Refrigerant PipingA Trane Air Conditioning Clinic

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

period one

Refrigerant Piping Requirements

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Vapor-Compression Refrigeration

expansionexpansiondevicedevice

condensercondenser

compressorcompressor

evaporatorevaporatorA B

CD

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Interconnecting Refrigerant Piping

compressorcompressor

condensercondenser

evaporatorevaporator

expansion deviceexpansion device

dischargedischargelineline

suctionsuctionlineline

liquidliquidlineline

A

B

C

D

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Refrigerant Piping Requirements

Return oil to compressor Ensure that only liquid refrigerant enters

the expansion device Minimize system capacity loss Minimize refrigerant charge Insulate lines that are routed through very

warm spaces (Liquid line)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Scroll Compressor

stationarystationaryscrollscroll

drivendrivenscrollscroll

intakeintake

dischargedischarge

intakeintake

dischargedischargeportport

motormotorshaftshaft

sealseal

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Return Oil to Compressors

compressorcompressor

condensercondenser

evaporatorevaporator

expansion expansion devicedevice

dischargedischargelineline

suctionsuctionlineline

liquidliquidlineline

warmwarmliquidliquid

hothotvaporvapor

coolcoolvaporvapor

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Thermostatic Expansion Valve (TXV)

external equalizerexternal equalizer

remote remote bulbbulb

evaporatorevaporator

TXVTXV

refrigerantrefrigerantvaporvapor

distributordistributor

liquid liquid refrigerantrefrigerant

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Subcooling

B

A

pres

sure

pres

sure

enthalpyenthalpy

{

subcoolingsubcooling

C

mixture of liquid mixture of liquid and vaporand vapor

saturatedsaturatedvapor curvevapor curve

saturatedsaturatedliquid curveliquid curve

expansionexpansiondevicedevice

condensercondenser

evaporatorevaporator

compressorcompressor

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Condenser

Evaporator

CompressorExpansion

Device

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Pressure Drop in a Suction Lineim

pact

on

syst

em p

erfo

rman

ce, %

impa

ct o

n sy

stem

per

form

ance

, %

capacitycapacitycapacitycapacity

100100

efficiencyefficiencyefficiencyefficiency

pressure drop, psipressure drop, psi (kPa)(kPa)pressure drop, psipressure drop, psi (kPa)(kPa)

22(13.8)(13.8)

22(13.8)(13.8)

9696

9292

9898

9494

909044

(27.6)(27.6)44

(27.6)(27.6)66

(41.4)(41.4)66

(41.4)(41.4)1010

(69.0)(69.0)1010

(69.0)(69.0)1212

(82.7)(82.7)1212

(82.7)(82.7)88

(55.2)(55.2)88

(55.2)(55.2)

R-22R-22R-22R-22

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Minimize Refrigerant Charge

liquid lineliquid line suction linesuction line

condensercondenser

evaporatorevaporator

filterfilterdrierdrier

compressorcompressordischargedischargelineline

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Involve the Manufacturer

If provided, use refrigerant line sizes recommended by manufacturer

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

General Piping Requirements

Use clean Type L copper tubing Copper-to-copper joints: BCuP-6 without flux Copper-to-steel (or brass) joints: BAg-28, non-acid flux

Properly support piping to account for expansion, vibration, and weight

Avoid installing piping underground Test entire refrigerant circuit for leaks

period two

Suction Line

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line

Requirements for Sizing and Routing

Ensure adequate velocity to return oil to compressor at all steps of unloading

Avoid excessive noise Minimize system capacity and efficiency loss

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line Sizing “Rules”

minimum velocity

1,000 fpm (5 m/s) based on diameter of riserfor vertical risers

500 fpm (2.5 m/s) percentage of minimum for horizontal sections riser velocity

maximum velocity

4,000 fpm (20 m/s) 4,000 fpm (20 m/s)

maximum pressure drop

3 psi (20 kPa) based on specific system requirements

old rules for R-22 new rules for R-22

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line Process for Sizing

1 Determine total length of piping

2 Calculate refrigerant velocity at maximum and minimum capacities

3 Select largest pipe diameter that results in acceptable velocity at both maximum and minimum capacities

4 Calculate total equivalent length of straight pipe and fittings

5 Determine pressure drop due to pipe and fittings

6 Add pressure drop due to accessories

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Unloading Refrigeration Circuits

reciprocating compressorreciprocating compressorwith cylinder unloaderswith cylinder unloaders scroll compressorsscroll compressors

manifolded on amanifolded on asingle circuitsingle circuit

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

velo

city,

fpm

(m/s

)ve

locit

y, fp

m (m

/s)

evaporator capacity, tons (kW)evaporator capacity, tons (kW)

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

1,0001,000(5.1)(5.1)

