 680
400
230 - 630 1158
9 33Ah HR in UPS 680 335 - 735 1351
15.5 50Ah HR 750 1430 - 600 1000 1000
26 75Ah HR 750 1430 - 900 1300 1500
) At full load and PF=0.8 lag. ) Based on BB Battery HR type ) Max. value for battery cabinet only
UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS
Common input Rectifier & Bypass Separated input Rectifier & Bypass
1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = Internal Battery
2 = Inverter 4 = Manual Bypass 6 = Load
Line protections and cable sections
Protections for mains voltages Battery protection
Cable sections (mm2) recommended by European Standards
3 x 380V / 400V / 415V Alternatively, local standards to be respected
kVA F1 F2 F3 (if external) A B C & D K (for external battery)
10 3x 20A 3 x 20A 3 x 20A 2 x 40A 4 x 2.5 4 x 2.5 5 x 2.5 3 x 6
15 3 x 25A 3 x 25A 3 x 25A 2 x 63A 4 x 4 4 x 4 5 x 4 3 x 10
20 3 x 35A 3 x 35A 3 x 35A 2 x 63A 4 x 6 4 x 6 5 x 6 3 x 10
30 3 x 50A 3 x 50A 3 x 50A 2 x 100A 4 x 10 4 x 10 5 x 10 2 x 25 + 16
40 3 x 63A 3 x 63A 3 x 63A 2 x 100A 4 x 10 4 x 10 5 x 10 2 x 25 + 16
Cable sections (mm2) recommended in Switzerland
F1, F2, F3, A, B, C, D: supplied by customer kVA A B C & D K (for external battery)
Battery protection: can be supplied by GE’s Critical Power 10 4 x 4 4 x 4 5 x 4 3 x 10
15 4 x 6 4 x 6 5 x 6 3 x 16
20 4 x 10 4 x 10 5 x 10 3 x 16
30 4 x 16 4 x 16 5 x 16 2 x 35 + 25
40 4 x 16 4 x 16 5 x 16 2 x 35 + 25
IMPORTANT NOTE! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 3 pole breakers should be used upstream the UPS input (see also IEC 60364-1, IEC 61140 and IEC 61557).
SGSE_010-040_S1_UPS dimension_GE_01
1'4
50
mm
800mm680mm
GE Digital Energy Power Quality
Technical Data Sheets Digital Energy™ Uninterruptible Power Supply SG-CE Series 60–80–100–120 kVA PurePulse® 400 Vac CE – Series 1
SG-CE Series 100 - 120 kVA PurePulse ®
SG-CE Series 60 - 80 kVA PurePulse®
SGSE
_060
-120
_S1_
UPS
_GE_
01
GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44
www.gedigitalenergy.com
GE imagination at work
Modifications reserved Page 2/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1
Model: SG-CE Series 60 – 80 – 100 – 120 kVA PurePulse® / Series 1
Issued by: Product Document Department – Riazzino - CH
Date of issue: 15.12.2008
File name: TDS_SGS_PCE_60K_M12_1GB_V020
Revision: 2.0
Identification No.
Up-dating
Revision Concern Date
2.0 ECN 1257 (Short-circuit characteristic) + 50Ah battery cabinet 15.12.2008
COPYRIGHT © 2008 by GE Consumer & Industrial SA All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Modifications reserved Page 3/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1
GENERAL DATA Topology VFI, double conversion with integrated transformer Nominal output power from PF=0.6 lag. to 0.9 leading KVA/kW 60/54 80/72 100/90 120/108
Overall efficiency at 100% load PF=0.9 lag. in VFI mode 91.4 91.4 91.7 91.2 Overall efficiency at 75% load PF=0.9 lag. in VFI mode +/-0.2% 91.8 91.8 92.0 91.8
Overall efficiency at 50% load PF=0.9 lag. in VFI mode
% (guaranteed values) 91.9 91.9 91.9 92.1
Overall efficiency at 100% load in SEM mode +/-0.2% % 97.9 97.9 97.8 97.9 Heat dissipation at 100% load in VFI mode, PF=0.8 lag. & charged battery kW 4.52 6.02 7.24 9.26 Cooling air (25°C ÷ 30°C) m3/h 1320 1760 2115 2710 Audible noise level dB(A) 63 63 63 63 Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd Operating temperature range UPS: 0°C ÷ 40°C Storage temperature range -25°C ÷ +55°C Relative Humidity Max. 95% (non-condensing) Max. altitude without power derating Power derating (according to EN/IEC 62040-3)
1000m 1500m: -5% / 2000m: -9% / 2500m: -14% / 3000m: -18%
Protection degree IP 20 (IEC 60529) Standards EN/IEC 62040, CE marking EMC EN/IEC 62040-2 (Category C2 as option), Burst & Surges 2kV L-L, 4kV L-PE Electrostatic discharge immunity 8kV contact / 15kV air discharge Internal protection All live parts shrouded Transport Cabinet suitable for handling by forklift Colour RAL 9003 (white), bottom air grids RAL 7021 (black) Installation Can be positioned against a wall and floor fixed Service access Front and top access only External cable connections Bottom at front of the cabinet (top as option) Cooling Enforced ventilation with fan speed control
Paralleling (RPA version) Up to 6 units parallelable for redundancy or capacity in RPA configuration (optional).
