Upload
insansoft6498
View
218
Download
1
Embed Size (px)
Citation preview
8/4/2019 06_01_TransformerProt
1/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F1 of 44
Transformer Protection in Transmission Networks
ABB
Transformer Protection
in
Transmission Networks
8/4/2019 06_01_TransformerProt
2/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F2 of 44
Transformer Protection in Transmission Networks
ABB
Power transformers in a power system
400 kV AC Transmission
Generation
130 kV Subtransmission
Distribution
M
MV
LV
8/4/2019 06_01_TransformerProt
3/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F3 of 44
Transformer Protection in Transmission Networks
ABB
Different vector group and neutral connections
Y d + zYN d11 + zn
Y y
YN yn0 (d1)
Y d
YN d1
D y
D yn11
8/4/2019 06_01_TransformerProt
4/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F4 of 44
Transformer Protection in Transmission Networks
ABB
Different winding arrangements
2 windings+ unloaded
tertiary
3 windings Autotransformer+ tertiarye.g. Yy 6 d1e.g. YN Auto d1
2-winding transf.
+ Auxiliary
transformer
0
8/4/2019 06_01_TransformerProt
5/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F5 of 44
Transformer Protection in Transmission Networks
ABB
Possible FaultsInsulation breakdown
Short circuits phase-to-phase
Inter-turns
Ground faults
Overvoltage U> (overexcitation U/f>)
Overtemperature
Oil leakage or contamination
Oil level monitor
Reduced cooling
8/4/2019 06_01_TransformerProt
6/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F6 of 44
Transformer Protection in Transmission Networks
ABB
Possible Transformer Failures
Winding failures
Tap changer failures
Bushing failures
Core failures
Miscellaneous failures
8/4/2019 06_01_TransformerProt
7/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F7 of 44
Transformer Protection in Transmission Networks
ABB
Selective Protection of:- two or
- three winding transformer
- autotransformer- generator-transformer unit
Detection of:
- all-phase faults
- earth-faults at solidly orlow-impedance earthed systems
- interturn faults
8/4/2019 06_01_TransformerProt
8/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F8 of 44
Transformer Protection in Transmission Networks
ABB
Recommended Transformer Protection
Functions Rating
up to 2 MVA 2 - 5 MVA less 60 MVA over 60 MVA
Gas Detector
Relay (Buchholz)Overload Protection
(Thermal or
temperature
monitoring relay)
Overcurrent
ProtectionDifferential
Protection
Ground Fault
Protection
Voltage Regulating
Relay
Overexcitation for exposed overvoltage
situations
Oil level monitor
8/4/2019 06_01_TransformerProt
9/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F9 of 44
Transformer Protection in Transmission Networks
ABB
Transformer Protection Basic VersionsTransformer Protection Basic Versions
Type of Transformer Unit High-Voltage Side Medium-Voltage Side Low-Voltage Si
Prot. Prot. 1 Prot. 2 Prot. 1 Prot. 2
(Main) (Back-up) (Main) (Back-up)
2-Winding (Star/Delta) Id I> + IN + TH + SBEF I>
Id REF I> + IN + TH + SBEF I>
2-Winding (Star/Stern) Id I> + IN + TH I> + IN + SBEF
Id REF I> + IN + TH REF I> + IN + SBEF
2-Winding (Star/Delta) + Earth.transf. Id I> + IN + TH I> + IN + SBEF
Id REF I> + IN + TH I> + IN + SBEF
3-Winding (Star/Star/Delta) Id I> + IN + TH I> + IN + SBEF I>
Id REF I> + IN + TH REF I> + IN + SBEF I>
3-Winding (Star/Star/Delta) + Earth.transf. Id I> + IN + TH I> + IN I> + IN + SBE
Id REF I> + IN + TH REF I> + IN I> + IN + SBE
2-Winding (Auto) Id + REF I> + IN + TH I> + IN
3-Winding (Auto) Id + REF I> + IN + TH I> + IN I>
Remark: The SBEF-Function (Stand-by EF Prot.) is only needed if earthing resistor is installed
Transformer Rating
S < 60 MVA S > 60 MVA
8/4/2019 06_01_TransformerProt
10/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F10 of 44
Transformer Protection in Transmission Networks
ABB
Bu / LOL
OT / WT
I >
IN
TH
I
IN
I >REF
I >>
Transformer protection example (1)
IN
8/4/2019 06_01_TransformerProt
11/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F11 of 44
Transformer Protection in Transmission Networks
ABB
Transformer protection example (2)