500500(2.5)(2.5)

2,0002,000(10.2)(10.2)

5,0005,000(25.4)(25.4)

2020(70)(70)

22(7.0)(7.0)

1/2 (1

2)

1/2 (1

2)

5/8 (1

5)

5/8 (1

5)

7/8 (2

2)

7/8 (2

2)

1 1/8

(28)

1 1/8

(28)

1 3/8

(35)

1 3/8

(35)

1 5/8

(42)

1 5/8

(42)

2 1/8

(54)

2 1/8

(54)

2 5/8

(67)

2 5/8

(67)

3 1/8

(79)

3 1/8

(79)

3 5/8

(105)

3 5/8

(105)

R-22R-22

suction line

Determine Refrigerant Velocitypipe diameter, in. (mm)pipe diameter, in. (mm)

3/8 (1

0)

3/8 (1

0)

4 1/8

(130)

4 1/8

(130)3/4

(18)

3/4 (1

8)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line

Determine Refrigerant Velocity

velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)

20 tons 20 tons (70.3 kW)(70.3 kW)

10 tons 10 tons (35.2 kW)(35.2 kW)

1 1/8 (28)1 1/8 (28) 7,000 (35.6)7,000 (35.6) 3,500 (17.8)3,500 (17.8)1 3/8 (35)1 3/8 (35) 4,600 (23.4)4,600 (23.4) 2,300 (11.7)2,300 (11.7)1 5/8 (42)1 5/8 (42) 3,250 (16.5)3,250 (16.5) 1,625 (8.3)1,625 (8.3)2 1/8 (54)2 1/8 (54) 1,850 (9.4)1,850 (9.4) 925 (4.7) 925 (4.7)2 5/8 (67)2 5/8 (67) 1,200 (6.1)1,200 (6.1) 600 (3.1) 600 (3.1)3 1/8 (79)3 1/8 (79) 850 (4.3)850 (4.3) 425 (2.2) 425 (2.2)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

riserriser horiz/drophoriz/drop3/8 (10)3/8 (10) 370 (1.9)370 (1.9) 275 (1.4)275 (1.4)1/2 (12)1/2 (12) 460 (2.3)460 (2.3) 350 (1.8)350 (1.8)5/8 (15)5/8 (15) 520 (2.6)520 (2.6) 390 (2.0)390 (2.0)3/4 (18)3/4 (18) 560 (2.8)560 (2.8) 420 (2.1)420 (2.1)7/8 (22)7/8 (22) 600 (3.1)600 (3.1) 450 (2.3)450 (2.3)

1 1/8 (28)1 1/8 (28) 700 (3.6)700 (3.6) 525 (2.7)525 (2.7)1 3/8 (35)1 3/8 (35) 780 (4.0)780 (4.0) 585 (3.0)585 (3.0)1 5/8 (42)1 5/8 (42) 840 (4.3)840 (4.3) 630 (3.2)630 (3.2)2 1/8 (54)2 1/8 (54) 980 (5.0)980 (5.0) 735 (3.7)735 (3.7)2 5/8 (67)2 5/8 (67) 1,080 (5.5)1,080 (5.5) 810 (4.1)810 (4.1)3 1/8 (79)3 1/8 (79) 1,180 (6.0)1,180 (6.0) 885 (4.5)885 (4.5)

3 5/8 (105)3 5/8 (105) 1,270 (6.5)1,270 (6.5) 950 (4.8)950 (4.8)4 1/8 (130)4 1/8 (130) 1,360 (6.9)1,360 (6.9) 1,020 (5.2)1,020 (5.2)

suction line

Minimum Allowable Velocitiesminimum velocity, fpm (m/s)minimum velocity, fpm (m/s)pipe diameter,pipe diameter,

in. (mm)in. (mm)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Select Suction Line Size

riserriser horiz/drophoriz/drop

20 (70.3)20 (70.3) 1,850 (9.4)1,850 (9.4)

10 (35.2)10 (35.2) 925 (4.7)925 (4.7)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocity for 2 1/8 in.minimum velocity for 2 1/8 in.(54 mm) pipe, fpm (m/s)(54 mm) pipe, fpm (m/s)

velocity insidevelocity inside2 1/8 in. (54 mm) 2 1/8 in. (54 mm) pipe, fpm (m/s)pipe, fpm (m/s)

980 (5.0)980 (5.0) 735 (3.7)735 (3.7)

riserriser horiz/drophoriz/drop

20 (70.3)20 (70.3) 3,250 (16.5)3,250 (16.5)

10 (35.2)10 (35.2) 1,625 (8.3)1,625 (8.3)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocity for 1 5/8 in.minimum velocity for 1 5/8 in.(42 mm) pipe, fpm (m/s)(42 mm) pipe, fpm (m/s)

velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)

