C O N V E N T I O N A L F I R E S Y S T E M S
1
CONTENTS
FP585 Control Panel 2
ES Detect 4
Vision 2020P 6
Vision 2020PT 8
Vision 2020R 10
Vision 2020F 12
Vision 2020HF 14
Optical Smoke Detectors 16
Heat Detectors 17
Beam Smoke Detectors 18
Manual Call Points 19
Electronic Sounder and Strobe Range 22
Electronic Sounder 24
Bells 25
Door Holders 26
Duct Smoke Detector 27
C O N V E N T I O N A L F I R E S Y S T E M S
2
ORDER CODES
2 Zone 75585-02NMB
4 Zone 75585-04NMB
8 Zone 75585-08NMB
Flush Surround 13270-29
8 Zone Repeat Panel 75586-08NMB
2.1Ah 12V SLA Battery 4015-502-Y
2.8Ah 12V SLA Battery 4015-509-Y
FP585 CONTROL PANEL
DIMENSIONS (mm)
395 87
89 89
197
19
274
For flush mounting, aperture size 378mm x 245mm x 60mm
TECHNICAL SPECIFICATION
No. of Zones 2 4 8 *8 Zone Repeat
Maximum Load per Zone 3mA N/A
No. of Sounder Circuits 2 4 8 N/A
Max. Sounder Circuit Load 0.5A per circuit Total load not to exceed 1A N/A
Batteries (not included) 2 x 12V, 2.1 Ah or 2 x 12V, 3.4 Ah2 x 12V, 3.4 Ah
2 x 12V, 2.1 Ah
Battery Standby (Using Batteries specified above)
72 hours plus 0.5 hours alarm load 72 hours
Aux. Relay Contacts 1 N/O and 1 N/C pair, 1A at 24V N/A
Approx Weight (with batteries) 5.8 Kg 6.2 Kg 5.8 Kg
Cable Entry 13 Top and 13 Rear
Cable Type BS 6387, 2 core, min 1.5mm2 CSA
Class Change FacilityVia normally open push button switch located no more than 100m from panel
N/A
Temperature Indoor, 0 - 40ºC
Standards EN54 Parts 2&4
Approvals BSI Approved
The FP585 panel complies fully
with the European standard
EN54 Parts 2 & 4 and can be
used on installations meeting
BS 5839: Part 1.
Each panel contains its own
integral power supply and
battery support for up to eight
alarm sounder circuits, two
auxiliary relay contacts, a zone
disablement facility and a one
man test and commission facility,
all simplifying system design,
installation and commissioning.
C O N V E N T I O N A L F I R E S Y S T E M S
3
FP585 CONTROL PANELSYSTEM ARCHITECTURE
Note: This schematic is for guidance only – please refer to product instructions during installation.
All cables are 2 core unless otherwise stated.
Repeat Panel
Smoke Detector
BeamTransmitter
AlarmSounder
SounderStrobe
AlarmSounder
AlarmSounder
SmokeDetector
HeatDetector
CallPoint
End ofLine
SmokeDetector
CallPoint
SmokeDetector
CallPoint
4 ZoneControl
Panel
SoundersCircuits
1 N/O, 1 N/C relay contactsto auxiliaryequipmentsuch as doorholders ormanned centrelink.
Class Change
DuctDetector
End ofLine
End ofLine
End of Line
BeamReceiver
End ofLine
End ofLine
3 Core Cable
Polarised Relay(to switch 230V equipment
eg. door holders)
24V
Beam Control Unit (24V required)
SounderStrobe
C O N V E N T I O N A L F I R E S Y S T E M S
4
Optical smoke detector:
Optical detector with software support to provide reliable detection and high degree of false
alarm resilience
Heat Detector Range
Range of Heat EN54-5 detectors:
- Rate of rise Type A1 for standard applications
- Fixed Temp Type A1S and high temp (Type BS) for higher ambient temperature applications
GENERAL SPECIFICATION
Operating voltage 8 to 42 V DC
Storage temperature -25 °C to 75 °C
Minimum operating temperature -20°C
Air humidity < 95 %
Type of protection IP43 (with base + option)
Material ABS
Color white, similar to RAL 9010
Weight800171, 800177, 800271 = 74g. 800371 = 110g
Dimensions Ø: 117 mm H: 49 mm (62 mm incl. base)
ES DETECT
Our ES Detect conventional range
offers a comprehensive range
of smoke and heat detectors.
The ES Detect automatic detector
is an non-addressable detector
specifically designed for operation
on conventional systems. The
range not only includes intelligent
algorithms for fire detection but
also a wide range of different
types of detectors.
Key Features
l Microprocessor controlled range of automatic fire detectors
l Software monitoring contamination, maintaining optimum sensitivity throughout the whole life
l Compatible with diode base allowing zone continuity while monitoring for detector removal
C O N V E N T I O N A L F I R E S Y S T E M S
5
ES DETECT
TECHNICAL SPECIFICATION
Type Heat - Fixed Temp Heat - Fixed Temp Type B Rate of Rise Optical smoke
Part number 800171 800177 800271 800371
Minimum reset time 100 m/sec
Alarm current @ 9 V DC typ. 9 mA
Air speed 0 to 25.4 m/s
Quiescent current approx. 25 μA approx. 30 μA
Application temperature
Up to 50 °C up to 65 °C up to 50 °C up to 72 °C
Detector category and approvals
EN 54-5 A1S EN 54-5 BS EN 54-5 A1R EN 54-7
ORDER CODES
Fixed heat detector 800171
Fixed heat detector, class B 800177
Rate-of-rise heat detector 800271
Optical smoke detector 800371
Standard Detector Base 805590
Detector base with diode 805590-D
Remote LED for ES Detect 781814
DIMENSIONS (MM)
Compatibility Statement:
The ES Detect range is only approved to be installed with FP585 Control Panels or with SenTRI via interface units. Refer to Technical Data sheet for details
FP585 Control Panels - 75585-02NMB, 75585-04NMB, 75585-08NMB
117
Z1
Z2
Z3
Z4
62
C O N V E N T I O N A L F I R E S Y S T E M S
6
VISION 2020P
Description
The 2020P Optical Smoke Detector is part of the Vision range of detectors. Vision is a range of
conventional detectors, which have been produced using the latest in manufacturing technology
and supplied with an array of installer-friendly advanced features, making them ideal for all your
conventional fire detection requirements.
