DATA SHEET
Armoured Cables SWA and AWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
1
CONSTRUCTION OF THE CABLE
CONDUCTORS Current carrying component of the cable.
Material Plain, stranded, compacted copper as per IEC: 60228
Aluminium, stranded, compacted conductors
INSULATION The rated voltage level of the cable depends on the dielectric strength and thickness of the insulation.
Material Cross-linked polyethylene (XLPE) Type GP8 as per BS
7655: Section 1.3.
FILLERS For providing circular shape to the cable, non-hygroscopic compatible fillers (wherever necessary) are
included between laid up cores.
BEDDING Extruded bedding serves as a bedding for the armour and as a protection for the laid-up cores.
Material Extruded PVC Type 9 Compound as per BS 7655. Reduced propagation flame retardant (RPLHCL)/R PPVC
Compound for reduced flame propagation characteristics.
ARMOUR Armour provides mechanical protection to the cable. It also serves as an Earth Continuity Conductor (ECC).
One layer of round wire is applied helically over the bedding.
Material 1. Galvanised round steel wire (GSWA) - FOR MULTICORE CABLE
2. Aluminium round wire armour (AWA) - FOR SINGLE CORE.
OVERSHEATH - FINISH General Purpose: Extruded PVC Type 9 Compound as per BS 7655 and also meet fire test requirement of IEC
60332-1.
Material 1. Medium Density Polyethylene (MDPE): Offers higher protection from water ingress and mechanical
abrasion.
2. Anti-Termite: Termite resistance can be built in both types described above by compounding with proper
additives.
3. Reduced Propagation (RP): Retards propagation of flame in fire situatio . O ge I de ≈ 3
4. Reduced Propagation and Low Acid Fumes (RPLHCL): Retards propagation of flames and gives low emission
of h drochloric acid fu es. OI ≈ 3 & acid gas e issio is less tha 8%
CHARACTERISTICS
Voltage Rating Uo/U= 0.6/1kV
Temperature Rating Fixed: -25°C to +90°C
Minimum Bending
Radius
1.5mm2 to 16mm2 - Fixed: 6 x overall diameter
25mm2 and above - Fixed: 8 x overall diameter
STANDARDS
BS 5467 for XLPE insulated armoured cables
BS 7889 for XLPE insulated single core unarmoured cables
IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured cables
IEC 60228/BS6360 for copper conductor
BS 7655 for Insulation, bedding and outersheath
IEC 60332 for Flame propagation
CORE IDENTIFICATION
1 core Red, Black
2 core Red, Black
3 core Red, Yellow, Blue.
4 core Red, Yellow, Blue, Black.
5 core Red, Yellow, Blue, Black, Yellow/ Green
APPLICATION
Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary fixed wiring cables for use in power networks, underground,
outdoor and indoor applications and for use in cable ducting.
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
2
ITEM No. 1 2 3 4
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 2 x 1.5 2 x 2.5 2 x 4 2 x 10
1 Type of Cable CU/XLPE/PVC/SWA/PVC
2 Standard BS 5467
3 Nominal voltage rating Volts 600/1000
4 Max. continuous current carrying capacity when laid
In air Amps 29 39 52 90
In ground Amps 38 49 65 109
In duct Amps 31 41 53 89
5 Conductors :
Material Plain Annealed Copper
No. of Cores No. 2 2 2 2
Nominal cross section mm² 1.5 2.5 4 10
6 Insulation of conductors :
Material XLPE
Minimum average thickness mm 0.6 0.7 0.7 0.7
7 Bedding :
Material Extruded PVC
Nominal thickness mm 0.8 0.8 0.8 0.8
Approx.diameter over bedding mm 7.8 9 10.1 13
8 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 0.9 0.9 0.9 0.9
Approx. diameter over armour mm 9.5 10.7 11.8 14.7
9 Sheath :
Material Extruded PVC
Nominal thickness mm 1.3 1.4 1.4 1.5
Approx. outer diameter of cable. mm 11.5 12.9 14 17
10 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 1.83
11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 2.33
12 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 2.33
13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.08