840 (4.3)840 (4.3) 630 (3.2)630 (3.2)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Selected Suction Line Sizes

compressorcompressor

evaporatorevaporator

2 1/8 in.2 1/8 in.(54 mm)(54 mm)

1 5/8 in. 1 5/8 in. (42 mm)(42 mm)riserriser

2 1/8 in.2 1/8 in.(54 mm)(54 mm)

dropdrop

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Double Suction Riser

20 (70.3)20 (70.3) 3,250 (16.5)3,250 (16.5)

5 (17.6)5 (17.6) 810 (4.1)810 (4.1)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocity forminimum velocity for1 5/8 in. (42 mm) riser, 1 5/8 in. (42 mm) riser,

fpm (m/s)fpm (m/s)

velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)

840 (4.3)840 (4.3)

20 (70.3)20 (70.3) 4,600 (23.4)4,600 (23.4)

5 (17.6)5 (17.6) 1,150 (5.9)1,150 (5.9)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocity forminimum velocity for1 3/8 in. (35 mm) riser, 1 3/8 in. (35 mm) riser,

fpm (m/s)fpm (m/s)

velocity insidevelocity inside1 3/8 in. (35 mm) 1 3/8 in. (35 mm) pipe, fpm (m/s)pipe, fpm (m/s)

780 (4.0)780 (4.0)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Double Suction Riser

largerlargerriserriser

smallersmallerriserriser

traptrap

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Sizing a Double Suction Riser

Sizing the smaller riser

Sizing the larger riser

5 (17.6)5 (17.6) 1,150 (5.8)1,150 (5.8)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocityminimum velocityfor 1 3/8 in. (35 mm) for 1 3/8 in. (35 mm) riser, fpm (m/s)riser, fpm (m/s)

velocity insidevelocity inside1 3/8 in. (35 mm) 1 3/8 in. (35 mm) pipe, fpm (m/s)pipe, fpm (m/s)

780 (4.0)780 (4.0)

15 (52.8)15 (52.8) 2,450 (12.4)2,450 (12.4)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocityminimum velocityfor 1 5/8 in. (42 mm) for 1 5/8 in. (42 mm) riser, fpm (m/s)riser, fpm (m/s)

velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)

840 (4.3)840 (4.3)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Calculate Total Equivalent Length

LLeqeq is based on r/d is based on r/d

radius of curvature (r)radius of curvature (r)

diameter (d)diameter (d)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Leq for Long-Radius Elbows

equivalent length, ft (m)equivalent length, ft (m)

““old” dataold” data ““new” datanew” data

1 1/8 (28)1 1/8 (28) 1.9 (0.6)1.9 (0.6) 0.8 (0.24)0.8 (0.24)1 3/8 (35)1 3/8 (35) 2.2 (0.7)2.2 (0.7) 0.9 (0.27)0.9 (0.27)1 5/8 (42)1 5/8 (42) 2.6 (0.8)2.6 (0.8) 1.0 (0.30)1.0 (0.30)2 1/8 (54)2 1/8 (54) 3.4 (1.0)3.4 (1.0) 1.4 (0.43)1.4 (0.43)2 5/8 (67)2 5/8 (67) 4.2 (1.3)4.2 (1.3) 1.5 (0.46)1.5 (0.46)3 1/8 (79)3 1/8 (79) 5.1 (1.6)5.1 (1.6) 1.7 (0.52)1.7 (0.52)

elbowelbowdiameter,diameter,in. (mm)in. (mm)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

pres

sure

dro

p, p

si/10

0 ft

(kPa

/10

m)

pres

sure

dro

p, p

si/10

0 ft

(kPa

/10

m)

evaporator capacity, tons (kW)evaporator capacity, tons (kW)

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

1.01.0(2.3)(2.3)

0.50.5(1.2)(1.2)

2.02.0(4.6)(4.6)

5.05.0(11.5)(11.5)

2020(70)(70)

22(7.0)(7.0)

2 1/

8 (5

4)2

1/8

(54)

2 5/

8 (6

7)2

5/8

(67)

3 1/

8 (7

9)3

1/8

(79)

R-22R-22

pipe diameter, in. (mm)pipe diameter, in. (mm)

1 5/

8 (4

2)1

5/8

(42)10.010.0

(23.0)(23.0)

suction line

Determine Pressure Drop

1 3/

8 (3

5)1

3/8

(35)

1 1/

8 (2

8)1

1/8

(28)

7/8

(22)

7/8

(22)

3/4

(18)

3/4

(18)

5/8

(15)

5/8

(15)

3 5/

8 (1

05)

3 5/

8 (1

05)

4 1/

8 (1

30)

