Man in the middle attacks on IEC 60870-5-104 Pete Maynard @pgmaynard ORCID 0000-0002-6267-7530

Man in the middle attacks on IEC 60870-5-104

Embed Size (px)

DESCRIPTION

Man in the middle attacks on IEC 60870-5-104 http://dx.doi.org/10.14236/ewic/ics-csr2014.5

Citation preview

Page 1: Man in the middle attacks on IEC 60870-5-104

Man in the middle attacks on IEC 60870-5-104

Pete Maynard

@pgmaynard ORCID 0000-0002-6267-7530

Page 2: Man in the middle attacks on IEC 60870-5-104

2

Introduction

● Pete Maynard● PhD Student● CSIT Queen's University Belfast, UK● Industrial Control System Security● Partnership with PRECYSE

Page 3: Man in the middle attacks on IEC 60870-5-104

3

What I do

● Attacks on SCADA protocols– Replay, MITM, DoS

● Develop detection and prevention methods ● Anomaly detection via machine learning

Page 4: Man in the middle attacks on IEC 60870-5-104

4

PRECYSE

● European FP7 Project● Prevention, protection and REaction to CYber

attackS to critical infrastructurEs● LINZ STROM GmbH (Electrical Distribution

Operator)

Page 5: Man in the middle attacks on IEC 60870-5-104

5

Talk Overview

● What's SCADA Used for● SCADA Threats● Introduction IEC 104● Attacking IEC 104

Page 6: Man in the middle attacks on IEC 60870-5-104

6

What's SCADA Used for?

Page 7: Man in the middle attacks on IEC 60870-5-104

7

How is SCADA used

● MODBUS, DNP3, IEC104, 61850, Profibus …

[1] S. Mohagheghi, J. Stoupis, and Z. Wang. Communication protocols and networks for powersystems-current status and future trends. In Power Systems Conference and Exposition,2009. PSCE ’09. IEEE/PES, pages 1–9, March 2009.

[1]

Page 8: Man in the middle attacks on IEC 60870-5-104

8

What does it do?

● Telemetry control● Change Settings ● Read/Write/Delete

files and directories● Update firmware

Page 9: Man in the middle attacks on IEC 60870-5-104

9

SCADA Threats

Page 10: Man in the middle attacks on IEC 60870-5-104

10

Attack Levels

Level Example

1 Accident Misconfigured, Firmware Update

2 Novice Script kiddie, port scanning

3 Experienced Replay attack, basic knowledge

4 Advanced Stuxnet, ICS domain knowledge

Page 11: Man in the middle attacks on IEC 60870-5-104

11

Threats

● Havex Malware● OPC to scan for SCADA devices● Reports back to command and control server● Recently detected July 2014

– European ICS

– Team Since 2011

● State sponsored?

Page 12: Man in the middle attacks on IEC 60870-5-104

12

Scanning for SCADA devices

● Readily available scanners– SCADA StrangeLove[1]

● Simple Python Script ● Return Device name,

IP, software version

[1] https://github.com/atimorin/scada-tools

Page 13: Man in the middle attacks on IEC 60870-5-104

13

SCADA Fuzzers

● Protocol Fuzzers● Project Robus[1]

– DNP3

– Identified many vulnerabilities

● Fuzzing can kill

[1] http://www.automatak.com/robus/

Page 14: Man in the middle attacks on IEC 60870-5-104

14

Protocol Analysers

Page 15: Man in the middle attacks on IEC 60870-5-104

15

Introduction IEC 104

Page 16: Man in the middle attacks on IEC 60870-5-104

16

Introduction IEC 60870-5-104

● International Electrotechnical Commission (IEC)

● IEC 60870 developed periodically between the years 1988 and 2000

● 6 Main Parts and four companion sections● Open Standard● 60870-5-104 defines transmission over

TCP/IP

Page 17: Man in the middle attacks on IEC 60870-5-104

17

IEC 60870-5-104 Security Issues

● Ported from serial links to TCP/IP● No authentication● No encryption● Uses IP address white-list

– Defined on the slave

● TLS encryption recommended – In practice not implemented

Page 18: Man in the middle attacks on IEC 60870-5-104

18

104 Payload

ASDU

Page 19: Man in the middle attacks on IEC 60870-5-104

19

Attacking IEC 104

Page 20: Man in the middle attacks on IEC 60870-5-104

20

Capturing Packets

● SPAN Port● DNS Poisoning● Content Addressable Memory (CAM) table

overflow● ARP Spoofing

Page 21: Man in the middle attacks on IEC 60870-5-104

21

Replay Attack● Novice level attack● Capture and replay packets

– Command, readings, alerts...