The 2020P Optical Smoke Detector uses a state of the art optical chamber combined with an
application specific integrated circuit (ASIC) to provide quick and accurate detection of fires.
A combination of the unique chamber design and other technically advanced features will
significantly extend the service intervals before cleaning of the detector becomes necessary.
A hand held laser tool can also be used in conjunction with the Vision range of detectors for
triggering the Vision detector. With a range of several metres, the hand held unit provides an
effortless way of remotely triggering the Vision detector.
The 2020P Detector has an integral LED, which illuminates to provide a local alarm signal. This
latches on, and remains illuminated until the detector is reset by a momentary power interruption.
An optional remote LED annunciator may be used to repeat any alarm signal.
A variety of detector bases can be used with the 2020P Detector, providing application flexibility
and compatibility with a wide range of conventional fire alarm panels, including our SMS range.
All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and
have a tamper resistant feature, which when activated prevents removal of the detector without
the use of a tool.
Please note: the laser triggering tool does not negate the requirement to test the detector as
specified in BS 5839 Pt 1:2002.
CONVENTIONAL OPTICAL SMOKE DETECTOR
ORDER CODES
Optical Smoke Detector 2020P
Bases
Standard Base – adds 9.5mm to
detector height 2020B
Standard Base with Schottky diode 2020BSD
Deep Base – adds 21mm to
detector height 2020DB
Deep Base with Schottky diode 2020DBSD
Accessories
Laser Triggering Tool 2020LT
PRODUCT OVERVIEW
Features
l Low profile design
l Low current draw
l Automatic drift compensation
l Remote alarm trigger feature
l Easy maintenance
l Range of detector bases available
l Remote LED Option
l Approved to EN54–7:2000 (Amendment 1)
C O N V E N T I O N A L F I R E S Y S T E M S
7
VISION 2020P
NOTES
It is essential to ensure that only known
compatible components are used in a fire
detection system. If in doubt, always consult
the fire control panel supplier/manufacturer.
TECHNICAL SPECIFICATION
ELECTRICAL
Operating Voltage Range 14 to 28VDC (Nominal 24VDC)
Maximum Standby Current @ 25ºC 60μA @ 24VDC
Maximum Alarm Current 70mA @ 28VDC
ENVIRONMENTAL
Application Temperature Range –30ºC to +70ºC
Humidity 5 to 95% Relative Humidity (non-condensing)
MECHANICAL
Height 32.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 75g (plus 45g for standard base)
Max Wire Gauge for Terminals 0.4mm2 to 2.0mm2
Colour Approximates RAL9016
Material ABS
Standards EN54 part 7
Approvals LPCB Approved and CE Approved
CONVENTIONAL OPTICAL SMOKE DETECTOR
DIMENSIONS (mm)
42102
C O N V E N T I O N A L F I R E S Y S T E M S
8
VISION 2020PT
Description
The 2020PT Multi-functional Detector is part of the Vision range of detectors. Vision is a range of
conventional detectors, which have been produced using the latest in manufacturing technology
and supplied with an array of installer-friendly advanced features, making them ideal for all your
conventional fire detection requirements.
The 2020PT Multi-functional Detector uses a state of the art optical chamber and heat element
combined with sophisticated algorithms to provide quick and accurate detection of fires. The
combination of optical and heat detection provides a faster response to ‘real fire’ situations, while
at the same time reducing the risk of unwanted environmentally generated alarms.
A hand held laser tool can also be used in conjunction with the Vision range of detectors for
triggering the Vision detector. With a range of several metres, the hand held unit provides an
effortless way of remotely triggering the Vision detector.
The 2020PT Detector also has an integral LED, which illuminates to provide a local alarm signal.
This latches on, and remains illuminated until the detector is reset by a momentary power
interruption. An optional remote LED annunciator may be used to repeat any alarm signal.
A variety of detector bases can be used with the Vision Detector, providing application flexibility
and compatibility with a wide range of conventional fire alarm panels, including our SMS range.
All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and
have a tamper resistant feature, which when activated prevents removal of the detector without
the use of a tool.
Please note: the laser triggering tool does not negate the requirement to test the detector as
specified in BS 5839 Pt 1:2002.
OPTICAL HEAT DETECTOR
ORDER CODES
Optical Heat Detector 2020PT
Bases
Standard Base – adds 9.5mm to
detector height 2020B
Standard Base with Schottky diode 2020BSD
Deep Base – adds 21mm to
detector height 2020DB
Deep Base with Schottky diode 2020DBSD
Accessories
Laser Triggering Tool 2020LT
PRODUCT OVERVIEW
Featuresl Low profile designl Low current drawl Automatic drift
compensationl Remote alarm trigger featurel Easy maintenancel Range of detector bases
availablel Remote LED Optionl Approved to EN54 – 7:2000
(Amendment 1)l EN54 – 5:2000 (Amendment
1) Class A1R; CEA 4021
C O N V E N T I O N A L F I R E S Y S T E M S
9
VISION 2020PT
NOTES
1. To avoid unwanted alarm conditions being
triggered by class A1R detectors, the maximum
ambient operating temperature should not
exceed 45ºC.
2. It is essential to ensure that only known
compatible components are used in a fire
detection system. If in doubt, always consult
the fire control panel supplier/manufacturer.