RECTIFIER
Rectifier bridge Three phase, IGBT rectifier, PurePulse® technology, overtemperature protection
Standard input voltage Nominal: 3 x 380V / 400V / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V
Other input voltages On request Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz) Power factor 0.99 Input current THD 2% at 100% load <2.5% at 75% load <3% at 50% load Inrush current Limited by soft-start circuit Power walk-in 15 seconds Output voltage tolerance +/- 1% DC voltage ripple <1% DC current ripple Max. 5% the battery capacity [Ah], expressed in A Battery charging characteristic IU (DIN 41773), T° compensated floating voltage Battery charging current limit Programmable Input power data kVA 60 80 100 120
at PF=0.8 lag. 52.5 70.0 87.3 105.3 Input power at inverter nominal load and charged battery at PF=0.9 lag. kW 59.1 78.8 98.2 118.5
Max. input power at inverter nominal load and max. battery recharge current (programmable) kW 66.0 87.8 109.5 131.6
at PF=0.8 lag. 33 44 55 65 Max. battery charging current (programmable) at the beginning of battery recharge at nominal load at PF=0.9 lag.
A 17 22 27 32
UPS OUTPUT POWER CAPABILITY
Output UPS power versus power factor for: − Inductive loads − Resistive loads − Capacitive loads
Modifications reserved Page 4/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1
BATTERY
Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)
Number of cells
VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells
Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells) Recharge time <5 hours up to 90% of battery capacity “Battery to earth” fault detection Standard Automatic and manual battery test Standard Automatic battery contactor Standard Battery power data kVA 60 80 100 120 DC power at full load and PF=0.8 lag. kW 50.8 67.8 84.7 101.6 DC power at full load and PF=0.9 lag. kW 57.2 76.2 95.3 114.3 DC power at full typical computer load (PF=0.66 lag.) kW 41.9 55.9 69.9 83.8 Matching battery cabinets See optional features on page 5
INVERTER Nominal output power at PF=0.6 ... 0.9 lag. 60 – 80 – 100 - 120 kVA Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N Inverter bridge SVM (Space Vector Modulation) and IGBT technology Output transformer (for galvanic separation) Standard Output waveform Sine wave Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ........................................ +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3% Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3% Output frequency 50/60 Hz (selectable) Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to .......................... +/- 4% Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load .......................................................... 120°: +/- 3% Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute
Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE
MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB class C or magn. trip at max. 10In) Crest factor >3:1
BYPASS Input connection Separate (dual input-recommended) or common to the rectifier input
Primary components
- Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and
inverter - 2 manual switches for maintenance bypass
Voltage limits for inverter/bypass load transfers +/- 10% (adjustable) Overload on bypass 200% for 5 minutes & 45 times In for 10 ms, non repetitive
INTERFACING 6 programmable signalling voltage-free contacts (available on Delta and block terminals)
- Standard information for easy integration and signalling - 27 user settable signals
Serial channel RS232 (on Delta 9 pin connector) Standard
Input signals - EMERGENCY POWER OFF (n/c contact, customer supplied) - GEN ON (emergency power supply ON, n/o contact, customer supplied) - 1 auxiliary signal, with settable functionality
Note: all indicated values are typical. Variations may be found from one unit to another.
Modifications reserved Page 5/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1
FRONT PANEL CONTROLS, SIGNALS AND ALARMS
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: • Back lit Graphic Display (LCD) with the
following characteristics: − Multilanguage communication
interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;
− Graphic diagram indicating UPS status.
• Command keys and parameters setting.
• UPS status control LED.