4 1/

8 (1

30)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line

Add Pressure Drop of Accessories

Suction filter = 2 psi (13.8 kPa) Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)

suction line filtersuction line filter

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

TXV Installation

external equalizer lineexternal equalizer line

remote remote bulbbulb

evaporatorevaporator

TXVTXV

refrigerantrefrigerantvaporvapor

distributordistributor

liquid liquid refrigerantrefrigerant

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

single distributor on circuit

Evaporator Coil Connection

TXVTXVbulbbulb

must rise abovemust rise aboveheight of evaporatorheight of evaporator

must drop belowmust drop belowheader outletheader outlet

suction headersuction header

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

single distributor on circuit

Evaporator Coil Connection

TXVTXVbulbbulb

must rise abovemust rise aboveheight of evaporatorheight of evaporator

must drop belowmust drop belowheader outletheader outlet

suction headersuction header

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

multiple distributors on circuit Evaporator Coil Connections

TXVTXVbulbbulb

must drop belowmust drop belowlowest header outletlowest header outlet double-elbowdouble-elbow

configurationconfiguration

must rise abovemust rise aboveheight of evaporatorheight of evaporator

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line

Riser Traps Are Not Required

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line Other Considerations Do not use suction riser traps: they are not

required Pitch horizontal sections to drain toward

evaporator Insulate entire suction line

Prevents condensation Minimizes loss of capacity due to heat gain

Install suction-line filter close to compressor Manual shutoff valves allow isolation for replacement

Install access ports to measure suction pressure and superheat

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Suction-Line Accumulator

Check with equipment manufacturer to determine if required, recommended, or discouraged

photo provided by Henry Technologiesphoto provided by Henry Technologies

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

suction line

Reciprocating Compressors

pipepipeanchoranchor

pitchpitch

period three

Discharge Line

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line

Requirements for Sizing and Routing

Ensure adequate velocity to return oil to compressor at all steps of unloading

Avoid excessive noise Minimize efficiency loss

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line Sizing “Rules”

minimum velocity

1,000 fpm (5 m/s) based on diameter of riserfor risers

500 fpm (2.5 m/s) percentage of minimum for horizontal sections riser velocity

maximum velocity

3,500 fpm (17.5 m/s) 3,500 fpm (17.5 m/s)

maximum pressure drop

6 psi (41 kPa) based on specific system requirements

old rules for R-22 new rules for R-22

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line Process for Sizing

1 Determine total length of piping

2 Calculate refrigerant velocity at maximum and minimum capacities

3 Select largest pipe diameter that results in acceptable velocity at both maximum and minimum capacity

4 Calculate total equivalent length of straight pipe and fittings

5 Determine pressure drop due to pipe and fittings

6 Add pressure drop due to accessories

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

1,0001,000(5.1)(5.1)

500500(2.5)(2.5)

2,0002,000(10.2)(10.2)

5,0005,000(25.4)(25.4)

2020(70)(70)

22(7.0)(7.0)

1/2 (1

2)

1/2 (1

2)

5/8 (1

5)

5/8 (1

5)

7/8 (2

2)

7/8 (2

2)

1 1/8

(28)

1 1/8

(28)

1 3/8

(35)

1 3/8

(35)

1 5/8

(42)

1 5/8

(42)

2 1/8

(54)

2 1/8

(54)

2 5/8

(67)

2 5/8

(67)

3 1/8

(79)

3 1/8

(79)

R-22R-22

discharge line

Determine Refrigerant Velocity

velo

city,

fpm

(m/s

)ve

locit

y, fp

m (m

/s)

evaporator capacity, tons (kW)evaporator capacity, tons (kW)

pipe diameter, in. (mm)pipe diameter, in. (mm)

3/8 (1

0)

3/8 (1

0)

3/4 (1

8)

3/4 (1

8)

5/16 (

8)

5/16 (

8)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line

Determine Refrigerant Velocity

7/8 (22)7/8 (22) 4,050 (20.6)4,050 (20.6) 2,025 (10.3)2,025 (10.3)1 1/8 (28)1 1/8 (28) 2,400 (12.2)2,400 (12.2) 1,200 ( 6.1)1,200 ( 6.1)1 3/8 (35)1 3/8 (35) 1,550 ( 7.9)1,550 ( 7.9) 775 ( 3.9) 775 ( 3.9)1 5/8 (42)1 5/8 (42) 1,100 ( 5.6)1,100 ( 5.6) 550 ( 2.8) 550 ( 2.8)2 1/8 (54)2 1/8 (54) 650 ( 3.3)650 ( 3.3) 325 ( 1.7) 325 ( 1.7)

velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)

20 tons 20 tons (70.3 kW)(70.3 kW)

