Upload
nhet-ra
View
185
Download
6
Embed Size (px)
DESCRIPTION
This is my slide presentation about AVR placement in radial distribution system. Please leave your comment if you find out that it has some mistake. Thank for viewing
Citation preview
Sizing and Optimal AVR Placement in
Radial Distribution System
Presented by: NHET RA
Faculty: Electrical and Energy Engineering
Adviser: Mr. KHUN Chanthea
2013 - 2014 1
ASSERTATION OF FINAL YEAR
MINISTRY OF EDUCATION,
YOUTH AND SPORTINSTITUTE OF TECHNOLOGY
OF CAMBODIA
ELECTRICAL AND ENERGY DEPARTEMENT
Content
Introduction1
Data Collection 2
Methodology3
Result Before and After AVR implemented4
Conclusion5
Recommendation 6
3
1. Sources
2. Step-Transformer
3. Transmission line
4. Primary Distribution
line
5. Secondary
distribution line
1 Introduction
4
1 Introduction
Rational
Voltage drop in a long distribution line.
Increasing load demand.
Shortage of source supply.
5
1 Introduction
Objectives
To maintain the voltage level within the limitation (±5%).
To minimize losses in the
power distribution system
To allow the MV load customer able to connect the EDC’s grid system
To provide a means document to further researcher
6
1 Introduction
• Line Configuration
7
A CB
0.7m 1.4m
Position1
A
C1.8 m
B
Position 2
2 Data Collection
• Line Parameter Computation
– Resistance Line
– Temperature Effect
– Skin Effect
8
dc
lR
A
22 1
1
T tR R
T t
( )ac dcR f x R
_
0.0635981.6093 dc km
fX
R
2 Data Collection(Conts)
9
2 Data Collection(Conts)
X K X K X K X K
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.00000
1.00000
1.00001
1.00004
1.00013
1.00032
1.00067
1.00124
1.00212
1.00340
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.00519
1.00758
1.01071
1.01470
1.01069
1.02582
1.03323
1.04205
1.05240
1.06440
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
1.07816
1.00375
1.11126
1.13069
1.15207
1.17538
1.20056
1.22753
1.25620
1.28644
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
1.31800
1.35102
1.38504
1.41900
1.45570
1.49202
1.52879
1.56587
1.60314
1.64051
– Line Inductance
– Reactance
– Impedance
10
0.2 ln /L
GMDL mH km
GMR
3L SA SB SCGMR D D D
312 23 13GMD D D D
2X Lf
Z R jX
2 Data Collection(Conts)
• Line Impedance
11
TYPEOverhead Line
AAC
Section [mm2] 70 150
Z [Ω/km]Position 1 0.5012+j0.3673 0.2358+j0.3434
Position 2 0.5012+j0.3700 0.2358+j0.3460
2 Data Collection(Conts)
Load Categories
12
Apparent
power (kVA)
Number of
Transformer
Load % Active
Power (kW)
Active Power
(kW)
1000 1 50% 475 156.12
500 1 50% 237.5 78.06
400 4 50% 190 62.44
320 1 50% 152 49.95
250 3 50% 118.75 39.03
160 5 50% 76 24.97
100 11 50% 47.5 15.61
63 1 65% 29.925 9.83
50 7 50% 23.75 7.80
30 2 50% 14.25 4.68
2 Data Collection(Conts)
• Capacitor Bank
13
N0 Capacitor Bank Rating (kVAr) Denomination
1 45 224
2 125 195
3 125 430
4 75 359
5 75 454
6 45 307
7 45 166
8 30 325
9 45 259
10 30 596
2 Data Collection(Conts)
14
The Voltage at source node 2 is taken as
In General
3 Methodology
1 1V 2 2V
1I
1 1Z= r jx
2 2P jQ
2 1 1 1V =V I Z
2 1V =n n j jV I Z
1 2
j
The Load Current at node is calculate by
The real and reactive power losses of branch ‘j’
can be calculated as
The current in each branch is calculated by
applying KCL
15
3 Methodology
*
i ii
i
P jQIL
V
2
i j jLP I r
2
i j jLQ I x 1,2,....,for j nb
1
0nb
j i
j
I IL
" "i
• DETERMINING REQUIRE REGULATOR TYPE AND SIZE
According to real nameplate 150 Amps
16
1000( )
3
three phase kVARated load Amps Three phase
line to linevolts
3 Methodology
6753 1000177.22
22000 3
kVARated load Amps Amps
volts
• Backtracking is a methodical way of trying out
various sequences of decisions, until you find one
that “works”
17
3 Methodology
1819 bus RDS before shifting of auto-voltage regulators
3 Methodology(Conts)
1919 bus RDS after shifting of auto-voltage regulators
3 Methodology(Conts)
START
Read System line and load data, base kV and kVA, iteration
count (IC) =1 and tolerance (e) = 0.0001
Perform load flow and calculate voltage at each bus,
real and reactive power losses
1. Using PSS/ADEPT study POWER FLOW
2. Find optimal point for placing AVR in radial power distribution systems
Yes
Noint?ref realV V Optimal po
END 20
21
4 Result
Result before AVR implemented with 50% on load
22
4 Result(Conts)
Result before AVR implemented with 70% on load
23
4 Result(Conts)
Result after AVR implemented with 50% load
24
4 Result(Conts)
Result after AVR implemented with 70% load
25
4 Result(Conts)
Power LossesBefore Using
BTAfter AVR Using
BT
Power losses with 50% on load
407.48 411.53
502.96 506.13
Power losses with 70% on load
914.56 758.57
1,348.29 1,156.17
( )lossesP kW
( )lossesQ kVAr
( )lossesQ kVAr
( )lossesP kW
Voltage profile before AVR is implemented
started to decrease lower than the limitation
(±5%) with a high power losses.
After AVR is implemented, Voltage profile
stay within the limitation even the power
consumption shoot up to 70%.
26
5 Conclusion
For further research, the decision makers may consider on:
Using Genetic Algorithm or Fuzzy Set to make the research study more accurate and precise.
Propose another alternative solution such as sub-transmission line, Optimal CAPO, or creating a new power Distribution Line.
27
6 Recommendations
Thank You for Your Attention.
Any Question?
28