Manual digsy ® compact Chapter D General Installation Guidelines Drawing - Number: 04 – 68 271 000/A Issued: 29.08.02 Stored: 29.08.02 Version: 1.0.0 File name: 04-68271A HB DCE Chapter D GIG Prepared by: Hans-Dieter Kaiser This manual was prepared with great care. The details and data in this document are regularly checked and updated and are at any time subject to change without notice. Nevertheless, INTER CONTROL does not assume liability for the correctness of the details/data in this document, since, despite great effort, mistakes cannot always be completely ruled out. In addition, INTER CONTROL reserves the right to make at any time technical changes to the product, which can also result in deviations from the contents of this document. The document includes information that enjoys protection of copyright. No part of this publication may be reproduced and/or translated into other languages without the prior written permission of INTER CONTROL. Of course, any ideas and suggestions regarding amendments, or notes concerning possible mistakes in this document are welcome. Please refer to INTER CONTROL. INTER CONTROL Hermann Köhler Elektrik GmbH & Co. KG Schafhofstraße 30 D-90411 Nürnberg Germany Tel.: ++49 911 9522-5 Fax: ++49 911 9522-857 E-mail: [email protected] Internet: http://www.intercontrol.de

04-68271A Manual DCE Chapter D GIG

Embed Size (px)

DESCRIPTION

04-68271A Manual DCE Chapter D GIG

Citation preview

Page 1: 04-68271A Manual DCE Chapter D GIG

Manual digsy®compact

Chapter D

General Installation Guidelines

Drawing - Number: 04 – 68 271 000/A

Issued: 29.08.02

Stored: 29.08.02

Version: 1.0.0

File name: 04-68271A HB DCE Chapter D GIG

Prepared by: Hans-Dieter Kaiser

This manual was prepared with great care. The details and data in this document are regularly checked and updated andare at any time subject to change without notice. Nevertheless, INTER CONTROL does not assume liability for thecorrectness of the details/data in this document, since, despite great effort, mistakes cannot always be completely ruled out.In addition, INTER CONTROL reserves the right to make at any time technical changes to the product, which can also resultin deviations from the contents of this document.The document includes information that enjoys protection of copyright. No part of this publication may be reproduced and/ortranslated into other languages without the prior written permission of INTER CONTROL.Of course, any ideas and suggestions regarding amendments, or notes concerning possible mistakes in this document arewelcome. Please refer to INTER CONTROL.

INTER CONTROLHermann Köhler Elektrik GmbH & Co. KGSchafhofstraße 30D-90411 NürnbergGermany

Tel.: ++49 911 9522-5Fax: ++49 911 9522-857E-mail: [email protected]: http://www.intercontrol.de

Page 2: 04-68271A Manual DCE Chapter D GIG

Chapter D - General Installation Guidelines Manualdigsy®

compact

04 – 68 271 000/AVersion 1.0.0

Page D-2

Table of contents

D GENERAL INSTALLATION GUIDELINES.............................................................................. D-3D.1 Connecting the protective conductor................................................................................ D-3D.2 Wiring proposal for switching gear cabinet ...................................................................... D-4D.3 General wiring guidelines................................................................................................. D-6

Table of figures

Figure D.1: Wiring of a control unit in a switchgear cabinet ........................................................... D-4Figure D.2: Cable connection in switchgear cabinet (see also Figure D.1) ................................... D-5

Page 3: 04-68271A Manual DCE Chapter D GIG

Chapter D - General Installation Guidelines Manualdigsy®

compact

04 – 68 271 000/AVersion 1.0.0

Page D-3

D GENERAL INSTALLATION GUIDELINES

D.1 Connecting the protective conductor

For safety reasons and for reasons of the Electro-Magnetic Compatibility (EMC) an optimalprotective ground terminal has to be assured.

The protective conductor (PE) or the ground of the vehicle is to be connected via the star-point(central GND bar) in the switchgear cabinet to the ground screw provided for on the systemhousing and/or the controller case (see illustration D.1 and illustration D.2).