14 Maximum Conductor short circuit capacity for one sec : kA 0.215 0.358 0.57 1.43
15 Max.conductor operating temperature. °C 90
16 Max. Conductor permissible temp under SC conditions. °C 250
17 Voltage drop mv/Amp/mt 31 19 12 4.7
18 Max. allowable tensile strength Kgf 18 30 48 120
19 Minimum allowable bending radius mm *6D *6D *6D *6D
20 Approx. weight of completed cable. kg/km 275 340 420 640
21 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
3
ITEM No. 5 6 7
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 2 x 6 2X16 2X25
1 Type of Cable CU/XLPE/PVC/SWA/PVC
2 Standard BS 5467
3 Nominal voltage rating Volts 600/1000
Number of Core(s) Nos 2 2 2
Nominal cross sectional area mm2 6 16 25
Approx. Diameter of Conductor mm 2.92 4.7 6.15
4 Insulation - XLPE
Color (s) Red, Black
Nominal Thickness mm 0.7 0.7 0.9
Approx. Diameter over Insulation mm 4.4 6.2 8.1
5 Core Laid up
Approx. Diameter over Laid Up mm 8.8 12.4 16.1
6 Extruded Bedding - PVC
Nominal Thickness mm 0.8 0.8 0.8
Approx. Diameter over bedding mm 10.9 14.5 18.2
7 Armor - Type: Steel Wire
Nominal Diameter of wire mm 0.9 1.25 1.25
Approx. Diameter over armour mm 12.6 16.9 20.6
8 Extruded Outer Sheath - PVC (Black)
Nominal Thickness mm 1.4 1.5 1.6
Approx. Diameter over outer sheath mm 14.8 19.2 23.1
9 Approx. Weight of complete cable kg / km 476 835 1171
Max. DC Resistance of Conductor at 20°C Ohm/km 3.08 1.15 0.727
Approx. AC Resistance of Conductor at Maximum
Operating Temperature Ohm/km 3.9274 1.4666 0.9273
Approx. Capacitance uF / km 0.42 0.39 0.41
Approx. Inductance mH / km 0.3 0.26 0.25
Approx. Inductive Reactance Ohm/km 0.088 0.081 0.079
Approx. Impedance Ohm/km 3.93 1.47 0.927
Approx. Voltage Drop mV/Amp/mt 7.9 2.9 1.9
10 CURRENT CARRYING CAPACITY based on the conditions
specified
Installation Type (Single Circuit)
Soil Thermal Resistivity oC.m/W 1.2 1.2 1.2
Ground temperature ˚C 15 15 15
Ambient air temperature ˚C 30 30 30
Burial depth mm 500 500 500
Laid in ground Amps 81 140 180
Laid in Duct Amps 67 115 145
In air Amps 66 115 152
Maximum conductor temperature for continuous
operation / Short Circuit Operation ˚C 90/250 90/250
90/25
0
11 Installation Parameters
Maximum pulling force (For Conductor) kgf 72 192 300
Minimum Bending Radius mm 90 120 144
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
4
ITEM No. 1 2 3 4 5
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10
1 Type of Cable CU/XLPE/PVC/SWA/PVC
2 Standard BS 5467
3 Nominal voltage rating Volts 600/1000
4 Max. continuous current carrying capacity when laid
In air Amps 25 33 44 56 78
In ground Amps 32 42 55 69 92
In duct Amps 26 34 45 56 75
5 Conductors :
Material Plain Annealed Copper
No. of Cores No. 3 3 3 3 3
Nominal cross section mm² 1.5 2.5 4 6 10
6 Insulation of conductors :
Material XLPE
Minimum average thickness mm 0.6 0.7 0.7 0.7 0.7
7 Bedding :
Material Extruded PVC
Nominal thickness mm 0.8 0.8 0.8 0.8 0.8
Approx.diameter over bedding mm 8.3 9.6 10.7 11.9 13.9
8 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 0.9 0.9 0.9 0.9 1.25
Approx. diameter over armour mm 10 11.3 12.4 13.6 16.3
9 Sheath :
Material Extruded PVC
Nominal thickness mm 1.3 1.4 1.4 1.4 1.5
Approx. outer diameter of cable. mm 12 13.5 14.6 15.8 18.6
10 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83
11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33
12 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33
13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.088 0.083
14 Maximum Conductor short circuit capacity for one sec : kA 0.22 0.358 0.57 0.858 1.43
15 Max.conductor operating temperature. °C 90
16 Max. Conductor permissible temp under SC conditions. °C 250
17 Voltage drop mv/Amp/mt 27 16 10 6.8 4
18 Max. allowable tensile strength Kgf 27 45 72 108 180
19 Minimum allowable bending radius mm *6D *6D *6D *6D *6D
