50
2011 NREP/OIP Annual Conference October 2011 David P. Horowitz, P.E., CSP Tighe & Bond 413.572.3211 (office) 413.250.2487 (cell) Twitter @dphorowitz [email protected] Tighe & Bond – A 2011 Best Firm! Flammable/Combustible Storage – Impact of the Energy Policy Act

Flammable/Combustible Storage - Impacts of the Energy Policy Act

Embed Size (px)

DESCRIPTION

This present was prepared for the National Registry of Environmental Professionals’ 2011 Annual Conference. The Conference was held in Las Vegas, October 3 – 5, 2011.

Citation preview

Page 1: Flammable/Combustible Storage - Impacts of the Energy Policy Act

2011 NREP/OIP Annual Conference

October 2011

David P. Horowitz, P.E., CSP

Tighe & Bond413.572.3211 (office)413.250.2487 (cell)Twitter @[email protected]

Tighe & Bond – A 2011 Best Firm!

Flammable/Combustible Storage – Impact of the Energy Policy Act

Page 2: Flammable/Combustible Storage - Impacts of the Energy Policy Act

International Symbol for ‘Choke’

Page 3: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Here’s My Favorite Team

Page 4: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Agenda - Storage Tank Flow Chart

Page 5: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Storage Tank Flow Chart

Page 6: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Aboveground Storage Tanks - Oil

■ SPCC (Federal - Only for oil)– 40 CFR 112

■ AST Requirements– NFPA 30 & 31 (National Code –

most states)

■ Oil-filled electrical equipment

■ Most states require registration (local)

■ Many states require tightness testing

Page 7: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Applicable Code - NFPA

■ “… reduce the worldwide burden of fire and other hazards on the quality of life by providing and advocating consensus codes and standards, research, training and education”

■ National Fire Protection Association (NFPA)– NFPA 30: Flammable and Combustible Liquids

Code– NFPA 30A: Motor Fuel Dispensing Facilities and

Repair Garages– NFPA 31: Installation of Oil-Burning Equipment

Page 8: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Applicable Code - UL

■ … an independent, not-for-profit product-safety testing and certification organization.

■ Underwriters Laboratory Inc. (UL)– UL 80: Standard for Steel Tanks for Oil-Burner

Fuel– UL 142: Standard for Steel Aboveground

Tanks for Flammable and Combustible Liquids– UL 2085: Standard for Protected

Aboveground Tanks fro Flammable and Combustible Liquids

– UL 1316: Standard for Glass-Fiber-Reinforced Plastic Underground Storage Tanks for Petroleum Products

Page 9: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Flammable/Combustible

Agency/Organization

Flash Point

(To be considered Flammable)

OSHA/NFPA ≤ 100°F

EPA ≤ 140°F

(Ignitability)

DOT < 141°F

Page 10: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Spill Prevention, Control and Countermeasure (SPCC) Planning Requirements

Aboveground Oil Storage

Page 11: Flammable/Combustible Storage - Impacts of the Energy Policy Act

SPCC Regulations 101

■ Oil Storage

■ 1,320 Gallons (above ground)

■ SPCC Plan

■ 2002 Regulatory Changes

■ Subsequent Regulatory Changes

Page 12: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Integrity Testing – Industry Standards

■ API 653 – Tank Inspection, Repair, Alteration and Reconstruction

■ API 575 – Inspection of Atmospheric and Low-Pressure Tanks

■ API 570 – Piping Inspection Code■ ASME B31.3 – Process Piping■ ASME 31.4 – Liquid Transportation Systems for

Hydrocarbons, Liquid Petroleum Gas, Anhydrous Ammonia and Alcohols

■ STI SP001 – Standard for the Inspection of Aboveground Storage Tanks

■ UL 142 – Steel Aboveground Tanks for Flammable and Combustible Liquids

Page 13: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Integrity Testing – Steel Tank Institute

SP001

ISSUED SEPTEMBER 2011

5th EDITION

Page 14: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Applicable federal, state ……

■ 40 CFR 112 – SPCC■ 40 CFR 261 – Hazardous Waste■ 40 CFR 279 – Used Oil■ 40 CFR 280 - USTs■ 40 CFR 372 - EPCRA■ NFPA 30/30A – Flammable & Combustible Liquids■ NFPA 31 – Oil-Burning Equipment■ UL 80■ UL 142 ■ UL 2085■ UL 1316 – Tank Construction■ State■ Local

Page 15: Flammable/Combustible Storage - Impacts of the Energy Policy Act

SP001 – AST Categories

Page 16: Flammable/Combustible Storage - Impacts of the Energy Policy Act

SP001 – Inspection Schedule

Page 17: Flammable/Combustible Storage - Impacts of the Energy Policy Act

STI Inspection Results

Page 18: Flammable/Combustible Storage - Impacts of the Energy Policy Act

ASTs

Page 19: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Normal Venting

Page 20: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Emergency Venting

Page 21: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Spill Containers

Page 22: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Overfill Prevention

Page 23: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Interstice

Page 24: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Compliance Issues

Why?