TECHNICAL SPECIFICATION
ELECTRICAL
Operating Voltage Range 14 to 28VDC (Nominal 24VDC)
Maximum Standby Current @ 25ºC 75μA @ 24VDC
Maximum Alarm Current 70mA @ 28VDC
ENVIRONMENTAL
Application Temperature Range (see note 1) –30ºC to +70ºC
Humidity 5 to 95% Relative Humidity (non-condensing)
MECHANICAL
Height 40.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 78g (plus 45g for standard base)
Max Wire Gauge for Terminals 0.4mm2 to 2.00mm2
Colour Approximates RAL9016
Material ABS
Standards EN54 Part 7 and EN54 Part 5
Approvals LPCB Approved and CE Approved
OPTICAL HEAT DETECTOR
DIMENSIONS (mm)
50102
C O N V E N T I O N A L F I R E S Y S T E M S
10
VISION 2020R
Description
The 2020R Rate of Rise Heat Detector is part of the Vision range of detectors. Vision is a range of
conventional detectors, which have been produced using the latest in manufacturing technology
and supplied with an array of installer-friendly advanced features, making them ideal for all your
conventional fire detection requirements.
The 2020R Heat Detector uses a state of the art heat element combined with an application
specific integrated circuit (ASIC) to provide quick and accurate detection of fires. The detector
incorporates both rate of rise and static elements and is suitable for all areas where the ambient
conditions do not normally exhibit rapid changes in temperature.
A hand held laser tool can also be used in conjunction with the Vision range of detectors for
triggering the Vision detector. With a range of several metres, the hand held unit provides an
effortless way of remotely triggering the Vision detector.
The 2020R Detector also has an integral LED, which illuminates to provide a local alarm signal.
This latches on, and remains illuminated until the detector is reset by a momentary power
interruption. An optional remote LED annunciator may be used to repeat any alarm signal.
A variety of detector bases can be used with the 2020R Detector, providing application flexibility
and compatibility with a wide range of conventional fire alarm panels, including our SMS range.
All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and
have a tamper resistant feature, which when activated prevents removal of the detector without
the use of a tool.
Please note: the laser triggering tool does not negate the requirement to test the detector as
specified in BS 5839 Pt 1:2002.
RATE OF RISE HEAT DETECTOR
ORDER CODES
Rate of Rise Detector 2020R
Bases
Standard Base – adds 9.5mm to
detector height 2020B
Standard Base with Schottky diode 2020BSD
Deep Base – adds 21mm to
detector height 2020DB
Deep Base with Schottky diode 2020DBSD
Accessories
Laser Triggering Tool 2020LT
PRODUCT OVERVIEW
Features
l Low profile design
l Low current draw
l Remote alarm trigger feature
l Easy maintenance
l Range of detector bases available
l Remote LED Option
l Approved to EN54 – 5:2000 (Amendment 1) Class A1R
C O N V E N T I O N A L F I R E S Y S T E M S
11
VISION 2020R
NOTES
1. To avoid unwanted alarm conditions being
triggered by class A1R detectors, the maximum
ambient operating temperature should not
exceed 45ºC.
2. It is essential to ensure that only known
compatible components are used in a fire
detection system. If in doubt, always consult
the fire control panel supplier/manufacturer.
TECHNICAL SPECIFICATION
ELECTRICAL
Operating Voltage Range 14 to 28VDC (Nominal 24VDC)
Maximum Standby Current @ 25ºC 70μA @ 24VDC
Maximum Alarm Current 70mA @ 28VDC
ENVIRONMENTAL
Application Temperature Range (see note 1) –30ºC to +70ºC
Humidity 5 to 95% Relative Humidity (non-condensing)
MECHANICAL
Height 40.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 70g (plus 45g for standard base)
Max Wire Gauge for Terminals 0.4mm2 to 2.0mm2
Colour Approximates RAL9016
Material ABS
Standards EN54 Part 5
Approvals LPCB Approved and CE Approved
RATE OF RISE HEAT DETECTOR
DIMENSIONS (mm)
102 50
C O N V E N T I O N A L F I R E S Y S T E M S
12
VISION 2020F
Description
The 2020F 58ºC Fixed Temperature Heat Detector is part of the Vision range of detectors. Vision
is a range of conventional detectors, which have been produced using the latest in manufacturing
technology and supplied with an array of installer-friendly advanced features, making them ideal
for all your conventional fire detection requirements.
The 2020F 58ºC Fixed Temperature Heat Detector uses a state of the art heat element combined
with an application specific integrated circuit (ASIC) to provide quick and accurate detection
of fires. The detector incorporates a static element and is suitable where ambient conditions
normally exhibit rapid changes in temperature e.g. kitchens.
A hand held laser tool can also be used in conjunction with the Vision range of detectors for
triggering the Vision detector. With a range of several metres, the hand held unit provides an
effortless way of remotely triggering the Vision detector.
The 2020F Detector also has an integral LED, which illuminates to provide a local alarm
signal. This latches on, and remains illuminated until the detector is reset by a momentary
power interruption. An optional remote LED annunciator may be used to repeat any
alarm signal.
A variety of detector bases can be used with the 2020F Detector, providing application flexibility
and compatibility with a wide range of conventional fire alarm panels, including our SMS range.
All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and
have a tamper resistant feature, which when activated prevents removal of the detector without
the use of a tool.
Please note: the laser triggering tool does not negate the requirement to test the detector as
specified in BS 5839 Pt 1:2002.
58ºC FIXED TEMPERATURE HEAT DETECTOR
ORDER CODES
58º Fixed Temperature
Heat Detector 2020F
Bases
Standard Base – adds 9.5mm to
detector height 2020B
Deep Base – adds 21mm to
detector height 2020DB
Standard Base with Schottky diode 2020BSD
Deep Base with Schottky diode 2020DBSD
Accessories
Laser Triggering Tool 2020LT
PRODUCT OVERVIEW
Features
l Low profile design
l Low current draw
l Easy maintenance
l Range of detector bases available
l Remote LED Option
l Approved to EN54 – 5:2000 (Amendment 1) Class A2S
l Remote alarm trigger feature
C O N V E N T I O N A L F I R E S Y S T E M S
13
VISION 2020F
NOTES
1. To avoid unwanted alarm conditions being
triggered by class A2S detectors the maximum
ambient operating temperature should not
exceed 45ºC.
2. It is essential to ensure that only known
compatible components are used in a fire
detection system. If in doubt, always consult
the fire control panel supplier/manufacturer.