20 Approx. weight of completed cable. kg/km 300 385 460 570 835
21 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
5
ITEM No. 6 7 8 9 10
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3 x 16 3 x 25 3 x 35 3x50 3x70
1 Type of Cable CU/XLPE/PVC/SWA/PVC
2 Standard BS 5467
3 Nominal voltage rating Volts 600/1000
4 Max. continuous current carrying capacity when laid
In air Amps 99 131 162 197 251
In ground Amps 115 150 180 215 265
In duct Amps 94 125 150 175 215
5 Conductors :
Material Plain Annealed Copper
No. of Cores No. 3 3 3 3 3
Nominal cross section mm² 16 25 35 50 70
6 Insulation of conductors :
Material XLPE
Minimum average thickness mm 0.7 0.9 0.9 1 1.1
7 Bedding :
Material Extruded PVC
Nominal thickness mm 0.8 1 1 1 1
Approx.diameter over bedding mm 15.8 17.6 19.6 23.1 25.2
8 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 1.25 1.6 1.6 1.6 2
Approx. diameter over armour mm 18.2 20.7 22.7 25 28.3
9 Sheath :
Material Extruded PVC
Nominal thickness mm 1.6 1.7 1.8 1.8 1.9
Approx. outer diameter of cable. mm 20.7 23.3 25.5 29 31.3
10 Maximum DC Resistance of conductor at 20°C Ohm/km 1.15 0.727 0.524 0.387 0.268
11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 1.47 0.927 0.668 0.494 0.342
12 AC Impedance per phase at 90°C(Approx) Ohm/km 1.47 0.93 0.67 0.5 0.35
13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.08 0.079 0.077 0.076 0.075
14 Maximum Conductor short circuit capacity for one sec : kA 2.29 3.58 5.01 7.15 10.1
15 Max.conductor operating temperature. °C 90
16 Max. Conductor permissible temp under SC conditions. °C 250
17 Voltage drop mv/Amp/mt 2.6 1.6 1.2 0.87 0.61
18 Max. allowable tensile strength Kgf 288 450 630 900 1260
19 Minimum allowable bending radius mm *6D *6D *6D *8D *8D
20 Approx. weight of completed cable. kg/km 1065 1550 1850 2380 3060
21 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
6
ITEM No. 11 12 13 14 15 16
Sr
# Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3x95 3x120 3x150 3x185 3x240 3x300
1 Type of Cable CU/XLPE/PVC/SWA/PVC
2 Standard BS 5467
3 Nominal voltage rating Volts 600/1000
4 Max. continuous current carrying capacity
when laid
In air Amps 304 353 406 463 546 628
In ground Amps 315 360 405 460 530 590
In duct Amps 260 300 335 380 440 495
5 Conductors :
Material Plain Annealed Copper
No. of Cores No. 3 3 3 3 3 3
Nominal cross section mm² 95 120 150 185 240 300
6 Insulation of conductors :
Material XLPE
Minimum average thickness mm 1.1 1.2 1.4 1.6 1.7 1.8
7 Bedding :
Material Extruded PVC
Nominal thickness mm 1.2 1.2 1.4 1.4 1.4 1.6
Approx.diameter over bedding mm 28.8 32.1 36 40.5 44.8 50.4
8 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 2 2.5 2.5 2.5 2.5 2.5
Approx. diameter over armour mm 32.7 36 40.9 45.4 49.7 55.2
9 Sheath :
Material Extruded PVC
Nominal thickness mm 2.1 2.2 2.3 2.4 2.6 2.7
Approx. outer diameter of cable. mm 36.1 39.6 44.7 49.3 54 59.7
10 Maximum DC Resistance of conductor at 20°C Ohm/km 0.19 0.153 0.124 0.099 0.075 0.06
11 Maximum AC Resistance per core at
90°C(Approx) Ohm/km 0.25 0.197 0.16 0.128 0.099 0.08
12 AC Impedance per phase at 90°C(Approx) Ohm/km 0.26 0.21 0.18 0.15 0.12 0.11
13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.07 0.072 0.073 0.073 0.072 0.072
14 Maximum Conductor short circuit capacity for
one sec : kA 13.6 17.2 21.5 26.5 34.4 42.9
15 Max.conductor operating temperature. °C 90
16 Max. Conductor permissible temp under SC
conditions. °C 250
17 Voltage drop mv/Amp/mt 0.45 0.36 0.3 0.25 0.21 0.19
18 Max. allowable tensile strength Kgf 1710 2000 2000 2000 2000 2000
19 Minimum allowable bending radius mm *8D *8D *8D *8D *8D *8D
20 Approx. weight of completed cable. kg/km 4180 5050 6400 7770 9650 11725
21 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
7
ITEM No. 1 2 3 4 5
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10
Manufacturer DUBAI CABLE COMPANY (PVT) LTD.
