Basic Short-Circuit Calculation Procedure (Follow-Up) June 26 th , 2008

Basic short circuit calculation procedure

Embed Size (px)

Citation preview

Page 1: Basic short circuit calculation procedure

Basic Short-Circuit Calculation Procedure (Follow-Up)

June 26th, 2008

Page 2: Basic short circuit calculation procedure

Calculation of Short-Circuit Currents- Point-To-Point Method

Adequate interrupting capacity and protection of electrical components are two essential aspects required by the National Electric Code in Sections 110-9, 110-10, 230-65, 240-1, and 250-95

Page 3: Basic short circuit calculation procedure

Interrupting Rating, InterruptingCapacity and Short-Circuit Currents

Interrupting capacity can be defined as “the actual short circuit current that a protective device has been tested to interrupt.”

The National Electrical Code Requires adequate interrupting ratings in section110-9.

Page 4: Basic short circuit calculation procedure

NEC Section 110-9

Equipment intended to break current at fault levels shall have an interrupting rating sufficient for the system voltage and the current which is available at the line terminals of the equipment.

Page 5: Basic short circuit calculation procedure

Calculation of Short-Circuit Currents-Point-To-Point Method

The first step to assure that system protective devices have the proper interrupting rating and provide component protection is to determine the available short-circuit currents.

Page 6: Basic short circuit calculation procedure

Calculation of Short-Circuit Currents-Point-To-Point Method

The application of the point-to-point method permits the determination of available short-circuit currents with a reasonable degree of accuracy at various points for either 3ph or 1ph electrical distribution systems.

Page 7: Basic short circuit calculation procedure

Calculation of Short-Circuit Currents-Point-To-Point Method

This method assumes unlimited primary short-circuit current (infinite bus).

Page 8: Basic short circuit calculation procedure

Step 1 (Ifla)

Determine Transformer full-load amperes fromName plateTransformer TableFormula= 3ph Transf Ifla= KVAx1000

E(L-L)

Page 9: Basic short circuit calculation procedure

Step 2 (Multiplier)

Find Transf. Mutilplier. Multiplier= __100__

Transf. %Z

Page 10: Basic short circuit calculation procedure

Step 3 (ISCA)

Determine transf. let-thru short-circuit current lSCA = IFLA x multiplier

Page 11: Basic short circuit calculation procedure

Step 4 (“f” factor)Calculate “f” factor 3ph faults f= 1.73 x L x ISCA

C x E(L-L)

L=length (feet) of circuit to the fault. C=Constant from Table 5-7-1. For parallel

runs, multiply C values by the number of conductors per phase.ISCA= available short-circuit current in amperes at beginning of circuit.

E= Voltage line to line

Page 12: Basic short circuit calculation procedure

Step 5 (“M”)

Calculate “M”M=__1__ 1+f

Page 13: Basic short circuit calculation procedure

Step 6 (ISCA @ fault)

Compute the available short-circuit current (symmetrical) at the fault ISCA = ISCA x M at

Fault

Page 14: Basic short circuit calculation procedure

Example of Short-Circuit Calculation

Page 15: Basic short circuit calculation procedure

Step 1 (Ifla)

Ifla = KVA x 100 EL-L x 1.73

Ifla = 300 x 1000 = 834 208 x 1.73

Page 16: Basic short circuit calculation procedure

Step 2 (Multiplier)

Multiplier=__100__Trans.%Z

Multiplier = 100 = 55.55 1.8

Page 17: Basic short circuit calculation procedure

Step 3 (ISCA)

ISCA = IFLA x MultiplierISCA = 834 x 55.55= 46,329A

Page 18: Basic short circuit calculation procedure

Step 4 (“f” factor)

f=1.73 x L x I 2 x C x E(L-L)

f= 1.73 x 20 x 46,329 = .1927 2 x 20,000 x 208

Page 19: Basic short circuit calculation procedure

Step 5 (“M”)

M= 1_ 1+f

M = ___1____ = .838 1 + .1927

Page 20: Basic short circuit calculation procedure

Step 6 (ISCA @ fault)

ISCA = ISCA X M Fault #1

ISCA = 46,329 x .838= 38,823 Fault #1

Page 21: Basic short circuit calculation procedure

Fault 2 Start at Step 4

Use ISCA @ Fault #1 to calculate F= 1.73 x L x ISCA

2 x C x E(L-L)

F= 1.73 x 20 x 38,823 = 1.29 5000 x 208

Page 22: Basic short circuit calculation procedure

Step 5

M=_1_ 1+f

=_1__ = .437 1+1.29

Page 23: Basic short circuit calculation procedure

Step 6

ISCA = ISCA x M Fault #2 Fault #1

ISCA = 38,823 x .437 = 16,965A Fault #2

Page 24: Basic short circuit calculation procedure

Peak Let-Thru CurrentEquipment withstand ratings can be described as : How Much Fault Current can the equipment handle, and for How Long ?

Page 25: Basic short circuit calculation procedure

Peak Let-Thru CurrentBased on present standards, data has been compiled through testing, resulting in Fuse Let-Thru Charts Peak let-thru current-mechanical forces Apparent prospective RMS symmetrical

let-thru current-heating effects.

Page 26: Basic short circuit calculation procedure

KRP-C Sp

Page 27: Basic short circuit calculation procedure

LPN RD SP

Page 28: Basic short circuit calculation procedure

LPS RK SP