OPTIONS
COMMUNICATION: 1. Additional Customer Interface Card 2. Advanced SNMP Card 3. GE Power Diagnostics 4. GE Data Protection 5. RSB - Remote Signalling Box (cable for connection to UPS not included)
BUILT-IN UPS OPTIONS: 1. RPA kit 2. Auxiliary Power Supply (APS) 24Vdc
OPTIONS IN ADDITIONAL CABINETS: Dimensions (WxDxH): 350x850x1900mm 500x850x1900mm 850x850x1900mm 1500x850x1900mm
1. Rectifier or bypass or UPS input transformer 2. EMC filter EN/IEC 62040-2 Category C2 (Class A) 3. Top entry cables cabinet
4. Special voltages: input and/or output On request 5. Empty battery cabinets 6. Battery cabinet 50Ah (without fuses) 7. Battery cabinet 75Ah (without fuses) BATTERY TABLE 8. Battery cabinet 2x50Ah (without fuses) At 75% load PF 0.8 At 100% load PF 0.8
9. Battery cabinet 2x75Ah (without fuses) UPS (kVA) 50Ah 75Ah 2x50Ah 2x75Ah 4x50Ah 4x75Ah 50Ah 75Ah 2x50Ah2x75Ah4x50Ah4x75Ah
60 13 min. 22 min. 31 min. 53 min. 77 min. 139 min. 9 min. 16 min. 22 min. 36 min. 53 min. 95 min.
80 9 min. 15 min. 22 min. 36 min. 52 min. 95 min. 6 min. 11 min. 16 min. 26 min. 36 min. 70 min.
100 _ 12 min. 17 min. 27 min. 37 min. 65 min. _ 8 min. 12 min. 20 min. 28 min. 45 min.
SGSE_060-120_S1_OPT_cabinet 500_01
50Ah
670 kg
SGSE_160-300_OPT_B1 cabinet_01
75Ah 1000 kg
2x50Ah 1170 kg
SGSE_160-300_OPT_B2 cabinet_01
2x75Ah
1800 kg
120 _ 9 min. 13 min. 22 min. 32 min. 51 min. _ 6 min. 9 min. 16 min. 22 min. 36 min.
500x850x1900mm 850x850x1900mm 1500x850x1900mm These runtimes can be achieved only with our High Rate batteries.
EXTERNAL ACCESSORIES: 1. ISM - Intelligent Synchronization Module 350mm x 190mm x 584mm 2. Parallel output cabinet with centralized maintenance bypass On request 3. Battery fuses box On request
Modifications reserved Page 6/6 TDS_SGS_PCE_60K_M12_1GB_V020.doc Technical Data Sheets SG-CE Series 60-80-100-120 kVA PurePulse® / S1
TECHNICAL DATA
WEIGHTS (kg) UPS cabinet Additional cabinet
UPS
Rat
ing
(kVA
)
UPS
sta
ndar
d (k
g)
Floo
r loa
ding
U
PS s
tand
ard
(kg/
m2 )
Rect
ifier
or
bypa
ss tr
ansf
orm
er
(500
x850
x190
0mm
)
EMC
filte
r EN
/IEC
6204
0-Ca
t. C2
(3
50x8
50x1
900m
m)
Top
entr
y ca
bles
ca
bine
t (3
50x8
50x1
900m
m)
60 550 kg 995 340 kg 110 kg 70 kg
80 630 kg 1140 380 kg 110 kg 70 kg
100 860 kg 1212 450 kg 125 kg 75 kg
SG-CE Series 60 & 80 kVA SGSE_060-080_S1_UPS dimensions_GE_01
850mm650mm
1'90
0mm
Dimensions (WxDxH): 650mm x 850mm x 1900mm
120 860 kg 1212 450 kg 125 kg 75 kg
SG-CE Series 100 & 120 kVA
SGSE_100-120_S1_UPS dimensions_GE_01
835mm850mm
1'90
0mm
Dimensions (WxDxH): 835mm x 850mm x 1900mm
Note: Single weights have to be added up for system configuration to get the total weight!
UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS
Common input Rectifier & Bypass Separated input Rectifier & Bypass
1 = Rectifier 3 = Electronic Bypass 5 = Mains 7 = External Battery 2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses
Protections and cable sections
Protections for mains voltages
3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards
Alternatively, local standards to be respected
Fuses AgL or equivalent MTCB Cable sections (mm2)
kVA
F1 F2 F3 F4 A B C & D & E K
60 3x100A 3x100A 3x100A 2x160A 3 x 25 + 16 4 x 25 4 x 25 + 16 2 x 50 + 25
80 3x125A 3x125A 3x125A 2x250A 3 x 35 + 25 4 x 35 4 x 35 + 25 2 x 120 + 70
100 3x160A 3x160A 3x160A 2x315A 3 x 50 + 25 4 x 50 4 x 50 + 25 2 x 150 + 95
120 3x200A 3x200A 3x200A 2x355A 3 x 70 + 35 4 x 70 4 x 70 + 35 2 x 185 + 95
Cable sections recommended in Switzerland (mm2)
F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & D & E K
K: supplied by GE only with battery 60 3 x 35 + 25 4 x 35 4 x 35 + 25 2 x 70 + 35
F4: can be supplied by GE. 80 3 x 50 + 25 4 x 50 4 x 50 + 25 2 x 150 + 95
100 3 x 70 + 35 4 x 70 4 x 70 + 35 2 x 185 + 95
120 3 x 95 + 50 4 x 95 4 x 95 + 50 2 x 240 + 120
IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557).