I> 51T u 49
REF 87N I0 51N
87TU> 59B
87T
- Differential prot. (87T)
- REF (87N)
- Overcurrent (51T)- E/F protection (51N)
- Thermal overload prot. (49)
- Overvoltage prot. (59)
8/4/2019 06_01_TransformerProt
12/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F12 of 44
Transformer Protection in Transmission Networks
ABB
Transformer protection example (3)
I
Bu / LOL
OT / WT
I>IN
TH
Id
I>
I>
I N
8/4/2019 06_01_TransformerProt
13/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F13 of 44
Transformer Protection in Transmission Networks
ABB
Transformer protection example (4)
I
Bu / LOL
OT / WT
I >
IN
TH
Id
I >
IN
I >REF
I >>
REF
8/4/2019 06_01_TransformerProt
14/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F14 of 44
Transformer Protection in Transmission Networks
ABB
Differential protection (87T)
Causes
phase faults in theprotection zone
effects
high currents potential damage to
transformer winding
expensive outage andrepair due to damage
Features / requirements
low impedance principle for two and three-winding
transformers
non-linear current-dependant
tripping characteristic high stability during through-
fault and CT-saturation
compensation for vector group
compensation for currentamplitude (CT-ratio)
inrush restraint
8/4/2019 06_01_TransformerProt
15/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F15 of 44
Transformer Protection in Transmission Networks
ABB
Differential Protectionincludes:
C.T. Ratio adaption
Connection group adaption
Back-up functions
Large setting ranges
Features
8/4/2019 06_01_TransformerProt
16/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F16 of 44
Transformer Protection in Transmission Networks
ABB
Differential protection (87T)
Id= I1+I2
by external faults can due to-ratio errors
-saturation
-losses in the transfomer
-tapchanger
a differential current can occur,therefore a stabilized tripping
characteristic is needed
Inrush can also provoke differential
current
87T Protectionzone
8/4/2019 06_01_TransformerProt
17/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F17 of 44
Transformer Protection in Transmission Networks
ABB
Differential protection (87T)Features
True measurement for three-wind.
transformer
compares the greatest current the with
sum of the two others
I-instantaneous independ. of inrush
Inrush
eval.ratio 2nd.harm to fundamental
detection of largest phase current
detection of energised transformer using
load current Adaptive characteristic (b-line)
g
v
g-high
b
Id/ IN
Ih/ IN
Trip for
I1 / IN < b or
I2 / IN < bTrip
No Trip
8/4/2019 06_01_TransformerProt
18/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F18 of 44
Transformer Protection in Transmission Networks
ABB
AI 1,2,3 AI 7,8,9
AD DIFF
AD
Differential protection (87T)
8/4/2019 06_01_TransformerProt
19/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F19 of 44
Transformer Protection in Transmission Networks
ABB
AI 1,2,3
AI 7,8,9
AD
DIFF
A
D
AD
AI 4,5,6
Differential protection for 3 windings
8/4/2019 06_01_TransformerProt
20/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F20 of 44
Transformer Protection in Transmission Networks
ABB
Differential protection 87T
CT's at the Aux. transformer
must have the same ratio as
the other two. Correction of the ratio with
Ref.-Value or a-Factor in the
protection function
G
87GT
10'000/ 5
10'000/ 5
800/ 5
300MVA
220/ 18 KV
300MVA18 KV
30MVA
18/ 6 KV
8/4/2019 06_01_TransformerProt
21/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F21 of 44
Transformer Protection in Transmission Networks
ABB
Fault inside protected zone
1
2
3
4
1 2 3 4 5 IH
DII1 I2
IH = 0
g
cos a < 0
8/4/2019 06_01_TransformerProt
22/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F22 of 44
Transformer Protection in Transmission Networks
ABB
Fault outside protected zoneLow short circuit current
Load
1
2
3
4
1 2 3 4 5 IH
DI
v=50%
I1 I2
IH = I1 = I2 =
ILoad < (1.5...3)*Irated g
I < (1.5...3) * Irated
cos a = 1
IH I1 I2 cos= a
8/4/2019 06_01_TransformerProt
23/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F23 of 44
Transformer Protection in Transmission Networks
ABB
Isc
1
