10-LO-F0440 Page 1 of 14 v_1.0
2012-10-23
TESTING REPORT THIS REPORT IS RENDERED TO FOSHAN MIDEA CARRIER AIR-CONDITIONING EQUIPMENT CO., LTD. AND PERTAINS TO THE ENERGY EFFICIENCY TESTING FOR THEIR PRODUCT – SPLIT TYPE AIR CONDITIONERS Applicant Name & Address: Foshan Midea Carrier Air-Conditioning Equipment Co., Ltd LinGang Road, No.5 Industrial District,Beijiao,ShunDe,Foshan, GuangDong, P.R.China Manufacturer: Foshan Midea Carrier Air-Conditioning Equipment Co., Ltd Listed Brand Name: Carrier Listee’s Name & Address: Carrier InterAmerica Corporation
Carrier InterAmerica Corportation, 10801 NW 103rd Street,Suite#1, MIAMI,
FL 33178, U.S.A. Product Listed: 38KCD109313G, 38KCL109313G 38KCD112313G, 38KCL112313G 38KCD118313G, 38KCL118313G 38KCD124313G, 38KCL124313G Relevant Standard: ANSI/AHRI 210/240-2008 ANSI/ASHRAE Standard 37-2005 COVENIN 3538: 1999 Date of Test: See individual page Report No.: 12CA23872-002 Report Prepared by: Ben Gu
Report Approved by: Bridge Xue
Associate Project Engineer Performance Manager Tel: 86-020-32131282 Tel: 86-512-68086400 ext.66560 Fax: 86-020-83486777 ext. 67282 Fax: 86-512-68084099 ext. 66560 Email: [email protected] Email: [email protected]
THIS MESSAGE AND ANY DOCUMENTS ACCOMPANYING IT IS INTENDED ONLY FOR THE USE OF THE INDIVIDUAL OR ENTITY TO WHICH IT IS ADDRESSED AND MAY CONTAIN INFORMATION THAT IS PRIVILEGED, CONFIDENTIAL, AND EXEMPT FROM DISCLOSURE UNDER APPLICABLE LAW. If the reader of this message is not the intended recipient, or the employee or agent responsible for delivering the message to the intended recipient, you are hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received the communication in error, please notify us immediately by return fax and advise whether you have destroyed the original message or are returning it to us through the mail.
10-LO-F0440 Page 2 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Test Summary:
The products are inverter type split air conditioners and the test models are 38KCD109313G, 38KCD112313G, 38KCD118313G and 38KCD124313G, which combined with indoor section 42KCD109313G, 42KCD112313G, 42KCD118313G and 42KCD124313G, respectively. The test items include Cooling Capacity, EER and SEER test. The result of models 38KCL109313G, 38KCL112313G, 38KCL118313G and 38KCL124313G in following pages were obtained from models 38KCD109313G, 38KCD112313G, 38KCD118313G and 38KCD124313G. The tested models are the same with the listed models except for the model designation. The indoor sections include KCD series and KCL series. KCD series are the same with KCL series except for the front panel and model designation. Please refer to Appendix A of this report for the model difference in detail.
Test Standard of Requirement:
ANSI/AHRI 210/240-2008 <Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment> ANSI/ASHRAE Standard 37-2005 <Methods of Testing for Rating Unitary Air-Conditioning and Heat Pump Equipment> COVENIN 3538: 1999 <Acondicionadores de Aire Methodos de Ensayo de Capacidad de Enfriamiento, Consumo de Energia y Eficiencia Energetica>
Test Laboratory/Location:
Foshan Midea Carrier Air-Conditioning Equipment Co., Ltd
Lingang 5th Industrial Zone Midea Industrial City Beijiao Shunde Foshan 528311, Guangdong, China.
Test Sample Description:
1. Received date: N/A 2. Sample Card:
Model No. Sample No.