Digital Energy
Technical Data Sheet Uninterruptible Power Supply
SG Series 160 PurePulse™ SG Series 200 - 250 - 300 PurePulse™
GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52
www.gepowerquality.com
g
imagination at work
SGSE_160_S3_UPS_01
SGSE_200-300_S3_UPS_01
Digital Energy
Modifications reserved Page 2/6
GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3
Model: SG Series 160 – 200 – 250 - 300 PurePulse™ CE S3
Issued by: Product Document Department – Riazzino - CH
Approved by: R & D Department – Riazzino - CH
Date of issue: 25.04.2012
File name: GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010
Revision: 1.0
Identification No.:
Up-dating
Revision Concern Date
COPYRIGHT © 2012 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE Digital Energy.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Digital Energy
Modifications reserved Page 3/6
GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3
GENERAL DATA Topology VFI, double conversion with integrated transformer
Nominal output apparent power from PF=0.6 lag. to 0.9 lag. and at 0.9 leading KVA 160 200 250 300
Nominal output active power from PF=0.9 lag. to 0.9 leading kW 144 180 225 270
Efficiency at 100% load PF=1 in VFI / eBoost Operation Modes %
93.6/98.4 93.7/98.4 93.4/98.4 93.5/98.5 Efficiency at 75% load PF=1 in VFI / eBoost Operation Modes 93.9/98.3 94.3/98.3 94.0/98.3 94.0/98.5 Efficiency at 50% load PF=1 in VFI / eBoost Operation Modes 94.2/98.1 94.6/98.1 94.1/98.1 94.2/98.3
Heat dissipation at 100% load, PF=0.8 lag. & charged battery (VFI) kW 8.2 10.1 13.2 15.6
Heat dissipation at 100% load, PF=0.9 lag. & charged battery (VFI) kW 9.2 11.3 14.9 17.6
Cooling air at PF=0.8 (25°C ÷ 30°C) m3/h 2389 2940 3850 4550
Cooling air at PF=0.9 (25°C ÷ 30°C) m3/h 2688 3308 4331 5119
Audible noise level dB(A) 69
Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd
Operating temperature range UPS: 0°C ÷ 40°C
Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the
storage time of the battery)
Relative Humidity Max. 95% (non-condensing)
Max. altitude without power derating Power derating (according to EN/IEC 62040-3)
1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%
Protection degree IP 20 (IEC 60529
Standards EN/IEC 62040, CE marking
EMC (Electromagnetic Compatibility) EN/IEC 62040-2 (Category C2 as option)
Electrostatic discharge immunity 4kV contact / 8kV air discharge
Internal protection All internal live parts shrouded
Transport Cabinet suitable for handling by forklift
Colour RAL 9005 (black)
Installation Can be positioned against a wall and floor fixed
Service access Front and top access only
External cable connections Bottom at front of the cabinet (top as option)
Cooling Enforced ventilation with fan failure detection
Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)
RECTIFIER Rectifier bridge Three phase, IGBT rectifier, PurePulse™ technology, overtemperature protection
Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V
Other input voltages On request
Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)
Power factor 0.99
Input current THD 2% at 100% load <2.5% at 75% load <3% at 50% load
Inrush current Limited by soft-start circuit
Power walk-in 15 seconds
Output voltage tolerance +/- 1%
DC voltage ripple <1%
DC current ripple Max. 5% the battery capacity [Ah], expressed in A
Battery charging characteristic IU (DIN 41773), T° compensated floating voltage
Battery charging current limit Programmable
Input power data kVA 160 200 250 300
Input power at inverter nominal load and charged battery at PF=0.8 lag.