10 tons 10 tons (35.2 kW)(35.2 kW)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line

Minimum Allowable Velocities

riserriser horiz/drophoriz/drop5/16 (8)5/16 (8) 220 (1.1)220 (1.1) 165 (0.8)165 (0.8)3/8 (10)3/8 (10) 250 (1.3)250 (1.3) 185 (0.9)185 (0.9)1/2 (12)1/2 (12) 285 (1.4)285 (1.4) 215 (1.1)215 (1.1)5/8 (15)5/8 (15) 315 (1.6)315 (1.6) 235 (1.2)235 (1.2)3/4 (18)3/4 (18) 345 (1.8)345 (1.8) 260 (1.3)260 (1.3)7/8 (22)7/8 (22) 375 (1.9)375 (1.9) 285 (1.4)285 (1.4)

1 1/8 (28)1 1/8 (28) 430 (2.2)430 (2.2) 325 (1.7)325 (1.7)1 3/8 (35)1 3/8 (35) 480 (2.4)480 (2.4) 360 (1.8)360 (1.8)1 5/8 (42)1 5/8 (42) 520 (2.6)520 (2.6) 390 (2.0)390 (2.0)2 1/8 (54)2 1/8 (54) 600 (3.0)600 (3.0) 450 (2.3)450 (2.3)2 5/8 (67)2 5/8 (67) 665 (3.4)665 (3.4) 500 (2.5)500 (2.5)3 1/8 (79)3 1/8 (79) 730 (3.7)730 (3.7) 550 (2.8)550 (2.8)

minimum velocity, fpm (m/s)minimum velocity, fpm (m/s)pipe diameter,pipe diameter,in. (mm)in. (mm)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Select Discharge Line Size

riserriser horiz/drophoriz/drop

20 (70.3)20 (70.3) 1,100 (5.6)1,100 (5.6)

10 (35.2)10 (35.2) 550 (2.8)550 (2.8)

circuitcircuitcapacity,capacity,tons (kW)tons (kW)

minimum velocity for 1 5/8 in.minimum velocity for 1 5/8 in.(42 mm) pipe, fpm (m/s)(42 mm) pipe, fpm (m/s)

velocity insidevelocity inside1 5/8 in. (42 mm) 1 5/8 in. (42 mm) pipe, fpm (m/s)pipe, fpm (m/s)

520 (2.6)520 (2.6) 390 (2.0)390 (2.0)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Selected Discharge Line Size

1 5/8 in.1 5/8 in.(42 mm)(42 mm)

compressorcompressor

condensercondenser 1 5/8 in. 1 5/8 in. (42 mm)(42 mm)riserriser

1 5/8 in. 1 5/8 in. (42 mm)(42 mm)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

pres

sure

dro

p, p

si/10

0 ft

(kPa

/10

m)

pres

sure

dro

p, p

si/10

0 ft

(kPa

/10

m)

evaporator capacity, tons (kW)evaporator capacity, tons (kW)

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

1.01.0(2.3)(2.3)

0.50.5(1.2)(1.2)

2.02.0(4.6)(4.6)

5.05.0(11.5)(11.5)

2020(70)(70)

22(7.0)(7.0)

7/8

(22)

7/8

(22)

1 1/8

(28)

1 1/8

(28)

1 3/8

(35)

1 3/8

(35)

2 1/8

(54)

2 1/8

(54)

2 5/8

(67)

2 5/8

(67)

3 1/8

(79)

3 1/8

(79)

R-22R-22

pipe diameter, in. (mm)pipe diameter, in. (mm)

1 5/8

(42)

1 5/8

(42)

10.010.0(23.0)(23.0)

discharge line

Determine Pressure Drop

3/4

(18)

3/4

(18)

5/8

(15)

5/8

(15)

1/2

(12)

1/2

(12)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line

Add Pressure Drop of Accessories

Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line Other Considerations

Do not use discharge riser traps: they are not required

Pitch horizontal sections to drain toward condenser

Insulate only to prevent accidental burns or when system must operate in cold ambient conditions

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

discharge line

Reciprocating Compressors

pipepipeanchoranchor

pitchpitch

period four

Liquid Line

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Requirements for Sizing and Routing

Ensure that only liquid refrigerant enters expansion device

Minimize refrigerant charge Avoid excessive noise and pipe erosion

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Subcooling

enthalpy, Btu/lb (kJ/kg)enthalpy, Btu/lb (kJ/kg)

241241(1,662)(1,662)

pres

sure

, psia

(kPa

)pr

essu

re, p

sia (k

Pa)

293293(2,020)(2,020) 125°F125°F

(51.7°C)(51.7°C)

subcoolingsubcooling

saturatedsaturatedliquid curveliquid curve

mixture of liquidmixture of liquidand vaporand vapor

110°F110°F(43.3°C)(43.3°C)