38KCD109313G (Combine with 42KCD109313G) 1#
38KCD112313G (Combine with 42KCD112313G) 2#
38KCD118313G (Combine with 42KCD118313G) 3#
38KCD124313G (Combine with 42KCD124313G) 4#
10-LO-F0440 Page 3 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Test Sample Description (cont’d): 3. Component List:
Components 38KCD109313G/ 38KCL109313G
38KCD112313G/ 38KCL112313G
38KCD118313G/ 38KCL118313G
38KCD124313G/ 38KCL124313G
Compressor Model DA108X1C-23EZ DA108X1C-20FZ3 DA130M1C-31FZ DA150S1C-20FZ
Compressor Manufacturer
GMCC GMCC GMCC GMCC
Indoor Fan motor Model
RPG20B RPG20B RPG28H YDK36-4CB(A)
Indoor Fan motor Manufacturer
Welling / Broad-ocean
Welling / Broad-ocean
Welling / Wolong
Welling
Outdoor Fan motor Model
YDK24-6KB(YDK24-6K)
YDK24-6GB(YDK24-6G-1)
YDK49-6B YDK53-6FB(B)
Outdoor Fan motor Manufacture
Welling Welling Welling Welling
10-LO-F0440 Page 4 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Model: 38KCD109313G Date of Test: From 2012-07-03 to 2012-09-06
1. Cooling Capacity, EER and SEER Test for Model 38KCD109313G
Item Unit A2 B2 EV B1 F1
Barometric Pressure inHg 29.66 29.65 29.90 29.85 29.83
Indoor Static Pressure inH2O 0.00 0.00 0.00 0.00 0.00
Indoor Airflow CFM 301.76 292.41 296.94 301.35 295.00
Indoor Capacity Btu/h 8868 9697 7790 4866 5661
EER/COP Btu/Wh 10.7 13.3 13.3 16.1 24.7
Indoor Air Inlet DB ℉ 80.06 80.06 80.06 80.06 80.06
Indoor Air Inlet WB ℉ 66.92 66.92 66.92 66.92 66.92
Indoor Air Outlet DB ℉ 60.39 58.98 61.70 65.79 64.13
Indoor Air Outlet WB ℉ 57.81 56.28 58.68 61.99 61.00
Outdoor Air Inlet DB ℉ 95.00 82.06 87.06 82.02 66.92
Outdoor Air Inlet WB ℉ 75.02 64.99 69.08 64.94 53.53
Voltage V 220.5 220.6 220.6 220.8 220.8
UUT Current A 4.10 3.62 2.92 1.56 1.17
UUT Power W 827 729 584 303 229
Frequency Hz 60.00 60.00 60.00 60.00 60.00
SEER = 15.0 (Btu/(W.h)), (Used Default Cd =0.25 for calculation)
10-LO-F0440 Page 5 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Model: 38KCD112313G Date of Test: From 2012-07-03 to 2012-09-07
2. Cooling Capacity, EER and SEER Test for Model 38KCD112313G
Item Unit A2 B2 EV B1 F1
Barometric Pressure inHg 29.56 29.66 29.86 29.88 29.89
Indoor Static Pressure inH2O 0.00 0.00 0.00 0.00 0.00
Indoor Airflow CFM 383.81 369.75 376.40 387.05 393.70
Indoor Capacity Btu/h 11778 12553 9175 5480 6009
EER/COP Btu/Wh 11.0 13.2 14.2 17.7 25.7
Indoor Air Inlet DB ℉ 80.08 80.06 80.06 80.06 80.06
Indoor Air Inlet WB ℉ 66.92 66.92 66.92 66.92 66.92
Indoor Air Outlet DB ℉ 59.22 58.03 61.48 67.03 66.22
Indoor Air Outlet WB ℉ 57.24 55.94 59.29 62.73 62.24
Outdoor Air Inlet DB ℉ 95.00 82.02 87.12 82.04 66.88
Outdoor Air Inlet WB ℉ 75.04 64.94 69.08 64.94 53.62
Voltage V 220.4 220.4 220.6 220.8 220.8
UUT Current A 5.38 4.73 4.17 1.55 1.17
UUT Power W 1075 950 644 310 234
Frequency Hz 60.00 60.00 60.00 60.00 60.00
SEER = 16.1 (Btu/(W.h)), (Used Default Cd =0.25 for calculation)
10-LO-F0440 Page 6 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Model: 38KCD118313G Date of Test: From 2012-07-03 to 2012-09-06
3. Cooling Capacity, EER and SEER Test for Model 38KCD118313G
Item Unit A2 B2 EV B1 F1
Barometric Pressure inHg 29.61 29.61 29.84 29.84 29.88
Indoor Static Pressure inH2O 0.00 0.00 0.00 0.00 0.00
Indoor Airflow CFM 485.17 482.81 484.58 491.93 506.82
Indoor Capacity Btu/h 17162 18592 14607 9345 10502
EER/COP Btu/Wh 10.5 12.8 14.0 17.6 24.6
Indoor Air Inlet DB ℉ 80.06 80.06 80.06 80.06 80.04