kW 136.8 170.8 214.1 256.7
at PF=0.9 lag. 153.9 192.1 240.9 288.8
Max. input power at inverter nominal load and max. battery recharge current (programmable)
kW 170.5 212.7 267.8 321.1
Max. battery charging current (programmable) at the beginning of battery recharge at nominal load
at PF=0.8 lag. A
85 105 130 160
at PF=0.9 lag. 40 50 70 80
UPS OUTPUT POWER CAPABILITY
Output UPS power versus power factor for:
Inductive loads
Resistive loads
Capacitive loads
Digital Energy
Modifications reserved Page 4/6
GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3
BATTERY Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)
Number of cells
VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells
Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells)
Recharge time <5 hours up to 90% of battery capacity
“Battery to earth” fault detection Standard
Automatic and manual battery test Standard
Battery power data kVA 160 200 250 300
DC power at full load and PF=0.8 lag. / PF=0.9 lag. kW 134.7 / 151.6 168.4 / 189.5 210.5 / 236.8 252.6 / 284.2
DC power at full typical computer load (PF=0.66 lag.) kW 111.2 138.9 173.7 208.4
Matching battery cabinets See option features on page 5
INVERTER Nominal output apparent power from PF=0.6 lag. to 0.9 lag. & at 0.9 leading 160 – 200 – 250 - 300 kVA
Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N
Inverter bridge SVM (Space Vector Modulation) and IGBT technology
Output transformer (for galvanic separation) Standard
Output waveform Sine wave
Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3%
Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%
Output frequency 50/60 Hz (selectable)
Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%
Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load ........................................................... 120°: +/- 3%
Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute
Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE
MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB class C or magn. trip at max. 10In)
Crest factor >3:1
eBoost™ OPERATION MODE (OPTION) eBoost Operation Mode characteristics (option)
Output waveform Continuously monitored
Inverter reaction time ms <2 (typical)
Transfer limits in eBoost Operation Mode (option)
Steady-State RMS tolerance Vrms +/- 10
Instantaneous voltage distortion (w.r.t. normal sine wave)
Magnitude Vp +/- 50
Duration us 500
Steady-State frequency tolerance Hz +/- 3
Instantaneous phase shift rad 0.15
BYPASS Input connection Separate for rectifier and bypass input or common to the rectifier input (option)
Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and inverter - 2 manual switches for maintenance bypass
Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)
Overload on bypass 150% for 1 minute & 45 times In for 10 ms, non repetitive
INTERFACING RS232 serial port Standard
EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard
Customer Interface board Standard 6 programmable signalling voltage-free contacts .............. (available on block terminals)
- Standard information for easy integration and signalling - 27 user settable signals
Connector RJ45 .................................................................................... With adaptation cable for a serial port RS232 / sub DB9 connection Input signals .......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)
- 1 auxiliary signal, with settable functionality Note: all indicated values are typical. Variations may be found from one unit to another.
Digital Energy
Modifications reserved Page 5/6
GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3
FRONT PANEL CONTROLS, SIGNALS AND ALARMS
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) with the following
characteristics:
Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;
Graphic diagram indicating UPS status.
Command keys and parameters setting.
UPS status control LED.
OPTIONS
COMMUNICATION:
1. Additional Customer Interface Card
2. 3-ph SNMP/WEB plug-in Adapter
3. GE Power Diagnostics
4. GE Data Protection
5. RSB - Remote Signalling Box (cable for connection to UPS not included)
BUILT-IN UPS OPTIONS:
1. eBoost™ Operation Mode
2. RPA kit (Redundant Parallel Architecture)
3. Kit for common input mains
4. Auxiliary Power Supply (APS) 24VDC
5. Surge suppressors
OPTIONS IN ADDITIONAL CABINETS:
Dimensions (WxDxH): 500x850x1900mm 850x850x1900mm 1000x850x1900mm 1500x850x1900mm
1. Rectifier or bypass or UPS input transformer 160 & 200 kVA / 250 & 300 kVA
2. EMC filter EN/IEC 62040-2 Category C2 (Class A)
3. Top entry cables cabinet
4. Special voltages: input and/or output On request
5. Empty battery cabinets
6. Battery cabinet 2x50Ah (without fuses) BATTERY TABLE
7. Battery cabinet 2x75Ah (without fuses) UPS At 75% load PF 0.8 At 100% load PF 0.8
2x50Ah
1170 Kg
2x75Ah
1800 Kg
2x50Ah 2x75Ah 4x50Ah 4x75Ah 2x50Ah 2x75Ah 4x50Ah 4x75Ah
160 9 min. 15 min. 22 min. 36 min. 6 min. 11 min. 16 min. 25 min.
200 6 min. 12 min. 17 min. 27 min. _ 8 min. 12 min. 19 min.
250 _ 8 min. 13 min. 21 min. _ 6 min. 8 min. 15 min.
300 _ _ 10 min. 17 min. _ _ 6 min. 12 min.
