1 Pulse Energy Webinar: 5 Common Energy Wasters in HVAC Systems

Pulse webinar, 5 HVAC Energy Wasters

Embed Size (px)

DESCRIPTION

James Smith, Pulse Energy’s Building Automation System (BAS) expert, presented this informative webinar on how you can identify and fix five common sources of energy waste in Heating, Ventilating, and Air Conditioning (HVAC) systems.James is a factory trained controls technician with over 18 years of hands-on experience installing and servicing HVAC automation systems for Siemens Building Technologies and Johnson Controls in office towers, universities and hospitals. During the webinar he: - presented five common sources of energy waste in these important building systems - shared ways to address them to lower energy costs, improve building performance and occupant comfort

Citation preview

Page 1: Pulse webinar, 5 HVAC Energy Wasters

1

Pulse Energy Webinar:

5 Common Energy

Wasters in HVAC Systems

Page 2: Pulse webinar, 5 HVAC Energy Wasters

3 Things You Want to Know About This Presentation

2

• The presentation will be 45-60

minutes, including Q&A

• You can sand your questions to

us via the GoToWebinar control

panel at any time

• We are recording the webinar

Page 3: Pulse webinar, 5 HVAC Energy Wasters

Agenda

3

• Intro

• 5 Common Energy Wasters• Bad marriage of pneumatic and electronic control

• Inappropriate temperatures in HW loops

• Duct leakage

• Simultaneous heating & cooling

• Forgotten overrides

• Quick overview of Pulse

• Q&A

Page 4: Pulse webinar, 5 HVAC Energy Wasters

Intro: James Smith

4

• 18 years experience as a factory trained controls

technician

• Installed and serviced HVAC automation systems

for Siemens Building Technologies and Johnson

Controls in office towers, universities and

hospitals

• Presenting 5 common issues which lead to

energy waste

Page 5: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

5

• Problem: DDC computer may not accurately

reflect the device position in the field

Page 6: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

6

• Problem: DDC computer may not accurately

reflect device position in the field

Page 7: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

7

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

Page 8: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

8

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

• Reliable

• Repeatable

Page 9: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

9

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

Page 10: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

10

• Large stock of pneumatic devices

0 – 100% Open

Page 11: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

11

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI

Page 12: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

12

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

4 – 9 PSI

3 – 8 PSI

Page 13: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

13

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

4 – 9 PSI

3 – 8 PSI

Page 14: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

14

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI

Page 15: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

15

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI4 – 9 PSI

20 PSI

Page 16: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

16

• One way to identify this problem: look for

unbelievable temperatures

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI4 – 9 PSI

20 PSI

Page 17: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

17

• Possible solutions:

• schedule both trades to work together

• cross train

Page 18: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

18

• Problem: inappropriate water temperatures for

terminal units

Page 19: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

19

• Most Boilers

• Consider manufacturers limits

• Consider terminal units

Page 20: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

20

• Local set point

Page 21: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

21

• Reset based on external variable

Page 22: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

22

• Reset based on external variable

• Possible to use Valve positions

Page 23: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

23

• Within the mfg limits for the boiler

Page 24: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

24

• Radiant Panels

Primary Loop Secondary Loop

Page 25: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

25

• Secondary Loop control

• Reduces losses on low demand

• Allows for set points that reflect the end devices

Primary Loop Secondary Loop

Page 26: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

26

• Radiant Panels typically require

175 to 185 deg F water (79 - 85 deg C)

Primary Loop Secondary Loop

Page 27: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

27

Page 28: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

28

Page 29: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

29

Page 30: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

30

Page 31: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

31

• Loop is reset based on outdoor temperature

• Loop is running at 60 deg C (20 less than typical)

• Even primary water is too cool for radiant panels

Page 32: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

32

• Loop is reset based on outdoor temperature

• Loop is running at 60 deg C (20 less than typical)

• Even primary water is too cool for radiant panels

Page 33: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

33

• Possible solutions:

• Read manufacturers literature on acceptable

operating temperatures for your terminal units

• Set up reset schedules based on these limits

• If you have radiant panels – run them hot

Page 34: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

34

• Problem: conditioned air leaking out of ducts

Page 35: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

35

• Indicator is ceiling space or return air path cooler

than the spaces served

• Seals fail over time

• Tenant retrofits do not always complete this detail

Page 36: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

36

• Seems harder to justify

• Definitely harder to quantify

• Absolutely wasted energy

• Protect your energy source

• Think of your conditioned air as energy

• Night job resealing ductwork

Page 37: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

37

• Problem: poor sequencing

• Correct sequencing of heating & cooling is critical

• For high humidity control, enthalpy must be a

factor in your free cooling calculation

• Delays in switching off consume excess

mechanical cooling

• Delays in switching on fail to take advantage of

available free cooling

Page 38: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

38

• Mixed Air Temp set points

• Difficult to set correctly

• Invite operator intervention

• Require tuning

• Add a layer of complication

• Get rid of them. Sequence your mixing

dampers directly with your heating and cooling

Page 39: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

39

• Hot and Cold Deck setpoints

• Use zone demand to calculate

• Create “just enough” heating or cooling to

satisfy your highest demand zone

• This applies to resetting your static pressure

Page 40: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

40

• For all sorts of good reasons operators override

devices temporarily.

• Too often, when the need has passed, the

override is long forgotten.

• When it is an entire system left running the cost

can add up quickly.

Page 41: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

41

Page 42: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

42

Page 43: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

43

Page 44: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

44

Page 45: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

45

• When you have an energy monitoring system

you can see the results of what you do.

• Alerts can notify you when demand exceeds

predictions by a defined threshold.

Page 46: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Occupant Engagement

46

Page 47: Pulse webinar, 5 HVAC Energy Wasters

Measuring and Reporting Energy Savings

Page 48: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Understanding Your Building

48

Page 49: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Understanding Your Building

49

Page 50: Pulse webinar, 5 HVAC Energy Wasters

50

Questions?

Page 51: Pulse webinar, 5 HVAC Energy Wasters

Thank you!