2
3
4
1 2 3 4 5 IH
DI
v=50%
I1 I2
IH = I1 = I2g
I > (1.5....3) * Irated
cos a = 1
v= infinite
IH I1 I2 cos= a
b
Fault outside protected zoneHigh short circuit current
8/4/2019 06_01_TransformerProt
24/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F24 of 44
Transformer Protection in Transmission Networks
ABB
vg
1 2 3b
Restraint
I
IN
OperationOperation for
I1
IN< b
orI2
IN< b
IH
IN
I 1 I 2Protected unit
2)-1;
12
211
H
21H
H
321
I(II-II
I;IofgreatestI:where
0cosfor0I0cosforcosIII
current.Restraint....................I
currentOperating....IIII
=
D=
=
8/4/2019 06_01_TransformerProt
25/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F25 of 44
Transformer Protection in Transmission Networks
ABB
Vector group adoption for Yd5 transformer
8/4/2019 06_01_TransformerProt
26/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F26 of 44
Transformer Protection in Transmission Networks
ABB
Restricted earth-fault protection (REF)
AI
Trip
REF
Id
REF
Id Trip
Used at direct and low
impedance earthing
Clears internal EFsinstantaneously
Unaffected by inrush currentand external fault
8/4/2019 06_01_TransformerProt
27/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F27 of 44
Transformer Protection in Transmission Networks
ABB
Thermal overload protection
Time
0,63
Rise of temperature
t
8/4/2019 06_01_TransformerProt
28/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F28 of 44
Transformer Protection in Transmission Networks
ABB
Definite
V/Hz inverse
t
V/Hz
Overexcitation protection
8/4/2019 06_01_TransformerProt
29/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F29 of 44
Transformer Protection in Transmission Networks
ABB
Requirements for overcurrent protection
Fast operation for primary short circuit
Non operation for inrush
Discrimination with other overcurrent
protectionNon operation at short or long term overload
Back up protection for network faults,
outside the transformer
8/4/2019 06_01_TransformerProt
30/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F30 of 44
Transformer Protection in Transmission Networks
ABB
Transformer protection
Control unit
Busbar protection
R
E
C
OFF 1
ON
OFF 2
Application, typical HV bay
8/4/2019 06_01_TransformerProt
31/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F31 of 44
Transformer Protection in Transmission Networks
ABB
Protection function structure
Ir12 = 0,80 A
Ir22 = 0,98 A
110 V3
Ur22 = 110/3 V
30 MVA
145 kV
11 kV
Ir1 = 120 A
Ir2 = 1575 A1600 / 1 A
150 / 1 A
11 kV3
150 / 1 A IrN12 = 0,80 A
A/D
conv.
BI
DIFF
TOC
REF
etc.
NOV
Trip
logic
Trip
F
il
t
e
r
in
g
>1
f
8/4/2019 06_01_TransformerProt
32/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F32 of 44
Transformer Protection in Transmission Networks
ABB
Main functions
Compact design including: Basic SW functions and transformer protection functions:
- Differential protection
- Overcurrent protection(Definite time or inverse functions)
- Thermal overload
- Overvoltage protection
- Metering U I f P Q
- Distance protection
- Overexcitation U/f
- FUPLA
- Logic functions,delay & counter
- Disturbance Recording
- Check functions (I, U)
T f P t ti i T i i N t k
8/4/2019 06_01_TransformerProt
33/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F33 of 44
Transformer Protection in Transmission Networks
ABB
Main Features- No interposing CT's
- Standard wiring diagram
- Inputs for external functions (Buchholz, temperature sensors) available
- Programmable indication of tripping and signalling
- Indication of measuring values
- Continuous self-monitoring- Modular SW protection functions
- 4 serial interfaces:* one front for local commmunication (PC)
* one rear for remote communication SPA or VDEW6* two others (spare)
- Member of the 316*4-family and part of PYRAMID
- Fits into ABB solution
T f P t ti i T i i N t k
8/4/2019 06_01_TransformerProt
34/36
ABB Power Automation LtdT2314 / trafoprot_a.ppt / F34 of 44
Transformer Protection in Transmission Networks
ABB
Transformer Protection Options
I> back up
Sensitive earth fault I0>for not grounded windings
Restricted earth fault
(High impedance principle) Thermal overload
U>, U