These runtimes can be achieved only with our High Rate batteries
EXTERNAL ACCESSORIES:
1. Parallel output cabinet with centralized maintenance bypass On request
2. Battery fuses box On request
SGSE_160-300_OPT_B1 cabinet_01
SGSE_160-300_OPT_B2 cabinet_01
Digital Energy
Modifications reserved Page 6/6
GE_UPS_TDS_SGS_PCE_M16_M30_3GB_V010.docx Technical Data Sheet SG Series 160 - 300 PurePulse™ CE S3
TECHNICAL DATA
SG Series 160 PurePulse™
Dimensions (WxDxH): 900mm x 850mm x 1900mm
WEIGHTS (kg) SG Series 200 - 250 - 300 PurePulse™
Dimensions (WxDxH): 1300mm x 850mm x 1900mm
UP
S R
ati
ng
(kV
A)
UPS cabinet Built-in UPS
options Options in additional
cabinet
UP
S s
tan
da
rd
(kg
)
Flo
or
loa
din
g
UP
S s
tan
da
rd (k
g/m
2)
eB
oo
st™
O
pe
rati
on
Mo
de
(k
g)
Re
ctif
ier
or
by
pa
ss t
ran
sfo
rme
r (8
50
/10
00
x85
0x1
90
0m
m)
EM
C f
ilte
r E
N/I
EC
62
04
0-C
at.
C2
(5
00
x85
0x1
90
0m
m)
Top
en
try
ca
ble
s c
ab
ine
t (5
00
x85
0x1
90
0m
m)
160 1050 1373 20 800 230 125
200 1220 1105
30
800 230 125
250 1470 1331 900 230 125
300 1560 1412 900 230 125
Note: Single weights have to be added up for system configuration to get the total weight!
UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS
Common input Rectifier & Bypass Separated input Rectifier & Bypass
1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = External Battery
2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses
Protections and cable sections
Protections for mains voltages
3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards
Alternatively, local standards to be respected
kVA Fuses AgL or equivalent MTCB Cable sections (mm
2)
F1 F2 F3 F4 A B C & E & D K
160 3x250A 3x250A 3x250A 2x400A 3x120+70 4x120 4x120+70 2x240+120
200 3x315A 3x315A 3x315A 2x500A 3x150+95 4x150 4x150+95 2x(2x120)+120
250 3x400A 3x400A 3x400A 2x630A 3x240+120 4x240 4x240+120 2x(2x150)+150
300 3x500A 3x500A 3x500A 2x800A 3x(2x120)+120 4x(2x120) 4x(2x120)+120 2x(2x240)+240
Cable sections recommended in Switzerland (mm2)
F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & E & D K
K: supplied by GE only with battery 160 3x150+95 4x150 4x150+95 2x(2x95)+95
F4 and Q3: can be supplied by GE. 200 3x185+95 4x185 4x185+95 2x(2x150)+150
250 3x(2x95)+95 4x(2x95) 4x(2x95)+95 2x(2x185)+185
300 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(3x185)+2x150
IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557).
SGSE_160_S3_UPS dimension_01
1'9
00
mm
900mm850mm
SGSE_200-300_S3_UPS dimension_01
1'300mm850mm
1'9
00
mm
Digital Energy
Technical Data Sheet Uninterruptible Power Supply
GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52
www.gepowerquality.com
g
imagination at work
SGSE_400-500_S3_UPS_01
Digital Energy
Modifications reserved Page 2/6
GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3
Model: SG Series 400 & 500 PurePulse™ CE S3
Issued by: Product Document Department – Riazzino - CH
Approved by: R & D Department – Riazzino - CH
Date of issue: 25.04.2012
File name: GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010
Revision: 1.0
Identification No.:
Up-dating
Revision Concern Date
COPYRIGHT © 2012 by GE Consumer & Industrial SA All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE Digital Energy.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Digital Energy
Modifications reserved Page 3/6
GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3
GENERAL DATA
Topology VFI, double conversion with integrated transformer
Nominal output apparent power from PF=0.6 lag. to 0.9 lag. and at 0.9 leading KVA 400 500
Nominal output power from PF=0.9 lag. to 0.9 leading kW 360 450
Overall efficiency at 100% load PF=1 in VFI Operation Mode / eBoost Operation Mode %
93.3 / 98.5% 93.2 / 98.7% Overall efficiency at 75% load PF=1 in VFI Operation Mode / eBoost Operation Mode 93.8 / 98.5% 93.7 / 98.7% Overall efficiency at 50% load PF=1 in VFI Operation Mode / eBoost Operation Mode 94.2 / 98.3% 94.2 / 98.6%
Heat dissipation at 100% load in VFI Operation Mode, PF=0.8 lag. and charged battery kW 21.4 27.2
Heat dissipation at 100% load in VFI Operation Mode, PF=0.9 lag. and charged battery kW 24.1 30.6
Cooling air at PF=0.8 (25°C ÷ 30°C) m3/h 6253 7933
Cooling air at PF=0.9 (25°C ÷ 30°C) m3/h 7035 8925
Audible noise level dB(A) 72
Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd
Operating temperature range UPS: 0°C ÷ 40°C
Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the
storage time of the battery)
Relative Humidity Max. 95% (non-condensing)
Max. altitude without power derating Power derating (according to EN/IEC 62040-3)
1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%
Protection degree IP 20 (IEC 60529)
Standards EN/IEC 62040, CE marking
EMC (Electromagnetic Compatibility) EN/IEC 62040-2
Electrostatic discharge immunity 4kV contact / 8kV air discharge
Internal protection All internal live parts shrouded
Transport Cabinet suitable for handling by forklift
Colour RAL 9005 (black)
Installation Can be positioned against a wall and floor fixed
Service access Front and top access only
External cable connections Bottom at front of the cabinet (top as option)
Cooling Enforced ventilation with fan failure detection and fan speed regulation
Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)
RECTIFIER
Rectifier bridge Three phase, IGBT rectifier, PurePulse™ technology, overtemperature protection
Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V
Other input voltages On request
Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)
Power factor 0.99
Input current THD 2% at 100% and 75% load <3% at 50% load <4.5% at 25% load
Inrush current Limited by soft-start circuit
Power walk-in 15 seconds
Output voltage tolerance +/- 1%
DC voltage ripple <1%
DC current ripple Max. 5% the battery capacity [Ah], expressed in A
Battery charging characteristic IU (DIN 41773), T° compensated floating voltage
Battery charging current limit Programmable
Input power data kVA 400 500
Input power at inverter nominal load and charged battery at PF=0.8 lag.