{

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Impact of Refrigerant Density Change

AA 7/8 (22)7/8 (22) highhigh 18.0 (10) -18.0 (10) - 5.7 (3.2) =5.7 (3.2) = 12.3 (6.8)12.3 (6.8)BB 1 1/8 (28)1 1/8 (28) highhigh 18.0 (10) -18.0 (10) - 3.8 (2.1) =3.8 (2.1) = 14.2 (7.9)14.2 (7.9)

AA 7/8 (22)7/8 (22) lowlow 12.9 (7.2) -12.9 (7.2) - 7.4 (4.1) =7.4 (4.1) = 5.5 (3.1)5.5 (3.1)BB 1 1/8 (28)1 1/8 (28) lowlow 7.2 (4.0) -7.2 (4.0) - 5.2 (2.9) =5.2 (2.9) = 2.0 (1.1)2.0 (1.1)

available subcooling, °F (°C)available subcooling, °F (°C)liquid lineliquid linediameter, diameter, in. (mm)in. (mm)

leaving leaving subcoolersubcooler

loss due loss due to pipingto piping

outdooroutdoortemperaturetemperature remaining remaining

at TXVat TXV

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line Sizing “Rules”

maximum pressure drop

6 psi (41 kPa) 5°F (2.8°C) subcoolingremaining at inlet to expansion device at all operating conditions

maximum velocity

360 fpm (1.8 m/s) 600 fpm (3 m/s)

old rules for R-22 new rules for R-22

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line Process for Sizing

1 Determine total length of piping

2 Obtain subcooling provided by condenser

3 Determine refrigerant velocity

4 Select smallest pipe diameter that results in acceptable velocity at maximum capacity

5 Calculate total equivalent length of pipe and fittings

6 Determine pressure drop due to pipe and fittings

7 Add pressure drop due to accessories

8 Calculate loss of subcooling due to pressure drop and elevation change

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

System Operating Envelope

saturated suction temperaturesaturated suction temperature

condensing unit,condensing unit,high OA temperaturehigh OA temperature

condensing unit, condensing unit, low OA temperaturelow OA temperature

evaporator,evaporator,high cooling loadhigh cooling load

evaporator,evaporator,low cooling loadlow cooling load

syst

em c

oolin

g ca

pacit

ysy

stem

coo

ling

capa

city

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

System Operating Envelope

high cooling load,high cooling load,high OA temperaturehigh OA temperature

A

B

D

C

high cooling load,high cooling load,low OA temperaturelow OA temperature

low cooling load,low cooling load,high OA temperaturehigh OA temperature

low cooling load,low cooling load,low OA temperaturelow OA temperature

saturated suction temperaturesaturated suction temperature

syst

em c

oolin

g ca

pacit

ysy

stem

coo

ling

capa

city

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

effect of cooling load and outdoor temperature

Subcooling Leaving Condenser

A highhigh highhigh 18 (10.0)18 (10.0) B lowlow highhigh 21 (11.7)21 (11.7)

C lowlow lowlow 13 (7.2) 13 (7.2) D highhigh lowlow 5 (2.8) 5 (2.8)

subcooling leaving subcooling leaving condenser*, °F (°C)condenser*, °F (°C)

cooling cooling loadload

outdooroutdoortemperaturetemperature

* This example system uses a TXV for the expansion device.* This example system uses a TXV for the expansion device.

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Involve the Manufacturer

If provided, use refrigerant line sizes recommended by manufacturer

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002 evaporator capacity, tons (kW)evaporator capacity, tons (kW)

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

100100(0.5)(0.5)

5050(0.25)(0.25)

200200(1.0)(1.0)

500500(2.5)(2.5)

2020(70)(70)

22(7.0)(7.0)

5/16 (

8)

5/16 (

8)3/8

(10)

3/8 (1

0)

1/2 (1

2)

1/2 (1

2)

5/8 (1

5)

5/8 (1

5)

2 1/8

(54)

2 1/8

(54)

1 5/8

(42)

1 5/8

(42)

R-22R-22

pipe diameter, in. (mm)pipe diameter, in. (mm)

1 1/8

(28)

1 1/8

(28)1,0001,000

(5.1)(5.1)

liquid line

Determine Refrigerant Velocityve

locit

y, fp

m (m

/s)

velo

city,

fpm

(m/s

)

7/8 (2

2)

7/8 (2

2)

1 3/8

(35)

1 3/8

(35)

1/4 (6

)1/4

(6)

3/4 (1

8)

3/4 (1

8)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Determine Refrigerant Velocity