● Replayed packets dropped by kernel● Tcpreplay alternatives to modify SEQ values

Page 22: Man in the middle attacks on IEC 60870-5-104

22

Man In the Middle Attack

● Intercept communications between two or more devices

● Modify and inject packets● Many tools available

– ettercap

– cain and abel

– DSniff

Page 23: Man in the middle attacks on IEC 60870-5-104

23

104 MITM Lab Experiment

● Modify Cause of transmission (CoT) field● Intercept and set an invalid CoT value● Detection with SNORT

Page 24: Man in the middle attacks on IEC 60870-5-104

24

Cause of Transmission

● CoT values can use the following number ranges: – 1-13 and 20-41 – 14-19 and 42-43 are reserved for future use.

Page 25: Man in the middle attacks on IEC 60870-5-104

25

Before and After Capture

Before

After

Page 26: Man in the middle attacks on IEC 60870-5-104

26

SNORT Alert

[**] [1:6666617:1] 17: SCADA_IDS: IEC 60870-5-104 – Suspicious Value of Transmission Cause Field [**][Classification: Potentially Bad Traffic] [Priority: 2] 09/09-14:06:10.462288 10.50.50.105:40734 -> 10.50.50.75:22TCP TTL:64 TOS:0x0 ID:60033 IpLen:20 DgmLen:60 DF******S* Seq: 0x9A0C38A1 Ack: 0x0 Win: 0x3908 TcpLen: 40TCP Options (5) => MSS: 1460 SackOK TS: 1382076960 0 NOP WS: 7

alert tcp $104_CLIENT any -> $104_SERVER $104_PORTS (flow: established; content:"|68|"; offset:0; depth:1; pcre:"/[\S\s]{5}(\x2D|\x2E|\x2F|\x30|\x64|\x65)/iAR"; content:!"|06|"; offset: 8; depth: 1; msg:"17: SCADA_IDS: IEC 60870-5-104 – Suspicious Value of Transmission Cause Field"; classtype:bad-unknown; sid:6666617; rev:1; priority:2;)

Rule

Alert

Page 27: Man in the middle attacks on IEC 60870-5-104

27

Earth Fault

● Real world situation where an earth fault in the physical electrical grid occurs

Page 28: Man in the middle attacks on IEC 60870-5-104

28

Linz Test-bed

Page 29: Man in the middle attacks on IEC 60870-5-104

29

Operator View

Page 30: Man in the middle attacks on IEC 60870-5-104

30

104 MIM TestBed Environment

● Intercept value, so operators unable to view fault

● 104's Information Objects, M_SP_TB_1 stores the 'ON/OFF' value

● First bit of the SIQ is the SPI field, storing the ON/OFF value.

Page 31: Man in the middle attacks on IEC 60870-5-104

31

ON/OFF Value Modification

Before

After

Page 32: Man in the middle attacks on IEC 60870-5-104

32

Conclusion

● Attackers with varying skill levels can compromise SCADA systems– Man-In-The-Middle attacks hiding an earth fault

● New implementations of ICS need to take precautions

● Monitor logs, network, everything● Enable attack mitigations

Page 33: Man in the middle attacks on IEC 60870-5-104

33

Future Work

● Identify features of the IEC104 protocol for anomaly detection

● Propose to develop an Anomaly Detection module for the IEC104 protocol– Detect similar network attacks

● Work on MITM attack for IEC 61850

Page 34: Man in the middle attacks on IEC 60870-5-104

34

Questions