kW 343.0 429.2
at PF=0.9 lag. 385.9 482.8
Max. input power at inverter nominal load and max. battery recharge current (programmable)
kW 430 539
Max. battery charging current (programmable) at the beginning of battery recharge at nominal load
at PF=0.8 lag. A
215 270 at PF=0.9 lag. 110 140
UPS OUTPUT POWER CAPABILITY
Output UPS power versus power factor for:
Inductive loads
Resistive loads
Capacitive loads
Digital Energy
Modifications reserved Page 4/6
GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3
BATTERY
Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
Float voltage at 20°C 400V ÷ 436V (dependent on the number of cells)
Number of cells
VRLA at 2.27V/cell: 177÷192 cells Vented lead acid at 2.23V/cell, no boostcharge: 180÷195 cells Vented lead acid at 2.23V/cell, with boostcharge at 2.35 V/cell: 180÷185 cells NiCd at 1.41V/cell, no boostcharge: 284÷309 cells NiCd at 1.41V/cell, with boostcharge at 1.55 V/cell: 281 cells
Min. discharge voltage (programmable) Up to 310V (dependent on the number of cells)
Recharge time <5 hours up to 90% of battery capacity
“Battery to earth” fault detection Standard
Automatic and manual battery test Standard
Battery power data kVA 400 500
DC power at full load and PF=0.8 / PF=0.9 kW 336.8 / 378.9 421.0 / 473.7
DC power at full typical computer load (PF=0.66) kW 277.9 347.4
INVERTER
Nominal output apparent power from PF=0.6 lag. to 0.9 lag. & at 0.9 leading 400 & 500 kVA
Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N
Inverter bridge SVM (Space Vector Modulation) and IGBT technology
Output transformer (for galvanic separation) Standard
Output waveform Sine wave
Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ 5 ms - output voltage THD for 100% linear load ............................ Max. 1.5% - output voltage THD for 100% non-linear load (EN 62040) Max. 3%
Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%
Output frequency 50/60 Hz (selectable)
Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%
Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load ........................................................... 120°: +/- 3%
Overload capability (at 25°C ambient temperature) 125% - 10 minutes, 150% - 1 minute
Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.7 times In for 200 ms between phase and phase 4.0 times In for 200 ms between phase and N/PE
MTCB clearance capability (selectivity) 20% In within 5-10ms (with MTCB with magnetic trip at max. 10In)
Crest factor >3:1
eBoost™ OPERATION MODE (OPTION)
eBoost Operation Mode characteristics (option)
Output waveform Continuously monitored
Inverter reaction time ms <2 (typical)
Transfer limits in eBoost Operation Mode (option)
Steady-State RMS tolerance Vrms +/- 10
Instantaneous voltage distortion (w.r.t. normal sine wave)
Magnitude Vp +/- 50
Duration us 500
Steady-State frequency tolerance Hz +/- 3
Instantaneous phase shift rad 0.15
BYPASS
Input connection Separate for rectifier and bypass input or common to the rectifier input (option)
Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass & inverter - 2 manual switches for maintenance bypass
Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)
Overload on bypass 150% for 1 minute & 45 times In for 10 ms, non repetitive
INTERFACING
RS232 serial port Standard
EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard
Customer Interface board Standard 6 programmable signalling voltage-free contacts .............. (available on block terminals)
- Standard information for easy integration and signalling - 27 user settable signals
Connector RJ45 .................................................................................... With adaptation cable for a serial port RS232 / sub DB9 connection Input signals .......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)
- 1 auxiliary signal, with settable functionality
Note: all indicated values are typical. Variations may be found from one unit to another.
