Transformer & Substation Testing System (TRAX) · Transformer & Substation Testing System...

Preview:

Citation preview

1

Transformer & Substation Testing System

(TRAX)

NETA Power Test 2016

Fort Worth, TX

2

TRAX

Transformer & Substation Test System

3

Job Order Perform following tests on a D-Y 500 kV/138 kV 400 MVA

• Turns Ratio

• Winding Resistance

• Power Factor

• Leakage Reactance

• DRM for LTC diagnostics

Perform following test on a SF6 500 HV Circuit Breaker

• Contact Resistance

• Breaker Motion and Timing

TRAX – Instrument view (”My TRAX”)

TRAX – TTR @ 250/2000 V

TRAX – Excitation Current

TRAX – Power Factor Amplifier

TRAX – Power Factor @ 12 kV

TRAX – Winding Resistance @ 16/100 A

TRAX – Adaptive Demagnetization

Measure/calculate voltage-time integral (V*s) at high current (above

saturation current)

Create demagnetization cycles by reducing Vs value (typically 20%

reduction/step)

Effective • Verified against true AC demagnetization. Similar results in excitation current

and magnetic balance verification measurements

Fast • Significantly faster than static demagnetization algorithms for smaller

transformers (40 cycles demagnetization in less than 1 minute for 0.5 MVA

transformer)

Adaptive demagnetization

Magnetic balance after AC demag b-n Magnetic balance after adaptive demag b-n

a-n b-n c-n a-n b-n c-n

100% 68% 31% 100% 68% 31%

50% 100% 50% 50% 100% 50%

32% 67% 100% 31% 68% 100%

DRM on LTC - Patent pending Measure current , HV voltage, LV voltage (LV open)

R1 and R2 transition resistor values per tap (value/10). All within spec (± 10%)

Current

”ripple”

HV

voltage LV voltage

TRAX – Short-Circuit Impedance (Leakage Reactance)

Circuit Breaker Testing

TRAX – Contact Resistance @ 100 A

TRAX – Relay/timing

TRAX Solution – Apps!

10.4” touch screen

Dial

TRAX Top Panel

21

AUX

LINK

Ethernet

MAIN FUSES

MAINS

INPUT

AUX GROUND

AC OUTPUT

200A

800A

DC OUTPUT

100A

DC

OUTPUT

16A

DC OUTPUT

300V

AC

OUTPUT

2200V

AC

OUTPUT

250V

GROUN

D

AUX

POWER

TRAX Side Panel

DC INPUTS

VOLTAGE INPUTS CURRENT INPUTS

FUSE 1-4 500

mA

LED indicators

TRAX – Top Panel - Analog Inputs

TRAX Solution – Apps!

25

TRAX – Test Report w/ Nameplate Info

26

Manual Operation

27

TRAX Objective - Simplification

30

New Megger Products

Visit us at

Booth 225

SMRT46D MWA SPI225 DLRO-100

Recommended