1/2 (12)1/2 (12) 850 (4.3)850 (4.3)5/8 (15)5/8 (15) 525 (2.7)525 (2.7)3/4 (18)3/4 (18) 350 (1.8)350 (1.8)7/8 (22)7/8 (22) 250 (1.3)250 (1.3)

1 1/8 (28)1 1/8 (28) 150 (0.8)150 (0.8)1 3/8 (35)1 3/8 (35) 100 (0.5)100 (0.5)

velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)

20 tons 20 tons (70.3 kW)(70.3 kW)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Calculate Total Equivalent Length

evaporatorevaporator

condensercondenser

5/8 in.5/8 in.(15 mm)(15 mm)riserriser

5/8 in.5/8 in.(15 mm)(15 mm)

5/8 in.5/8 in.(15 mm)(15 mm)dropdrop

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002 evaporator capacity, tons (kW)evaporator capacity, tons (kW)

11(3.5)(3.5)

55(17.6)(17.6)

1010(35)(35)

5050(176)(176)

100100(352)(352)

200200(703)(703)

2020(70)(70)

22(7.0)(7.0)

R-22R-22

pipe diameter, in. (mm)pipe diameter, in. (mm)

liquid line

Determine Pressure Droppr

essu

re d

rop,

psi/

100

ft (k

Pa/1

0 m

)pr

essu

re d

rop,

psi/

100

ft (k

Pa/1

0 m

)

1.01.0(2.3)(2.3)

2.02.0(4.6)(4.6)

5.05.0(11.5)(11.5)

10.010.0(23)(23)

20.020.0(46)(46)

50.050.0(115)(115)

5/8

(15)

5/8

(15)

7/8

(22)

7/8

(22)

1 1/

8 (2

8)1

1/8

(28)

1 3/

8 (3

5)1

3/8

(35)

1 5/

8 (4

2)1

5/8

(42)

1/2

(12)

1/2

(12)

3/4

(18)

3/4

(18)

2 1/

8 (5

4)2

1/8

(54)

3/8

(10)

3/8

(10)

5/16

(8)

5/16

(8)

1/4

(6)

1/4

(6)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Add Pressure Drop of Accessories

Filter-drier = 6 psi (41.4 kPa) Solenoid valve = 4 psi (27.6 kPa) Sight glass = 1 equivalent ft (0.3 m) Angle valve = 1 psi (6.9 kPa) Ball valve = 1 equivalent ft (0.3 m)

solenoidsolenoidvalvevalve

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Pressure Drop Due to Elevation

evaporatorevaporator

condensercondenser 15 ft 15 ft (4.6 m)(4.6 m)vertical rise vertical rise creates creates pressure droppressure drop

11 ft 11 ft (3.4 m)(3.4 m)vertical drop vertical drop creates creates pressure gainpressure gain

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Pressure Drop Due to Elevation

liquid temperature, °F (°C)liquid temperature, °F (°C)

pres

sure

dro

p/ne

t liq

uid

rise,

psi/

ft (k

Pa/m

)pr

essu

re d

rop/

net l

iqui

d ris

e, p

si/ft

(kPa

/m)

4040(4.4)(4.4)

6060(15.6)(15.6)

8080(26.7)(26.7)

100100(37.8)(37.8)

120120(48.9)(48.9)

140140(60.0)(60.0)

160160(71.1)(71.1)

0.4250.425(9.6)(9.6)

0.4500.450(10.2)(10.2)

0.4750.475(10.7)(10.7)

0.5000.500(11.3)(11.3)

0.5250.525(11.9)(11.9)

0.5500.550(12.4)(12.4)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Calculate Loss of Subcooling

liquid temperature, °F (°C)liquid temperature, °F (°C)

loss

of s

ubco

olin

g, p

si/°F

(kPa

/°C)

loss

of s

ubco

olin

g, p

si/°F

(kPa

/°C)

4040(4.4)(4.4)

6060(15.6)(15.6)

8080(26.7)(26.7)

100100(37.8)(37.8)

120120(48.9)(48.9)

140140(60.0)(60.0)

160160(71.1)(71.1)

00(0)(0)

1.01.0(12.4)(12.4)

2.02.0(24.9)(24.9)

3.03.0(37.3)(37.3)

4.04.0(49.7)(49.7)

5.05.0(62.2)(62.2)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Subcooling Remaining at Expansion Device

