Appendix: Technical Specifications and Special Features of the S7-400
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.2
Technical Specifications of the S7-300 CPUs (1)CPU
Execution time in µs Bit instruction Word instruction Integer (+/-) Real (+/-)
User memory Work memory Load memory integr. Load memory extern
Addresses Bit memories Clock memories Timers Counters
Block Types/Number FBs FCs DB's
Size of process image I/O in bytes
max. I/O address area in bytes
Interfaces
314 IFM
0.3 - 0.61.22.050.0
32 KB48 KB(4 MB)
2048812864
128128127
124 each
752 each
MPI
315-2 DP
0.3 - 0.61.02.050.0
64 KB96 KB4 MB
2048812864
192192255
128 each
1024 each
MPI, DP
315
0.3 - 0.6 1.02.050.0
48 KB80 KB4 MB
2048812864
192192255
128 each
768 each
MPI
312 IFM
0.6 - 1.22.03.060.0
6 KB20 KB-
102486432
323263
32 each
32 each
MPI
314
0.3 - 0.61.22.050.0
24 KB40 KB4 MB
2048812864
128128127
128 each
768 each
MPI
313
0.6 - 1.22.03.060.0
12 KB20 KB4 MB
2048812864
128128127
128 each
32 each
MPI
316-2 DP
0.3 - 0.6 1.02.050.0
128 KB192 KB4 MB
2048812864
256512511
128 each
1024 each
MPI, DP
318-2 DP
0.10.10.10.6
512 KB64 KB4 MB
81928512512
102410242047
256 each (2048)
8192 each
MPI/DP, DP
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.3
313
OB No.110203540-10080-82, 85, 87121,122
1536
8 KB8
4/4
4
1
1
22 bytes
CPU
Organization blocksFree cycleTime-of-day interruptsTime-delay interruptsCyclic interruptsHardware interruptsBackground executionStartupErrors, asynchronous
Errors, synchronous
Local data in bytes
max. block lengthBlock nesting depth per execution level
CommunicationMax. connectionsstatic/dynamic
Global data communi-cation via MPI:GD circles per CPU
Send GD packets per GD circle
Receive GD packet perGD circle
max. user data size of a packet
Technical Specifications of the S7-300 CPUs (2)314 IFM
OB No.110203540-10080-82, 85, 87121,122
1536
8 KB8
4/8
4
1
1
22 bytes
315-2 DP
OB No.110203540-10080-82, 8587121,122
1536
16 KB8
4/8
4
1
1
22 bytes
315
OB No.110203540-10080-82, 85,87121,122
1536
16 KB8
4/8
4
1
1
22 bytes
312 IFM
OB No.1---40-100-
-
512
8 KB8
4/2
4
1
1
22 bytes
316-2 DP
OB No.110203540-10080-82, 8587121,122
1536
16 KB8
4/8
4
1
1
22 bytes
318-2 DP
OB No.110,1120,2132,3540,4190100,10280-82, 8587121,122
4096(8192)
64 KB20
32
8
1
2
54 bytes
314
OB No.110203540-10080-82, 85, 87121,122
1536
8 KB8
4/8
4
1
1
22 bytes
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.4
Technical Specifications of the S7-400 CPUs (1)CPU
Execution time in µs Bit instruction Word instruction Integer (+/-) Real (+/-)
User memory Work memory int. Load memory integr. Load memory extern
Addresses Byte memories Clock memories Timers Counters
Block Types/Number FBs FCs DB's
Size of process image I/O in bytes
max. I/O address area in bytes
Interfaces
414-3
0.10.10.10.6
2x 384 KB256 KB64 MB
8 K8256256
102410241023
8 K each
8 K each
MPI/DP2xDP
416-3
0.080.080.080.48
2x 1.6 MB256 KB64 MB
16 K8512512
204820484096
16 K each
16 K each
MPI/DP2x DP
416-2
0.080.080.080.48
2x 0.8 MB256 KB64 MB
16 K8512512
204820484096
16 K each
16 K each
MPI/DPDP
412-1
0.20.20.20.6
2x48 KB256 KB64 MB
4 K8256256
256256511
4 K each
4 K each
MPI/DP
414-2
0.10.10.10.6
2x128 KB256 KB64 MB
8 K8256256
102410241023
8 K each
8K each
MPI/DPDP
412-2
0.20.20.20.6
2x48 KB256 KB64 MB
4 K8256256
256256511
4 K each
4 K each
MPI/DPDP
417-4
0.10.10.10.6
2x2 MB256 KB64 MB
16 K8512512
614461448191
16 K each
16 K each
MPI/DP3x DP
417H
0.10.10.10.6
2x2 MB256 KB64 MB
16 K8512512
614461448191
16 K each
16 K each
MPI/DPDP
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.5
CPU
Organization blocksFree cycleTime-of-day interruptsTime-delay interruptsCyclic interrupsHardware interruptsMulticomputingBackground executionStartupErrors, asynchronousErrors, synchronous
Local data in bytes