This measure serves to improve the interference immunity.

ATTENTION: From ground screw (PE) of the system housing a connection of wire cross-section min. 2.5mm must be leaded as short as possible to the PE section ofthe power supply unit or chassis/ground in the vehicle.

When using connectors featuring metal hoods and a shield, it ispossible to eliminate an additional overall-shield connection to theground terminal of the control unit housing.

In the case of shielded cables use always metal hoods.

The metal hoods must be conductively fastened to the housing.

In the case of potential differences between several PE - (GND) - points(e.g., in the case of separated power supplies via different circuits) theshield of the connecting cable must only be grounded on one sideof the control unit.

If twisted-pair, shielded cables are used the connector housings has tobe connected to GND too.

The individual shields on the open cable end mustnot be connected to the overall shield or PE.

Page 4: 04-68271A Manual DCE Chapter D GIG

Chapter D - General Installation Guidelines Manualdigsy®

compact

04 – 68 271 Version 1.0.

D.2 Wiring proposal for switching gear cabinet

Figure D.1: W

,

e e

Mains orpower line

EMC Filter for powerline

EMC Filter for data

Data cabl

000/A0

Page D-4

iring of a control unit in a switchgear cabinet

PE - machin

Page 5: 04-68271A Manual DCE Chapter D GIG

Chapter D - General

04 – 68 271 000/AVersion 1.0.0

P

Figure D.2: Cable connection in switchgear

A = Prior to connecting painted housing parconnection has to be removed.

B = Fold the shield backward and ground it

C = PE-bar or ground-bar made of Al, Cu o

D = Nickel-plated or varnished mounting plaholes (coating or lacquer must have be

E = Fastening bolts on the mounting plate o

F = PE- GND connection to the machine. Wfrom the switchgear cabinet to the chasconnection from the mounting plate to t

G = Nickel-plated washer to insure a condu

H = Nickel-plated cable clamp.

K = Connection (large-surface contact) to s

PE or GND bar

Installation Guidelines Manualdigsy®

compact

age D-5

cabinet (see also Figure D.1)

ts the lacquer/varnish coat on the points of

coaxially with the nickel-plated cable clamps.

r Fe nickel-plated.

te with bare/un-insulated area around the fasteningen removed).

f the switchgear cabinet.

hen using the device in a vehicle, the connectionsis has to be established in the same way as thehe switchgear cabinet.

cting connection.

witching cabinet door (e.g. braided Cu-conductor).

PE or GND bar

Page 6: 04-68271A Manual DCE Chapter D GIG

Chapter D - General Installation Guidelines Manualdigsy®

compact

04 – 68 271 000/AVersion 1.0.0

Page D-6

D.3 General wiring guidelines

The following wiring rules should always be considered:

PE-conductors must always be wired according to VDE-regulations or equivalent regulations.

In addition, the whole mounting plate is to be used as a grounding surface.

That means: all metal parts such as housing, rails etc. are to be connected via short low-resistanceHF-connections to the mounting plate (braided Cu-conductors, nickel-plated screws etc.).

ATTENTION: The connecting points must be free from coating/oxide, i.e., prior to connectionthe varnish/coating has to be removed from the surface (see Figure D2)

The areas of the control electronics, power electronics and mains-ON/OFF must be geometricallyseparated (they must not be located next to each other). This area of separation also applies to theclosed cabinet door.

ATTENTION: All the metal parts must have low-resistance HF-connections.

1. Bright and bare connecting points

2. Surfaces protected against corrosion, e.g.: nickel-plating.

3. If possible, no oxide films on the blank surface (no coating or anodization)!

4. Connections of large-surface contact

5. Connections must be as short as possible

Beside to the normal connection to PE or GND, the VDE-rules or their equivalents of othercountries have to be considered with respect to metal parts and their HF-characteristics.