TECHNICAL SPECIFICATION
ELECTRICAL
Operating Voltage Range 14 to 28VDC (Nominal 24VDC)
Maximum Standby Current @ 25ºC 70μA @ 24VDC
Maximum Alarm Current 70mA @ 28VDC
ENVIRONMENTAL
Application Temperature Range (see note 1) -30ºC to +70ºC
Humidity 5 to 95% Relative Humidity (non-condensing)
MECHANICAL
Height 40.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 70g (plus 45g for standard base)
Max Wire Gauge for Terminals 0.4mm² to 2.0mm2
Colour Approximates RAL9016
Material ABS
Standards EN54 part 5
Approvals LPCB Approved and CE Approved
58ºC FIXED TEMPERATURE HEAT DETECTOR
DIMENSIONS (mm)
102 50
C O N V E N T I O N A L F I R E S Y S T E M S
14
VISION 2020HF
Description
The 2020HF 78ºC Fixed Temperature Heat Detector is part of the Vision range of detectors. Vision
is a range of conventional detectors, which have been produced using the latest in manufacturing
technology and supplied with an array of installer-friendly advanced features, making them ideal
for all your conventional fire detection requirements.
The 2020HF 78ºC Fixed Temperature Heat Detector uses a state of the art heat element combined
with an application specific integrated circuit (ASIC) to provide quick and accurate detection
of fires. The detector incorporates a static element and is suitable where ambient conditions
normally exhibit rapid changes in temperature above 45ºC e.g. boiler houses.
A hand held laser tool can also be used in conjunction with the Vision range of detectors for
triggering the Vision detector. With a range of several metres, the hand held unit provides an
effortless way of remotely triggering the Vision Detector.
The 2020HF Detector also has an integral LED, which illuminates to provide a local alarm signal.
This latches on, and remains illuminated until the detector is reset by a momentary power
interruption. An optional remote LED annunciator may be used to repeat any alarm signal.
A variety of detector bases can be used with the 2020HF Detector, providing application flexibility
and compatibility with a wide range of conventional fire alarm panels, including our SMS range.
All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and
have a tamper resistant feature, which when activated prevents removal of the detector without
the use of a tool.
Please note: the laser triggering tool does not negate the requirement to test the detector as
specified in BS 5839 Pt 1:2002.
78ºC FIXED TEMPERATURE HEAT DETECTOR
ORDER CODES
78º Fixed Temperature
Heat Detector 2020HF
Bases
Standard Base – adds 9.5mm to
detector height 2020B
Standard base with Schottky diode 2020BSD
Deep Base – adds 21mm to
detector height 2020DB
Deep Base with Schottky diode 2020DBSD
Accessories
Laser Triggering Tool 2020LT
PRODUCT OVERVIEW
Features
l Low profile design
l Low current draw
l Easy maintenance
l Range of detector bases available
l Remote LED Option
l Approved to EN54 – 5:2000 (Amendment 1) Class BS
l Remote alarm trigger feature
C O N V E N T I O N A L F I R E S Y S T E M S
15
VISION 2020HF
NOTES
1. To avoid unwanted alarm conditions being
triggered by class BS detectors the maximum
ambient operating temperature should not
exceed 65ºC.
2. It is essential to ensure that only known
compatible components are used in a fire
detection system. If in doubt, always consult
the fire control panel supplier/manufacturer.
TECHNICAL SPECIFICATION
ELECTRICAL
Operating Voltage Range 14 to 28VDC (Nominal 24VDC)
Maximum Standby Current @ 25ºC 75μA @ 24VDC
Maximum Alarm Current 70mA @ 28VDC
ENVIRONMENTAL
Application Temperature Range (see note 1) –30ºC to +70ºC
Humidity 5 to 95% Relative Humidity (non-condensing)
MECHANICAL
Height 40.5mm (plus 9.5mm for standard base)
Diameter 102mm
Weight 70g (plus 45g for standard base)
Max Wire Gauge for Terminals 0.4mm² to 2.0mm2
Colour Approximates RAL9016
Material ABS
Standards EN54 Part 5
Approvals LPCB Approved and CE Approved
78ºC FIXED TEMPERATURE HEAT DETECTOR
DIMENSIONS (mm)
102 50
C O N V E N T I O N A L F I R E S Y S T E M S
16
ORDER CODES
Optical Smoke Detector 72441-25NM
Low profile base 17800-02
Low profile base
with diode 17801-02
Base less diode 17800-01
(surface cabling)
Base with diode 17801-01
(surface cabling)
Remote LED Module 72499-24NM
Repeat Relay 17899-44
OPTICAL SMOKE DETECTORS
DIMENSIONS (mm)
104
1046 73
wit
h b
ase
TECHNICAL SPECIFICATION
Operating Voltage Range 8 - 28V dc
Quiescent Current 60μA @ 28V
Alarm Current 26mA - 34mA
Ambient Temperature 0oc to +50oc
Colour White (comparable to RAL9010)
Ingress Protection IP30
Approx. Weight 0.11 Kg
Operating Temperature -10ºC to +50ºC
Standards EN54 Part 7
Approvals LPCB Approved
SPECIAL FEATURE
The use of the Diode Base
allows monitoring of a
removed detector to comply
with BS 5839.
N.B. Maximum of 20 per zone.
Possibly the earliest form of
smoke detection, optical smoke
detectors are ideal at detecting
visually smoky fires which are
likely to be slow, smouldering
fires.
ABS casing with red LED fire
indicator.
C O N V E N T I O N A L F I R E S Y S T E M S
17
DIMENSIONS (mm)
ORDER CODES
Fixed Temperature 72451-25NM
Rate of Rise 72461-25NM
High Fixed Temperature 72470-25NM
Low profile base 17800-02
Low profile base
with diode 17801-02
Base less diode 17800-01
(surface cabling)
Base with diode 17801-01
(surface cabling)
Remote LED Module 72499-24NM
Repeat Relay 17899-44
HEAT DETECTORS
TECHNICAL SPECIFICATION
Fixed Temp. Rate of Rise High Fixed Temp.
