Page 1: Pulse webinar, 5 HVAC Energy Wasters

1

Pulse Energy Webinar:

5 Common Energy

Wasters in HVAC Systems

Page 2: Pulse webinar, 5 HVAC Energy Wasters

3 Things You Want to Know About This Presentation

2

• The presentation will be 45-60

minutes, including Q&A

• You can sand your questions to

us via the GoToWebinar control

panel at any time

• We are recording the webinar

Page 3: Pulse webinar, 5 HVAC Energy Wasters

Agenda

3

• Intro

• 5 Common Energy Wasters• Bad marriage of pneumatic and electronic control

• Inappropriate temperatures in HW loops

• Duct leakage

• Simultaneous heating & cooling

• Forgotten overrides

• Quick overview of Pulse

• Q&A

Page 4: Pulse webinar, 5 HVAC Energy Wasters

Intro: James Smith

4

• 18 years experience as a factory trained controls

technician

• Installed and serviced HVAC automation systems

for Siemens Building Technologies and Johnson

Controls in office towers, universities and

hospitals

• Presenting 5 common issues which lead to

energy waste

Page 5: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

5

• Problem: DDC computer may not accurately

reflect the device position in the field

Page 6: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

6

• Problem: DDC computer may not accurately

reflect device position in the field

Page 7: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

7

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

Page 8: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

8

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

• Reliable

• Repeatable

Page 9: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

9

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

Page 10: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

10

• Large stock of pneumatic devices

0 – 100% Open

Page 11: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

11

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI

Page 12: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

12

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

4 – 9 PSI

3 – 8 PSI

Page 13: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

13

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

4 – 9 PSI

3 – 8 PSI

Page 14: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

14

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI

Page 15: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

15

• Problem: DDC computer may not accurately

reflect device position in the field

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI4 – 9 PSI

20 PSI

Page 16: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

16

• One way to identify this problem: look for

unbelievable temperatures

0 – 100% Open

0 – 5 VDC

0 – 20 PSI

3 – 8 PSI4 – 9 PSI

20 PSI

Page 17: Pulse webinar, 5 HVAC Energy Wasters

#1: Pairing Pneumatic & Electronic Control

17

• Possible solutions:

• schedule both trades to work together

• cross train

Page 18: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

18

• Problem: inappropriate water temperatures for

terminal units

Page 19: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

19

• Most Boilers

• Consider manufacturers limits

• Consider terminal units

Page 20: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

20

• Local set point

Page 21: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

21

• Reset based on external variable

Page 22: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

22

• Reset based on external variable

• Possible to use Valve positions

Page 23: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

23

• Within the mfg limits for the boiler

Page 24: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

24

• Radiant Panels

Primary Loop Secondary Loop

Page 25: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

25

• Secondary Loop control

• Reduces losses on low demand

• Allows for set points that reflect the end devices

Primary Loop Secondary Loop

Page 26: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

26

• Radiant Panels typically require

175 to 185 deg F water (79 - 85 deg C)

Primary Loop Secondary Loop

Page 27: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

27

Page 28: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

28

Page 29: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

29

Page 30: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

30

Page 31: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

31

• Loop is reset based on outdoor temperature

• Loop is running at 60 deg C (20 less than typical)

• Even primary water is too cool for radiant panels

Page 32: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

32

• Loop is reset based on outdoor temperature

• Loop is running at 60 deg C (20 less than typical)

• Even primary water is too cool for radiant panels

Page 33: Pulse webinar, 5 HVAC Energy Wasters

#2: Heating Water Loop Temperature

33

• Possible solutions:

• Read manufacturers literature on acceptable

operating temperatures for your terminal units

• Set up reset schedules based on these limits

• If you have radiant panels – run them hot

Page 34: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

34

• Problem: conditioned air leaking out of ducts

Page 35: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

35

• Indicator is ceiling space or return air path cooler

than the spaces served

• Seals fail over time

• Tenant retrofits do not always complete this detail

Page 36: Pulse webinar, 5 HVAC Energy Wasters

#3: Duct leakage

36

• Seems harder to justify

• Definitely harder to quantify

• Absolutely wasted energy

• Protect your energy source

• Think of your conditioned air as energy

• Night job resealing ductwork

Page 37: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

37

• Problem: poor sequencing

• Correct sequencing of heating & cooling is critical

• For high humidity control, enthalpy must be a

factor in your free cooling calculation

• Delays in switching off consume excess

mechanical cooling

• Delays in switching on fail to take advantage of

available free cooling

Page 38: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

38

• Mixed Air Temp set points

• Difficult to set correctly

• Invite operator intervention

• Require tuning

• Add a layer of complication

• Get rid of them. Sequence your mixing

dampers directly with your heating and cooling

Page 39: Pulse webinar, 5 HVAC Energy Wasters

#4: Simultaneous Heating & Cooling

39

• Hot and Cold Deck setpoints

• Use zone demand to calculate

• Create “just enough” heating or cooling to

satisfy your highest demand zone

• This applies to resetting your static pressure

Page 40: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

40

• For all sorts of good reasons operators override

devices temporarily.

• Too often, when the need has passed, the

override is long forgotten.

• When it is an entire system left running the cost

can add up quickly.

Page 41: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

41

Page 42: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

42

Page 43: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

43

Page 44: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

44

Page 45: Pulse webinar, 5 HVAC Energy Wasters

#5: Forgotten overrides

45

• When you have an energy monitoring system

you can see the results of what you do.

• Alerts can notify you when demand exceeds

predictions by a defined threshold.

Page 46: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Occupant Engagement

46

Page 47: Pulse webinar, 5 HVAC Energy Wasters

Measuring and Reporting Energy Savings

Page 48: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Understanding Your Building

48

Page 49: Pulse webinar, 5 HVAC Energy Wasters

Pulse EMS: Understanding Your Building

49

Page 50: Pulse webinar, 5 HVAC Energy Wasters

50

Questions?

Page 51: Pulse webinar, 5 HVAC Energy Wasters

Thank you!

•Additional questions? Contact Pulse Energy

•1-877-331-0530

[email protected]

•http://www.pulseenergy.com/company/contact

•More energy management best practices

•On-demand webinars:

http://www.pulseenergy.com/resources/energy-

management-webinars/

•Pulse blog: http://blog.pulseenergy.com/

51


Recommended