max. block lengthBlock nesting depthper execution level
CommunicationMax. connectionsstatic/dynamic
Global data communi-cation via MPI:GD circles per CPU
Send GD packets per GD circle
Receive GD packets perGD circle
max. user data size of a packet
Technical Specifications of the S7-400 CPUs (2)414-3
OB No.110-1320-2332-3540-436090100-10280-87121,122
8 KB
64 KB16
32
8
1
2
54 bytes
416-3
OB No.110-1720-2330-3840-476090100-10280-87121,122
16 KB
64 KB16
64
16
1
2
54 bytes
416-2
OB No.110-1720-2330-3840-476090100-10280-87121,122
16 KB
64 KB16
64
16
1
2
54 bytes
412-1
OB No.110,1120,2132,3540,416090100-10280-87121,122
4 KB
48 KB16
16
8
1
2
54 bytes
414-2
OB No.110-1320-2332-3540-436090100-10280-87121,122
8 KB
64 KB16
32
8
1
2
54 bytes
412-2
OB No.110,1120,2132,3540,416090100-10180-87121,122
4 KB
64 KB16
16
8
1
2
54 bytes
417-4
OB No.110-1720-2330-3840-476090100-10280-87121,122
32 KB
64 KB16
64
16
1
2
54 bytes
417H
OB No.110-1720-2330-3840-476090100,10280-87121,122
32 KB
64 KB24
64
16
1
2
54 bytes
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.6
Main Differences to the S7-300
Larger memory and more I/Q/M/T/C
Addresses of input/output modules selectable
Can connect EUs from S5 and use S5 CP/IP modules
More system functions, e.g. programmed block communication
Block size up to 64KB and twice as many DBs
Complete restart and restart
Setpoint/actual comparison of configuration on startup
Modules can be removed without disconnecting the power supply
Several part process images
Priorities of OBs are parameter-assignable
Several OBs for cyclic, hardware and time-of-day interrupts
Block nesting up to 16 levels
Size of L Stack selectable for each execution level
4 accumulators
Multicomputimg
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.7
Components of the S7- 400
CPUsCPUs
CPU 412-1, 412-2CPU 414-1, 414-2,CPU 416-2, 416-3CPU 417-4, 417H
RacksRacks
- Universal rack (UR 1/2) for use as CR and ER- Extension rack (ER 1/2)- Segmented central rack (CR2)
Signal modules (SM)Signal modules (SM)
- DI/DO 32,16,8 channels
- DO with relay output- AI/AO 16,8 channels- diagnostics-capable
modules
Communicationprocessors (CP)
Communicationprocessors (CP)
- Point-to-Point CP441-1, 1- channel CP441-2, 2- channel- Networks
Profibus Ethernet
Power Supplies (PS)Power Supplies (PS)
- AC 120V/230V, 4A/10A/20A- DC 24V, 4A/10A/20A
Function modules (FM)
Function modules (FM)
- Counting- Positioning- Closed-loop control
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.8
Racks of the S7 - 400
UR1 / UR2(Universal Rack)
Type of Rack Centralrack
Extensionrack
Usable in
Yes Yes
P bus
ER1 / ER2(Extension Rack)
No Yes
P bus
K bus
CR2(Central Rack)
NoYes
P bus, Segment 1
K bus
P bus, Segment 2
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.9
Module Parameters: Logical Addresses
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.10
CPU Parameters: Startup
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.11
CPU Parameters: Interrupts
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.12
CPU Parameters: Local Data
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.13
Configuring Multicomputing Operation
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.14
SFC 35 for Synchronization in Multicomputing Operation
Parameter Declaration Data type Memory Description
JOB INPUT BYTE I, Q, M, D, L, Const. Task identifier (possible values: 1 to 15)
RET_VAL OUTPUT INT I, Q, M, D, L Return value (error code).
SIMATIC S7Siemens Engenharia e Service 2002. Todos os direitos reservados.
Data: 13/04/23Arquivo: S7-Bas-15.15
Remove and Insert Interrupt
Module exists
Module available
Remove/Insert interrupt
Parameter assignment of module through the operating system
Removing amodule
Inserting amodule
max.
1s
max.
1s