Operating Voltage Range 8-28V dc
Quiescent Current 30μA @28V dc
Ingress Protection IP30
Approx. Weight 0.07 Kg
Operating Temperature 0ºC to +85ºC
Trigger Temperature 58ºCNA (Factory preset 58ºC)
85ºC
Sensitivity Grade 1 Grade 2
Standards EN54 Part 5
Approvals LPCB Approved
97
1044
Heat detectors operate when a certain temperature is reached and are better suited to smokey, dusty or steamy environments than smoke detectors.
High fixed temperature devices are advised for kitchens or boiler rooms. Standard fixed temperature devices are suitable for areas where the temperature fluctuates for natural reasons or due to certain industrial processes.
ABS casing with red LED fire indicator.
C O N V E N T I O N A L F I R E S Y S T E M S
18
BEAM SMOKE DETECTORS
ORDER CODES
Transmitter / Receiver Beam pair 07011-41
Combined Reflective Beam 07011-40
(includes 1x Detector Head
Assembly, 4x prisms, 1x Test filter,
1x cable Interface)
Power Supply 05214-24-EN
TECHNICAL SPECIFICATION
Transmitter / Receiver Beam Pair
Combined Reflective Beam
Operating Voltage Range 11.5V dc to 28V dc 10.2V dc to 30V dc
Quiescent Current @ 24VdcReceiver and Controller <8mA <4mA
Transmitter: - 5.6mA
Alarm Current @24V: Controller and Receiver <16.5mA <15mA
Approx WeightControl Unit: 1.8KgTransmitter + Receiver inc. brackets: 650 gms.
0.67 Kg
IP Rating IP50
Ambient Temperature -10oC to 50oC -30oC to 55oC
Beam Length 10m - 100m 50m - 100m
Standards EN54 Part 12
DIMENSIONS (mm)
DIMENSIONS (mm)
65 101
140
210
210
85
100 9.5
260
9512
0
126 10
0
Transmitter / Receiver Beam Smoke Detector
Combined Reflective Beam
Prisms
Optical beam smoke detectors
are ideally suited for large open
areas such as warehouses, atria,
leisure centres and shopping
centres where the installation
of single point detectors may be
difficult and uneconomical.
These are also perfect for
applications such as churches
and museums that require an
unobtrusive fire safety system.
Beam detectors can be installed
with separate transmitter and
receiver or combined transceiver
unit and reflector.
Features:
l Low current consumption
l Automatic self check drift compensation
l Selectable sensitivity/threshold levels
l Small, unobtrusive detectors allow for a discreet installation.
Note: An additional 24V dc
power supply is required.
C O N V E N T I O N A L F I R E S Y S T E M S
19
ORDER CODES
Surface Mounted c/w back box
EN54 version 71150-52NMA-EN
Surface Mounted with cover and
back box EN54 version 71150-55NMA-EN
Key Operated, Surface Mounted
c/w back box 14115-08
Flush Mounted Call Point 71150-51NMA
Red Surface Mounted for NO
and NC connections 71150-62NM
MCP Square Glasses with ref to
EN54 Pt 11 (pack 10) 71150-90NM-EN
MCP Square Glasses without
ref to standards (pack 10) 71150-91NM
MCP Square Glasses branded
Senator II (pack 10) 78150-91NM
Plastic Test Keys (pack 10) 71150-92NM
MCP Surface Weather
Resistant Kit 71150-93NM
MCP Semi Flush Spacer 14112-20
MCP Semi-Flush Kit, current
range onto 1102 box 14112-29
MCP Flush Fixing Plate 19289-01
Round Glasses (1102 range)
(pack 10) 14111-99
MANUAL CALL POINTS
DIMENSIONS (mm)
TECHNICAL SPECIFICATION
Nominal Voltage 24V dc
Ingress Protection IP54 with gasket
Approx. Weight 0.15 Kg
Operating Temperature 0ºC to 50ºC
Standards EN54 Part 11
87
87
55 20
Surface Flush
Accessories & Spares
Key Operated Call Point – Preventing unauthorised operation for use in areas with a high risk
of tampering or vandalism.
Test Keys – For testing call points without breaking the glass.
Weather Resistant Kit – Allowing a call point to be used externally, providing weather resistance
to IP54.
Semi-flush Spacing Kit – For part recessing call points.
NB: this range will be discontinued from 31st December 2012.
Manual call points are
manufactured from ABS with
plastic covered push break glasses
for safe and simple operation.
No hammer is required.
A polycarbonate cover version
is available for applications
susceptible to inadvertent
operation, such as sports halls.
Note: All manual call points can
be flush mounted by using a
flush fixing plate.
C O N V E N T I O N A L F I R E S Y S T E M S
20
ORDER CODES
Flush Call Point with
470 Ohm resistor and
NO contact c/w glass MCP1A-R470FG -01
Surface Outdoor Call Point with
470 Ohm resistor and
NO contact c/w glass WCP1A-R470SG-01
Key Operated Surface Mounted WR9102
Surface call point with
470ohm resistor and
NO Contact
c/w resettable element MCP1A-R470SF-01
Surface call point c/o
comes with
glass element MCP3A-R000SG-01
Spare Glasses for MCP1A and
WCP1A (Pack of 10) XENS-891
Resettable element for
MCP1A (pack of 10) XENS-890
Hinged protective cover
(pack of 10) XENS-892
Surface Backbox for MCP1A
range of MCP (pack of 10) XENS-895
Pack of test keys (pack of 10)
for use with MCP1A and
WCP1A range XENS-899
MANUAL CALL POINTS
The Manual Call Points from SMS are both with a 470 Ohm resistor and Normally Open contact,
complete with glass. Available in semi-flush mounting or surface mounting options. The Call
Points are designed to provide a manual alarm interface to non addressable fire alarm control
panels. Both call points are supplied in the standard red colour.
Installation time is significantly reduced by the two part connector located at the back of the
device.