Digital Energy
Modifications reserved Page 5/6
GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3
FRONT PANEL CONTROLS, SIGNALS AND ALARMS
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) with the
following characteristics:
Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;
Graphic diagram indicating UPS status.
Command keys and parameters setting.
UPS status control LED.
OPTIONS
COMMUNICATION:
1. Additional Customer Interface Card
2. 3-ph SNMP/WEB plug-in Adapter
3. GE Power Diagnostics
4. GE Data Protection
5. RSB - Remote Signalling Box (cable for connection to UPS not included)
BUILT-IN UPS OPTIONS:
1. eBoost™ Operation Mode
2. RPA kit (Redundant Parallel Architecture)
3. Kit for common input mains
4. Auxiliary Power Supply (APS) 24Vdc
5. Surge suppressors
OPTIONS IN ADDITIONAL CABINETS:
1. Rectifier or bypass or UPS input transformer Dimensions (WxDxH): 1300 x 950 x 1900mm
2. Battery isolator switch Q3 cabinet
3. Top entry cable cabinet
4. Battery isolator switch Q3 and Top entry cable cabinet
Dimensions (WxDxH): 570 x 950 x 1900mm
EXTERNAL ACCESSORIES:
1. Parallel output cabinet with centralized maintenance bypass On request
2. Battery fuses box On request
SGSE_400-500_S1_Transformer cabinet_01SGSE_400-500_S1_Q3 cabinet_01
Digital Energy
Modifications reserved Page 6/6
GE_UPS_TDS_SGS_PCE_M40_M50_3GB_V010.docx Technical Data Sheet SG Series 400 & 500 PurePulse™ CE S3
TECHNICAL DATA
SG Series 400 & 500 PurePulse™ SG Series 400 & 500 PurePulse™ with Battery isolator switch Q3 cabinet and/or Top entry cable cabinet (option)
Dimensions (WxDxH): 1800 x 950 x 1900 mm Dimensions (WxDxH): 2370 x 950 x 1900 mm
WEIGHTS
UPS model
UPS cabinet Built-in UPS options Options in additional cabinet
UP
S
sta
nd
ard
Flo
or
loa
din
g
UP
S
sta
nd
ard
eB
oo
st™
O
pe
rati
on
Mo
de
Ba
tte
ry Is
ola
tor
swit
ch
Q3
c
ab
ine
t
Top
en
try
ca
ble
c
ab
ine
t
Ba
tte
ry Is
ola
tor
Sw
itc
h Q
3 a
nd
To
p e
ntr
y c
ab
le
ca
bin
et
Re
ctif
ier
or
by
pa
ss o
r
UP
S in
pu
t tr
an
sfo
rme
r
SG Series 400 PurePulse™ 2190 kg 1281 kg/m2 75 kg 180 kg 200 kg 220 kg 1350 kg
SG Series 500 PurePulse™ 2470 kg 1445 kg/m2 75 kg 180 kg 200 kg 220 kg 1600 kg
Note: Single weights have to be added up for system configuration to get the total weight!
UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS
Common input Rectifier & Bypass Separated input Rectifier & Bypass
1 = Rectifier 3 = Automatic Bypass 5 = Mains 7 = External Battery
2 = Inverter 4 = Manual Bypass 6 = Load F4 = External Battery Fuses
Protections and cable sections
Protections for mains voltages
3x380/220V, 3x400/230V, 3x415/240V Cable sections recommended by European Standards
Alternatively, local standards to be respected
kVA Fuses AgL or equivalent MTCB Cable sections (mm
2)
F1 F2 F3 F4 A B C & E & D K
400 3x630A 3x630A 3x630A 2x1000A 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(4x120)+2x120
500 3x800A 3x800A 3x800A 2x1250A 3x(2x240)+240 4x(2x240) 4x(2x240)+240 2x(3x240)+2x185
Cable sections recommended in Switzerland (mm2)
F1, F2, F3, F4, A, B, C, D, E, (K): supplied by customer kVA A B C & E & D K
K: supplied by GE only with battery 400 3x(2x185)+185 4x(2x185) 4x(2x185)+185 2x(4x150)+2x150
F4 and Q3: can be supplied by GE 500 3x(3x150)+240 4x(3x150) 4x(3x150)+240 2x(4x185)+2x185
IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60364, IEC 61140, IEC 61557).
SGSE_400-500_S3_UPS dimension_01
1'9
00
mm
1'800mm950mm
SGSE_400-500_S3_UPS+Q3 dimension_01
1'9
00
mm
1800mm950mm
570mm
2370mm