Why?

Page 25: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Ultra-Sonic Thickness Testing

Page 26: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Ideal Installation – Single Wall Tank

Page 27: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Ideal Installation – Double Wall Tank

Page 28: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Ideal Installation – Generator Tank

Page 29: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Observation Results

■ 200+ Tanks observed for tank integrity

■ One* with >75% wall thickness losses– Compared to existing

standards

■ Some with evident corrosion– Interior of double wall– External

FIN

DIN

GS

Page 30: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Observation Results

■ Most with regulatory, code compliance, operational issues– Vent heights & vent

configuration/operation– No overfill protection/Level detection

devices– Not UL 142 standard construction– No spill prevention devices– Improper protection from vehicular

impact

■ Consistent with Florida Leak Autopsy Study (FLAS)– Mott-Smith Consulting Group

FIN

DIN

GS

Page 31: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Storage Tank Flow Chart

Page 32: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Underground Storage Tanks - Oil

■ UST Requirements (Federal)– 40 CFR 280 (UST Regulations)– 40 CFR 281 & 282 (State Approval)

■ UST Requirements (States)– Often cite NFPA 30 & 31

■ Most states require registration (local)

■ Many states require tightness testing

Page 33: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Question?

■ What is the minimum tank volume for applicability under 40 CFR 280?

■ 110 Gallons– 40 CFR 280.10(b)(4)

Page 34: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Energy Policy Act of 2005

■ Underground Storage Tank Compliance Act of 2005

■ Reduce releases to environment

■ Focus on preventing releases

■ Expanded Leaking Underground Storage Tank (LUST) Trust Fund

■ Inspections, operator training, delivery prohibition, secondary containment and financial responsibility

Page 35: Flammable/Combustible Storage - Impacts of the Energy Policy Act

The Big Picture

■ 611,500 USTs

■ 223,000 sites

■ 2/3 of active USTs are compliant

■ UST releases declining

Page 36: Flammable/Combustible Storage - Impacts of the Energy Policy Act

The Big Picture

Page 37: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Underground Storage Tank Systems

Page 38: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Inspection Overview

■ Facility Records

■ Spill Protection

■ Overfill Prevention

■ Tank Leak Detection

■ Piping Leak Detection

■ Corrosion Protection

Page 39: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Records Review

■ Pre-Inspection– Federal

» Financial Assurance– State

» Environmental Registry– Local

» Fire Department Permits» Registration

– Facility» Inventory Monitoring» Release Prevention

■ Inspection– Verify record documents

match registries

Page 40: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Financial Assurance

■ Use state financial assurance funds

■ Obtain insurance coverage■ Obtain a guarantee■ Obtain a surety bond■ Obtain a letter of credit■ Pass a financial test■ Set up a trust fund

■ Local, State & Feds = OK!

Page 41: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Spill Buckets

■ Below Grade Spill Buckets– Sits under access hand hole, not exposed to elements, plows

Page 42: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Overfill Prevention

Automatic Shut Off

Ball Float Vent

High Level Alarm

Page 43: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Tank Leak Detection

■ Interstitial Monitoring

■ Automatic Tank Gauging– Continuous In-Tank Leak Detection System (CLSD)

■ Manual Tank Gauging– ≤2,000 gallons

■ Statistical Inventory Reconciliation (SIR)– Vendor or approved in-house data analysis – 2 year tightness testing interval

■ Soil Vapor Monitoring– Site assessment

■ Groundwater Monitoring– Site assessment

Page 44: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Piping Leak Detection

■ Interstitial Monitoring

■ Automatic Line Leak Detectors (ALLD)

■ European Suction– Check valve immediately

beneath pump/dispenser

■ American Suction– Check valve at UST

■ Tightness Testing– 3 year interval

Page 45: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Corrosion Protection

■ Galvanic Protection– STI-P3– 3 Year NACE Inspection

» -0.850 Volt, soil to tank potential

■ Impressed Current– 60 day Operator Inspection– Annual NACE Inspection

■ Non-Metal Construction– Clad Steel Tanks– FRP

Page 46: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Inspection Shortfalls

■ Shear Valves

■ Vapor Recovery

■ Regulatory Confusion

Page 47: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Water in the Sump?

Page 48: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Typical Deficiencies – 175+ USTs Observed (No Retail)

Deficiency % Identified

Maintenance 91%

Financial Assurance 84%

Sump Monitoring 66%

Registration 61%

Overfill Prevention 38%

Cathodic Protection 18%

Double Wall Piping Issues 12%

Shear Valve 11%

‘Extra’ Vents 6%

Page 49: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Operator Training - FUTURE

■ Required by August 8, 2012– Three classes of operator

■ Owner/Operator Inspections– Monthly– Semi-annual– Annual

Page 50: Flammable/Combustible Storage - Impacts of the Energy Policy Act

Thank You!

■ David P. Horowitz, P.E., CSP

[email protected]

@dphorowitz