2 Country of Origin U.A.E
3 Type of Cable CU/XLPE/PVC/SWA/PVC
4 Standard BS 5467
5 Nominal voltage rating Volts 600/1000
6 Max. continuous current carrying capacity when laid
In air Amps 25 33 44 56 78
In ground Amps 32 42 55 69 92
In duct Amps 26 34 45 56 75
7 Conductors :
Material Plain Annealed Copper
No. of Cores No. 4 4 4 4 4
Nominal cross section mm² 1.5 2.5 4 6 10
8 Insulation of conductors :
Material XLPE
Minimum average thickness mm 0.6 0.7 0.7 0.7 0.7
9 Bedding :
Material Extruded PVC
Nominal thickness mm 0.8 0.8 0.8 0.8 0.8
Approx.diameter over bedding mm 9.0 10.5 11.8 13.1 15.3
10 Armouring :
Material Galvanised steel wire
Armour wire dia. mm 0.90 0.90 0.9 1.25 1.25
Approx. diameter over armour mm 10.7 12.2 13.5 15.5 17.7
11 Sheath :
Material Extruded PVC
Nominal thickness mm 1.3 1.4 1.4 1.5 1.5
Approx. outer diameter of cable. mm 12.7 14.4 15.7 17.8 20.0
12 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83
13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33
14 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33
15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.088 0.083
16 Maximum Conductor short circuit capacity for one sec : kA 0.215 0.358 0.570 0.858 1.430
17 Max.conductor operating temperature. °C 90
18 Max. Conductor permissible temp under SC conditions. °C 250
19 Voltage drop mv/Amp/mt 27 15 10 6.2 4
20 Max. allowable tensile strength Kgf 36 60 96 144 240
21 Minimum allowable bending radius mm *6D *6D *6D *6D *6D
22 Approx. weight of completed cable. kg/km 355 445 550 760 985
23 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
8
ITEM No. 1 2 3 4 5 6
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95
1 Manufacturer DUBAI CABLE COMPANY (PVT) LTD.
2 Country of Origin U.A.E
3 Type of Cable CU/XLPE/PVC/SWA/PVC
4 Standard BS 5467
5 Nominal voltage rating Volts 600/1000
6 Max. continuous current carrying capacity when laid
In air Amps 99 131 162 197 251 304
In ground Amps 115 150 180 215 265 315
In duct Amps 94 125 150 175 215 260
7 Conductors :
Material Plain Annealed Copper
No. of Cores No. 4 4 4 4 4 4
Nominal cross section mm² 16 25 35 50 70 95
8 Insulation of conductors :
Material XLPE
Minimum average thickness mm 0.7 0.9 0.9 1.0 1.1 1.1
9 Bedding :
Material Extruded PVC
Nominal thickness mm 0.8 1.0 1.0 1.0 1.2 1.2
Approx.diameter over bedding mm 17.5 19.9 22.7 25.4 29.1 33.1
10 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 1.25 1.6 1.6 1.6 2.0 2.0
Approx. diameter over armour mm 19.9 23.0 25.8 28.5 33.0 37.0
11 Sheath :
Material Extruded PVC
Nominal thickness mm 1.6 1.7 1.8 1.9 2.1 2.2
Approx. outer diameter of cable. mm 22.4 25.6 28.6 31.5 36.4 40.6
12 Maximum DC Resistance of conductor at 20°C Ohm/km 1.15 0.727 0.524 0.387 0.268 0.193
13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 1.47 0.927 0.668 0.494 0.342 0.247
14 AC Impedance per phase at 90°C(Approx) Ohm/km 1.47 0.93 0.67 0.5 0.35 0.26