15 (8.3)15 (8.3) -- 9.9 (5.5)9.9 (5.5) == 5.1 (2.8)5.1 (2.8)

leavingleavingcondensercondenser

subcooling, °F (°C)subcooling, °F (°C)

loss due toloss due toliquid lineliquid line

remaining at remaining at expansion expansion devicedevice

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Evaporator Coil Connections

TXVTXV

distributordistributor

evaporatorevaporator

solenoidsolenoidvalvevalve

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line

Refrigerant Accessories

sightsightglassglass

TXVTXV

liquid lineliquid line

solenoid solenoid valvevalve

filter-drierfilter-drier

evaporatorevaporator

condensercondenser

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Liquid Line Routing

route the horizontal leg below the riserroute the horizontal leg below the riser

evaporatorevaporatorcondensercondenser

condensercondenser

evaporatorevaporator

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

liquid line Other Considerations

Pitch horizontal sections to run alongside suction or discharge line

Insulate lines that are routed through very warm spaces

period five

Hot-Gas Bypass Line

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

hot-gas bypass line

Requirements for Sizing and Routing

Ensure that oil and refrigerant are not trapped in piping

Avoid excessive noise Proper routing is more critical than pipe

diameter

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Hot-Gas Bypass to Evaporator Inlet

evaporatorevaporator

condensercondenser

compressorcompressor

hot-gas hot-gas bypass valvebypass valve

TXVTXV

distributordistributor

suction linesuction line

liquid lineliquid line

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Hot-Gas Bypass Valve Installation

condensercondenser

compressorcompressor

hot-gas hot-gas bypass valvebypass valve

pitch back toward pitch back toward discharge linedischarge line

pilotpilotlineline

suctionsuctionlineline

dischargedischargelineline

pitch awaypitch awayfrom hot-gasfrom hot-gasbypass valvebypass valve

hot-gas hot-gas bypass linebypass line

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Hot-Gas Bypass Risers

hot-gashot-gasbypass riserbypass riser

suctionsuctionlinelinecompressorcompressor

drain legdrain leg

oil-returnoil-returnlineline

condensercondenser

hot-gas hot-gas bypass valvebypass valve

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

hot-gas bypass line

Connection to Evaporator

evaporatorevaporator

distributordistributor

liquidliquidlineline

hot-gas hot-gas bypass linebypass line

solenoidsolenoidvalvevalve

TXVTXV

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

hot-gas bypass line

Connection to Evaporator

evaporatorevaporator

distributordistributor

hot-gas hot-gas bypass linebypass line

solenoidsolenoidvalvevalve

checkcheckvalvesvalves

TXVTXV

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Hot-Gas Bypass to Suction Line

evaporatorevaporator

condensercondenser

compressorcompressor

hot-gas hot-gas bypass valvebypass valve

suction linesuction line

liquid lineliquid line

liquid-injection liquid-injection valvevalve

TXVTXV

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

hot-gas bypass line

Connection to Suction Line

condensercondenser

compressorcompressor suction linesuction line

liquidliquidlineline

hot-gas hot-gas bypass valvebypass valve

liquid-injection liquid-injection valvevalve

solenoidsolenoidvalvevalve

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Hot-Gas Bypass Line Sizing

1/2 (12)1/2 (12) 6,700 (34.0)6,700 (34.0)5/8 (15)5/8 (15) 4,200 (21.3)4,200 (21.3)3/4 (18)3/4 (18) 2,825 (14.4)2,825 (14.4)7/8 (22)7/8 (22) 2,025 (10.3)2,025 (10.3)

1 1/8 (28)1 1/8 (28) 1,200 ( 6.1)1,200 ( 6.1)1 3/8 (35)1 3/8 (35) 775 ( 3.9)775 ( 3.9)

velocity, fpm (m/s)velocity, fpm (m/s)pipepipediameter,diameter,in. (mm)in. (mm)

10 tons 10 tons (35.2 kW)(35.2 kW)

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

hot-gas bypass line Other Considerations

Insulate entire line to prevent refrigerant vapor from condensing

Minimize overall length of the line Install solenoid valve if system includes a

pump-down cycle

period six

Review

Refrigerant Piping

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Review—Period One

Refrigerant Piping Requirements Return oil to compressor Ensure that only liquid refrigerant (no vapor) enters

the expansion device Minimize system capacity loss Minimize refrigerant charge

If provided, use line sizes recommended by the manufacturer

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Review—Period Two

Suction line Ensure adequate velocity to return oil to the

compressor at all steps of unloading Avoid excessive noise Minimize system capacity and efficiency loss

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Review—Period Three

Discharge line Ensure adequate velocity to return oil to the

compressor at all steps of unloading Avoid excessive noise Minimize efficiency loss

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Review—Period Four

Liquid line Ensure that only liquid refrigerant enters the

expansion device Minimize refrigerant charge Avoid excessive noise and pipe erosion

Air Conditioning Clinic TRG-TRC006-ENAir Conditioning Clinic TRG-TRC006-EN© American Standard Inc. 2002

Review—Period Five

Hot-gas bypass line Ensure that oil and refrigerant are not trapped in the

piping Avoid excessive noise Proper routing is more critical than pipe diameter

Recommended