Indoor Air Inlet WB ℉ 66.90 66.92 66.92 66.92 66.87
Indoor Air Outlet DB ℉ 57.15 56.07 58.95 63.01 62.22
Indoor Air Outlet WB ℉ 55.54 54.46 57.38 61.01 60.42
Outdoor Air Inlet DB ℉ 94.98 82.04 87.06 82.04 66.79
Outdoor Air Inlet WB ℉ 74.98 64.94 69.06 64.98 53.53
Voltage V 220.4 220.6 221.0 221.5 221.7
UUT Current A 9.33 8.29 6.03 3.11 2.46
UUT Power W 1639 1450 1041 530 427
Frequency Hz 60.00 60.00 60.00 60.00 60.00
SEER = 15.9 (Btu/(W.h)), (Used Default Cd =0.25 for calculation)
10-LO-F0440 Page 7 of 14 v_1.0
Testing Report
Project No.: 12CA23872 File No.: TC8978
Model: 38KCD124313G Date of Test: From 2012-07-03 to 2012-09-05
4. Cooling Capacity, EER and SEER Test for Model 38KCD124313G
Item Unit A2 B2 EV B1 F1
Barometric Pressure inHg 29.53 29.55 29.81 29.79 29.85
Indoor Static Pressure inH2O 0.00 0.00 0.00 0.00 0.00
Indoor Airflow CFM 621.66 621.19 587.70 592.76 589.46
Indoor Capacity Btu/h 22891 24396 17227 12529 13962
EER/COP Btu/Wh 10.3 12.5 14.9 18.3 25.7
Indoor Air Inlet DB ℉ 80.06 80.06 80.08 80.08 80.08
Indoor Air Inlet WB ℉ 66.94 66.92 66.94 66.96 66.94
Indoor Air Outlet DB ℉ 56.77 55.87 59.34 62.24 61.43
Indoor Air Outlet WB ℉ 55.08 54.19 57.67 60.37 59.54
Outdoor Air Inlet DB ℉ 95.00 82.04 87.12 82.04 66.88
Outdoor Air Inlet WB ℉ 75.02 64.96 69.13 64.96 53.94
Voltage V 220.0 220.0 220.1 220.2 219.8
UUT Current A 10.76 9.18 5.41 3.47 2.78
UUT Power W 2230 1954 1159 684 544
Frequency Hz 60.00 60.00 60.00 60.00 60.00
SEER = 16.3 (Btu/(W.h)), (Used Default Cd =0.25 for calculation)
10-LO-F0440 Page 8 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
5.1 Photo of the units (Cont’d) Model Number: 38KCD109313G/ 38KCL109313G Outdoor Section: 38KCD109313G/ 38KCL109313G
Indoor Section: 42KCD109313G
Indoor Section: 42KCL109313G
10-LO-F0440 Page 9 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
5.2 Photo of the units (Cont’d) Model Number: 38KCD112313G/ 38KCL112313G Outdoor Section: 38KCD112313G/ 38KCL112313G
Indoor Section: 42KCD112313G
Indoor Section: 42KCL112313G
10-LO-F0440 Page 10 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
5.3 Photo of the units (Cont’d) Model Number: 38KCD118313G/ 38KCL118313G Outdoor Section38KCD118313G/ 38KCL118313G
Indoor Section: 42KCD118313G
Indoor Section: 42KCL118313G
10-LO-F0440 Page 11 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
5.4 Photo of the units (Cont’d) Model Number: 38KCD124313G/ 38KCL124313G Outdoor Section: 38KCD124313G/ 38KCL124313G
Indoor Section: 42KCD124313G
Indoor Section: 42KCL124313G
10-LO-F0440 Page 12 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
6. Nameplate of the units
10-LO-F0440 Page 13 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
6. Nameplate of the units (cont’d)
10-LO-F0440 Page 14 of 14 v_1.0
Testing Report Project No.: 12CA23872 File No.: TC8978
Appendix A, Model difference between tested model and listed model
Tested Model Number Listed Model Number Model
Difference Brand Name
Model Number Brand Name
Model Number
Carrier
38KCD109313G
Carrier
38KCL109313G
Model
Designation
38KCD112313G 38KCL112313G
38KCD118313G 38KCL118313G
38KCD124313G 38KCL124313G
Tested Model Number of indoor section Listed Model Number of indoor section Model
Difference Brand Name
Model Number Brand Name
Model Number
Carrier
42KCD109313G
Carrier
42KCL109313G
Front Panel and Model
Designation
42KCD112313G 42KCL112313G
42KCD118313G 42KCL118313G
42KCD124313G 42KCL124313G
END