  • NewsletterMay2007ElectricalSystemsRulesofThumb

    XCELEnergyLightingRebates

    EnergyComplianceforCommercial

    Buildings

    LEEDInnovationinDesignPoints

    PlugIntotoIndustryEvents

    ElectricalSystemsRulesofThumb

    Daylighting

    ELECTRICALSYSTEMSRULESOFTHUMB:

    1.ElectricalRoomRequirements

    a. Onlargerfacilities,themainroomtypicallyneedstwodoors,oneateachendofroom(notdoubledoorsatonelocation).

    b. Doorsmustopeninthedirectionofegressfromtheroom.c. Doorsmusthavepanichardware.d. RatedConstruction:Itisnottypicalthatthisroomberequiredtohavea1hour

    rating.Iftheelectricalengineerneedsalargetransformer(atransformerwitharatingover112.5KVA)inthisroom,theyshouldnotifytheArchitectthattheroomwillberequiredtohavea1hourratingduetotheNationalElectricalCoderequirements.

    2.ElectricalRoomSizingforTypicalFacilities(recreationcenters,multifamily,generalcommercial)

    SizeofFacility

    MainElecRoom RemoteElecRoomsRqd?

    RemoteElecRoomSize Notes

    020,000sf,onelevel

    10x20 Typicallynot N/A (1)

    20,00040,000sfmultilevels

    15x20 Oneonmainlevelandoneper20,000sfonupperlevel(s)

    8x10each (1)

    +40,000sf 15x20 Oneachlevel,oneper20,000sfandspace200apart

    8x10each (1)

    HulaTooAd

  • (1)Additionalremoteelectricalroomsshouldbeconsideredforbuildingswithdistinctspacelayoutswhichmaybenefitfromadditionallocalizeddistributionequipment.(i.e.Anindividualwingofbuildingthatisseparatedfromthemainbuildingbymultistoryopenatrium).

    3.ExteriorServiceTransformer(notethatallspecificelectricalutilitytransformerrequirementsaretobecoordinatedwiththelocalutilityengineerfortheprojectasmostutilitycompaniesvarytheirrequirements)

    a. Lessexpensiveiftransformerislocatednearelectricalroom.b. Formediumtolargefacilitiesanticipate8x8padsize.c. Provide36cleararoundthreesides,and12ofclearanceonfrontside.d. Typicallydriveupaccessisrequiredfortheutilitycompany.e. Itisdesirabletolocatetheelectricalroomonanexteriorwall,nearthefinal

    utilitytransformerlocation.

    4.Phone/dataRooms

    a. Typicallyatleastoneperlevelofanybuildingtype.Cablecanberouted300fromdevicetoroom,soadditionalroomswouldberequiredforbuildingslongerthan300inanydirection.

    b. RoomsizesvarybasedupontheITdepartmentsneeds,butanticipate10x10formaintelephoneroomsand6x6forremoterooms.

    5.Wallsthroughoutthefacilitycontainingrecessedelectricalpanelboardsshouldbeaminimumof6deep.

    LIGHTINGSYSTEMSRULESOFTHUMB:

    1.Lightingis30%oftheoverallbuildingpowerusage.Savingsintheoverallwatts/sfusedforlightingcanhaveasignificantimpact.

    2.Typical2x4lightingfixturespacingis8x10.

    3.Wallmountedlightingfixturescanonlybemountedbelow68iftheyproject4orlessfromthewall.

    4.Atypicalbuildingwillendupwithanoveralllightingloadof1.01.5wattspersquarefoot.

    5.Energyefficiencyoftypicallamps

    a. One32wattfluorescentT8hastheequivalentlightoutputtothree60wattincandescentALamps(thestandardhouseholdscrewinlamp)ortwo60watthalogenMR16lamps.

    b. FluorescentHighOutputT5similarefficiencytotheT8fluorescentbutitssmallersizecanleadtomoreefficientfixturedesign.

    c. MetalHalideisapproximately15%lessefficientthanfluorescent.d. LEDactuallyhasaverylowlightoutputperwatt.Itsoverallenergyefficiencyis

    similartostandardhalogen,farlessthanfluorescentlamps.ThereasonLEDtechnologyissaidtobesoefficientisbecauseitdirectsmostofthelightinonedirectionsoitisgoodforsigns,stoplights,wayfinders,andotherdirectionallighting,butnotnecessarilyefficientforoverallroomillumination.

    6.Typicallamplife

    a. FluorescentT820,000hours,or3yearsat18hours/dayb. FluorescentHighOutputT520,000hours,or3yearsat18hours/dayc. MetalHalide20,000hours,or3yearsat18hours/dayd. IncandescentALamp750hours,or2monthsat18hours/day

    e. IncandescentMR16Halogen10,000hours(withspeciallamp),or11/2years

  • at18hours/dayf. LED100,000hours,or+15yearsat18hours/day

    7.Tohelpwithpreliminarysitebudgetcosts,beforeanengineermaybeinvolvedonaproject,thetypicalspacingofpolelightsinaparkinglotisapproximately100oncenterwithananticipatedinstalledcostfornondecorativepolesof$2,000each.Decorativepoleswilltypicallybeapproximately$3,000installed.

    8.DuetotheadoptionoftheInternationalBuildingCodes,compliancewiththeInternationalEnergyConservationCodeisalsotypicallyrequired.Uponsubmissionofthe100%CDdrawingstothebuildingdepartment,itshouldbeanticipatedthatstampedcopiesofthecomplianceformsbesubmittedbytheelectricalandmechanicalengineers.