Both break glass, supplied, and resettable operating elements can be used in the standard unit
by a yellow strip on the element which becomes visible when activated. With the addition of a
hinged transparent cover the element may be protected against accidental operation. A specialist
test key may be inserted into the bottom of the unit to lower the glass and release the micro-
switch and thus a full functional test is achieved.
l Certified to EN54, Part 11
l Re-settable operating element option
l Resistive and clean contact connections
l Semi-flush or surface mounting
l Backward compatibility
C O N V E N T I O N A L F I R E S Y S T E M S
21
TECHNICAL SPECIFICATION – SURFACE MOUNTED WATERPROOF MANUAL CALL POINT
Operating Voltage 30V dc maximum
Current Rating 2A (switching only)
Ingress Protection IP67
Approx. Weight 0.24 Kg
Operating Temperature -30ºC to 70ºC
Relevant Humidity Up to 95% non-condensing
Standards Certified to EN54 Part 11
TECHNICAL SPECIFICATION – FLUSH MOUNTED MANUAL CALL POINT AND SURFACE RESETTABLE CALL POINT
Operating Voltage 30V dc maximum
Current Rating 2A (switching only)
Ingress Protection IP24D
Approx. Weight 0.11 - 0.16 Kg
Operating Temperature -10ºC to 55ºC
Relevant Humidity 93± 3% non-condensing
Standards Certified to EN54 Part 11
MANUAL CALL POINTS
DIMENSIONS (mm)
89
93
27.5 32
DIMENSIONS (mm)
93
97.5 71
C O N V E N T I O N A L F I R E S Y S T E M S
22
ORDER CODES
IP55 Electronic Sounder
red (100 dBA) CONV-IP-SN-R
IP31 Electronic Sounder
red (100 dBA) CONV-SN-R
IP55 Electronic Sounder Strobe
red body, red lens 100 dBA* CONV-SN-ST-RR
IP55 Ultra low current Strobe
red body, red lens* CONV-IP-ST-RR
IP55 Voice Enhanced Electronic
Sounder red (100 dBA) CONV-IP-VP-R
IP55 Voice Enhanced Electronic
Sounder and Strobe red body
red lens (100 dBA)* CONV-IP-VP-ST-RR
ELECTRONIC SOUNDER AND
The Electronic Sounder and Strobe range incorporates sound, speech and strobe effects all in one
range of alarm devices. The range offers all variants in the choice of 2 colours, red or white, with
either a shallow base version sealed to IP31 or a deep base version sealed to IP55. All the low
profile sounders have the option of an integral strobe.
STROBE RANGE
TECHNICAL SPECIFICATION
Sounder Sounder/Strobe Strobe Only
Sound Output at 1m See Tone Table See Tone Table N/A
Strobe Flash Rate See Tone Table See Tone Table Variable
Strobe Output N/AEquivalent to a 3W Xenon flasher
Equivalent to a 3W Xenon flasher
Average Current See Tone Table See Tone Table 6 mA
Operating Voltage Range 10.8V – 28.8V 10.8V – 28.8V 10.8V – 28.8V
Maximum Reverse Monitoring Voltage
30V/20μA 30V/20μA <20μA @30V
Ingress Protection IP55 with the Deep Base, IP31 with the Shallow Base
Approx Weight 0.3Kg 0.3Kg 0.3Kg
Operating Temperature -10ºC to 50ºC -10ºC to 50ºC -10ºC to 50ºC
Standards (Sounder only) EN54 Part 3 EN54 Part 3 N/A
Approvals LPCB Approved (CONV-IP-SN-R. CONV-SN-R. CONV-SN-ST-RR only)
See overleaf for Tone Table.* This product is not a visual alarm device and does not meet EN 54-23
l Very low power consumption means more sounders and strobes per circuit
l The strobe option is equivalent to a standard 3W xenon beacon and uses 1/20th of the power
l 4 Voice phrases and bell sound are available as standard
l 32 sounder tones are available
l Sounders are compatible with 12V and 24V systems
l A third wire option allows the selection of 2 alternative sounds. Ideal for class change applications
l Combined sounder strobe reduces installation costs
C O N V E N T I O N A L F I R E S Y S T E M S
23
The current data in the table is for Red strobe only.
Note also the nominal sound frequencies stated in the table are based on the resonance frequency of the transducer.
ELECTRONIC SOUNDER AND STROBE RANGE
TONE TABLE FOR SOUNDER ONLY AND SOUNDER / STROBE VARIANTS12V 24V
dB(A) @1m
Operating Current dB(A) @1m
Operating Current
Signal 1 Strobe Description SW1 Switch Graphical representation
With Strobe mA
Without Strobe mA
With Strobe mA
Without Strobe mA Signal 2 Strobe Signal 3 Strobe
Tone 1 1Hz Alternating tone 800/ 970Hz @ 2Hz - FP 1063.1 Telecoms BS 5839: Part 1 6 5 4 3 2 1
ON
101.8 16.5 7.4 101.8 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz
Tone 2 1Hz Alternating tone 800/ 970Hz @ 1Hz - BS 5839: Part 1 6 5 4 3 2 1
ON
101.7 16.5 7.3 101.7 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz
Tone 3 1Hz Intermittent tone 970Hz @ 1Hz LF back up alarm - BS 5839: Part 1 6 5 4 3 2 1
ON
101.6 15.5 4.5 101.6 8.2 2.0 Tone 5 0.8Hz Tone 6 1Hz
Tone 4 1Hz Intermittent tone 2850Hz @ 1Hz HF back up alarm - 2nd tone BS 5839: Part 1
6 5 4 3 2 1 ON
103.7 15.8 5.5 103.7 8.5 2.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 5 0.8Hz Intermittent tone 970Hz 0.25s - on, 1s off - BS 5839: Part 1 6 5 4 3 2 1
ON
101.2 12.0 2.0 101.4 6.0 1.0 Tone 2 0.5Hz Tone 6 1Hz
Tone 6 1Hz Continuous @ 970Hz - BS 5839: Part 1 6 5 4 3 2 1 ON
102.0 16.5 8.0 102.1 9.8 3.7 Tone 3 0.5Hz Tone 1 1Hz
Tone 7 0.5Hz Slow sweep 300Hz- 1200Hz over 2s - Vds2300 Signal 6 5 4 3 2 1
ON
99.3 13.0 7.9 99.3 7.0 3.7 Tone 3 0.5Hz Tone 6 1Hz
Tone 8 1Hz Fast sweep 800Hz - 970Hz @ 7Hz - BS 5839: Part 1 6 5 4 3 2 1
ON
93.5 16.3 8.2 93.7 9.4 3.7 Tone 3 0.5Hz Tone 6 1Hz
Tone 9 1Hz Medium sweep 800Hz - 970Hz @ 1Hz - BS 5839: Part 1 6 5 4 3 2 1
ON
94.1 16.5 8.7 94.3 9.5 4.0 Tone 3 0.5Hz Tone 6 1Hz
Tone 10 1Hz Continuous @ 2850Hz 6 5 4 3 2 1 ON
104.4 16.5 9.7 104.7 10.2 4.4 Tone 3 0.5Hz Tone 6 1Hz
Tone 11 1Hz Sweep 2400 - 2850Hz @ 7Hz 6 5 4 3 2 1 ON
100.2 16.5 11.2 100.8 10.6 5.4 Tone 12 0.5Hz Tone 10 1Hz
Tone 12 1Hz Sweep 2400 - 2850Hz @ 1Hz 6 5 4 3 2 1 ON
101.9 16.5 12.0 102.7 11.5 5.8 Tone 3 0.5Hz Tone 10 1Hz
Tone 13 0.86Hz Slow whoop 500Hz - 1200Hz over 3s with 0.5s off 6 5 4 3 2 1
ON
98.8 15.5 7.5 99.2 8.7 3.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 14 1Hz Sweep 1200Hz @ 1200Hz - 500Hz @ 1Hz with 10ms silence - German DIN tone evacuate
6 5 4 3 2 1 ON
96.6 16.2 7.3 98.1 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 15 1Hz Alternating tone 2400/ 2850Hz @ 2Hz 6 5 4 3 2 1 ON
101.7 16.5 12.0 102.5 11.8 6.2 Tone 12 0.5Hz Tone 10 1Hz
Tone 16 1Hz Alternating tone 554Hz for 100mS then 440Hz for 400ms - French AFNOR tone 6 5 4 3 2 1
ON
89.3 15.8 5.2 89.6 8.7 2.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 17 1Hz Alternating tone 440Hz / 554Hz @ 2Hz - Turn out Sweden 6 5 4 3 2 1
ON
90.1 15.8 5.7 90.3 8.9 2.8 Tone 19 0.5Hz Tone 18 1Hz
Tone 18 1Hz Continuous 700Hz - All clear Sweden 6 5 4 3 2 1 ON
95.9 16.2 7.0 96.3 9.8 3.3 Tone 1 0.5Hz Tone 3 1Hz
Tone 19 1Hz
6s - On 12s - Off
Intermittent tone 700Hz 6s On 12s Off - Pre- vital message Sweden 6 5 4 3 2 1
ON
95.9 6.1 4.0 96.3 5.0 2.3 Tone 17 0.5Hz Tone 18 1Hz
Tone 20 1Hz Intermittent tone 1000Hz @ 1Hz - Local warning Sweden 6 5 4 3 2 1
ON
100.6 15.5 5.8 101.0 8.5 2.7 Tone 17 0.5Hz Tone 25 1Hz
Tone 21 1Hz Rising 1s, constant 4s, fall 1s @ 1000Hz - Industrial alarm Germany 6 5 4 3 2 1
ON
100.9 16.0 10.0 101.2 10.0 4.0 Tone 3 0.5Hz Tone 6 1Hz
Tone 22 1Hz
4s - On 4s - Off
Intermittent tone 700Hz 4s On , 4s Off - Industrial alarm Germany 6 5 4 3 2 1
ON
101.4 8.7 5.7 101.9 6.4 3.0 Tone 19 0.5Hz 6s - On 12s - Off Tone 6 1Hz
Tone 23 Sync. pulses
Emergency evacuation to ISO 8201 - ISO 8201 Tone 6 5 4 3 2 1
ON
104.0 12.0 4.0 104.5 6.0 1.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 24 1Hz Slow whoop 500Hz - 1000Hz over 4.5s - Evacuate Netherlands 6 5 4 3 2 1
ON
99.6 16.0 7.2 100.2 9.5 3.4 Tone 3 0.5Hz Tone 6 1Hz
Tone 25 1Hz Siren (ramp up from 500Hz - 1200Hz in 3s then ramp down 1200Hz - 500Hz in 3s)
6 5 4 3 2 1 ON
98.2 16.0 7.5 98.5 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz
Tone 26 1Hz Fast whoop 500Hz - 1000Hz @ 7Hz 6 5 4 3 2 1 ON
95.8 15.8 7.0 96.0 8.7 3.3 Tone 24 0.5Hz Tone 25 1Hz
Tone 27 Sync. pulses US temporal tone LF
6 5 4 3 2 1 ON
100.6 12.0 3.0 100.6 5.5 1.0 Tone 3 0.5Hz Tone 6 1Hz
Tone 28 Sync. pulses US temporal tone HF
6 5 4 3 2 1 ON
99.0 11.8 2.5 99.0 5.3 0.8 Tone 4 0.5Hz Tone 6 1Hz
Tone 29 1Hz LF buzz 800Hz- 970Hz @ 50Hz 6 5 4 3 2 1 ON
98.8 16.3 9.4 99.2 10.0 4.3 Tone 3 0.5Hz Tone 6 1Hz
Tone 30 1Hz Alternate 2500/ 3100 @ 2Hz - Security alarm 6 5 4 3 2 1
ON
101.6 16.5 13.0 102.2 10.8 6.4 Tone 3 0.5Hz Tone 31 1Hz
Tone 31 1Hz Alternate 2500 / 3100 @ 4Hz 6 5 4 3 2 1 ON
101.2 16.5 13.0 102.0 10.8 6.4 Tone 3 0.5Hz Tone 8 1Hz
Tone 32 1Hz Define during manufacture - default is a fast siren 6 5 4 3 2 1
ON
98.8 16.0 7.5 99.2 9.5 3.5 Tone 3 0.5Hz Tone 6 1Hz
C O N V E N T I O N A L F I R E S Y S T E M S
24
ELECTRONIC SOUNDER
TECHNICAL SPECIFICATION
Shallow Base
Deep Base BedheadSounder Base
IP Rating IP54 IP65 IP54
Approximate Weight 0.24kg 0.26kg 0.11kg 0.15kg
Operation Continuous
Operating Voltage Range 9-28V d.c.