15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.081 0.079 0.077 0.076 0.075 0.073
16 Maximum Conductor short circuit capacity for one sec : kA 2.29 3.58 5.01 7.15 10.10 13.60
17 Max.conductor operating temperature. °C 90
18 Max. Conductor permissible temp under SC conditions. °C 250
19 Voltage drop mv/Amp/mt 2.6 1.6 1.2 0.87 0.61 0.45
20 Max. allowable tensile strength Kgf 384 600 840 1200 1680 2000
21 Minimum allowable bending radius mm *6D *8D *8D *8D *8D *8D
22 Approx. weight of completed cable. kg/km 1300 1840 2340 2930 4130 5300
23 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
PVC SHEATHED
DATA SHEET Armoured Cables SWA
ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com
Pa
ge
9
ITEM No. 7 8 9 10 11 12
Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 120 4 x 150 4 x 185 4 x 240 4 x 300 4 x 400
1 Manufacturer DUBAI CABLE COMPANY (PVT) LTD
2 Country of Origin U.A.E
3 Type of Cable CU/XLPE/PVC/SWA/PVC
4 Standard BS 5467
5 Nominal voltage rating Volts 600/1000
6 Max. continuous current carrying capacity when laid
In air Amps 353 406 463 546 628 728
In ground Amps 360 405 460 530 590 667
In duct Amps 300 335 380 440 495 570
7 Conductors :
Material Plain Annealed Copper
No. of Cores No. 4 4 4 4 4 4
Nominal cross section mm² 120 150 185 240 300 400
8 Insulation of conductors :
Material XLPE
Minimum average thickness mm 1.2 1.4 1.6 1.7 1.8 2.0
9 Bedding :
Material Extruded PVC
Nominal thickness mm 1.4 1.4 1.4 1.6 1.6 1.8
Approx.diameter over bedding mm 36.5 40.6 45.6 51.0 56.5 63.9
10 Armouring :
Material Galvanised steel wire.
Armour wire dia. mm 2.5 2.5 2.5 2.5 2.5 3.15
Approx. diameter over armour mm 41.4 45.5 50.5 55.8 61.3 70.0
11 Sheath :
Material Extruded PVC
Nominal thickness mm 2.3 2.4 2.6 2.7 2.9 3.2
Approx. outer diameter of cable. mm 45.2 49.4 54.8 60.3 66.2 75.4
12 Maximum DC Resistance of conductor at 20°C Ohm/km 0.153 0.124 0.0991 0.0754 0.0601 0.0470
13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 0.197 0.16 0.128 0.0989 0.0802 0.0641
14 AC Impedance per phase at 90°C(Approx) Ohm/km 0.21 0.18 0.15 0.12 0.11 0.1
15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.072 0.073 0.073 0.072 0.072 0.072
16 Maximum Conductor short circuit capacity for one sec : kA 17.20 21.50 26.50 34.40 42.90 57.20
17 Max.conductor operating temperature. °C 90
18 Max. Conductor permissible temp under SC conditions. °C 250
19 Voltage drop mv/Amp/mt 0.36 0.3 0.25 0.21 0.19 0.18
20 Max. allowable tensile strength Kgf 2000 2000 2000 2000 2000 2000
21 Minimum allowable bending radius mm *8D *8D *8D *8D *8D *8D
22 Approx. weight of completed cable. kg/km 6750 8110 9800 12320 14910 19280
23 Conditions of installations :
Soil thermal resistivity °C m/W 1.2
Ground temperature °C 15
Air temperature °C 30
Burial depth meters 0.5
Note : *D = Overall diameter
Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)