Typical Sound Output @ 1m, 12V d.c. 93dBA 94dBA 87dBA
Typical Sound Output @ 1m, 24V d.c. 100dBA 97dBA 93dBA
Current Consumption 8mA @ 12V, 18mA @24V
Ambient Temperature -25ºC to +70ºC
ORDER CODES
Multitone Low Profile Sounder,
red with shallow base 74451-24NM
Multitone Low Profile Sounder,
red with deep base 74452-24NM
Sounder Base, white 3 tone 74456-24NM
Sounder Base Cover Plate 74456-61NM
Bedhead Sounder 74455-24NM
SPECIAL FEATURE
These sounders are useful for
small rooms such as Halls of
Residences. They may be used
with a detector which reduces
the number of fixing points or
as a standalone sounder with a
cover plate.
DIMENSIONS (mm)
30
42
10573
86
Bedhead Sounder
Shallow Base
Sounder Base
112
Deep Base93
A versatile 24V electronic
sounder for use in a wide range
of applications.
Sound signals may be set in
3 ways; continuous,
intermittent or warble.
C O N V E N T I O N A L F I R E S Y S T E M S
25
ORDER CODES
Electronic Solenoid Bell 24V DC,
Red IP21 74430-88NM
Electronic Solenoid Bell 24V DC,
Red Weather Resistant IP44 74432-88NM
Electronic Solenoid Bell 230V AC,
Grey Weather Resistant IP44 74333-50NM
Electronic Solenoid Bell 12V DC,
Grey IP21 74431-66NM
TECHNICAL SPECIFICATION
Voltage 12 Vdc 24 Vdc 230 Vdc
Current12 Vdc 55 - 65mA24 Vdc 25 - 35mA
230 Vdc 20 - 30mA
Sound Output 93 - 95dB(A)
Monitoring Reverse polarity (dc only)
Protection IP44C ( Weather Resistant Option )
Construction Gong - steel, base - polycarbonate
Weight12 Volt 1.1KG24 Volt 1.1KG230 Volt 1.2KG
ColoursGong - Red or Grey
Base - Black
DIMENSIONS (mm)
155 85
155
130
BELLS
An electronic bell for a wide
range of uses. Metal casing
available in red or grey finish.
Suitable for semi flush or surface
mounting.
SMS offers an electronic bell for
a wide range of applications.
The combination of a miniature
solenoid with an integrated
control circuit allows excellent
sound coverage, minimum
current consumption and
increased reliability. The
improved aesthetics make the
bell suitable for all applications
including the most prestigious
locations.
FEATURES
l Modern design l Clip together assembly l Weatherproof kit option l High “ring” output
BENEFITS
l Suitable for all locations l Easy to fit l Provides protection up
to IP44C With Weather Resistant Option
l Easily identified signal
C O N V E N T I O N A L F I R E S Y S T E M S
26
DIMENSIONS (mm)
DOOR HOLDERS
Wall mountedFloor mounted Keeper plates
96
38.5
51
87
46
4 no. holes ø 5.0 on 54.0 PCD
Manual release button
51 95
45º
110
70
ø 20Cable Entry
80
TECHNICAL SPECIFICATION
Floor Mounted Wall Mounted
Voltage 24V dc 24V dc 230V ac
Approx Weight 700g 360g
Current Consumption 45mA 50mA 12mA
Ambient Temperature 0oC to 35oC 0oC to 40oC
Holding Force 200N
Residual Holding Force Zero
Finish White painted housing, zinc plated magnet White Fire Resistant ABS
Standards NA EN1155 :1997 (CPD Approved)
FEATURES
l Low profi le design l 200N holding force l Easy cable entry & exit l A.C. or D.C. options l Push button release/test l Floor mounting bracket
available l Anti-residual magnetism
feature l D.C. version polorised and
suppressed feature
ORDER CODES
Wall Mounted Door Holder
24V dc 04390-31
Wall Mounted Door Holder
230V ac 04390-55
Floor Mounted Door Holder
04390-41
Floor Bracket; fixing door holder
at right angle to floor 04390-92
Door Keeper Plate; metal keeper
plate in two pieces 04390-99
Door Holder Transformer Rectifier Power
Supply 2amp 24vdc HLS-PSU-TR20
Door Holder Transformer Rectifier Power
Supply 4amp 24vdc HLS-PSU-TR40
To close fire doors in an
emergency and prevent the
spread of fire and smoke.
Moulded ABS and steel
enclosure capable of floor or
wall mounting.
Complies with BS 5839-3.
C O N V E N T I O N A L F I R E S Y S T E M S
27
ORDER CODES
Duct Detector
Includes Venturi tube and
Duct Kit Mounting 17815-01
Remote Relay Module 17899-44
Optical Smoke Detector 72441-25
DUCT SMOKE DETECTOR
The Duct Detector kit is comprised of a conventional detector and duct detector housing. The
Duct Detector is mounted on the outside of the air duct. A venturi tube protrudes into the duct
and draws a sample of the air which passes over the sensor and returns back into the duct. When
the smoke density in the sampled air reaches the trigger level of the smoke detector an alarm will
be signalled on the fire alarm control panel.
TECHNICAL SPECIFICATION
Ingress Protection IP54
Operating Temperature -10oC to +60oC
Approx Weight 0.7Kg
Finish ABS plastic (Grey)
Air Velocity 1M/S to 20M/S
Quiescent Current 90μA
DIMENSIONS (mm)
300 120
110
Recommended